Lifebreath RNC155, RNC20, RNC10, RNC120D, RNC5-TPD User Manual

...
TI-RNC
0108
Residential Heat Recovery Ventilators (HRV)
Manufactured with
2 Speed RNC Electronics
Installation Instructions for Heat Recovery Ventilators with 2 Speed RNC Electronics
RNC Series
Models
RNC155
RNC200
RNC120D
RNC5-TPD
Introduction.........................................................................2
Engineering Data - RNC95 .............................................3-4
Engineering Data - RNC155...............................................5
Engineering Data - RNC200...............................................6
Engineering Data - RNC10.................................................7
Engineering Data - RNC20.................................................8
Engineering Data - RNC5-TPD..........................................9
Engineering Data - RNC120D ....................................10-11
Remote Control Devices...................................................12
Locating and Suspending the HRV ..................................13
Locating and Suspending the RNC120D..........................14
Drain Connection..............................................................15
Installation Methods .........................................................16
Simplified Installation ......................................................17
Partially Dedicated Installation.........................................18
Fully Dedicated Installation..............................................19
Grilles and Weatherhoods.................................................20
Electrical ...........................................................................21
Changing OFF to Standby/
Increasing Low Speed to Medium....................................21
Mode DIP Switch Settings................................................21
Wiring the Controls ..........................................................22
Defrost Operation .............................................................23
Defrost Cycle DIP Switch Settings...................................23
Air Flow Balancing .....................................................24-27
Interlocking HRV Operation to an
Air Handler/Furnace Blower ............................................28
Wiring Diagrams .........................................................29-31
Troubleshooting................................................................32
Maintenance......................................................................33
The Lifebreath HRV (Heat Recovery Ventilator) is designed to introduce fresh outdoor air into a building while exhausting an equal amount of stale indoor air.
During the heating season, heat energy from the stale exhausting air is transferred to the fresh, incoming air via Lifebreath's patented aluminum core.
During the air conditioning season, the HRV will help cool the incoming fresh air with the cooler stale exhausting air.
RNC electronics offers standard 2-speed operation of low/high. There is also an installer selectable 2-speed operation of medium low/high (refer to "Increasing Low Speed to Medium Low" in this manual).
The RNC circuit board also includes an interlock relay which is used to Interlock the HRV to an Air Handler/Furnace. Refer to "Interlocking HRV Operation to an Air Handler/Furnace Blower" in this manual.
We recommend using one of the Optional Main Controls (refer to "Remote Control Devices" in this manual) for normal operation.
2
Table of Contents Introduction
RNC Electronics
Leave this Manual for the Homeowner
TO BE COMPLETED BY CONTRACTOR AFTER INSTALLATION
Installing Contractor _________________________________________Telephone / Contact _____________________
Serial Number______________________________________________Installation Date ________________________
Model _________________________________________________________________________________________
IMPORTANT
Please read this manual before
installing the HRV
(Heat Recovery Ventilator).
Before installation, careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipment, i.e. a forced air furnace or air handler, operating at a higher static. After installation, the compatibility of the two pieces of equipment must be confirmed by measuring the airflows of the HRV (Heat Recovery Ventilator) by using the balancing procedure found in this manual. NEVER install a ventilator in a situation where its normal operation, lack of operation or partial failure may result in the backdrafting or improper functioning of vented combustion equipment.
NOTE
Due to ongoing research and product development, specifications, ratings and dimensions are subject to change without notice.
CAUTION
3
SP-RNC95
DIMENSIONS RNC95
inches (mm)
All units conform to CSA and UL standards
Date: _______________________________________________
Tag: __________________________Qty:__________________
Project: _____________________________________________
Engineer:____________________________________________
Contractor: __________________________________________
Supplier: ____________________________________________
Quote#: _____________________________________________
Submitted by: ________________________________________
*Sensible Efficiency – thermal **Latent Efficiency – moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency – takes into account all power inputs
Performance (HVI certified)
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 76 (36)
@ 0.2" (50 Pa) 73 (34)
@ 0.3" (75 Pa) 70 (33)
@ 0.4" (100 Pa) 66 (31)
@ 0.5" (125 Pa) 60 (29)
Max. Temperature Recovery 88%
Sensible Effectiveness @ 60 cfm (28 L/s) 32°F (0°C) 88%
*Sensible Efficiency @ 60 cfm (28 L/s) 32°F (0°C) 75%
*Sensible Efficiency @ 61 cfm (29 L/s) -13°F (-25°C) 68%
VAC @ 60HZ 120
WATTS / Low speed. 60
WATTS / High speed 150
Amp rating 0.9
5 - High Speed
Engineering Data - HRV Model RNC95
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor. 2 speed fan operation.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of the cabinet designed to accept PVC reinforced polyester straps that are supplied with the unit.
