Lifebreath 850FD-DD, 700FD-DD, 700ERV, 500DCS, 500ERV User Manual

...
Page 1
CLEAN • FRESH • AIR
OPERATION AND
INSTALLATION MANUAL
®
For Models:
500DCS ControlAir 15 850FD/DDAnalog Controls 700FD/DD Analog Controls 1200FD/DD Analog Controls
500ERV ControlAir 15 700ERV Analog Controls 1200ERV Analog Controls
TO BE COMPLETED BY CONTRACTOR AFTER INSTALLATION
CAUTION
Before installation, careful consideration must be given to how the system will operate if connected to any other piece of mechanical equipment, i.e. a forced air furnace or air handler, operating at a higher static. After compatibility confirmed, by measuring the airflow’s of the Heat/Energy Recovery Ventilator (HRV/ERV), by using the balancing procedure in this manual.
It is always important to assess how the operation of any HRV/ERV may interact with vented combustion equipment (ie. Gas Furnaces, Oil Furnaces, Wood Stoves, etc.).
NEVER install an HRV/ERV in a situation where its normal operation, lack of operation or partial failure may result in the backdrafting or improper functioning of vented combustion equipment!!!
NOTE: ALTHOUGH SOME MODELS DIFFER IN OPERATION, THE BASIC STEPS ARE SIMILAR.
installation, the
of the two pieces of equipment must be
Installing Contractor
Telephone / Contact
Serial Number
Installation Date Model
* LEAVE FOR HOMEOWNER
NOTE: Due to ongoing research and product development, specifications,
ratings and dimensions are subject to change without notice.
TI-72C-NE
0105
Page 2
Table of Contents
INTRODUCTION
Introduction .................................................................... 2
ERV Questions and Answers ......................................... 3
Select Correct HRV/ERV to Match Climate.....................4
Select the Correct Size HRV/ERV ................................ 5
Technical Data - Model 500DCS ................................... 6
Technical Data - Model 850FD/DD ............................... 7
Technical Data - Model 700FD/DD ............................... 8
Technical Data - Model 1200FD/DD ............................. 9
Technical Data - Model 500ERV ................................. 10
Technical Data - Model 700ERV ................................. 11
Technical Data - Model 1200ERV ............................... 12
Location for Mounting ................................................. 13
The Ductwork System ............................................. 13
Outside Weatherhoods ............................................... 14
Ducting from Weatherhoods ....................................... 14
Warmside Ducting - General ....................................... 14
Stale Air Return System ............................................. 14
Fresh Air Supply ......................................................... 15
The Integrated HVAC System ..................................... 15
Various Installation Types ........................................... 17
HRV - Aluminum Core
A Heat Recovery Ventilator (HRV) is designed to provide fresh air into a building while exhausting an equal amount of stale air. During the winter months, the incoming cold fresh air is warmed by utilizing the heat recovered from the stale air before it is exhausted to the outdoors. During summer months when the indoor space is air conditioned, the Heat Recovery Ventilator will help in cooling the incoming fresh air with the stale air that is being exhausted.
ERV - Enthalpic Paper Core
An Energy Recovery Ventilator (ERV) is designed to provide fresh air into a building while exhausting an equal amount of stale air. An ERV is designed for use in warm humid areas with heavy air conditioning use. The ERV will transfer both sensible and latent heat from the incoming fresh air to the outgoing stale air thereby reducing the load (due to ventilation) on the air conditioning system.
Electrical Connections ............................................. 18
Fan Defrost (700, 850, 1200) ...................................... 18
Damper Defrost (700, 850, 1200)................................. 18
Self Test of Defrost Systems (700, 850, 1200) ............ 18
Speed Selection and Controls (700, 850, 1200) .......... 19
Optional Remote Controls (700, 850, 1200) ................ 19
ControlAir 15 (500 Only) ............................................. 20
Function And Control (500 Only) ................................ 21
Mode of Operation for ControlAir 15 (500 Only) ......... 22
Pitot Tube Air Flow Balancing ................................. 23
Service/Maintenance ................................................ 24
Motor ........................................................................... 24
HRV Core .................................................................... 24
ERV Core .................................................................... 24
Filters .......................................................................... 25
Condensate Drains ..................................................... 25
Duct Work ................................................................... 25
Damper Motor ............................................................. 25
Troubleshooting your HRV/ERV System ................ 26
ERVs are not suitable for climates where the temperature drops below -4˚C (25˚F).
