Lifebreath CAF-02-MB User Manual

Page 1
CAF-02-MB
0707
Hydronic Models with Built-in
Heat Recovery Ventilator (HRV)
MANUFACTURED WITH
AIRCOM ELECTRONICS
Operation, Sizing and Installation Manual
Models: CAF-U-S4A-24-P16(E16), CAF-D-S4A-24-P16(E16), CAF-H-S4A-24-P16(E16), CAF-U-L4A-36-P16(E16),
Page 2
2
Introduction.......................................................................3
Overview of the CAF........................................................3
Description and Purpose ..................................................4
Operation Heating/Cooling...............................................4
The Recovery Core ...........................................................5
Combo System Basic Principle.........................................6
Plumbing......................................................................7-13
Installation .................................................................14-16
Pitot Tube Air Flow Balancing..................................17-18
Function and Controls ...............................................19-20
Optional Remote Control Devices..................................21
Wiring the Controls.........................................................22
Aircom Relays ................................................................23
Service and Maintenance ................................................25
Troubleshooting.........................................................26-27
Model Number Nomenclature Breakdown.....................28
Specifications ............................................................29-37
System Commissioning ..................................................38
Work Sheets...............................................................39-44
Wiring Diagrams .......................................................45-46
Leave this manual for the homeowner!
Installing Contractor
Telephone / Contact
Serial Number
Installation Date Model
TO BE COMPLETED BY CONTRACTOR AFTER INSTALLATION
CAUTION
Table of Contents
It is always important to assess how the operation of any HRV/ERV may interact with vented combustion equipment (ie. Gas Furnaces, Oil Furnaces, Wood Stoves, etc.).
CAUTION
Never install an HRV/ERV in a situation where its normal operation, lack of operation or partial failure may result in the backdrafting or improper functioning of vented combustion equipment!
Page 3
3
You will notice that the heated air in your home feels more comfortable than air heated by a conventional furnace. One reason for this is that LIFEBREATH's hydronically heated air is uniform and temperate... no short blasts of hot air or hot and cold temperature spikes. The air flowing from your hot air vents will not feel as hot to the touch as air from a conventional furnace.
With a high efficiency, adequately sized natural gas, propane or oil hot water heater/boiler, you will always have plenty of hot water for showers and baths, washing dishes and clothes, and all other normal domestic hot water needs. If there is an unusually high demand for hot water, such as filling a large hot tub, then all you need to do is allow more time for the task so the water heater/boiler can keep up to its job of providing hot water for the heating system as well as other household uses.
Once it is correctly installed, safety will never be an issue with your LIFEBREATH furnace. No flames, fumes or flue gases to be concerned about. Your domestic hot water heater/boiler now provides the heat source for your furnace.
This Operation and Installation Guide will help you learn about your LIFEBREATH Clean Air Furnace quickly and easily. The table of contents will show you where to find information on every feature of this unit along with easy to understand operating instructions. If, however, you do encounter a question that is not covered in this Guide you should call the LIFEBREATH dealer who installed your furnace. Chances are that he will be able to give you a satis­factory answer but if he is unable to do so then we invite you to contact us directly.
Nutech Brands Inc.
Introduction
Overview of the Clean Air Furnace
Hydronic Coil and Pump Compartment
Recovery Core and Ventilation Compartment
Aircom Electronics and Fan Compartment
Page 4
4
IMPORTANT NOTE
The purpose of this manual is to act as an installation guide only for the LIFEBREATH Clean Air Furnace. Manufacturers' instructions for other components, such as the waterheater/boiler, must be followed.
All national and local code requirements must be met when installing a LIFEBREATH Clean Air Furnace. Be sure to consult the proper authorities.
Note: Temperatures greater than 130°F (54°C) pose a seri-
ous risk of scalding individuals running domestic hot water for potable use.
This appliance complies with IAS Canada Inc. Requirement CR95-003, Additional Require-ments for Fan Coil Units for use with Potable Water Heaters.
All piping and components connected to this appliance shall be suitable for use with potable water.
Toxic chemicals, such as used for boiler treatment, shall not be introduced into the potable water heater system.
When using this system and the hot water for space heating is set to a higher temperature than for other uses, an anti­scald valve shall be used to ensure water for common use is reduced in temperature to minimize a scalding hazard.
Combining two or more end uses such as space heating and the heating of domestic hot water in a single system has the potential to increase efficiency and reduce overall capital costs. However, the proper design, installation, and com­missioning of these systems are critical if these advantages are to be realized.
This manual provides a guideline of good engineering prac­tice in the design, installation and commissioning of Integrated Combo Systems. The guidelines in the manual are designed for residential forced warm air Integrated Combo Systems which utilize domestic water heaters or boilers and the LIFEBREATH furnace. Heating and cooling loads shall be calculated in accordance with recognized Residential Heat Loss and Heat Gain Calculation methods. Duct design shall comply with recognized Residential Air System Design methods. This manual provides worksheets to be used for the purpose of sizing residential water heaters and the combo furnace.
The LIFEBREATH Clean Air Furnace is a volume ventila­tion system. Use the optional Lifebreath Bathroom Exhaust System Kit (Part 99-CAF-BESKIT) if you wish to exhaust from specific locations such as bathrooms.
Description and Purpose
Operation Heating/Cooling
When the room thermostat calls for heat, it activates a cir­culation pump located inside the Clean Air Furnace. This pump delivers hot water from the water heater, through the furnace coil and back to the water tank. Simultaneously, the furnace blower switches on to high speed and will start cir­culating air across the coil, which picks up heat and delivers it to the rest of your home.
Once the thermostat's temperature is reached the pump will shut off, and the blower will return to its pre-set speed or off.
Note: When the furnace blower is left running on low speed the air in the home circulates continuously. When the heat is called for the blower will automatically switch to a higher speed. After the required hot air has been delivered the blower will switch back to low speed.
When the thermostat calls for cooling (evaporator coil and condensing unit required), the furnace blower activates to high speed and the outdoor condenser unit is energized. After the thermostat temperature is reached, the condensing unit will shut off and the blower will return to its preset speed or off.
Ventilation
The heat recovery ventilation (HRV) portion of the Clean Air Furnace, is automatic. Once set, a desired amount of fresh air will be drawn into the home while the furnace blower is activated.
To reduce humidity, increased ventilation may be required during heating season. An optional remote dehumidistat can be installed. The dehumidistat will increase the speed of the furnace blower to high and will return to its original setting when humidity levels decrease. Your dehumidistat must be switched off during warmer months. A quality humidifier should be added if you wish to increase winter humidity levels
Typically the air flow for ventilation will be set to 50 ­70cfm, for low speed furnace operation, and 100 - 150cfm at high speed. The pleated furnace filter should be checked regularly and replaced as needed. The HRV filter should be washed twice a year or more often if needed.
Off Season Circulation Timer
All models are equipped with a circulation timer. It is nor­mal operation for these models to automatically run the circulation pump intermittently for a short period of time.
Page 5
5
HRV - Aluminum Core
A Heat Recovery Ventilator (HRV) is designed to provide fresh air into a building while exhausting an equal amount of stale air. During the winter months, the incoming cold fresh air is warmed by utilizing the heat recovered from the stale air before it is exhausted to the outdoors. During sum­mer months when the indoor space is air conditioned, the Heat Recovery Ventilator will help in cooling the incoming fresh air with the stale air that is being exhausted.
ERV - Enthalpic Paper Core
An Energy Recovery Ventilator (ERV) is designed to pro­vide fresh air into a building while exhausting an equal amount of stale air. An ERV is designed for use in warm humid areas with heavy air conditioning use. The ERV will transfer both sensible and latent heat from the incoming fresh air to the outgoing stale air thereby reducing the load (due to ventilation) on the air conditioning system.
The Recovery Core
e
Stale Air from Building
ATTENTION
The ERV - Enthalpic Core is not suitable for climates where the outdoor temperature drops below -4°C (25°F).
Fresh Outdoor Air
Fresh Air to Building
Stale Air to Outsid
Page 6
6
Closed Loop System
A system becomes closed when a Check Valve or a back­flow prevention valve is installed in the cold water piping upstream of the water heater.
A check valve will prevent water being relieved into the cold water system due to pressure created when water is heated in the water heater.
Combo System Basic Principles
Open and Closed Systems
Open and Closed systems both deliver hot water and space heating.
Water systems that incorporate a pressure tank (i.e. well systems) are normally Open Systems and most municipal water systems are Closed Systems.
Drain Valve
A drain valve is required to allow the heating loop to be drained for service or repair and to remove air from the heating loop when commissioning a system. The drain valve should be near the low point of the return piping sys­tem to be near the water heater. Ball, Globe or Gate Valves are suitable for drain valves.
IMPORTANT
Refer to local codes, local bylaws and installation manuals supplied with water heater before starting any installation work.
Conventional Cooling (Not available through Nutech)
This Check Valve minimizes Thermo-Siphoning. Thermo Siphoning is the cold water backflowing through the heating loop when domestic hot water is called for.
ATTENTION
Check valves should always be installed in a vertical rise with the flow of water shown.