DEFROST
Recirculating defrost system.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD.
WEIGHT 52 lbs. (23.6 kg) Shipping Weight 56 lbs. (25.4 kg)
CONTROLS - HRV System Control
HRV defaults to LOW SPEED when plugged in. HIGH SPEED option is accessible by connecting remote controls to designated terminals inside electrical box of HRV.
Standard LOW SPEED SETTING can be increased to medium low. Off (Standby)/Low or OFF/HIGH speed operation is also available.
OPTIONAL MAIN CONTROLS (only one main control can be installed on the system) 99-116 Dehumidistat Ventilation Control - Dehumidistat Dial, ON/OFF Switch and
LOW/HIGH Switch (3 wire) 20 gauge wire (min.) 100' length (max.)
99-2040 20/40 ON/OFF Dehumidistat - Dehumidistat Dial, ON/OFF Switch and 20/40 Switch.
The 20/40 Switch will toggle from continuous low speed ventilation to intermittent low speed ventilation of 20 minutes fan ON and 40 minutes fan OFF. (4 wire) 20 gauge wire (min.) 100' length (max.)
99-RECIRC Recirculation Control - Dehumidistat Dial, ON/OFF Switch and Recirculation Switch.
The Recirculation Switch will toggle from continuous low speed ventilation to continuous low speed recirculation. (4 wire) 20 gauge wire (min.) 100' length (max.)
99-130 Remote Dehumidistat - Dehumidistat Dial only. (2 wire) 20 gauge wire (min.) 100'
length (max.)
OPTIONAL TIMERS
99-132 20 Minute Fan Timer - initiates high speed ventilation for 20 minutes. (3 wire) 20 gauge
wire (min.) 100’ length
99-104 Digital Electronic Timer- initiates high speed ventilation for 20, 40 or 60 minutes, (3
wire) 20 gauge wire (min.) 100' length
99-101 60 Minute Crank Timer - initiates high speed ventilation for up to 60 minutes, (2 wire)
20 gauge wire (min.) 100' length (max.)
WARRANTY
Units carry a lifetime warranty on the heat recovery core and a 5 year replacement parts warranty.
80
5
75
70
65
Air Flow (c fm)
60
55
50
0 0.10.20.30.40.50.6
Static Pressure (in w.g.)
24.5"
18.5"
(470 mm)
(622 mm)
FRONT TOP
Heat Recovery
Drain Pan
Drain spout
side mounting of
EXHAUST return port
6" round collar
converted to oval
Removable
Core
knockout for
minimum
18 inches (459 mm)
required for
service access
SIDE
Hanging
straps (4)
16"
(406 mm)
Threaded inserts (4) at corners
SUPPLY
Fresh air
from outside
5" round collar
SUPPLY
Fresh air
to building
6" round
(conv. to oval)
collar
18.5"
(470 mm)
EXHAUST
Stale Air
to outside
5" round collar
EXHAUST
Return air
from building
Choice of port location
Knockouts on top and side of unit (use 1 only) 6" round (conv. to oval)
collar supplied
4
RNC95 Specifications
The RNC95 HRV (Heat Recovery Ventilator) has been designed to allow the installer to choose between two possible positions on the cabinet for the Stale Air Exhaust (from building) port. Illustrations in this manual show standard (side mounted) port location. The same specifications apply to both RNC95 setups, regardless of which port position is selected.
Variable Port Location / Installation (Model RNC95 only)
The exhaust return port collar is not factory installed. Installer may choose either side mounted or alternate top mounted port by simply removing one of the two knock-out plates and attaching a port collar (supplied). To remove knock-out plate, insert a utility knife into the knock-out slits and trace them completely to puncture protective film underneath. Then, cut the solid tabs between the slits, using tin snips or side cutters, and remove the knock-out plate. If any protective film still blocks the opening, remove it now.
In order to make the RNC95 as space efficient as possible, the INDOOR supply and return ports are converted from round to oval shape. Overall size of the port remains the same. Simply bend a standard duct fitting to the correct shape, and attach to the oval port using the same method as for a round port.
RNC95 Air Flow
Stale air enters the FRONT RIGHT side port. The air will pass down the front half of the core, then up the back half of the core and out the RIGHT REAR port.
Fresh outdoor air will enter the LEFT REAR port and pass down the back half of the core. It will then pass up the front half of the core, and out the LEFT FRONT port.
SIDE MOUNTED PORT TOP MOUNTED PORT
standard location alternate location
Round port bent to oval
Port Configuration and Airflow Model RNC95
5
Engineering Data - HRV Model RNC155
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two air streams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor. 2 speed fan operation.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit.