Wiring Diagrams ............................................. 27-29
Warranty .................................................................... 30
2
Page 3
ERV Questions & Answers
What is the difference between an HRV and an ERV?
The core in an HRV (Heat Recovery Ventilator) transfers heat from one air stream to the other. This is called sensible heat. The term ERV (Energy Recovery Ventilator) is usually used to describe a unit with an enthalpic core that transfers moisture as well as heat from one air stream to the other. This (moisture transfer) is called latent heat.
Enthalpic - what does it mean?
Enthalpy is the term used to describe the energy content of air. This energy is a combination of the sensible and latent heat. Therefore, a core which transfers energy is called an enthalpic core.
Is an ERV better than an HRV?
NOT NECESSARILY!! In cold climates such as most of North America, an HRV works better than an ERV. This is because the air inside the home during the winter months will be more humid than the outside air. An ERV would transfer the latent heat (humidity) from the exhaust air back into the incoming airstream. This will aggravate moisture problems in the home and encourage the growth of mold and mildew. If the air in the home is too dry for comfort, an ERV will not help. A humidifier should be used to increase the humidity to a comfortable level.
and damp situation. In fact, about 2/3 of the energy used by the air conditioner system is to remove moisture. Therefore, when ventilating in the summer, less moisture brought into the home means less work for the air conditioner, and energy savings for you.
During the winter, an ERV recovers some humidity from the exhaust air, reducing the need for humidification if the required ventilation rate would make the home too dry.
,
What's the difference between this type of core and a rotary type?
Here's a list of characteristics of the fixed plate core.
1. No rotating parts, so maintenance is easy and the unit lasts a long time.
2. It is very flexible in terms of installation.
3. The core can easily be changed.
4. Because the supply and exhaust air streams are
completely separate, there is very little cross leakage of any dust or germs.
Can the core become clogged with dust?
Because the surface of the core is a turbulent flow area, dust sticks to it easily; however, because the inside of the element is a laminar flow area, virtually no dust sticks to it.
Where do you use an ERV instead of an HRV?
An ERV is recommended for warm, humid areas with heavy air conditioning use. As there is no defrost in an ERV it is not recommended for areas where the temperature drops below -4˚C (25˚F)
Why transfer moisture in the summer (cooling season)?
The enthalpic core will allow moisture to be transferred from a humid air flow to a dry air flow. This property is useful in the cooling season if an air conditioning system is used to lower the indoor humidity. You will then have dry, cool air in the exhaust of the ERV, and warm humid air in the supply stream. With these conditions, the ERV will be able to transfer the moisture and heat of the supply air to the exhaust air. In this way, the ERV will supply to the home air which is cooler and drier than outside. Remember that an ERV is not a dehumidifier, and on its own will not take moisture out of the air.
So why use an ERV?
A properly operating air conditioner will not only lower the temperature in your house, but will also lower the humidity level. This prevents an uncomfortable cold
What is the maintenance?
About once a year you should use a vacuum cleaner to remove the dust from the core's surface. DO NOT WASH WITH WATER!!
Is an air filter needed?
To prevent clogging of the core, an air filter should always be installed on the supply and exhaust sides of the core.
How much ventilation do I need?
During seasons when your windows and doors are closed, the ERV should operate continuously when the dwelling is occupied, and either continuously or intermittently when not occupied.
For most installations the ERV will normally be set to operate continuously on low speed with the option of going to high speed as the need arises. For example; if you are entertaining and there is a large number of people present (some may be smoking), the unit should be switched to high speed.
Your ERV may be equipped with automatic or manual switches, but all ERVs will have a manual speed control override.