COLD WATER INLET
EXPANSION TANK OR OTHER MEANS
(WHEN REQUIRED)
CHECK
VALV E
VALV E
(shut off)
WATER HEATER
DOMESTIC HOT WATER
ANTI-SCALD VALVE
(WHEN REQUIRED)
VALV E
(shut off)
VALV E
(shut off)
VALV E
(balancing)
CHECK
VALV E
HEATING COIL
HRV/ERV CORE
DRAIN VALV E
BLOWER
SUPPLY AIR
COOLING COIL
(OPTIONAL)
RETURN AIR
Page 7
7
Plumbing
In order to improve serviceability of our products, the check valve is included with our manual kit for field instal­lation between the air-handler and hot water source.
The check valve should be installed in a vertical run of pipe with the flow of water in an upward direction.
An arrow on the check valve indicates its correct orienta­tion and must match the direction of water flow.
This will allow for ease of service to remove any installa­tion debris or service required due to extended hard water conditions.
Note:Take care during soldering to avoid debris or solder from lodging in the check valve. Note:It is critical to follow the piping configuration shown.Maintain a minimum distance of 12” above the CAF/AH. This will minimize thermal siphoning in the combo system.
* It should be noted that problems have been observed when using the side tappings on certain water heaters; therefore, it is strongly recommended to use the top
water tappings as indicated in Figure 1 to minimize t
hermal siphoning and related
issues.
Figure 1
Figure 2
To
House
Min. 12" (305 mm)above
12"
top of CAF / AH
Check
Val ve
Water
Heater
CAF
or
AH
To
House
Water
Heater
Check
Valve
Min. 12" (305 mm)
12"
above top of CAF / AH
CAF
or
AH
Page 8
8
Expansion Tanks
Expansion tanks are required in addition to a Check Valve for Closed Systems because pressure is created when water is heated in the water heater.
The expansion tank has an air bladder which will contract to relieve pressure in the system. The tank should always be connected to the cold water piping between the water heater shut off valve and the cold water inlet to the water heater.
Anti-Scald Valve
An anti-scald valve is required when the water heater ther­mostat is set above 140°F (60°C). Also, an anti-scald valve may be required for all installations by the “authority hav­ing jurisdiction”. The valve is placed in the hot water supply piping from the water heater downstream of the heating loop connection and upstream of any domestic hot water connection.
The purpose of the valve is to limit the maximum tempera­ture available for domestic hot water by mixing hot water from the water heater with cold water from the municipal supply.
The Anti-Scald valve must be thermostatically controlled and approved to the ASSE standard No. 1016 and 1017 for use as an anti-scald device.
Plumbing
Closed Loop System
Time to Scald
(1st degree burns)
Temperature Time
120°F 8 min.
130°F 20 sec.
140°F 3 sec.
160°F <1 sec.
Conventional Cooling (Not available through Nutech)
COLD WATER INLET
CHECK
VALV E
VALV E
(shut off)
EXPANSION TANK OR OTHER MEANS
(WHEN REQUIRED)
WATER HEATER
DOMESTIC HOT WATER
ANTI-SCALD VALVE
(WHEN REQUIRED)
VALV E
(shut off)
VALV E
(shut off)
VALV E
(balancing)
CHECK
VALV E
HEATING COIL
HRV/ERV CORE
DRAIN VALV E
BLOWER
SUPPLY AIR
COOLING COIL
(OPTIONAL)
RETURN AIR
Page 9
Valves
(a) Located on the cold water side of the Heater.
This valve has the ability to isolate the hot water (domestic and space heating) from the household cold water supply. Every water heater requires this valve regardless of space heating use.
(b) Located on the hot water supply side of the heating
loop, downstream of its connection to the domestic water.
(c) Located on the return side of the heating loop upstream
of its connection to the domestic cold water.
9
Plumbing
Ball Valve
The Ball Valve can be used as a shut off or drain valve. When in the open position, a full bore ball valve has very little resistance to flow, and these valves tend to be both the least expensive and the least susceptible to seizing over time. Do not use reduced bore ball valves as they are very restrictive to water flow.
Gate Valve
The Gate Valve can be used as a shut off or drain valve. When in the open position, there is very little resistance to flow. Gate valves tend to be less expensive than other types of valves but are susceptible to chatter (noise) and malfunc­tion with age.
Globe Valve
The Globe valve can be used as a shut off, drain or throt­tling valve. Even in the open position, the valve is fairly restrictive to flow. It has a much greater equivalent length (resistance.) than the other types of valves.
Balancing (Throttling) Valve
The Balancing (Throttling) Valve is used to reduce the water flow rate and thereby increase the water temperature drop. This is done to ensure proper activation of the water heater thermostat.
A Globe Valve could also be used for Balancing (Throttling) but has more resistance than the Balancing Valve.
These two valves isolate the heating loop for service or repair.
H
(a)
C
Supply
(b)
(c)
Return
Page 10
10
Call for Space Heating
There are two thermostats controlling every combo system, the water heater thermostat (controlling the hot water tem­perature) and the room thermostat (controlling the room air temperature).
When the room thermostat calls for heat, the circulation pump is activated. Hot water is then drawn from the top of the water heater through the air handler, and then returned to the water heater.
Plumbing
Open Loop System
Hot Water Temperature Drop
The water heater thermostat will initiate the water heater as required as long as there is a 20°F (11°C) temperature drop between the hot water supplied to the air handler and the returning water.
A temperature drop less than 20°F (11°C) can cause the water heater thermostat not to initiate. This will result in a lower hot water supply temperature or poor space heating performance with fluctuating domestic water temperatures.
Call for Domestic Hot Water and Space Heating
When both return water from the space heating loop and new cold water (replacing domestic water being used) enters the water heater, the mixed entering water is cool enough to activate the thermostat quickly. In this situation, the water heater must be capable of satisfying the combined need for domestic hot water and and space heating at the same time.
Conventional Cooling (Not available through Nutech)
COLD WATER INLET
VALV E
(shut off)
WATER HEATER
DOMESTIC HOT WATER
ANTI-SCALD VALVE
(WHEN REQUIRED)
VALV E
(shut off)
VALV E
(shut off)
COOLING COIL
(OPTIONAL)
RETURN AIR
VALV E
(balancing)
CHECK
VALV E
SUPPLY AIR
ATTENTION
HEATING COIL
HRV/ERV CORE
DRAIN VALV E
BLOWER
ATTENTION
Plumbing components and system configuration may vary from diagrams portrayed.
Chemicals (such as boiler system additives) cannot be added to a domestic hot water system.
Page 11
11
Plumbing
Air System
A circulation fan draws cool house air at approx. 70°F (21°C) from the return ductwork, forces it through the water coil where it is heated, and then distributes it to the various rooms of the house through the supply ductwork.
Water System Pressures
Within the water system of an Integrated Combo system, there are three terms that the designer/installer must under­stand.
1. Hot water supply temperature (EWT)
2. Hot water flow rate (GPM)
3. Air handler return temperature
4. Air handler flow rate (CFM)
Head Pressure
Head pressure is the pressure created by the circulation pump to push water through the piping system. It is this pressure which is used to overcome the resistance to water flow (friction) caused by the water pipe and fittings. It is similar in concept to the external static pressure in an air duct system. Head pressure is measured in feet of water (millimeters of water).
Water Flow Rate
Water flow rate is the amount of water flowing in the sys­tem. It is directly related to the head pressure and the resistance to flow. Flow rate is measured in gallons per minute (liters per minute).
The circulation pump is factory installed within the air han­dler. The water flow rate will vary depending on the pumps performance and the head pressure (resistance) of the com­plete heating loop system.
The piping and fittings used to connect the water heater and air handler must be sized to handle the volume of hot water required by the air handler within the pressure limitations of the circulation pump. All piping, fittings solders, and fluxes must be acceptable for use with domestic hot water.
Pressure Drop (PD)
Pressure drop (PD) is the reduction in total pressure caused by components added to a piping system such as coils, valves, and fittings. The measurement of pressure drop is the difference in pressure on the inlet side of the component and the outlet side. Pressure drop is measured in feet of water (millimeters of water).
When connecting the water lines for heating loop (air han­dler) to the domestic water system, the pipes should be connected with a “tee” to the side of a vertical domestic water pipe or the bottom of a horizontal domestic water pipe. This is to help prevent air from entering the heating loop. The connections should be as near as practical to the water heater.
Water Pump Performance Specifications
NOTE
The vertical height of the heating loop does not impact on the head pressure as the pressure required to push the water up the vertical height is offset by the weight of the water in the vertical drop on the other side of the heating loop.
S2 and S4 Models
16
14
12
10
8
6
Total Head in Feet
4
2
0
1 2 4 6 8 10 12
Capacity on U.S. gpm
L2 and L4 Models
16
14
12
10
8
6
Total Head in Feet
4
2
0
1 2 4 6 8 10 12 14 16 18 20
Capacity on U.S. gpm
Page 12
12
Air Handler Output Capacity
There are four factors that will significantly affect the heat­ing output of the air handler.
They are:
• Hot water supply temperature (EWT)
• Hot water flow rate (GPM)
• Air Handler return air temperature
• Air Handler air flow rate (CFM)
Hot Water Supply Temperature
The hot water supply temperature is controlled by the water heater thermostat. This is set by the installing contractor to provide the required temperature at the hot water outlet of the water heater.
The hot water supply temperature is typically 140°F (60°C). If this temperature must be increased to achieve higher out­puts from the furnace an anti-scald valve must be used to prevent domestic hot water temperatures above 140°F (60°C). The manufacturer of the Hot water Tank should be consulted for temperatures higher than 140°F.