DEFROST
Recirculating damper defrost system.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections two - 1/2" (12mm) OD.
WEIGHT 71 lbs. (32.5 kg) SHIPPING WEIGHT 73 lbs. (33.5 kg)
CONTROLS - HRV System Control
HRV defaults to LOW SPEED when plugged in. HIGH SPEED option is accessible by connecting remote controls to designated terminals inside electrical box of HRV.
Standard LOW SPEED SETTING can be increased to medium low. Off (Standby)/Low or OFF/HIGH speed operation is also available.
OPTIONAL MAIN CONTROLS (only one main control can be installed on the system)
99-116 Dehumidistat Ventilation Control - Dehumidistat Dial, ON/OFF Switch and
LOW/HIGH Switch (3 wire) 20 gauge wire (min.) 100' length (max.)
99-2040 20/40 ON/OFF Dehumidistat - Dehumidistat Dial, ON/OFF Switch and 20/40 Switch.
The 20/40 Switch will toggle from continuous low speed ventilation to intermittent low speed ventilation of 20 minutes fan ON and 40 minutes fan OFF. (4 wire) 20 gauge wire (min.) 100' length (max.)
99-RECIRC Recirculation Control - Dehumidistat Dial, ON/OFF Switch and Recirculation Switch.
The Recirculation Switch will toggle from continuous low speed ventilation to continuous low speed recirculation. (4 wire) 20 gauge wire (min.) 100' length (max.)
99-130 Remote Dehumidistat - Dehumidistat Dial only. (2 wire) 20 gauge wire (min.) 100'
length (max.)
OPTIONAL TIMERS
99-132 20 Minute Fan Timer - initiates high speed ventilation for 20 minutes. (3 wire) 20 gauge
wire (min.) 100’ length
99-104 Digital Electronic Timer- initiates high speed ventilation for 20, 40 or 60 minutes, (3
wire) 20 gauge wire (min.) 100' length
99-101 60 Minute Crank Timer - initiates high speed ventilation for up to 60 minutes, (2 wire)
20 gauge wire (min.) 100' length (max.)
WARRANTY
Units carry a lifetime warranty on the heat recovery core and a 5 year replacement parts warranty.
DIMENSIONS RNC155
inches (mm)
*Sensible Efficiency – thermal **Latent Efficiency – moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency – takes into account all power inputs
Performance (HVI certified)
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 150 (71)
@ 0.2" (50 Pa) 146 (69)
@ 0.3" (75 Pa) 134 (63)
@ 0.4" (100 Pa) 121 (57)
@ 0.5" (125 Pa) 106 (50)
@ 0.6" (150 Pa) 92 (43)
Max. Temperature Recovery 78%
Sensible Effectiveness @ 65 cfm (31 L/s) 32°F (0°C) 76%
*Sensible Efficiency @ 65 cfm (31 L/s) 32°F (0°C) 64%
*Sensible Efficiency @ 68 cfm (32 L/s) -13°F (-25°C) 66%
VAC @ 60HZ 120
WATTS / Low speed. 49
WATTS / High speed 120
Amp rating 1.4
SP-RNC155
Date: _______________________________________________
Tag: __________________________Qty:__________________
Project: _____________________________________________
Engineer:____________________________________________
Contractor: __________________________________________
Supplier: ____________________________________________
Quote#: _____________________________________________
Submitted by: ________________________________________
All units conform to CSA and UL standards
FRESH AIR
FROM OUTSIDE
RECIRCULATING
DEFROST
DAMP ER
CORE
FILTERS
STALE AIR
FROM INSIDE
BLOWERS
MOTOR
19"
(483)
160
3
140
120
100
80
Air Flow (cfm)
2
60
1
40
20
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
Static Pres sur e (in w.g. )
*NOTE: Front clearance of 25 inches (635 mm) is recommended for servicing unit.
3 - High Speed *2 - Medium Low Speed *1 - Low speed
* Manufacturers Dat a
STALE AIR
TO OUTSIDE
CONDENSATE DRAINS
33 5/8"
(850mm)
BALANCING DAMPER
FRESH AIR
TO INSIDE
14 3/4"
(375)
*All Duct Connections 6" (150mm)
6
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two air streams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor. 2 speed fan operation.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit.
DEFROST
Recirculating damper defrost system.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections two - 1/2" (12mm) OD.
WEIGHT 71 lbs. (32.5 kg) SHIPPING WEIGHT 73 lbs. (33.5 kg)
CONTROLS - HRV System Control
HRV defaults to LOW SPEED when plugged in. HIGH SPEED option is accessible by connecting remote controls to designated terminals inside electrical box of HRV.