3
Page 4
4
Page 5
Selecting the Correct Size HRV/ERV
Commercial and Institutional Requirements
For outdoor air requirements, ASHRAE has produced the Ventilation Standard 62-1989 that is used to determine acceptable ventilation rates. This standard is referenced directly or used as “Good Engineering Practice” in most Code documents or design criteria.
Small restaurants, Donut Shops and Fast food stores
Seats 40 Employees 5 Total 45 ASHRAE requirement 20 cfm (10L/s) per person Ventilation required 45 x 20 = 900 cfm (450 L/s)
Bar or Tavern
Seats 50 Employees 7 Total 57 ASHRAE requirement 30 cfm (15L/s) per person Ventilation required 57 x 30 = 1710 cfm (855 L/s)
Classroom and School Portables
Seats 29 Teacher 1 Total 30 ASHRAE requirement 15 cfm (7.5L/s) per person Ventilation required 30 x 15 = 450 cfm (255 L/s)
Beauty Salon
Customers 12 Employees 6 Total 18 ASHRAE requirement 25 cfm (12.5L/s) per person Ventilation required 18 x 25 = 450 cfm (255 L/s)
Bank
Customers 25 Staff 9 Total 34 ASHRAE requirement 20 cfm (10L/s) per person Ventilation required 34 x 20 = 680 cfm (320 L/s)
Bingo Hall
Customers 180 Staff 20 Total 200 ASHRAE requirement 30 cfm (15L/s) per person Ventilation required 200 x 30 = 6000 cfm (3000 L/s)
Print Shop, Duplicating
Square footage of shop 2000 square ft (m
ASHRAE requirement 0.5 cfm/ft2 (2.5L/s - m
per person
Ventilation required 2000 x 0.5 = 1000 cfm (500 L/s)
Swimming Pools
Refer to “Pool” Models Installation Manuals.
2
)
2
)
MAKE UP HEAT REQUIREMENT at 1200 CFM (566L/s)
Nominal Nominal Nominal
Outdoor Temp. kW Req. for kW Req. for kW Req. for
20°C (68°F) 25°C (77°F) 30°C (86°F)
Air Delivery Air Delivery Air Delivery
0 32 7 10 14
-10 14 10 14 17
-20 -4 12 15 19
-30 -22 15 19 22
-40 -40 17 21 24
5
Page 6
Model 500DCS
SPECIFICATIONS
CORES
Modular (4 section) patented aluminum heat recovery cores arranged for high efficiency crossflow ventilation.
MOTORS
Two PSC, 5 speed double shafted, 120 VAC, 3.15 Amps each (6.3 total on high speed). HP - 1/10, 1625 RPM. Watts - total on High Speed - 610.
FILTERS
Washable air filters in exhaust and supply air streams.
BLOWERS
Centrifugal type rated at 530 cfm (250 L/s) free air delivery. Each air stream has two centrifugal blowers driven by two PSC motors.
CONNECTION DUCT SIZES
Four - 14" x 8" (356 mm x 200 mm).
MOUNTING
Unit to be set on support brackets hung by threaded rod type apparatus (brackets and rods not included).
CASE
20 gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated with foil faced insulation duct liner where required to prevent exterior condensation. Drain connection, One - 1/2" (12 mm) O.D.
CONTROLS ControlAir 15 DEFROST
Supply bypass damper routes indoor air to defrost cores. WEIGHT 178 lbs. (81 kg) SHIPPING WEIGHT 203 lbs. (92 kg)
PERFORMANCE
AIRFLOWS (Each Air Stream)
282 (600)
235 (500)
190 (400)
143 (300)
94 (200)
AIRFLOW L/s (CFM)
42 (100)
25 (.1)  50 (.2) 75 (.3) 100 (.4) 125 (.5)
EXTERNAL STATIC PRESSURE IN PASCALS (in. W.C.)
