Operators available left hand mount.Must be inverted for
right hand mount. Limits and motor direction must be
reversed when changing handing.(See Pages 14 - 15)
The Fire Door Controller, FDC, is an integrated fire door control system. It is designed to interface with a
normally close (NC) or normally open (NO) dr y contact alar m system to control the operation of a fire door.
The control station is the standard B2 wiring, momentary contact to open, close and stop, plus wiring for
sensing device to reverse and auxiliary devices to open and close with open override.
N OTICE
WARNING
THIS OPERA T OR IS NO T A FIRE ALARM SYSTEM. IT
CAN NOT DETECT A FIRE CONDITION.
FUNCTIONAL OPERATION
1. Battery Backup (management system)
The batteries are charged, tested, and monitored automatically by the microprocessor based
system.
The batteries are tested under load every thirty days, if for any reason the batteries fail this
load test, the on board buzzer will sound for 3 seconds of every minute to indicate that the
batteries need to be replaced. If the batteries are not replaced within 45 days (from initial
test) the door will automatically close, and remain inoperable until the batteries have been
replaced.
The battery voltage is continuously monitored, if for any reason the voltage drops below 22
VDC (this is the minimum operating voltage for the brake controls) the unit will activate the
optional warning signal and automatically close the door.The door will remain inoperable
until such time that the batteries come back to charge, or they are replaced.Low batter y
condition will be indicated by the on board buzzer sounding 3 seconds out of every minute,
and the low battery indicator (located on the key test station) flashing, until the batteries
come to the full charge or are replaced.
2. Unit has AC power & no alarm condition:
The B2 control station is used to operate the door electrically.
Activation of the safety edge while the door is closing will cause the door to reverse to the
full open limit.
Activation of the safety edge while the door is opening will NOT effect operation, the door will
continue to the open limit.
Activating the key-test switch for at least 6 seconds will put the operator in alarm
active mode.(see ACTIVE ALARM section for detail operation of alarm active mode)
3. Unit has AC power & active alarm condition (ALARM #1 - smoke alarm etc.):
The unit will activate the OPTIONAL warning signal, the door will automatically close after
the preset time delay. (powered down by motor) The time delay is set by means of DIP
switch 1.
If the door is in the open position and an alarm condition occurs, the door will automatically
close under motor operation. In the event the door should meet an obstruction while closing,
it will reverse and return to the full open position, and then start the closing cycle (with delay
and warning) again. If the obstruction is not removed, the door will close stopping at the
lowest possible position holding the brake for 2 seconds, then releasing the door to Gravity
Close (controlled descent). If after the door has finished the cycling mode and the
obstruction has been removed, the door will proceed to the floor.
In the event of a failure in motor operation, the operator will gravity close.(controlled
descent)
3
FUNCTIONAL OPERATION CONTINUED
4. Unit has AC power & active alarm condition (ALARM #2 - Fire Sensor, thermal sensor etc.):
The unit will activate the optional warning signal, the door will automatically close after the preset time delay.
(powered down by motor) The time delay is set by means of DIP switch 1.
If the door is in the open position and the alarm condition occurs, the door will automatically close under
motor operation. In the event the door should meet an obstruction while closing, the door will stop for 2 sec
onds, then release the door to Gravity Close (controlled descent).After the obstruction has been removed,
the door will proceed to the floor.
In the event of a failure in motor operation, the operator will gravity close (controlled descent)
All control station functions will be rendered inactive in this condition.
The safety edge will remain active.
5. Unit has No AC power & No active alarm condition:
The Close and Stop buttons of the B2 control station are functional.
The door's descending speed is controlled by the integrated braking system.
The door will stop if an obstruction is encountered while closing.
The Open button is not functional
6. Unit has No AC power & active alarm condition (Alarm #1 or Alarm #2):
The unit will activate the OPTIONAL warning signal, the door will automatically close after the preset time
delay. (controlled by integrated braking system) The time delay is set by means of DIP switch 1.
If the door encounters an obstruction while closing , the door will stop on the obstruction, and
release the brake after (2) seconds.If the obstruction is then removed the unit will perform a
controlled drop of the door.(not powered down by the motor)
7. Activation of the internal Thermal Sensor:
Will activate an alarm #2 switch.
With AC power present the unit will react as stated in paragraph 4.
With No AC power present the unit will react as stated in paragraph 6.
8. Activation of the Key Test Station:
Key must be activated for 6 seconds
The unit will activate the OPTIONAL warning signal, the door will automatically close after the preset time
delay. (controlled by integrated braking system) The time delay is set by means of DIP switch
1. (to test the signal devices and the delay time)
The door will close using gravity close mode (Controlled Descent) in order to test the door
balance, descent speed, and the moment of the door.
All sensing devices and control devices will be active. (In order to test these devices)
(See page 5 for procedures)
4
DOOR SYSTEM TESTING PROCEDURES
Before beginning any testing, secure the door area, keep unauthorized personnel from entering the area during testing.