Standard LOW SPEED SETTING can be increased to medium low. Off (Standby)/Low or OFF/HIGH speed operation is also available.
OPTIONAL MAIN CONTROLS (only one main control can be installed on the system) 99-116 Dehumidistat Ventilation Control - Dehumidistat Dial, ON/OFF Switch and LOW/HIGH
Switch (3 wire) 20 gauge wire (min.) 100' length (max.)
99-2040 20/40 ON/OFF Dehumidistat - Dehumidistat Dial, ON/OFF Switch and 20/40 Switch.
The 20/40 Switch will toggle from continuous low speed ventilation to intermittent low speed ventilation of 20 minutes fan ON and 40 minutes fan OFF. (4 wire) 20 gauge wire (min.) 100' length (max.)
99-RECIRC Recirculation Control - Dehumidistat Dial, ON/OFF Switch and Recirculation Switch.
The Recirculation Switch will toggle from continuous low speed ventilation to continuous low speed recirculation. (4 wire) 20 gauge wire (min.) 100' length (max.)
99-130 Remote Dehumidistat - Dehumidistat Dial only. (2 wire) 20 gauge wire (min.) 100' length
(max.)
OPTIONAL TIMERS
99-132 20 Minute Fan Timer - initiates high speed ventilation for 20 minutes. (3 wire) 20 gauge
wire (min.) 100’ length
99-104 Digital Electronic Timer- initiates high speed ventilation for 20, 40 or 60 minutes, (3
wire) 20 gauge wire (min.) 100' length
99-101 60 Minute Crank Timer - initiates high speed ventilation for up to 60 minutes, (2 wire)
20 gauge wire (min.) 100' length (max.)
WARRANTY
Units carry a lifetime warranty on the heat recovery core and a 5 year replacement parts warranty.
Dimensions RNC200
inches (mm)
Performance (HVI certified)
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 207 (97) @ 0.2" (50 Pa) 200 (94) @ 0.3" (75 Pa) 184 (87) @ 0.4" (100 Pa) 171 (80) @ 0.5" (125 Pa) 152 (71) @ 0.6" (150 Pa) 130 (61) @ 0.7" (175 Pa) 116 (55) @ 0.8" (200 Pa) 86 (40)
Max. Temperature Recovery 74%
Sensible Effectiveness @ 66 cfm (31 L/s) 32°F (0°C) 74%
*Sensible Efficiency @ 66 cfm (31 L/s) 32°F (0°C) 64%
*Sensible Efficiency @ 109 cfm (51 L/s) -13°F (-25°C) 62%
VAC @ 60HZ 120
WATTS / Low speed. 87
WATTS / High speed 164
Amp rating 1.4
*Sensible Efficiency – thermal **Latent Efficiency – moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency – takes into account all power inputs
Engineering Data - HRV Model RNC200
Date: _______________________________________________
Tag: __________________________Qty:__________________
Project: _____________________________________________
Engineer:____________________________________________
Contractor: __________________________________________
Supplier: ____________________________________________
Quote#: _____________________________________________
Submitted by: ________________________________________
All units conform to CSA and UL standards
SP-RNC200
FRESH AIR
FROM OUTSIDE
RECIRCULATING
DEFROST
DAMPER
CORE
STALE AIR
TO OUTSIDE
CONDENSATE DRAINS
FILTERS
33 5/8"
(850 mm)
STALE AIR
FROM INSIDE
BLOWERS
MOTOR
FRESH AIR
TO INSIDE
BALANCING DAMPER
19"
(483 mm)
220
3
200
180
160
140
120
2
Air Flow (cfm)
100
1
80
60
40
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
14 3/4"
(375 mm)
Static Pressure (in w.g.)
*NOTE: Front clearance of 25 inches (635 mm) is recommended for servicing unit.
*All Duct Connections 6" (150 mm)
3 - High Speed *2 - Medium Low Speed *1 - Low speed
* Manufacturers Dat a
7
All units conform to CSA and UL standards
Engineering Data - HRV Model RNC10
Date: _______________________________________________
Tag: __________________________Qty:__________________
Project: _____________________________________________
Engineer:____________________________________________
Contractor: __________________________________________
Supplier: ____________________________________________
Quote#: _____________________________________________
Submitted by: ________________________________________
SP-RNC10
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two air streams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor. 2 speed fan operation.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four PVC reinforced polyester straps that are supplied with the unit.
DEFROST
Damper defrost system; defrosts automatically as the outdoor temperature falls.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections two - 1/2" (12mm) OD.