TEMPERATURE EFFECTIVENESS
100%
90%
EFFECTIVENESS
80%
94
(200)
143
(300)
AIRFLOW IN L/s (CFM)
SPEED
5 4
3 2 1
NOTE: Exhaust Relative Humidity (RH) at 40%
190
(400)
235
(500)
6.3 HIGH
3.8 MED
3.1 LOW
282
(600)
TOTAL CURRENT DRAW (AMPS) @ 120 VAC
DIMENSIONS 500DCS
EXHAUST AIR
TO OUTSIDE
NOTE:  Service clearance is 760 mm (30 in.)
SUPPLY AIR
FROM OUTSIDE
DEFROST
DRAIN CONNECTION
1245 mm
(
49"
)
FRONT VIEW
OPTIONS
99-104 Digital Electronic Timer - 20/40/60 min. (3 wire) 99-105 Programmable Ventilation Control
99-109 Air Sentry™ Air Quality Monitor designed to accept 99-250 Ventilation Dehumidistat - Dehumidistat designed
DATE: __________________________
PROJECT: ________________________________________
MECHANICAL CONTRACTOR: ________________________________
includes Programmable Time Clock, Dehumidistat and Air Sentry™
remotely mounted Control Pad
to accept remotely mounted Control Pad.
EXHAUST AIR
FROM BUILDING
475 mm
(
18 3/4"
SUPPLY AIR
TO BUILDING
6
32 mm
)
(
1 1/4")
INTERIOR DUCT
CONNECTION SIDE
All units conform to CSA and UL standards.
WARRANTY
Units carry a 15 year warranty on the heat recovery core and a 2 year replacement parts warranty.
356 mm
(14")
717 mm
(
28 1/4 "
inches (mm)
150 mm
(
5 7/8"
)
200 mm
(8")
)
475 mm
(
18 3/4"
MOUNTING POINTS
150 mm (
5 7/8"
)
35 mm
)
(
1 3/8"
)
EXTERIOR DUCT
CONNECTION SIDE
511 McCormick Blvd. London, Ontario
Ph: (519) 457-1904 Fx: (519) 457-1676 Email: nutech@lifebreath.com Website: www.lifebreath.com
356 mm
(14")
717 mm
(
28 1/4"
200 mm
(8")
)
N5W 4C8
TI-110-NE
0011
Page 7
Model 850FD/DD
SPECIFICATIONS
CORES
Modular (6 section) patented aluminum heat recovery cores arranged for high efficiency crossflow ventilation.
MOTORS
Two PSC, 3 speed double shafted, 120 VAC, 3.95 Amps each (7.9 total on high speed). HP - 1/4, 1625 RPM. Watts - total on High Speed - 848.
FILTERS
Washable air filters in exhaust and supply air streams.
BLOWERS
Centrifugal type rated at 950 cfm (448 L/s) free air delivery. Each air stream has one double shafted motor driving two centrifugal blowers.
CONNECTION DUCT SIZES
Three - 20" x 8" (508 mm x 200 mm). Stale air intake - 26" x 8" (660 mm x 200 mm). Model 850DD - additional 20" X 8" defrost port
MOUNTING
Unit to be set on support brackets hung by threaded rod type apparatus. (brackets and rods not provided).
CASE
20 gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated with foil faced insulation where required to prevent exterior condensation. Drain connections, Two - 1/2" (12 mm) O.D.
CONTROLS
Illuminated power switch, 3 speed blower control, low voltage (24 VAC) terminals for connection of remote controls and defrost light indicating automatic operation.
DEFROST CONTROLS
Model 850FD - Interrupts supply air while exhaust air defrosts core. Model 850DD - Supply bypass routes indoor air to defrost core.
WEIGHT 255 lbs. (116 kg) SHIPPING WEIGHT 280 lbs. (127 kg)
PERFORMANCE
AIRFLOWS (Each Air Stream)
475 (1000) 425 (900) 378 (800) 329 (700) 282 (600) 235 (500) 190 (400) 143 (300) 94 (200)
AIRFLOW L/s (CFM)
42 (100)
25 (.1) 50 (.2) 75 (.3) 100 (.4) 125 (.5) 150 (.6) 175 (.7)
EXTERNAL STATIC PRESSURE IN PASCALS (in. W.C.)