Be sure ac power is present at the operator. (the green "AC" led will be lighted on the operators control board) and that
the batteries are connected and fully charged. (the red "DC" led will NOT be lighted on the operators control board)
1. Begin the test with your door at the full "OPEN" position.
2. Make cer tain dip switch #2 is in the "ON" position "FIREDOOR" mode.
3. If your door is equipped with safety photo eyes, make certain dip switch #4 is in the "ON" position.
Note: If 2 minutes total time elapses from the beginning of step #11and the conclusion of step #15, the unit will automatically exit the "TEST" mode.To re-enter the "TEST" mode repeat step #4, and continue testing.
4.Turn the wall mounted key test switch to the "TEST" position and hold for a minimum of 6 seconds. This action simulates an “ALARM” signal.
5. If dip switch #1 is in the "ON" position, the door should begin to close immediately.If dip switch #1 is in the "OFF"
position, the door should begin to close after 10 seconds time has elapsed. (the door will not motor down, it will gravity
descend)
6. Using a "stop-watch" verify that your door is closing between 6" and 24" per second. (i.e.. A 10ft high door should
close in a time between 5 and 20 seconds.) Your door should now be fully closed.
7. Open the door by depressing the "OPEN" button on the three button control station.
8. Repeat step #4.
9.When the door is approximately 3 to4 feet from the floor, activate the doors safety edge, using a crate, skid or
alike.Do not introduce any part of your body to the door system during testing. The door should reverse
to the full open position. Remove the obstruction.
10.The door will begin to close within 1 sec., If dip switch #1 is in the "ON" position. If dip switch # 1 is in the "OFF"
position, the door will wait 10 sec. Before beginning to close.The door should fully close to the floor. (the door will not
motor down, it will gravity descend)
11. Repeat steps #7 and #8.
12.When the door is approximately ½ way to the floor, interrupt the safety photo eye beam, by blocking with a
piece of cardboard or alike. Do not introduce any part of your body to the door system during testing. The
door should reverse to the full open position.Remove the obstruction.
13. Step #10 repeats.
14.When the door is approximately ½ way to the floor, depress and hold the "STOP" button on the three button control
station.The door should stop.
15. Release the "STOP" button on the control station. Step #10 repeats.
16. Depress the "OPEN" button on the three button control station. The door should open to the full open position. The
unit is now ready to be returned to service.
5
OPERATOR MOUNTING
Before your operator is installed, be sure the door has been properly aligned and is working smoothly. The operator may be wall mounted or mounted on a bracket or shelf. Ref er to the illustr ation and instructions below that suits
your application. This motor operator is an integral part of the door system. The motor operator, controls door
descent speed under power outage conditions, therefore the motor operator mounting surface is of major importance.The mounting must provide the following:
- All surfaces should be flat, square, and parallel to the door shaft
- The mounting surface must be rigid, and braced off as required
- When wall mounting the motor operator, it should be through bolted to the wall
- All (8) motor operator mounting points MUST be used
- All mounting hardware should be a minimum of grade 5
1a. Bracket or Shelf Mounting
The operator may be mounted either above or
below the door shaft.The optimum distance
between the door shaft and operator drive shaft is
between 12” - 15”. Refer to Figure 1.
NOTE:The door hood, end plates, and mounting
bracket must be rigid, and provide adequate structural
support.
FIGURE 1
(Right Hand Unit Shown)
1b. Wall Mounting
The operator should generally be installed below
the door shaft, and as close to the door as possible.The optimum distance between the door shaft
and operator drive shaft is between 12”- 15”. Refer
to Figure 2.
Through bolts as required
(8 places)
Load spreading plate
mounted to wall both sides
(supplied by others)
FIGURE 2
(Right Hand Unit Shown)
1c. Place door sprocket on the door shaft.Do not
insert the key at this time.
2.Wrap drive chain around door sprocket and join
roller chain ends together with master link. (Link
clip should face away from operator.)
3.Raise operator to approximate mounting position
and position chain over operator sprocket.
4.Raise or lower operator until the chain is taut (not
tight). Make sure the operator output shaft is parallel to door shaft and sprockets are aligned.When
in position, secure the operator to wall or mounting
bracket.
5. Install all remaining drive keys and set screws.
Apply “Loctite-262” or equivalent locking
compound to set screws.(Check that all mounting
hardware is tight, and the drive chains are taut.
WARNING
THIS FIREDOOR CONTROLLER WILL NONOTT CLOSE A
BALANCED DOOR IN THE ABSENCE OF AC
POWER.THE DOOR SYSTEM MUST BE ABLE TO
GENERATE A MINIMUM BACKDRIVING TORQUE OF
100 IN/LBS.,AT THE OPERATOR OUTPUT SHAFT.
STICKING OR BINDING DOORS MUST BE
REPAIRED. DOORS, DOOR SPRINGS, BRACKETS
AND THEIR HARDWARE MAY BE UNDER EXTREME
TENSION AND CAN CAUSE SERIOUS PERSONAL
INJURY. CALL A PROFESSIONAL DOOR SERVICEMAN TO MOVE OR ADJUST DOOR SPRINGS OR
HARDWARE.