WEIGHT 63 lbs. (28.7 kg) SHIPPING WEIGHT 67 lbs. (30.4 kg)
CONTROLS - HRV System Control
HRV defaults to LOW SPEED when plugged in. HIGH SPEED option is accessible by connecting remote controls to designated terminals inside electrical box of HRV.
Standard LOW SPEED SETTING can be increased to medium low. Off (Standby)/Low or OFF/HIGH speed operation is also available.
OPTIONAL MAIN CONTROLS (only one main control can be installed on the system) 99-116 Dehumidistat Ventilation Control - Dehumidistat Dial, ON/OFF Switch and LOW/HIGH
Switch (3 wire) 20 gauge wire (min.) 100' length (max.)
99-2040 20/40 ON/OFF Dehumidistat - Dehumidistat Dial, ON/OFF Switch and 20/40 Switch.
The 20/40 Switch will toggle from continuous low speed ventilation to intermittent low speed ventilation of 20 minutes fan ON and 40 minutes fan OFF. (4 wire) 20 gauge wire (min.) 100' length (max.)
99-130 Remote Dehumidistat - Dehumidistat Dial only. (2 wire) 20 gauge wire (min.) 100' length
(max.)
OPTIONAL TIMERS
99-132 20 Minute Fan Timer - initiates high speed ventilation for 20 minutes. (3 wire) 20 gauge
wire (min.) 100’ length
99-104 Digital Electronic Timer- initiates high speed ventilation for 20, 40 or 60 minutes, (3
wire) 20 gauge wire (min.) 100' length
99-101 60 Minute Crank Timer - initiates high speed ventilation for up to 60 minutes, (2 wire)
20 gauge wire (min.) 100' length (max.)
WARRANTY
Units carry a lifetime warranty on the heat recovery core and a 5 year replacement parts warranty.
*Sensible Efficiency - thermal **Latent Efficiency - moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency - takes into account all power inputs
Dimensions RNC10
inches (mm)
Performance (HVI certified)
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 177 (83)
@ 0.2" (50 Pa) 164 (77)
@ 0.3" (75 Pa) 156 (73)
@ 0.4" (100 Pa) 143 (67)
@ 0.5" (125 Pa) 123 (58)
@ 0.6" (150 Pa) 100 (47)
@ 0.7" (175 Pa) 38 (18)
Max. Temperature Recovery 78%
Sensible Effectiveness @ 67 cfm (32 L/s) 32°F (0°C) 76%
*Sensible Efficiency @ 67 cfm (32 L/s) 32°F (0°C) 66%
*Sensible Efficiency @ 68 cfm (32 L/s) -13°F (-25°C) 60%
VAC @ 60HZ 120
WATTS / Low speed. 63
WATTS / High speed 173
Amp rating 1.4
3 - High Speed *2 - Medium Low Speed *1 - Low speed
200
180
3
160
140
120
2
100
Air Flow (cfm)
1
80
60
40
20
0 0 .1 0.2 0.3 0 .4 0 .5 0.6 0.7 0 .8
Static Pressure (in w.g.)
*Manufacturer’s Data
FRESH AIR
FROM OUTSIDE
DEFROST
DAMPER
DEFROST
PORT
FILTERS
STALE AIR
FROM INSIDE
CONDENSATE DRAINS
33-5/8"
BALANCING DAMPER
STALE AIR
TO OUTSIDE
BLOWERS
FRESH AIR
TO INSIDE
*NOTE:
Front clearance of 25 inches (635 mm) is recommended for servicing unit.
14 3/4"
(375)
19"
(483)
*All Duct
Connections 6"(150mm)
8
All units conform to CSA and UL standards
Engineering Data - HRV Model RNC20
Date: _______________________________________________
Tag: __________________________Qty:__________________
Project: _____________________________________________
Engineer:____________________________________________
Contractor: __________________________________________
Supplier: ____________________________________________
Quote#: _____________________________________________
Submitted by: ________________________________________
SP-RNC20
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two air streams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor. 2 speed fan operation.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four PVC reinforced polyester straps that are supplied with the unit.
DEFROST
Damper defrost system; defrosts automatically as the outdoor temperature falls.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections two - 1/2" (12mm) OD.
WEIGHT 63 lbs. (28.7 kg) SHIPPING WEIGHT 67 lbs. (30.4 kg)
CONTROLS - HRV System Control
HRV defaults to LOW SPEED when plugged in. HIGH SPEED option is accessible by connecting remote controls to designated terminals inside electrical box of HRV.
Standard LOW SPEED SETTING can be increased to medium low. Off (Standby)/Low or OFF/HIGH speed operation is also available.
OPTIONAL MAIN CONTROLS (only one main control can be installed on the system) 99-116 Dehumidistat Ventilation Control - Dehumidistat Dial, ON/OFF Switch and LOW/HIGH
Switch (3 wire) 20 gauge wire (min.) 100' length (max.)