TEMPERATURE EFFECTIVENESS
90%
80%
EFFECTIVENESS
70%
282
235
(600)
(500)
AIRFLOW IN L/s (CFM)
HIGH SPEED
MED SPEED
LOW SPEED
NOTE: Exhaust Relative Humidity (RH) at 40%
329
378
(700)
(800)
(900)
7.9 HIGH
7.0 MED
6.6 LOW
425
TOTAL CURRENT DRAW (AMPS) @ 120 VAC
DIMENSIONS 850
EXHAUST AIR
TO OUTSIDE
NOTE:  Service clearance is 760 mm (30 in.)
SUPPLY AIR
FROM OUTSIDE
DEFROST AIR
DD MODELS ONLY
1188 mm
(46 3/4")
DRAIN CONNECTION
FRONT VIEW
OPTIONS
99-101 Sixty Minute Timer 99-130 Remote Wall Mount Dehumidistat Control
24 VAC only
DATE: __________________________
PROJECT: ________________________________________
MECHANICAL CONTRACTOR: ________________________________
EXHAUST AIR
FROM BUILDING
SUPPLY AIR
TO BUILDING
CONTROLS
200 mm
( 8")
172 mm
(6 3/4")
508 mm
1055 mm
(41 1/2")
INTERIOR DUCT
CONNECTION SIDE
All units conform to CSA and UL standards
WARRANTY
All units carry a 15 year warranty on the heat recovery cores and a 2 year replacement parts warranty.
7
mm (inches)
660 mm
(26")
(20")
190 mm (7 1/2 ")
263 mm
(10 3/8 ")
200 mm
(8")
625 mm (24 5/8")
MOUNTING POINTS
263 mm
(
10 3/8"
508 mm
)
(20")
149 mm
(5 7/8")
508 mm
(20")
EXTERIOR DUCT
CONNECTION SIDE
511 McCormick Blvd. London, Ontario
Ph: (519) 457-1904 Fx: (519) 457-1676 Email: nutech@lifebreath.com Website: www.lifebreath.com
200 mm
(8")
200 mm
(8")
N5W 4C8
TI-111
0011
Page 8
Model 700
FD/DD
SPECIFICATIONS
CORES
Modular (2 section) patented aluminum heat recovery cores arranged for efficient cross-flow ventilation.
MOTORS
Two PSC, 3 speed single shafted, 120 VAC, 2.75 Amps each (5.5 total on high speed). HP - 1/10, 1625 RPM. Watts - total on high speed - 648.
FILTERS
Washable air filters in exhaust and supply air streams.
BLOWERS
Centrifugal type rated at 329 L/s (700 CFM) free air delivery. Each air stream has one single shafted motor driving a centrifugal blower.
CONNECTION DUCT SIZES
Four - 356 mm x 200 mm (14" x 8" ).
MOUNTING
Unit to be set on support brackets hung by threaded rod type apparatus (brackets and rods not provided).
CASE
20 gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated with foil faced insulation where required to prevent exterior condensation. Drain connections; two - 12 mm (1/2") O.D.
CONTROLS
Illuminated power switch, 3 speed blower control, low voltage (24 VAC) terminals for connection of remote controls and defrost light indicating automatic operation.
DEFROST CONTROLS
MODEL 700 FD - Interrupts supply air while exhaust air defrosts core. MODEL 700DD - Supply bypass routes indoor air to defrost core. WEIGHT 64.4 kg (142 lbs.) SHIPPING WEIGHT 75.8 kg (167 lbs.)
PERFORMANCE
MODEL 700FD, 700DD
AIRFLOWS (Each Air Stream)
423 (900) 378 (800) 329 (700) 282 (600) 235 (500) 190 (400) 143 (300) 94 (200)
AIRFLOW L/s (CFM)
42 (100)
25 (.1) 50 (.2) 75 (.3) 100 (.4) 125 (.5) 150 (.6) 175 (.7)
EXTERNAL STATIC PRESSURE IN PASCALS (IN. W.C.)