It is important that a warning label be placed near the water heater thermostat telling the homeowner not to change the thermostat setting. The label is included with the furnace.
Hot Water Flow Rate
The hot water entering the water coil is the source of heat to the air handler. The effect of changing the amount of water entering the coil is the same as changing the water tempera­ture. As water flow is reduced, the output of the air handler and the air temperature rise will both be lowered.
Air Handler Return Air Temperature
The return air temperature entering the air handler is approx. 60°F (33°C) below the hot water inlet temperature. If the return air temperature entering the air handler is reduced, more heat transfer will occur and the output of the air handler will increase.
Air Handler Air Flow Rate
The air entering the air handler can only be warmed by the temperature difference between the hot water and the cool air. As the volume (CFM (L/s)) of air is reduced, the amount of heat which can be transferred is also reduced.
Air Handler Temperature Rise
In a fuel fired furnace, the combustion gases can be 1000°F (538°C) above the return air temperature. These units typi­cally have a temperature rise from 50°F (10°C) to 90°F (32°C) and therefore delivers air at the diffuser at 120°F (49°C) to 160°F (71°C).
With an Integrated Combo System, the hot water tempera­ture is approx. 130°F (54°C) which is 60°F (15.5°C) above the return air temperature. These units typically have a tem­perature rise of 35°F (2°C) to 40°F (4°C) and therefore would deliver air at the diffuser at approximately 105°F (40.5°C) to 110°F (43°C).
Room Thermostat
The room thermostat controls both the water circulation pump and the air circulation fan. It should be on a centrally located, inside wall away from any source of heat such as diffusers, appliances and direct sunlight.
Energy Saving Room Thermostat
A set back thermostat or “smart stat” can be used with a combo system, but care must be taken in the timing of the temperature changes. The timing of morning warm up should be early enough that the desired air temperature has been reached before the people begin to use domestic hot water. The highest demand for space heating is during the morning warm up and the highest demand for domestic hot water is during morning showers. Even if the water heater is properly sized, it may not be able to meet this combined load. Therefore, large set backs should be avoided.
Design vs. Field Conditions
The factors discussed between design parameters and actual field conditions can impact greatly on output capacity. Therefore, it is important to do a thorough and complete commissioning of the integrated combo system to ensure the design parameters are met.
Plumbing
NOTE
Although the water in the combo system is pressur­ized by the domestic water system the pump is required to create water flow in the heating loop. The domestic water system applies the same pres­sure to the supply and return sides of heating loop.
Page 13
13
Plumbing
Drain Line
The ventilation portion of the Clean Air Furnace has two drain pans for removing condensation, which may occur on the heat recovery core during cold weather.
Piping
The hot water piping between the hot water tank and the Clean Air Furnace should be new copper type, and should not be treated with chemicals, sealant or anything else, that will interfere with the purity of the potable water. Only non­lead, low temperature solder is permitted for sealing copper joints.
Where possible the length of pipe should not exceed 200' total equivalent length. Any piping running through uncon­ditioned space must be insulated to prevent heat loss, and possible freezing of the line.
Look inside the furnace and locate the pump. Attach the "Hot Water In" (Supply) to the pipe running to the pump. Attach the "Hot Water Out" (Return) to the pipe running to the coil. Do not reverse these lines, as this will cause the unit to malfunction.
For piping conventional water heaters, connections to and from the Clean Air Furnace to the water tank should be made at the point where the pipes leave the tank vertically. A "T" fitting used in each vertical line, with the Clean Air Furnace piping connected to the horizontal side of this fit­ting, will work best in avoiding air locks in the circulation pump of the furnace.
*Note: Remove shipping block from underneath pump and discard.
T
HRV Drain Line Diagram
KNOCKOUT
DRAIN
SPOUT
TA P E
2” (50 mm)
TEE
CONNECTOR
THROUGH KNOCKOUT
TO DRAIN
DRAIN
SPOUT
KNOCKOU
Page 14
This manual gives the contractor guidelines for installing the LIFEBREATH Clean Air Furnace. All national and local codes relating to this type of equipment must be fol­lowed.
Locating The Unit
The Clean Air Furnace is designed to be installed vertical­ly, (unless it is designated as a Horizontal unit ”H”), in a conditioned space, where the surrounding temperature does not fall below 50°F (10°C). Attic installations are not recommended. Typically the unit is installed in a mechani­cal area of the basement, or other partitioned mechanical room, elsewhere in the home.
A location close to an outside wall is recommended, as the ventilation supply and exhaust portion will need to be duct­ed to the outside air. Sufficient clearance around the unit is required for service of the filter, heat recovery core and components. As a rule this unit should be installed adjacent to the hot water heater. If this is not possible, or if the pip­ing layout is complex, the total head pressure on the pump should be calculated.
Duct Connections
To accommodate various installations, the Clean Air Furnace has knockouts for the return air plenum and venti­lation ducts, on both sides of the cabinet. Special care and attention should be given to determining which knockouts are to be removed.
Slide Heat Recovery Core out to remove ventilation knock­outs. Never install ductwork directly to the cabinet that is smaller than the opening provided.
Penetrations from sheet metal screws used to fasten the ductwork to the cabinet of the unit should only be placed into the duct flange provided. This is to avoid contact and damage of the heating/air conditioning coils and internal wiring.
14
Option 1 - Upflow Models
NOTE: Return plenum opening can be on either side of cabinet and is not dependent on which side the ventilation ports are on.
Ventilation Ports Off Left
Ventilation Ports Off Right
Installation
Remove circular metal knockout
Remove styrofoam knockout
Remove circular metal knockout
Remove styrofoam knockout
Page 15
Ducting
The duct sizing for the furnace section can be determined using HRAI Residential Air System Design Manual, SMACNA, or any other industry-recognized manuals.
Note: "Combo units" normally deliver air at approx. 110°F (43°C), and therefore may require larger than nor­mal ductwork. When installing the Clean Air Furnace as a replacement unit on a retrofit application, always cal­culate the size of duct that is there.
Any ductwork running through unconditioned space must be sealed properly and insulated to prevent heat loss. All local codes must be followed in determining the amount of insulation needed.
The ventilation section consists of two 6" (15.2cm) round ports located on the side of the cabinet, which vent to the outside. Insulated ducting with a vapour barrier such as flex-ducting, or ridged pipe wrapped in pipe sleeve, is required to prevent condensation from occurring on the pipe. Also the airflow in these lines is designed to be bal­anced. (See "Balancing Airflows" in this manual, for damper location and procedure).
15
Option 2 - Downflow Models
Ventilation Ports Off Left
Ventilation Ports Off Right
Horizontal Models
Installation
Remove styrofoam knockout
Remove styrofoam knockout
Remove styrofoam knockout
Remove styrofoam knockout
Remove circular metal knockout
WARNING
A Backdraft Damper is required in the exhaust air duct to prevent cold air from entering the unit when the Clean Air Furnace is not running.
Page 16
Locating Intake Weatherhood
The intake weatherhood should be located as follows:
• 4 - 6' from ventilation exhaust hood, and upstream of prevailing winds, if possible.
• At least 6' from a dryer vent, oil fill pipes, combustion outlets, gas meters, garbage containers or anything else, which may contaminate the air.
• Do not locate fresh air intake in garages, crawl spaces or attics.
• Install 18" (45.72 cm) above grade, or above expected snow accumulation.
Locating the Exhaust Weatherhoods
The Exhaust Weatherhood should be located as follows:
• At least 4-6' from the supply inlet
• At least 18" (45.72 cm) above grade or expected snow accumulation
At least 3' from gas meters, combustion vents, or dryer vents
Do not install in garages, crawl spaces or attics
Outside Ducting the Weatherhoods
The ventilation portion of the Clean Air Furnace can be vented off either side of the unit by removing knockouts provided. Once the knockouts in are removed, a bead of silicone can be placed on the plastic thermo-collars (pro­vided), to form a seal between the collars and the cabinet. The collars can then be fastened into place with screws. Note the exhaust outlet is always the port on the bottom, and the supply inlet is always the port on the top, both ports should be labeled from the factory as such.
The ductwork from the outside weatherhoods to the unit, is usually flexible ducting, although rigid pipe may be needed if the runs are greater than 10 feet. In either case the pipes (both exhaust and supply and the added fittings) must be insulated, with a complete vapor barrier.
To minimize restriction in airflows the ducting should be short, with as few bends as possible. See diagram below for recommended connection of insulated ducting to out­side weatherhoods.
16
Locating Weatherhood
Installation
WEATHERHOODINSTALLATION
ATTENTION
It is extremely important to design and install the fresh air intake in an area where the hoods will gather the freshest air.
1/4"(6mm)SCREEN
(frontview)
COLLARISSUPPLIEDTO
SCREEN
(sideview)
12"galvanized
pipesupplied
EXTERIOR
WALL
1. ThermalCollarslidesovergalvanized sleeveofWeatherhood.
2. FastenThermalCollartoBelt.
3. SlidetheInsulatedFlexibleDuctingover theWeatherhood'sgalvanizedsleeveand fastenittotheThermalCollar.
4. Hoodishingedtoallowforeasyaccess
 forcleaningofbirdscreen.