99-RECIRC Recirculation Control - Dehumidistat Dial, ON/OFF Switch and Recirculation Switch.
The Recirculation Switch will toggle from continuous low speed ventilation to continuous low speed recirculation. (4 wire) 20 gauge wire (min.) 100' length (max.)
99-130 Remote Dehumidistat - Dehumidistat Dial only. (2 wire) 20 gauge wire (min.) 100' length
(max.)
OPTIONAL TIMERS
99-132 20 Minute Fan Timer - initiates high speed ventilation for 20 minutes. (3 wire) 20 gauge
wire (min.) 100’ length
99-104 Digital Electronic Timer- initiates high speed ventilation for 20, 40 or 60 minutes, (3
wire) 20 gauge wire (min.) 100' length
99-101 60 Minute Crank Timer - initiates high speed ventilation for up to 60 minutes, (2 wire)
20 gauge wire (min.) 100' length (max.)
WARRANTY
Units carry a lifetime warranty on the heat recovery core and a 5 year replacement parts warranty.
Dimensions RNC20
inches (mm)
*Sensible Efficiency - thermal **Latent Efficiency - moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency - takes into account all power inputs
Performance (HVI certified)
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 214 (101)
@ 0.2" (50 Pa) 206 (97)
@ 0.3" (75 Pa) 193 (91)
@ 0.4" (100 Pa) 184 (87)
@ 0.5" (125 Pa) 170 (80)
@ 0.6" (150 Pa) 155 (73)
@ 0.7" (175 Pa) 137 (65)
Max. Temperature Recovery 69%
Sensible Effectiveness @ 119 cfm (56 L/s) 32°F (0°C) 67%
*Sensible Efficiency @ 119 cfm (56 L/s) 32°F (0°C) 60%
*Sensible Efficiency @ 117 cfm (55 L/s) -13°F (-25°C) 60%
VAC @ 60HZ 120
WATTS / Low speed. 70
WATTS / High speed 182
Amp rating 1.4
1
2
3
3 - High Speed *2 - Medium Low Speed *1 - Low speed
240
220
200
180
160
140
120
Air Flow (c fm)
100
80
60
40
20
0 0 .1 0.2 0.3 0 .4 0 .5 0.6 0.7 0 .8
Static Pressure (in w.g.)
*Manufacturer’s data
FRESH AIR
FROM OUTSIDE
DEFROST
DAMPER
DEFROST
PORT
FILTERS
STALE AIR
FROM INSIDE
33-5/8"
CONDENSATE DRAINS
STALE AIR
TO OUTSIDE
BLOWERS
FRESH AIR
TO INSIDE
BALANCING DAMPER
*NOTE:
Front clearance of 25 inches (635 mm) is recommended for servicing unit.
14 3/4"
(375)
19"
(483)
*All Duct
Connections 6"(150mm)
9
All units conform to CSA and UL standards
Engineering Data - HRV Model RNC5-TPD
Date: _______________________________________________
Tag: __________________________Qty:__________________
Project: _____________________________________________
Engineer:____________________________________________
Contractor: __________________________________________
Supplier: ____________________________________________
Quote#: _____________________________________________
Submitted by: ________________________________________
SP-RNC5-TPD
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has an independent motorized impeller. 2 speed fan operation.
FILTERS
Washable air filters in exhaust and supply air streams.
DEFROST
Recirculating damper defrost system.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections 1/2" (12 mm) OD.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit.
DUCT CONNECTIONS
4 - 5” (127 mm) duct connections.
WEIGHT 61 lbs. (28 kg) SHIPPING WEIGHT 64 lbs. (29 kg)
CONTROLS- HRV System Control
HRV defaults to user selected speed from switch on top of cabinet when plugged in. HIGH SPEED option is accessible by connecting remote controls to designated terminals inside electrical box of HRV.
OFF(Standby)/LOW or OFF/HIGH speed operation is also available.
OPTIONAL MAIN CONTROLS (only one main control can be installed on the system) 99-116 Dehumidistat Ventilation Control - Dehumidistat Dial, ON/OFF Switch and
LOW/HIGH Switch (3 wire) 20 gauge wire (min.) 100' length (max.)
99-2040 20/40 ON/OFF Dehumidistat - Dehumidistat Dial, ON/OFF Switch and 20/40 Switch.
The 20/40 Switch will toggle from continuous low speed ventilation to intermittent low speed ventilation of 20 minutes fan ON and 40 minutes fan OFF. (4 wire) 20 gauge wire (min.) 100' length (max.)