6
ENTRAPMENT PROTECTION ACCESSORIES
SENSING EDGES
All types of sensing edges with an isolated normally
open (N.O.) output are compatible with your operator.
This includes pneumatic edge. If your door does not
have a bottom sensing edge and you wish to purchase one, contact the supplier of your operator.
The operator has been pre-wired to accept connection of a reversing edge device. Connect the normally
open contacts to terminals J2-5 and J2-6 on the PCB
Board. The auxiliary limit switch will de-activate the
safety device during the last few inches of the door's
downward travel.
NOTE: F or wiring connections refer to wiring diagram
supplied with operator.
Important Notes:
a) Proceed with Limit Switch Adjustments before
making any sensing edge wiring connections to
operator as described below.
b) Electrician must hardwire the junction box to the
operator electrical box in accordance with local
codes.
TAKE-UP REEL: Take-up reel should be installed 12”
above the top of the door.
COIL CORD: Connect operator end of coil cord to
junction box (not supplied) fastened to the wall
approximately halfway up the door opening.
LIMIT SWITCH ADJUSTMENT
MAKE SURE THE LIMIT NUTS ARE POSITIONED BETWEEN THE LIMIT SWITCH ACTUATORS BEFORE
PROCEEDING WITH ADJUSTMENTS. BE CERTAIN THAT DIP SWITCH #2 IS IN THE “OFF”POSITION (CDO
MODE) BEFORE MAKING ADJUSTMENTS.
1. To adjust limit nuts depress retaining plate to allow
nut to spin freely. After adjustment, release plate
and ensure it seats fully in slots of both nuts.
2. To increase door travel, spin nut away from actuator.To decrease door travel, spin limit nut toward
actuator.
3. Adjust open limit nut so that door will stop in open
position with the bottom of the door even with top
of door opening.
4. Repeat Steps 1 and 2 for close cycle. Adjust close
limit nut so that actuator is engaged as door fully
seats at the floor.
SAFETY
(Aux. Close) Limit Switch
SPARE
Limit Switch
(Shown as LEFT
Hand Unit)
WARNING
TO AVOID SERIOUS PERSONAL INJURY OR DEATH
FROM ELECTROCUTION, DISCONNECT ELECTRIC
POWER BEFORE MANUALLY MOVING LIMIT NUTS.
If other problems persist, call our toll-free number for
assistance - 1-800-528-2806
Actuator
RPM Board
Depress Plate
OPEN Limit Switch
7
Rotator Cup
CLOSE Limit Switch
NOTICE:
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant
to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications .Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the
interference at his own expense.
INSTALLATION MODE
The motor operator installs as a standard commercial operator with standard wiring functionalty. Once installation is completed and all alarm devices are connected, and tested,
the operator is then switched (DIP switch 2) to Fire Door Mode. Upon completion of installation,the units functionality should be chec ked by activ ating the key test station.If for any
reason your unit does not respond as described in this manual, check that you have read
and followed all installation and operating instructions. If difficulties persist contact the
Lift-Master technical hotline.
1-800-528-2806.
WARNING
IT IS THE END USERS SOLE RESPONSIBILITY TO CHECK
THAT ALL SYSTEMS ARE INSTALLED AND FUNCTIONAL.
THE MOTOR OPERATOR MUST BE SWITCHED TO THE
“FIREDOOR” MODE TO ENABLE ALL ALARM, AND WARNING SYSTEMS. DIP SWITCH #2 MUST BE SWITCHED TO
THE “ON” POSITION TO ENABLE THE “FIREDOOR” MODE.
FAILURE TO DO SO, COULD RESULT IN LOSS OF LIFE
AND PROPERTY.
Alarm Inputs:
Alarm Input #1: Used for electronic alarm devices such as smoke detection devices or similar
alarm systems.Devices may be N/O or N/C.Switchable using DIP Switch #3.This alarm will activate a motored closure of the door, and all sensing and control devices will remain active.
It is imperative that the alarm signal contact is maintained for a time period greater than the alarm
delay to close setting.I.E.If dip switch #1 is in the “OFF” position (10 seconds) the alar m system
must supply a “DRY” contact signal to ter minals J2-11 & J2-12 for a minimum of 12 seconds.
Alarm Input #2: Used for the ther mal sensors (electronic fusible links) or similar systems. (N.C.
state only) This alarm condition will activate a motored closure of the door, and all sensing
devices and control stations will be rendered inactive. EXCEPT THE SAFETY EDGE.This alarm
will override any other alarm condition or input.
8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.