TEMPERATURE EFFECTIVENESS
70%
60%
50%
EFFECTIVENESS
143
(300)
HIGH SPEED MED SPEED LOW SPEED
NOTE: Exhaust Relative Humidity (RH) at 40%
190
(400)
AIRFLOW IN L/s (CFM)
235
(500)
(600)
282
329
(700)
5.5 HIGH
5.0 MED
4.7 LOW
TOTAL CURRENT DRAW (AMPS) @ 120 VAC
SUPPLY AIR
FROM OUTSIDE
FD MODEL ONLY
NOTE:  Service clearance is 760 mm (30 in.) from front  access doors
EXHAUST AIR
FROM BUILDING
OPTIONS
DD MODEL ONLY
DRAIN CONNECTION
FRONT VIEW
753 mm (29 5/8")
DIMENSIONS 700
EXHAUST AIR
TO OUTSIDE
625 mm
(24 5/8 ")
HEAT RECOVERY VENTILATORS (HRVs)
¤
SUPPLY AIR
TO BUILDING
CONTROLS
DISCHARGE SIDE
All units conform to CSA and UL standards.
99-101 Sixty Minute Timer
WARRANTY
99-130 Remote Wall Mount Dehumidistat Control
24 VAC only
All units carry a 15 year warranty on the heat recovery cores and a 2 year replacement parts warranty.
DATE: __________________________
PROJECT: ________________________________________
MECHANICAL CONTRACTOR: ________________________________
8
mm (inches)
356 mm
(14")
200 mm
(8")
730 mm
(28 3/4")
210 mm
(8 1/4")
165 mm
MOUNTING POINTS
(6 1/2")
165 mm
(6 1/2")
356 mm
(14")
159 mm (6 1/4")
200 mm
(8")
730 mm
(28 3/4")
INLET SIDE
511 McCormick Blvd. London, Ontario
Ph: (519) 457-1904 Fx: (519) 457-1676 Email: nutech@lifebreath.com Website: www.lifebreath.com
N5W 4C8
TI-103
0011
Page 9
Model 1200FD/DD
SPECIFICATIONS
CORES
Modular (3 section) patented aluminum heat recovery cores arranged for efficient cross-flow ventilation.
MOTORS
Two PSC, 3 speed double shafted, 120 VAC, 4 Amps each (8.1 total on high speed). HP - 1/4, 1625 RPM. Watts - total on high speed - 972.
FILTERS
Washable air filters in exhaust and supply air streams.
BLOWERS
Centrifugal type rated at 1200 cfm (566 L/s) free air delivery. Each air stream has one double shafted motor driving a centrifugal blower.
CONNECTION DUCT SIZES
Four - 20" x 8" (508 mm x 200 mm).
MOUNTING
Unit to be set on support brackets hung by threaded rod type apparatus. (brackets and rod not provided).
CASE
20 gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated with foil faced insulation where required to prevent exterior condensation. Drain connections; two - 1/2" (12 mm) O.D.
CONTROLS
Illuminated power switch, 3 speed blower control, low voltage (24 VAC) terminals for connection of remote controls and defrost light indicating automatic operation.
DEFROST CONTROLS
MODEL 1200FD - Interrupts supply air while exhaust air defrosts core. MODEL 1200DD - Supply bypass routes indoor air to defrost core. WEIGHT 191 lbs. (87 kg) SHIPPING WEIGHT 215 lbs. (98 kg)
AIRFLOW L/s (CFM)
613 (1300) 566 (1200) 518 (1100) 472 (1000) 423 (900) 378 (800) 329 (700) 282 (600) 235 (500)
70%
60%
EFFECTIVENESS
50%
PERFORMANCE
AIRFLOWS (Each Air Stream)
8.1 HIGH
518
(1100)
7.8 MED
7.1 LOW
566
(1200)
HIGH SPEED
MED SPEED
LOW SPEED
25 (.1) 50 (.2) 75 (.3) 100 (.4) 125 (.5) 150 (.6) 175 (.7)
EXTERNAL STATIC PRESSURE IN PASCALS (in. W.C.)
