Lytecaster
®
Recessed Downlighting 1170M1
Page 1 of 2 6 3/4" Aperture Basic White Reflector Reflector Trim
7 1/2”
1170M1/1100 DEEP IC Series
Incandescent Insulated Ceiling
1170M1/1102P1
Standard Incandescent
Complete Fixture consists of Reflector Trim & Frame-In Kit. Select each separately.
Reflector Trim
1170M1
Basic White
Frame-In Kit — See Individual Frame-In Kit Specification Sheets
Incandescent Fluorescent
Frame-In Kit Ceiling Type Lamping Height Frame-In Kit Ceiling Type
1102P1
1103R
1100IC
1100AICM
1104IC/N
1104ICR
1104ICX/N
1100DICM
1100DAICM
1104IC/N
1104ICR
Non-IC
Non-IC Remodeler
IC
AirSeal® IC
AirSeal® IC
IC Remodeler
AirSeal®-IC
Deep IC
Deep AirSeal®-IC
Non-IC
Non-IC Remodeler
75W A19, PAR30*
85W BR30
75W PAR30
85W BR30
90W PAR38†
75W PAR30*
85W BR30
75W PAR30
85W BR30
6 5/8"
6 5/8"
7 5/16"
7 5/16"
7 1/2"
7 1/2"
7 1/4"
9 1/2"
9 1/2"
7 1/2"
7 1/2"
1104F13 Series
1104F18** Series
1104F26** Series
1100FTU Series
1100AICMFT
1910XDH1
1910XFH1
1170M1/1104IC/N
0
Convertible
™
IC/Non-IC
6 5/8”
1170M1/1103R
0
Remodeler Ring
IC (1) Quad/Triple 13W (GX24q-1) 7 1/2"
IC (1) Quad/Triple 18W (GX24q-2) 7 1/2"
IC (1) Quad/Triple 26W (GX24q-3) 7 1/2"
Non-IC (1) Triple 26/32W (GX24q-3) 6 5/8"
AirSeal®-IC (1) Triple 26/32W (GX24q-3) 6 7/8"
Conversion Kit (2) Quad 13W (GX23-2) 6 5/8"
Conversion Kit (1) Quad 13W (GX23-2) 6 5/8"
* Use Socket Extender 1968 For Short Neck PAR30.
** Lightolier recommends the use of triple tube lamps
™
Lamping
Non-IC
Height
Features
1. Reflector: Hydroformed aluminum, .040" thick (18 ga.) ; non-yellowing,
scruff-resistant Perma White finish with 88% reflectance; white trim flange.
2. Cone: Injection molded high temperature opaque white polymer.
3. Frame-In Kit: (1102P1 standard frame shown). Other frames listed above
and shown on the right. See Frame-In Kit specification sheets for more
details.
Accessories
Medium Base Socket Extender: 1968 - For short neck Par30 lamp
Labels
UL (Suitable for Damp Locations), I.B.E.W.
US Patent Numbers: 4,751,624; 5,045,985
Other US & Foreign Patents Pending.
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
Lightolier a Genlyte company www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2007 Genlyte Group LLC • E0507
Lytecaster
200
400
600
0
30
60
90
180 150 120
ACROSS
45
ALONG
60
50
40
30
20
10
AVERAGE INITIAL FOOTCANDLES
ROOM SURFACE REFLECTANCES:
80% Ceiling; 60% Walls; 20% Floor
925 Lumens Per Lamp
Large Room (RCR=1)
Small Room (RCR=5)
®
Recessed Downlighting 1170M1
Page 2 of 2 6 3/4" Aperture Basic White Reflector Reflector Trim
SPACING RATIO = 0.9
RECESSED LYTECASTER DOWNLIGHT,
5 1/2” DIA. APERTURE, BASIC PERMA-WHITE
ONE PHILIPS 85W BR30 FLOOD LAMP,. LUMEN RATING = 925 LMS.
ANGLE MEAN CP LUMENS
0 678
5 670 36
10 642
15 582 164
20 502
25 428 200
30 369
35 322 203
40 281
45 223 167
50 136
55 70 71
60 42
65 30 31
70 23
75 16 17
80 9
85 5 6
90 2
ZONE LUMENS % LAMPS % LUMINAIRE
0-30 426 46.14 46.29
0-40 629 68.09 68.32
0-60 868 93.89 94.20
DATE: DATE APRIL 10, 1997
PREPARED FOR:
LIGHTOLIER, FALL RIVER, MA
0-90 922 99.68 100.00
40-90 292 31.58 31.68
60-90 53 5.78 5.80
90-180 0 .00 .00
0-180 922 99.68 100.00
** EFFICIENCY = 99.7% **
80 70 50 30 10
% WALL REFLECTANCE
50 30 10 50 30 10 50 30 10 50 30 10 50 30 10 0
1 1.09 1.06 1.04 1.07 1.04 1.02 1.03 1.01 .99 .99 .97 .96 .96 .94 .93 .91
2 1.00 .96 .92 .99 .94 .91 .95 .92 .89 .92 .90 .87 .90 .87 .85 .83
3 .92 .87 .82 .91 .86 .82 .88 .84 .80 .86 .82 .79 .83 .80 .78 .76
4 .85 .79 .74 .84 .79 .74 .82 .77 .73 .80 .76 .72 .78 .74 .71 .70
5 .79 .72 .67 .78 .71 .67 .76 .70 .66 .74 .69 .66 .73 .69 .65 .64
6 .73 .66 .61 .72 .66 .61 .70 .65 .61 .69 .64 .60 .68 .63 .60 .58
7 .67 .60 .56 .66 .60 .55 .65 .59 .55 .63 .58 .54 .62 .58 .54 .53
8 .62 .55 .51 .61 .55 .50 .60 .54 .50 .59 .54 .50 .58 .53 .50 .48
ROOM CAVITY RATIO
9 .57 .51 .46 .57 .50 .46 .56 .50 .46 .55 .49 .45 .54 .49 .54 .44
10 .53 .46 .42 .52 .46 .42 .51 .46 .42 .51 .45 .41 .50 .45 .41 .40
20% FLOOR CAVITY REFLECTANCE
Conversion Factors: 2 Lt. 13W Quad Tube, C. U. x 0.40, 1 Lt. 13W Qyad Tube, C. U. x
0.45. 75W A19, C. U. x 0.50.
To convert lighting data for a lower wattage incandescent lamp of the same type, multiply the footcandle (or candlepower) values by the ratio of the lumens of the two lamps.
The coefficients of utilization remain the same.
Job Information Type:
Lightolier a Genlyte company www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2007 Genlyte Group LLC • E0507