ENSUREVAPOURBARRIER
IS100%SEALEDTO
WALLPLATE
Page 17
It is necessary to have balanced air flows in an HRV. The volume of air brought in from the outside must equal the volume of air exhausted by the unit. If the air flows are not properly balanced then:
• The HRV may not operate at its maximum efficiency
• A negative or positive air pressure may occur in the house
• The unit may not defrost properly
• Failure to balance the HRV may void warranty
Prior to balancing, ensure that:
1. All sealing of the ductwork system has been completed.
2. All of the HRV's components are in place and function­ing properly.
3. Balancing dampers are fully open.
4. Unit is on high speed.
5. After taking readings of both the stale air to the HRV duct and fresh air to the house duct, the duct with the lower CFM ([L/s] velocity) reading should be left alone, while the duct with the higher reading should be dampered back to match the lower reading.
6. Return unit to appropriate fan speed for normal opera­tion.
Balancing Procedure
The following is a method of field balancing an HRV using a Pitot tube, advantageous in situations when flow stations are not installed in the ductwork. Procedure should be per­formed with the HRV on high speed.
Choose the straightest section of duct between the HRV and the weatherhoods. This will be used for both the sup­ply and return ducts.
Drill a small hole in the duct (about 3/16"), three feet downstream of any elbows or bends, and one foot upstream of any elbows or bends. These are recommended distances but the actual installation may limit the amount of straight duct.
The Pitot tube should be connected to a magnehelic gauge or other manometer capable of reading from 0 to 0.25 in. (0 - 62 Pa) of water, preferably to 3 digits of resolution. The tube coming out of the top of the Pitot is connected to the high pressure side of the gauge. The tube coming out of the side of the Pitot is connected to the low pressure or ref­erence side of the gauge.
Insert the Pitot tube into the duct, pointing the tip into the airflow.
For general balancing it is sufficient to move the Pitot tube around in the duct and take an average or typical reading. Repeat this procedure in the other (supply or return) duct. Determine which duct has the highest airflow (highest reading on the gauge). Then damper that airflow back to match the lower reading from the duct. The flows should now be balanced.
Actual airflow can be determined from the gauge reading. The value read on the gauge is called velocity pressure. The Pitot tube comes with a chart that will give the air flow velocity based on the velocity pressure indicated by the gauge. This velocity will be either feet per minute or metres per second. To determine the actual airflow, the velocity is multiplied by the cross sectional area of the duct being measured.
17
Figure A
Pitot Tube and Gauge
Figure B
Placement of the Pitot Tube
Pitot Tube Air Flow Balancing
Note: For best results keep Pitot tube well away from dampers.
Pitot Tube
Page 18
This is an example for determining the airflow in a 6" duct. The Pitot tube reading was 0.025inches of water. From the chart, this is 640 feet per minute.
The 6" (15.2 cm) duct has a cross sectional area of:
= [3.14 x (6"÷12)
2
]÷4
= 0.2 square feet
The airflow is then:
640 ft./min. x 0.2 square feet = 128 cfm
For your convenience, the cross sectional area of some common round duct is listed below:
DUCT DIAM. (inches) CROSS SECTION AREA (sq. ft.)
5.0 (125 mm) .14
6.0 (150 mm) .20
7.0 (175 mm) .27
The accuracy of the airflow reading will be affected by how close to any elbows or bends the readings are taken. Accuracy can be increased by taking an average of multiple readings as outlined in the literature supplied with the Pitot tube.
18
Figure C
Push and turn with slotted screwdriver. Damper automatically locks when pressure is released.
When connecting ductwork to the collar, take note where screws are located. Screws should be located no further than 1/2” (12.70 mm) from out­side edge of collar, so as not to impede operation of the damper.
1/2” (12 mm)
Insulated flexible
ducting
Balancing Collar Instructions
Figure D
Pitot Tube Air Flow Balancing
Back Draft Damper
The back draft damper (not included) can be located any­where in a vertical rise of the exhaust duct.
INSULATED PIPE
WITH VAPOUR
BARRIER
OUTSIDE
BUILT-IN
BALANCING
DAMPERS
BACK DRAFT
DAMPER
WARNING
A Backdraft Damper is required in the exhaust air duct to prevent cold air from entering the unit when the Clean Air Furnace is not running.
Page 19
19
Standard 24 Volt Thermostat Connection
(Thermostats are not avail­able through Nutech)
Thermostat Heat Anticipator Settings
Mechanical Thermostats - start at .5 amp and may need to be increased depending upon the residual heat left in the hydronic coil and duct work.
Electronic Thermostats - to be set on electric style heat.
Off Season Circulation Timer
Water is periodically circulated through the space heating loop during the summer and other periods of infrequent use. The concern is that water which remains stationary in the heating loop during the summer may be less than desirable as domestic hot water when it is returned to the water heater at system startup in the fall.
Basic Functions
C - Common
R - 24 volt Supply
W - Medium or High Fan Relay with Circulation Pump
(The speed depends on Dip Switch # 6 setting)
Y&G- Medium or High Fan Relay
(The speed depends on Dip Switch # 7 setting)
G - Low Speed Fan Relay
O - High Speed Fan Relay with Circulation Pump
Function and Controls Standard Motor
Standard Motor DIP Switch Settings (DIP #1-8 OFF is Factory Setting)
DIP #2 to ON will disable the Off Season Circulation Timer
DIP #6 to ON will select Medium Speed for heating (Factory setting is OFF for High Speed)
DIP #7 to ON will select Medium Speed for cooling switch (Factory setting is OFF for High Speed)
T1
T4 T5 T6 T7 T8 T9 T10 T11 T12 T13 T14 T15 T16 T17
T2 T3
Line
T21 T22 T23 T24
AUX1AUX
F1
MAX
1
amp
C1
VDR1
P1
C
T26 T27 GRNYEL
8 7 6 5 4 3 2 1
2
SW1
DIP SWITCHES TO BE ADJUSTED BY QUALIFIED TECHNICIANS ONLY.
RWY G
Thermostat
To “ C”
ON
Neutral
TP1
Digital Controls
To “ Y”
ON
DET
CR1
A/C Unit
T18 T19
C6 C7
N.O.
COM
K7 K1 K2K8
T32
T33
T34
Contact 2 Contact 3 Contact 4
T35
T36
COM
T37
T38
T39
N.O.
T40
RELAY
FEED
T20
SPARE
T43
N.C
T42
T41
COM
F2 MAX 2 amp
P2 P3
Defrost
Freeze
C5
C4
N.O.
K6
R
T29T28REDOGYWRCT25
Fan Hi Fan Med Fan Low
N.O.
COM
K3 K4 K5
N.0. COM N.C. N.0. COM N.C. N.0. COM N.C. N.0 . COM
24Vac12Vac Com
T30
T31
Contact 1
8 7 6 5 4 3 2 1
WARNING
Do not adjust any other DIP switches than indicated above.
WARNING
Do not energize the CAF until the plumbing is connected and commissioned. Failure to do so will damage the pump.
Page 20
20
O
a
M
Standard 24 Volt Thermostat Connection
(Thermostats are not avail­able through Nutech)
Basic Functions
• Thermostat fan switch will control low speed fan operation
• Call for heating - high speed
• Call for cooling - high speed
Function and Controls ECM Motor
ECM Motor DIP Switch Settings
ECM Motor DIP Switch Settings (DIP 6&7 ON is Factory Setting)
DIP #2 to ON will disable the Off Season Circulation Timer
Factory Setting
Thermostat Heat Anticipator Settings
Mechanical Thermostats - start at .5 amp and may need to be increased depending upon the residual heat left in the hydron­ic coil and duct work.
Electronic Thermostats - to be set on electric style heat.
T1
T2 T3
T4 T5 T6 T7 T8 T9 T10 T11 T12 T13 T14 T15 T16 T17
Line
T21 T22 T23 T24
AUX1AUX
F1
MAX
1
amp
C1
VDR1
C
T26 T27 GRNYEL
8 7 6 5 4 3 2 1
2
DIP SWITCHES TO BE ADJUSTED BY QUALIFIED TECHNICIANS ONLY.
P1
SW1
Neutral
ON
CR1
TP1
Digital Controls
DET
F2 MAX 2 amp
P2 P3
Defrost
Freeze
COM
C5
C4
K6
R
Fan Hi
N.O.
COM
K3
K8
N.0. CO
24Vac12Vac Com
T30
T29T28REDOGYWRCT25
To “Y”
RWY G
To “ C”
Thermostat
A/C Unit
ON
Cont
N.
T31
Switch Setting
Cool Switches
Both OFF
1 0N - 2 OFF
1 OFF - 2 ON
1 ON - 2 ON
COOL HEAT
T2
T1
12 34 56 7 8
off on
COOL
Switch Setting
Heat Switches
Both OFF
3 0N - 4 OFF
3 OFF - 4 ON
3 ON - 4 ON
Switch Setting
Adjust Switches
Both OFF
5 0N - 6 OFF
5 OFF - 6 ON
5 ON - 6 ON
ADJUST DELAY
HEAT
ADJUST DELAY
Fan Speeds
Med High
Med Low
Fan Speeds
Med High
Med Low
Fan Speeds
Heat
Normal
Increase 15%
Decrease 15%
Normal
SW1
Cool
High
Low
Heat
High
Low
Cool
Normal
Increase 15%
Decrease 15%
Normal
8 7 6 5 4 3 2 1
WARNING
Do not adjust any other DIP switches than indicated above.
