• High efficiency 3-speed direct drive ECM
blower motor is standard on all models.
• 2 stage heating* & 2 stage cooling.
• Add on cooling capacity 2 to 5 tons.
• Heating output 17,000 to 75,000 BTUH.
• Heat pump compatible.
• 36 airflow combinations available
on each unit.
* 2nd stage heating is standard on all units except the 5kW
Lifebreath Electric
Furnace
Output
Model AH-ELE-5KW-24-E16 (17,000 BTUH)
Install up to 2 tons of add on air conditioning
Model AH-ELE-9KW-30-E16 (30,000 BTUH)
Install up to 2.5 tons of add on air conditioning
Model AH-ELE-15KW-36-E16 (51,000 BTUH)
Install up to 3 tons of add on air conditioning
Model AH-ELE-18KW-48-E16 (60,000 BTUH)
Install up to 4 tons of add on air conditioning
Model AH-ELE-22KW-60-E16 (75,000 BTUH)
Install up to 5 tons of add on air conditioning
For more information visit www.lifebreath.com
Model AH-ELE-22KW-60-E16
Voltage 240 VAC 60 Hz
Hp 1
Amps (total) 120
Breaker Amps 60
(Feeder 1)
Breaker Amps 60
(Feeder 2)
Breaker Amps 20
(Feeder 3)
Stages 2 stage Heat/
2 stage Cool
Return Air 23" x 18" or 23” x 14.25”
Opening 584 mm x 457 mm or
584 mm x 362 mm
Supply Air 17.25" x 16"
Opening 438 mm x 406 mm
Net Weight 165 lbs. Shipping Weight 180 lbs.
Model AH-ELE-18KW-48-E16
Voltage 240 VAC 60 Hz
Hp 3/4
Amps (total) 100
Breaker Amps 60
(Feeder 1)
Breaker Amps 60
(Feeder 2)
Stages 2 stage Heat/2
stage Cool
Return Air 23" x 18" or 23” x 14.25”
Opening 584 mm x 457 mm or
584 mm x 362 mm
Supply Air 17.25" x 16"
Opening 438 mm x 406 mm
Model AH-ELE-15KW-36-E16
Voltage 240 VAC 60 Hz
Hp 1/2
Amps (total) 80
Breaker Amps 40
(Feeder 1)
Breaker Amps 60
(Feeder 2)
Stages 2 stage Heat/2
stage Cool
Return Air 14.25" x 23.25"
Opening 362 mm x 591 mm
Supply Air 17.25" x 16"
Opening 438 mm x 406 mm
Specifications AH-04
Note:
All connections to be made by
qualified contractors.
5 year replacement parts warranty on
all components.
Models
AH-ELE-5KW-24-E16
AH-ELE-9KW-30-E16
AH-ELE-15KW-36-E16
Models
AH-ELE-18KW-48-E16
AH-ELE-22KW-60-E16
Model AH-ELE-5KW-24-E16
Voltage 240 VAC 60 Hz
Hp 1/2
Amps (total) 30
Breaker Amps 40
Stages 1 stage Heat/2
stage Cool
Return Air 14.25" x 23.25"
Opening 362 mm x 591 mm
Supply Air 17.25" x 16"
Opening 438 mm x 406 mm
Net Weight 140 lbs. Shipping Weight 155lbs.
Model AH-ELE-9KW-30-E16
Voltage 240 VAC 60 Hz
Hp 1/2
Amps (total) 60
Breaker Amps 60
Stages 2 stage Heat/2
stage Cool
Return Air 14.25" x 23.25"
Opening 362 mm x 591 mm
Supply Air 17.25" x 16"
Opening 438 mm x 406 mm
Net Weight 140 lbs. Shipping Weight 155lbs.
Net Weight 140 lbs. Shipping Weight 155lbs.
Net Weight 165 lbs. Shipping Weight 180 lbs.
98-AH-04-SALES
Revised: 06/06
16”
(406 mm)
19”
(483 mm)
17.25”
(438 mm)
29.75”
(756 mm)
Duct
Opening
16”
(406 mm)
21”
(533 mm)
17.25”
DUCT
OPENING
(438 mm)
29.75”
(756 mm)
Side
23.25”
(591 mm)
Return
Air
Opening
29.75”
(756 mm)
Service Clearance 1' (305 mm)
Side
23”
(584 mm)
Return
18”
Air
(457 mm)
Opening
14.25”
(362 mm)
29.75”
(756 mm)
Service Clearance 1' (305 mm)
14.25”
(362 mm)
Service Clearance 3' (914 mm)
Service Clearance 3' (914 mm)
Fron t
Fron t
19”
(483 mm)
21”
(533 mm)
33.5”
851 mm
37.5”
(953 mm)