99-RECIRC Recirculation Control - Dehumidistat Dial, ON/OFF Switch and Recirculation Switch.
The Recirculation Switch will toggle from continuous low speed ventilation to continuous low speed recirculation. (4 wire) 20 gauge wire (min.) 100' length (max.)
99-130 Remote Dehumidistat - Dehumidistat Dial only. (2 wire) 20 gauge wire (min.) 100'
length (max.)
OPTIONAL TIMERS
99-132 20 Minute Fan Timer - initiates high speed ventilation for 20 minutes. (3 wire) 20
gauge wire (min.) 100’ length
99-104 Digital Electronic Timer- initiates high speed ventilation for 20, 40 or 60 minutes, (3
wire) 20 gauge wire (min.) 100' length
99-101 60 Minute Crank Timer - initiates high speed ventilation for up to 60 minutes, (2 wire)
20 gauge wire (min.) 100' length (max.)
WARRANTY
Units carry a lifetime warranty on the heat recovery core and a 5 year replacement parts warranty.
1
2
3
0
20
40
60
80
100
120
140
160
180
0 0 .1 0.2 0.3 0.4 0.5 0.6 0.7 0 .8 0.9 1 1.1
Static Pressure (in w.g.)
Air Flow (cfm)
3 - High Speed *2 - Medium Low Speed *1 - Low speed
* Manufacturers Dat a
*Sensible Efficiency - thermal **Latent Efficiency - moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency - takes into account all power inputs
Performance (H.V.I. certified)
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 169 (80) @ 0.2" (50 Pa) 156 (73) @ 0.3" (75 Pa) 149 (70) @ 0.4" (100 Pa) 136 (64) @ 0.5" (125 Pa) 126 (59) @ 0.6" (150 Pa) 116 (54) @ 0.7" (175 Pa) 103 (48) @ 0.8" (200 Pa) 89 (42) @ 0.9" (225 Pa) 77 (36) @ 1.0" (250 Pa) 58 (27)
Max. Temperature Recovery 78%
Sensible Effectiveness @ 66 cfm (31 L/s) 32°F (0°C) 74%
*Sensible Efficiency @ 66 cfm (31 L/s) 32°F (0°C) 61%
*Sensible Efficiency @ 76 cfm (36 L/s) -13°F (-25°C) 63%
VAC @ 60HZ 120
WATTS / Low speed. 69
WATTS / High speed 147
Amp rating 1.7
Dimensions RNC5-TPD
inches (mm)
27”
(690 mm)
15”
(378 mm)
2-1/4”
(57 mm)
18-3/4”
(475 mm)
SPEED SELECTION SWITCH
10
All units conform to CSA and UL standards
Engineering Data - HRV Model RNC120D
Date: _______________________________________________
Tag: __________________________Qty:__________________
Project: _____________________________________________
Engineer:____________________________________________
Contractor: __________________________________________
Supplier: ____________________________________________
Quote#: _____________________________________________
Submitted by: ________________________________________
SP-RNC120D
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has an independent motorized impeller. 2 speed fan operation.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit.
DEFROST
Recirculating damper defrost system.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections- 1/2" (12 mm) OD.
DUCT CONNECTIONS
5” duct connections.
WEIGHT 42 lbs. (19 kg.) SHIPPING WEIGHT 45 lbs. (20.5 kg.) CONTROLS - HRV System Control
HRV defaults to LOW SPEED when plugged in. HIGH SPEED option is accessible by connecting remote controls to designated terminals inside electrical box of HRV.
Standard LOW SPEED SETTING can be increased to medium low. Off (Standby)/Low or OFF/HIGH speed operation is also available. OPTIONAL MAIN CONTROLS (only one main control can be installed on the system) 99-116 Dehumidistat Ventilation Control - Dehumidistat Dial, ON/OFF Switch and
LOW/HIGH Switch (3 wire) 20 gauge wire (min.) 100' length (max.)
99-2040 20/40 ON/OFF Dehumidistat - Dehumidistat Dial, ON/OFF Switch and 20/40 Switch.
The 20/40 Switch will toggle from continuous low speed ventilation to intermittent low speed ventilation of 20 minutes fan ON and 40 minutes fan OFF. (4 wire) 20 gauge wire (min.) 100' length (max.)
99-RECIRC Recirculation Control - Dehumidistat Dial, ON/OFF Switch and Recirculation Switch.
The Recirculation Switch will toggle from continuous low speed ventilation to continuous low speed recirculation. (4 wire) 20 gauge wire (min.) 100' length (max.)
99-130 Remote Dehumidistat - Dehumidistat Dial only. (2 wire) 20 gauge wire (min.) 100'
length (max.)