Delay Switches are for future use - no function at this time
Note:
Refer to individual specification pages for Airflow
Performance specifications. Above settings correspond
to DIP switch settings on the ECM circuit board only.
Do not adjust DIP switches on MAIN Circuit Board.
WARNING
Do not energize the CAF until the plumbing is connected and commissioned. Failure to do so will damage the pump.
ATTENTION
DIP switches #6 & #7 must be ON for the ECM motor to function (factory setting).
Page 21
21
Optional Remote Control Devices
Remote Dehumidistat
• The Dehumidistat initiates high speed fan operation when humidity level exceeds selected setting.
• This main control should be located in a central “easy access” location.
• Use 2 lead 18 gauge wire for the control connections.
• Install only one of these controls on a system
• Low Voltage
• Never install more than one dehumidistat to a system.
Part No. 99-130W
Digital Electronic Timer
• Boosts unit to high speed ventilation for 20, 40 or 60 minutes.
• Install up to 4 timers on a system.
• Use 3 lead 18 gauge wire for the control connections.
• Mounts in a standard 2x4 electrical box.
• Illustrated here with a "decora" cover plate.
• Low Voltage.
Part No. 99-104
DEHUMIDISTAT initi­ates high speed fan operation when humidi­ty level exceeds selected setting.
20/40/60 minute status lights
Touch pad operation
Page 22
22
Wiring the Controls
Optional Digital Electronic Timer
Yellow to YEL
Green to GRN
Red to RED
Part No. 99-104
T26 T27 GRNYEL
C
DET
T28REDOGYWRCT25
R
T29
24Vac12Vac Com
T30
Contact 1
T31
T32
T33
Contact 2 Contact 3 Contact 4
T34
T35
T36
T37
T38
T39
T40
T41
VDR1
P1
C1
DIP SWITCHES TO BE
ADJUSTED BY QUALIFIED
TECHNICIANS ONLY.
T21 T22 T23 T24
AUX
1
AUX
2
MAX
amp
F1
1
SW1
T1
T2 T3
T4 T5 T6 T7 T8 T9 T10 T11 T12 T13 T14 T15 T16 T17
Line
8 7 6 5 4 3 2 1
Optional Remote Dehumidistat
Digital Controls
TP1
CR1
P2 P3
Freeze
Defrost
T42
N.0. COM N.C. N.0. COM N.C. N.0. COM N.C. N.0 . COM
F2 MAX 2 amp
K7 K1 K2K8
SPARE
N.C
T43
ON
COM
K6
COM
K3 K4 K5
COM
COM
Neutral
C4
N.O.
N.O.
N.O.
N.O.
T20
Fan Hi Fan Med Fan Low
RELAY
FEED
C5
T18 T19
Red to T23
Black to T24
Part No. 99-130W
Page 23
23
Aircom Relays
The Aircom circuit board has three available “dry contact” relays. Contact 3 is not available.
Maximum 115V 10 amp resistive load.
Contact 1
This relay is a dry contact (no power supplied from board). The relay switches upon a call for heat.
This relay can be used to switch the heat demand signal for boiler operation.
Power (if required) must be supplied to common from an external source.
Max. voltage - 120 volts
Max. Amperage - 10 amps
Contact 2 and 4
These relays are dry contacts (no power supplied from board). The relays switche whenever the CAF blower motor is operating.
These relays can be used to interlock Humdifiers, Air Cleaning Equipment, etc.
Power (if required) must be supplied to common from an external source.
Max. voltage - 120 volts
Max. Amperage - 10 amps
T39
T40
SPARE
T43
N.C
T42
T41
F2 MAX 2 amp
P2 P3
Defrost
Freeze
K7 K1 K2K8
N.0. COM N.C. N.0. COM N.C. N.0. COM N.C. N.0 . COM
R
24Vac
T30T29T28
T31
Contact 1
T32
T33
T34
T35
T36
T37
Contact 2 Contact 3 Contact 4
T38
Boiler
Contact
T39
T40
SPARE
T43
N.C
T42
T41
MAX 2 amp
P3
Defrost
K7 K1 K2K8
N.0. COM N.C. N.0. COM N.C. N.0. COM N.C. N.0 . COM
R
24Vac
T30T29T28
T31
Contact 1
T32
T33
T34
T35
T36
T37
Contact 2 Contact 3 Contact 4
T38
Humidifier
Contact
Page 24
24
In order for any appliance to work properly it must be set up and tested by a knowledgeable technician.
The following conditions must be met prior to start-up
1. Ensure that connecting water lines are purged and free of
debris. Caution: solder or other debris may cause the furnace pump or check valve to malfunction.
2. Blower wheel rotates freely inside its housing.
3. Wiring connections are tight.
4. Water is sitting in the "P" trap below the
HRV core.
5. All duct and pipe connections are sealed.
6. Check that styrene block is removed from under pump.
7. Front access door is on tight.
8. Fan speed selection:
a) Heating/Cooling - factory setting is at high speed and can be changed in the electrical box to medium-high or medium if required. b) Ventilation - low speed is controlled by the Thermostat Fan switch.
Once all of the necessary connections have been made, the Clean Air Furnace Start-Up Procedure is as follows:
1. Close shut-off valves separating the Clean Air Furnace from the water heater.
2. Set up water heater according to manufacturer's instruc­tions.
3. Purge air from unit. To do so, open the supply shut-off valve to the furnace. Attach a garden hose to drain valve, and drain water until you get a continuous flow. Close the drain valve and purge the pump. To purge the air from the pump, turn the large screw on the face of the pump counterclockwise until water leaks out, then tight­en. Open the supply shut-off valve.
4. Turn on power supply to Clean Air Furnace.
5. Switch the room thermostat to heat. The thermostat should be set higher than the current room temperature in order to energize the pump and commence the heating cycle. (If the pump does not start, or the Clean Air Furnace is not producing heat, refer to the Troubleshooting Section in this manual.
6. Set room thermostat at desired temperature setting.
Start-Up Procedure
Page 25
25
A dedicated maintenance program will prolong the life of the equipment, and maintain its optimum performance.
We recommend at least two (2) full inspections and clean­ings per year under normal operating conditions, and more if circumstances warrant it (i.e. situations of heavy smoke may require servicing every one to two months).
Service should include:
• Cleaning of screens protecting outside hoods.
• Cleaning of the HRV (aluminum) core.
• Inspect filters and replace as necessary.
• Wipe down drain pans and inside of cabinet, using a mild disinfectant.
• Ensure condensate drain has free flow of moisture.
• Inspect operation of blowers and electrical panel.
• Confirm operation.
Clean Core Twice a Year
a) Open access door.
b) Carefully grip ends of core, and pull evenly outward.
Core may be snug, but will slide out of the "H" channel.
c) Once removed from the cabinet, remove the foam filters.
d) Wash the core in warm soapy water (do not use dish-
washer).
e) Install the clean filters
f) Install the clean core.
Service/Maintenance
Ultra-efficient heating coil
Tempered fresh air to heating coil
Heated fresh air to registers
Hot water circulation pump
Hot water to coil
Fresh air intakes to HRV
Stale air to outside
Return air from house
Domestic water heater
Hot water return
Heat recovery ventilator heat exchanger
PSC type hi-efficiency motor
Page 26
26
Lack of heat
1. Check that the room thermostat is set to the desired tem­perature.
2. Confirm the units have power and the shut-off valves are open.
3. Ensure there is power to the unit and that the pump is working. If the pump is not working properly it may be stuck. Disconnect power and remove screw in center face of the pump. Using a screwdriver, turn the pump shaft several times to free it from sticking. Replace center­screw and re-connect power. If pump still fails to start, it may require replacement.
4. Confirm that the hot water heater is working and that hot water is entering the Clean Air Furnace.
5. Verify that the airflow in and out of the system matches designed specs. If airflow is low, check for blockage in the filter or some other obstruction.
6. Make sure your water heater is sized large enough for heat load of house and for domestic hot water use.
7. Air may still be in the water lines. If so, re-purge the sys­tem according to the start up procedure.
8. Confirm that the inlet and outlet pipe connections are not reversed.
9. Ensure that there are no other restrictions in the water lines, such as faulty valves, or debris.
Pump is noisy
Pumps can become noisy when air remaining in the lines interfere with their operation. If this occurs re-purge the system as indicated in the Start-Up Procedure.
HRV core freezes up
1. Make sure that the supply and exhaust lines are balanced according to the "Balancing Procedure" in this manual.
2. If out of balance, ensure that the balancing dampers have not been moved and that there are no obstructions in the outside hoods.
During cooling cycle, hot water circulates through the coil
If the check valve inside the cabinet is stuck in the open position, hot water may infiltrate the heating coil. This occurs when the hot pipes are not capped-off during instal­lation or service and foreign debris enters the piping. This debris can settle under the check valve seat and permit hot water to flow into the coil. The problem can be corrected by repeatedly flushing the heating loop until it is clean.
Water sits in drain pipes
1. Check drain pans or lines for plugs.
2. Confirm that the HRV core is installed according to man­ufactures recommendations.
3. Check the drain line for kinks.
4. Make sure that the O-ring in the drain nozzles sit flat.
5. Ensure the drain line has enough "fall" to it.
Condensation/ice forming inside ventilation ducts
A rip in the vapor barrier or poorly sealed joints may cause condensation or ice to form on the ducting. If this occurs, replace the entire line.
Troubleshooting
Page 27
27
Winter humidity levels are too low
1. If you have installed a dehumidistat ensure that its setting is correct. (Summer - OFF) (Winter - 30% RH to 45% RH).
2. Check humidifier settings. (Summer - OFF) (Winter ­30% RH to 45% RH). NOTE: Humidifier should always be 10% lower than dehumidistat.
3. Change thermostat fan switch from manual to automatic.
Summer humidity levels are too high
1. If you have installed a dehumidistat ensure its setting is correct. (Summer - OFF)(Winter - 30% RH to 45% RH).
2. Change thermostat fan switch from automatic to manual.
NOTE: The CAF has the ability to dehumidify during the heating season. (When outside air is less humid than indoor air). If you are in a region where outdoor humidity levels are typically higher than indoor humidity levels, a dehumidistat should not be used in this system.
Troubleshooting
Winter Setting 30% to 45%
Summer Setting “OFF”
Optional Dehumidistat
This control will reduce winter humidity levels when outdoor air approaches or exceeds freezing.
Page 28
28
Model Number Nomenclature Breakdown
Example Model Number CAF - U - S2A - 24 - P16
Model Configuration
CAF - Clean Air Furnace
(Built-in HRV)
AH - Air Handler (No HRV)
Configuration
U - Upflow D - Downflow H - Horizontal
Hydronic Coil Size
S2A - Small Coil - 2 Row (see specifications) S4A - Small Coil - 4 Row (see specifications) L2A - Large Coil - 2 Row (see specifications) L4A - Large Coil - 4 Row (see specifications) L2B - Large Coil - 2 Row (see specifications) 00 - No Hydronics (No Heating Coil, No Pump)
* CFM (High Speed) Cooling Capacity
Note:
Refer to individual specification
pages for Hydronic Coil and
Blower configurations.
Refer to individual specification pages for
This sheet is for pre-configured
Hydronic Coil and Blower outputs and
Model Number Breakdown only.
configurations.
ATTENTION
24 - 2 tons 30 - 2.5 tons 36 - 3.0 tons 48 - 4.0 tons
*Cooling coils not available from Nutech
Motor Configuration
P16 - Standard PSC Motor 120V/60Hz E15 - Upgrade ECM Motor 120V/50Hz E16 - Upgrade ECM Motor 120V/60Hz E25 - Upgrade ECM Motor 220V/50Hz E26 - Upgrade ECM Motor 220V/60Hz
Page 29
29
Core Ventilation system has patented aluminum heat recovery core (standard) or an enthalpic energy recovery core (optional) for ener-
gy-efficient ventilation. Enthalpic cores are recommended for regions where the temperature does not drop below 25°F (-4°C).
Filters Washable air filters in exhaust and supply air streams of ventilation section, 1" (25 mm) pleated in return plenum side.
Case Prepainted galvanized steel for superior corrosion resistance.
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
Options
99-186 Weatherhoods, Two - 6" (150 mm) c/w
1/4" (6 mm) mesh screen
99-130W Remote Wall Mount Dehumidistat
Control 24 VAC only
99-RSK6 6” (150 mm) back draft damper
99-104 DET - Digital Electronic Timer
Warranty
Units carry a lifetime warranty on the heat recovery (aluminum) core, a five year warranty on the energy recovery (enthalpic) core and a five year replacement parts warranty on all other components.
Model CAF-U-S4A-24-P16
Voltage 120 VAC 60 Hz
Hp 1/3
Amps (total) 8
Water
1/2" (12 mm) Copper
Connections Soldered Connection
Airflow (High) .25 in wg
1030 CFM
.5 in. wg 890 CFM
Ventilation 100 - 140 CFM Airflow
Effectiveness 70% (Aluminum Core)
Total Efficiency 50% (Enthalpic Core)
Net Weight 150 lbs.
Shipping Weight 165 lbs.
Dimensions & Clearances
Note: Ventilation ports and return plenum
opening available off either side of cabinet. All
units conform to CSA and UL Standards.
Model CAF-U-S4A-24-P16
16”
29.5”
(749 mm)
(406 mm)
Supply Air
To p
17.25”
19”
(438 mm)
(483 mm)
Side
12"
(305 mm)
Ventilation
6"
Supply Air
(150 mm)
4”
(100 mm)
14"
(356 mm)
(SERVICE CLEARANCE 1') (SERVICE CLEARANCE 3')
6"
(150 mm)
Inlet
Ventilation Exhaust Air Outlet
22”
(559 mm)
Return Air
29.5"
(749 mm)
Front
Latches
Blower Section
19"
(483 mm)
47.5" (1207 mm
Page 30
Core Ventilation system has patented aluminum heat recovery core (standard) or an enthalpic energy recovery core (optional) for ener-
gy-efficient ventilation. Enthalpic cores are recommended for regions where the temperature does not drop below 25°F (-4°C).
Filters Washable air filters in exhaust and supply air streams of ventilation section, 1" (25 mm) pleated in return plenum side
Case Prepainted galvanized steel for superior corrosion resistance.
30
Dimensions & Clearances
Model CAF-U-L4A-36-P16
Voltage 120 VAC 60 Hz
Hp 1/2
Amps (total) 10.6
Water
3/4" (19 mm) Copper
Connections Soldered Connection
Airflow (High) .25 in wg
1350 CFM
.5 in. wg 1180 CFM
Ventilation 100 - 140 CFM Airflow
Effectiveness 70% (Aluminum Core)
Total Efficiency 50% (Enthalpic Core)
Net Weight 150 lbs.
Shipping Weight 165 lbs.
Note: Ventilation ports and return plenum
opening available off either side of cabinet.
All units conform to CSA and UL Standards.
Options
99-186 Weatherhoods, Two - 6" (150 mm)
c/w 1/4" (6 mm) mesh screen
99-130W Remote Wall Mount Dehumidistat
Control 24 VAC only
99-RSK6 6” (150 mm) back draft damper
99-104 DET - Digital Electronic Timer
Warranty
Units carry a lifetime warranty on the heat recovery (alu­minum) core, a five year warranty on the energy recovery (enthalpic) core and a five year replacement parts warranty on all other components.
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
Model CAF-U-L4A-36-P16
29.5"
(749 mm)
22.25"
(565 mm)
Supply Air
To p
17.25”
19”
(438 mm)
(483 mm)
Side
12"
(305 mm)
Ventilation
6"
Supply Air
(150 mm)
4”
(100 mm)
(356 mm)
Inlet
Ventilation
6"
Exhaust Air
(150 mm)
Outlet
(559 mm)
14"
Return Air
29.5"
(749 mm)
(SERVICE CLEARANCE 1') (SERVICE CLEARANCE 3')
Front
Latches
47.5" (1207 mm)
22”
Blower Section
19"
(483 mm)
Page 31
31
Options
99-186 Weatherhoods, Two - 6" (150 mm)
c/w 1/4" (6 mm) mesh screen
99-130W Remote Wall Mount Dehumidistat
Control 24 VAC only
99-RSK6 6” (150 mm) back draft damper
99-104 DET - Digital Electronic Timer
Warranty
Units carry a lifetime warranty on the heat recovery (alu­minum) core, a five year warranty on the energy recovery (enthalpic) core and a five year replacement parts warranty on all other components.
Core Ventilation system has patented aluminum heat recovery core (standard) or an enthalpic energy recovery core (optional) for ener-
gy-efficient ventilation. Enthalpic cores are recommended for regions where the temperature does not drop below 25°F (-4°C).
Filters Washable air filters in exhaust and supply air streams of ventilation section, 1" (25 mm) pleated in return plenum side
Case Prepainted galvanized steel for superior corrosion resistance.
Dimensions & Clearances
Model CAF-D-S4A-24-P16
Voltage 120 VAC 60 Hz
Hp 1/3
Amps (total) 8
Water
1/2" (12 mm) Copper
Connections
Soldered Connection
Airflow (High) .25 in wg
1030 CFM
.5 in. wg 890 CFM
Ventilation 100 - 140 CFM Airflow
Effectiveness 70% (Aluminum Core)
Total Efficiency 50% (Enthalpic Core)
Net Weight 150 lbs.
Shipping Weight 165 lbs.
Note: Ventilation ports and return plenum opening available off either side of cabinet.
All units conform to CSA and UL Standards.
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
Model CAF-D-S4A-24-P16
19"
(483 mm)
19"
(483 mm)
To p
14"
(356 mm)
Bottom
(559 mm)
17.25"
(438 mm)
22"
Return Air
29.5"
(749 mm)
29.5”
(749 mm)
16"
(406 mm)
Supply Air
47.5"
(1207 mm)
19"
(483 mm)
Blower Section
Latches
Ventilation Exhaust Air Outlet
Ventilation Supply Air Inlet
SideFront
29.5"
(749 mm)
Return Air
22"
(559 mm)
(SERVICE CLEARANCE 1') (SERVICE CLEARANCE 3')
14”
6”
(150 mm)
6”
(150 mm)
12"
(305 mm)
4"
(100 mm)
(356 mm)
Page 32
32
Options
99-186 Weatherhoods, Two - 6" (150 mm)
c/w 1/4" (6 mm) mesh screen
99-130W Remote Wall Mount Dehumidistat
Control 24 VAC only
99-RSK6 6” (150 mm) back draft damper
99-104 DET - Digital Electronic Timer
Note: Ventilation ports and return plenum opening available off either side of cabinet.