OPTIONAL TIMERS
99-132 20 Minute Fan Timer - initiates high speed ventilation for 20 minutes. (3 wire) 20 gauge
wire (min.) 100’ length
99-104 Digital Electronic Timer- initiates high speed ventilation for 20, 40 or 60 minutes, (3
wire) 20 gauge wire (min.) 100' length
99-101 60 Minute Crank Timer - initiates high speed ventilation for up to 60 minutes, (2 wire)
20 gauge wire (min.) 100' length (max.)
WARRANTY
Units carry a lifetime warranty on the heat recovery core and a 5 year replacement parts warranty.
*Sensible Efficiency - thermal **Latent Efficiency - moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency - takes into account all power inputs
Performance (HVI certified)
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 142 (67) @ 0.2" (50 Pa) 137 (64) @ 0.3" (75 Pa) 131 (62) @ 0.4" (100 Pa) 128 (60) @ 0.5" (125 Pa) 123 (58) @ 0.6" (150 Pa) 115 (54) @ 0.7" (175 Pa) 113 (53) @ 0.8" (200 Pa) 105 (49) @ 0.9" (225 Pa) 102 (48) @ 1.0" (250 Pa) 96 (45)
Max. Temperature Recovery 72%
Sensible Effectiveness @ 70 cfm (33 L/s) 32°F (0°C) 68%
*Sensible Efficiency @ 70 cfm (33 L/s) 32°F (0°C) 59%
*Sensible Efficiency @ 67 cfm (32 L/s) -13°F (-25°C) 56%
VAC @ 60HZ 120
WATTS / Low speed. 70
WATTS / High speed 160
Amp rating 1.5
3
2
1
3 - High Speed *2 - Medium Low Speed *1 - Low speed
* Manufacturers Dat a
Dimensions RNC120D
inches (mm)
All duct collars are 5” diameter (127 mm)
Front View (if mounting vertically) Bottom View (if mounting horizontally)
STALE AIR TO OUTSIDE
22”
(559 mm)
FRESH AIR FROM OUTSIDE
25 1/8”
(637 mm)
STALE AIR FROM BUILDING
FRESH AIR TO BUILDING
9 1/8”
(232 mm)
160
140
120
100
80
Air Flow (c fm)
60
40
20
0 0 .1 0.2 0.3 0.4 0.5 0.6 0.7 0 .8 0.9 1 1 .1 1.2 1.3
Static Pressure (in w.g.)
11
Engineering Data - HRV Model RNC120D
Option 1 - Horizontal Duct Configuration Dimensions inches
Option2-Vertical Duct Configuration Dimensions inches
The HRV can be installed horizontally or vertically as illustrated on the following pages. The unit should be suspended using the provided hanging straps. The unit must be level for proper
condensate drainage.
Sufficient clearance below the access door is required for servicing the air filters and core. A minimum of 25" (635mm) clearance is recommended so the door can be removed. Four PVC reinforced polyester hanging straps are provided for hanging the HRV.
STALE AIR TO OUTSIDE
22”
(559 mm)
BOTTOM VIEW FOR HORIZONTAL MOUNT
SERVICE CLEARANCE FROM BOTTOM
9-1/8”
(232 mm)
SIDE VIEW FOR HORIZONTAL MOUNT
FRESH AIR FROM OUTSIDE
25 1/8”
(637 mm)
OF UNIT IS MINIMUM 3’0”
STALE AIR FROM BUILDING
FRESH AIR TO BUILDING
STALE AIR TO OUTSIDE
ALL DUCT COLLARS ARE 5” DIAMETER
HANGING STRAPS
FRESH AIR FROM OUTSIDE
ACCESS DOOR
STALE AIR FROM BUILDING
Connect drain hose to spout located in door.
FRESH AIR TO BUILDING
STALE AIR TO OUTSIDE
22”
(559 mm)
SERVICE CLEARANCE FROM BOTTOM
9-1/8”
(232 mm)
FRESH AIR
FROM OUTSIDE
25 1/8”
SIDE VIEW FOR VERTICAL MOUNT
TOP VIEW FOR VERTICAL MOUNT
(637 mm)
OF UNIT IS MINIMUM 3’0”
STALE AIR TO OUTSIDE
STALE AIR FROM BUILDING
FRESH AIR TO BUILDING
ALL DUCT COLLARS ARE 5” (127 mm) DIAMETER
ACCESS DOOR
Connect drain hose to the two field installed
spouts located on the bottom of the unit.
HANGING STRAPS
FRESH AIR FROM OUTSIDE
STALE AIR FROM BUILDING
“L” BRACKETS
(not included)
May be installed if wall mounting is desired for the vertical installation.
FRESH AIR TO BUILDING