All units conform to CSA and UL Standards.
Dimensions & Clearances
Model CAF-D-L4A-36-P16
Voltage 120 VAC 60 Hz
Hp 1/2
Amps (total) 10.6
Water
3/4" (19 mm) Copper
Connections Soldered Connection
Airflow (High) .25 in wg
1350 CFM
.5 in. wg
1180 CFM
Ventilation 100 - 140 CFM Airflow
Effectiveness 70% (Aluminum Core)
Total Efficiency 50% (Enthalpic Core)
Net Weight 150 lbs.
Shipping Weight 165 lbs.
Warranty
Units carry a lifetime warranty on the heat recovery (alu­minum) core, a five year warranty on the energy recovery (enthalpic) core and a five year replacement parts warranty on all other components.
Core Ventilation system has patented aluminum heat recovery core (standard) or an enthalpic energy recovery core (optional) for ener-
gy-efficient ventilation. Enthalpic cores are recommended for regions where the temperature does not drop below 25°F (-4°C).
Filters Washable air filters in exhaust and supply air streams of ventilation section, 1" (25 mm) pleated in return plenum side
Case Prepainted galvanized steel for superior corrosion resistance.
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
Model CAF-D-L4A-36-P16
19"
(483 mm)
19"
(483 mm)
To p
14"
(356 mm)
Bottom
17.25"
(438 mm)
22"
(559 mm)
Return Air
29.5"
(749 mm)
29.5"
(749 mm)
22.25"
(565 mm)
Supply Air
47.5"
(1207 mm)
(483 mm)
Blower Section
Front
19"
Ventilation Exhaust Air Outlet
Ventilation Supply Air Inlet
Latches
Side
29.5"
(749 mm)
Return Air
22"
(559 mm)
(305 mm)
(SERVICE CLEARANCE 1') (SERVICE CLEARANCE 3')
6"
(150 mm)
6"
(150 mm)
12"
4"
(100 mm)
14"
(356 mm)
Page 33
33
Core Ventilation system has patented aluminum heat recovery core (standard) or an enthalpic energy recovery core (optional) for ener-
gy-efficient ventilation. Enthalpic cores are recommended for regions where the temperature does not drop below 25°F (-4°C).
Filters Washable air filters in exhaust and supply air streams of ventilation section, 1" (25 mm) pleated in return plenum side.
Case Prepainted galvanized steel for superior corrosion resistance. Service drain 1/2” (12 mm) or 3/4” (19 mm) NPT.
Note: All units conform to CSA and UL Standards.
Model CAF-H-S4A-24-P16
Voltage 120 VAC 60 Hz
Hp 1/3
Amps (total) 8
Water
1/2" (12 mm) Copper
Connections
Soldered Connection
Airflow (High) .25 in wg
1030 CFM
.5 in. wg 890 CFM
Ventilation 100 - 140 CFM Airflow
Effectiveness 70% (Aluminum Core)
Total Efficiency 50% (Enthalpic Core)
Net Weight 150 lbs.
Shipping Weight 165 lbs.
Options
99-186 Weatherhoods, Two - 6" (150 mm)
c/w 1/4" (6 mm) mesh screen
99-130W Remote Wall Mount Dehumidistat
Control 24 VAC only
99-RSK6 6” (150 mm) back draft damper
99-104 DET - Digital Electronic Timer
Warranty
Units carry a lifetime warranty on the heat recovery (alu­minum) core, a five year warranty on the energy recovery (enthalpic) core and a five year replacement parts warranty on all other components.
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
Model CAF-H-S4A-24-P16
Dimensions & Clearances
14"
(356 mm)
To p
Return Air
29.5"
(749 mm)
19"
(483 mm)
14"
(356 mm)
22"
(559 mm)
22"
(559 mm)
Return Air
29.5"
(749 mm)
Ventilation
Exhaust
Air Outlet
6”
(150 mm)
4" (100 mm)
Ventilation
Supply
Air Inlet
6”
(150 mm)
Return Air End
(483 mm)
12"
(305 mm)
19"
Blower Section
17.25"
19"
(438 mm)
(483 mm)
Supply Air End
47.5"
(SERVICE CLEARANCE 10")
(1207 mm)
16"
(406 mm)
29.5"
(749 mm)
Latches
Supply Air
Front
Service
Drain
Page 34
34
Options
99-186 Weatherhoods, Two - 6" (150 mm)
c/w 1/4" (6 mm) mesh screen
99-130W Remote Wall Mount Dehumidistat Control 24
VAC only
99-RSK6 6” (150 mm) back draft damper
99-104 DET - Digital Electronic Timer
Core Ventilation system has patented aluminum heat recovery core (standard) or an enthalpic energy recovery core (optional) for ener-
gy-efficient ventilation. Enthalpic cores are recommended for regions where the temperature does not drop below 25°F (-4°C).
Filters Washable air filters in exhaust and supply air streams of ventilation section, 1" (25 mm) pleated in return plenum side.
Case Prepainted galvanized steel for superior corrosion resistance. Service drain 1/2” (12 mm) or 3/4” (19 mm) NPT.
Warranty
Units carry a lifetime warranty on the heat recovery (alu­minum) core, a five year warranty on the energy recovery (enthalpic) core and a five year replacement parts warranty on all other components.
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
Dimensions & Clearances
Model CAF-H-L4A-36-P16
Voltage 120 VAC 60 Hz
Hp 1/2
Amps (total) 10.6
Water
3/4" ( 19 mm) Copper
Connections Soldered Connection
Airflow (High) .25 in wg
1350 CFM
.5 in. wg 1180 CFM
Ventilation 100 - 140 CFM Airflow
Effectiveness 70% (Aluminum Core)
Total Efficiency 50% (Enthalpic Core)
Net Weight 150 lbs.
Shipping Weight 165 lbs.
Note: All units conform to CSA and UL Standards.
Model CAF-H-L4A-36-P16
14"
(356 mm)
29.5"
(749 mm)
19"
(483 mm)
Return Air
14"
(356 mm)
22"
(559 mm)
(559 mm)
Return Air
29.5"
(749 mm)
22"
Ventilation
Exhaust
Air Outlet
6"
(150 mm)
4" (100 mm)
Ventilation
Supply
Air Inlet
(150 mm)
Return Air End
6"
(305 mm)
19"
(483 mm)
Side
19"
(483 mm)
12"
Supply Air End
Blower Section
(SERVICE CLEARANCE 10")
17.25"
(438 mm)
47.5"
(1207 mm)
(559 mm)
Supply Air
29.5"
(749 mm)
Latches
22"
Front
Service
Drain
Page 35
35
Options
99-186 Weatherhoods, Two - 6" (150 mm)
c/w 1/4" (6 mm) mesh screen
99-130W Remote Wall Mount Dehumidistat Control 24
VAC only
99-RSK6 6” (150 mm) back draft damper
99-104 DET - Digital Electronic Timer
Dimensions & Clearances
Core Ventilation system has patented aluminum heat recovery core (standard) or an enthalpic energy recovery core (optional) for
energy-efficient ventilation. Enthalpic cores are recommended for regions where the temperature does not drop below 25°F (-4°C).
Filters Washable air filters in exhaust and supply air streams of ventilation section, 1" (25 mm) pleated in return plenum side
Case Prepainted galvanized steel for superior corrosion resistance.
Note: Ventilation ports and return plenum
opening available off either side of cabinet.
All units conform to CSA and UL Standards.
Model CAF-U-L2A-48-P16
Voltage 120 VAC 60 Hz
Hp 1/2
Amps (total) 10.6
Water
1/2" (12 mm) Copper
Connections Soldered Connection
Airflow (High) .25 in wg
1888 CFM
.5 in. wg 1589 CFM
Ventilation 100 - 140 CFM Airflow
Effectiveness 70% (Aluminum Core)
Total Efficiency 50% (Enthalpic Core)
Net Weight 150 lbs.
Shipping Weight 165 lbs.
Warranty
Units carry a lifetime warranty on the heat recovery (alu­minum) core, a five year warranty on the energy recovery (enthalpic) core and a five year replacement parts warranty on all other components.
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
Model CAF-U-L2A-48-P16
29.5"
(749 mm)
22.25"
(565 mm)
Supply Air
To p
17.25"
19"
(483 mm)
(438 mm)
Side
12"
(305 mm)
6"
Ventilation Supply
(150 mm)
6"
(150 mm)
Return Air
Air Inlet
Ventilation Exhaust Air Outlet
22"
(559 mm)
29.5"
(749 mm)
4" (100 mm)
14"
(356 mm)
(SERVICE CLEARANCE 1') (SERVICE CLEARANCE 3')
Front
Latches
Blower Section
19"
(483 mm)
47.5" (1207 mm)
Page 36
36
Options
99-186 Weatherhoods, Two - 6" (150 mm)
c/w 1/4" (6 mm) mesh screen
99-130W Remote Wall Mount Dehumidistat Control 24
VAC only
99-RSK6 6” (150 mm) back draft damper
99-104 DET - Digital Electronic Timer
Core Ventilation system has patented aluminum heat recovery core (standard) or an enthalpic energy recovery core (optional) for
energy-efficient ventilation. Enthalpic cores are recommended for regions where the temperature does not drop below 25°F (-4°C).
Filters Washable air filters in exhaust and supply air streams of ventilation section, 1" (25 mm) pleated in return plenum side.
Case Prepainted galvanized steel for superior corrosion resistance.
Dimensions & Clearances
Model CAF-U-00-36-P16
Voltage 120 VAC 60 Hz
Hp 1/2
Amps (total) 10.6
*Airflow (High)
.25 in wg
1350 CFM
.5 in. wg
1180 CFM
Ventilation 100 - 140 CFM Airflow
Effectiveness 70% (Aluminum Core)
Total Efficiency 50% (Enthalpic Core)
Net Weight 115 lbs.
Shipping Weight 130 lbs.
* Airflow performance assumes an evaporator coil static pressure loss of .25” WC
Warranty
Units carry a lifetime warranty on the heat recovery (alu­minum) core, a five year warranty on the energy recovery (enthalpic) core and a five year replacement parts warranty on all other components.
Note: Ventilation ports and return plenum
opening available off either side of cabinet.
All units conform to CSA and UL Standards.
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
Model CAF-U-00-36-P16
29.5"
(749 mm)
22.25"
(565 mm)
Supply Air
To p
17.25”
19”
(438 mm)
(483 mm)
Side
12"
(305 mm)
Ventilation
6"
Supply Air
(150 mm)
4”
(100 mm)
(356 mm)
Inlet
Ventilation
6"
Exhaust Air
(150 mm)
Outlet
22”
(559 mm)
14"
Return Air
29.5"
(749 mm)
(SERVICE CLEARANCE 1') (SERVICE CLEARANCE 3')
Front
Latches
Blower Section
19"
(483 mm)
47.5" (1207 mm)
Page 37
37
Options
99-186 Weatherhoods, Two - 6" (150 mm)
c/w 1/4" (6 mm) mesh screen
99-130W Remote Wall Mount Dehumidistat Control 24
VAC only
99-RSK6 6” (150 mm) back draft damper
99-104 DET - Digital Electronic Timer
Core Ventilation system has patented aluminum heat recovery core (standard) or an enthalpic energy recovery core (optional) for ener-
gy-efficient ventilation. Enthalpic cores are recommended for regions where the temperature does not drop below 25°F (-4°C).
Filters Washable air filters in exhaust and supply air streams of ventilation section, 1" (25 mm) pleated in return plenum side.
Case Prepainted galvanized steel for superior corrosion resistance.
Dimensions & Clearances
Model CAF-U-00-48-P16
Voltage 120 VAC 60 Hz
Hp 1/2
Amps (total) 10.6
*Airflow (High)
.25 in wg
1888 CFM
.5 in. wg 1589 CFM
Ventilation 100 - 140 CFM Airflow
Effectiveness 70% (Aluminum Core)
Total Efficiency 50% (Enthalpic Core)
Net Weight 132 lbs.
Shipping Weight 147 lbs.
* Airflow performance assumes an evaporator coil static pressure loss of .25” WC.
Warranty
Units carry a lifetime warranty on the heat recovery (alu­minum) core, a five year warranty on the energy recovery (enthalpic) core and a five year replacement parts warranty on all other components.
Note: Ventilation ports and return plenum
opening available off either side of cabinet.
All units conform to CSA and UL Standards.
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
Model CAF-U-00-48-P16
29.5"
(749 mm)
22.25"
(565 mm)
Supply Air
To p
17.25”
19”
(438 mm)
(483 mm)
Side
12"
(305 mm)
Ventilation
6"
Supply Air
(150 mm)
4”
(100 mm)
(356 mm)
Inlet
Ventilation
6"
Exhaust Air
(150 mm)
Outlet
22”
(559 mm)
14"
Return Air
29.5"
(749 mm)
(SERVICE CLEARANCE 1') (SERVICE CLEARANCE 3')
Front
Latches
Blower Section
19"
(483 mm)
47.5" (1207 mm)
Page 38
38
System Commissioning
This section of the manual is designed to be used with the “Commissioning of Integrated Combo System” worksheet. The worksheet is designed to guide you through the start-up process in a logical, step by step method which should mini­mize the work and time involved in having the system meet the designed parameters.
The following conditions are assumed:
• The air filter is in place
• All supply diffusers and return grilles are fully open and unrestricted
• Hot water is available to the furnace
• The drain valve for the heating loop is closed
• The shut off valves for the heating loop are fully open
• The throttling valve for the heating loop (if applicable), is fully opened
• Electrical power is available at the furnace
• The return air temperature from the house is approxi­mately 70°F (21°C)
Page 39
39404142434445
Page 40
Page 41
Page 42
Page 43
Page 44
Page 45
Standard Motor Wiring Diagram
T20
FEED
RELAY
YELLOW
RED
54321
Fan
Motor
BLACK
BLUE
WHITE
BLUE
T18 T19
C6 C7
C5
C4
N.O.
COM
N.O.
COM
N.O.
Fan Hi Fan Med Fan Low
K3 K4 K5
COM
N.O.
K6
COM
Pump
WHITE
BLACK
BLACK
ON
Neutral
SPARE
K7 K1 K2K8
CR1
T43
N.C
F2 MAX 2 amp
TP1
T42
N.0. COM N.C. N.0. COM N.C. N.0. COM N.C. N.0 . COM
P2 P3
Digital Controls
T41
T40
T39
T38
T37
T36
T35
T34
T33
T32
T31
24Vac12Vac Com
R
Defrost
Freeze
DET
98-CAF-AH-01
Contact 2 Contact 3 Contact 4
Contact 1
T30
T29T28REDOGYWRCT25
A/C Unit
N.O. Normally open
Standard Motor CAF/Air Handler Wiring Diagram
N.C. Normally closed
COM Common
T# Terminal
P# Plug
K# Relay
F# Fuse
SW1
8 7 6 5 4 3 2 1
AUX
Line
T4 T5 T6 T7 T8 T9 T10 T11 T12 T13 T14 T15 T16 T17
T2 T3
T1
WHITE
BLACKBLACK
SW# Switch
GND
BLACK
BLACK
Door Switch
T21 T22 T23 T24
AUX
DIP SWITCHES TO BE
ADJUSTED BY QUALIFIED
TECHNICIANS ONLY.
2
P1
MAX
12/24Vac
C1
VDR1
1
amp
1
F1
Transformer
THERMISTOR
C
T26 T27 GRNYEL
RED
BLUE
WHITE
To “ Y”
RWY G
To “ C”
Thermostat
WARNING
Do not initiate power before plumbing is commissioned.
Page 46
46
ECM Wiring Diagram
1005
ADJUST DELAY
COOL HEAT
RED
98-CAF-ECM-01
SW1
ADJUST DELAY
HEAT
COOL
12 34 567 8
off on
T2
T1
WHITE
BLACK
PURPLE
Molex
Connectors
5
432
1
Jumper
(120 VOLT Only)
WHITE
BLACK
BLUE
BLACK/YELLOW
TAN
Pump
RED
BROWN
T20
FEED
Fan Motor
9
12345678
RELAY
N.O.
10111213141516
COM
BLUE
ORANGE
GREEN
YELLOW
N.O.
T18 T19
C6 C7
C4
COM
N.O.
Fan Hi Fan Med Fan Low
K3 K4 K5
COM
N.O.
K6
COM
SPARE
K7 K1 K2K8
T43
N.C
F2 MAX 2 amp
N.0. COM N.C. N.0. COM N.C. N.0. COM N.C. N.0 . COM
T42
P2 P3
T40
T39
T38
T37
T36
T35
T34
T33
T32
T31
24Vac12Vac Com
R
Defrost
Freeze
T41
Contact 2 Contact 3 Contact 4
Contact 1
T30
T29T28REDOGYWRCT25
THERMISTOR
PURPLE
BLUE
BROWN
TAN
GREEN
BLACK/YELLOW
YELLOW
WHITE
BLACK
RED
ECM - CAF/Air Handler Wiring Diagram
WHITE
GND
WHITE
BLACK
Neutral
ON
CR1
DET
TP1
Digital Controls
ECM
BLOCK
TERMINAL
(TBM)
A/C Unit
GO
SW1
1
To “ C”
To “ Y”
YY
8 7 6 5 4 3 2 1
Line
T4 T5 T6 T7 T8 T9 T10 T11 T12 T13 T14 T15 T16 T17
T21 T22 T23 T24
T2 T3
T1
BLACKBLACK
BLACK
BLACK
Door Switch
DIP SWITCHES TO BE
ADJUSTED BY QUALIFIED
TECHNICIANS ONLY.
2
AUX
1
AUX
1
F1
amp
MAX
12/24Vac
Transformer
P1
C1
VDR1
C
T26 T27 GRNYEL
RED
BLUE
WHITE
2
CRWW
N.O. Normally open
N.C. Normally closed
COM Common
T# Terminal
P# Plug
RWY G
K# Relay
F# Fuse
Thermostat
SW# Switch
WARNING
Do not initiate power before plumbing is commissioned.
Page 47
47
Page 48
The new BES is the perfect way to ventilate specific locations with a Clean Air Furnace. The BES allows you to exhaust multiple areas quietly and economically while also providing heat recovery through the Clean Air Furnace integrated heat recovery core.
Bathroom Exhaust System
Part # 99-CAF-BESKIT
Features
• BES Control Box
• Quantum 4/5/6 COMBI Fan
• Fan Speed Selection
NEW!
From Lifebreath
Loading...