TEMPERATURE EFFECTIVENESS
NOTE: Exhaust Relative Humidity (RH) at 40%
235
(500)
282
(600)
AIRFLOW IN L/s (CFM)
329
(700)
378
(800)
423
(900)
472
(1000)
TOTAL CURRENT DRAW (AMPS) @ 120 VAC
SUPPLY AIR
FROM OUTSIDE
FD MODEL ONLY
NOTE:  Service clearance is 760 mm (30 in.) from front  access doors
EXHAUST AIR
FROM BUILDING
DD MODEL ONLY
DRAIN CONNECTION
FRONT VIEW
DIMENSIONS 1200
EXHAUST AIR
TO OUTSIDE
HEAT RECOVERY VENTILATORS (HRVs)
759 mm (29 7/8")
¤
SUPPLY AIR
TO BUILDING
CONTROLS
DISCHARGE SIDE
mm (inches)
508 mm
(20")
1055 mm
(41 1/2")
OPTIONS
All units conform to CSA and UL standards
99-101 Sixty Minute Remote Timer 99-130 Remote Wall Mount Dehumidistat Control
24 VAC only
DATE: __________________________
PROJECT: ________________________________________
MECHANICAL CONTRACTOR: ________________________________
WARRANTY
All units carry a 15 year warranty on the heat recovery cores and a 2 year replacement parts warranty.
9
172 mm
(6 3/4")
200 mm
(8")
MOUNTING POINTS
263 mm (10 3/8")
625 mm
(24 5/8 ")
263 mm
(10 3/8")
508 mm
(20")
149 mm
(5 7/8")
200 mm
(8")
1055 mm
(41 1/2")
INLET SIDE
511 McCormick Blvd. London, Ontario
Ph: (519) 457-1904 Fx: (519) 457-1676 Email: nutech@lifebreath.com Website: www.lifebreath.com
N5W 4C8
TI-120
0011
Page 10
CLEAN • FRESH • AIR
®
Model 500ERV
SPECIFICATIONS
LATENT RECOVERY (MOISTURE) TRANSFER CORES
Modular (4 section) 2- Enthalpic, 2 Aluminum arranged for high efficiency crossflow ventilation. MOTORS - Two PSC, 5 speed double shafted, 120 VAC, 3.15 Amps each (6.3 total on high speed). HP - 1/10, 1625 RPM. Watts - total on High Speed - 610.
FILTERS - Washable air filters in exhaust and supply air streams. BLOWERS - Centrifugal type rated at 530 cfm (250 L/s) free air
delivery. Each air stream has two centrifugal blowers driven by two PSC motors.
CONNECTION DUCT SIZES Four - 14" x 8" (356 mm x 200 mm). MOUNTING - Unit to be set on support brackets hung by threaded
rod type apparatus (brackets and rods not included).
DEFROST - Damper defrost system. CASE - 20 gauge prepainted galvanized steel (G60) for superior
corrosion resistance. Insulated with foil faced insulation duct liner where required to prevent exterior condensation. Drain connection, One - 1/2" (12 mm) O.D.
CONTROLS - ControlAir 15 WEIGHT 178 lbs. (81 kg) SHIPPING WEIGHT 203 lbs. (92 kg)
PERFORMANCE
AIRFLOWS (Each Air Stream)
282 (600)
235 (500)
190 (400)
143 (300)
94 (200)
AIRFLOW L/s (CFM)
42 (100)
25 (.1)  50 (.2) 75 (.3) 100 (.4) 125 (.5)
EXTERNAL STATIC PRESSURE IN PASCALS (in. W.C.)
TEMPERATURE EFFECTIVENESS
100%
90%
EFFECTIVENESS
80%
94
(200)
143
(300)
AIRFLOW IN L/s (CFM)
SPEED
5 4
3 2 1
NOTE: Exhaust Relative Humidity (RH) at 40%
190
(400)
235
(500)
6.3 HIGH
3.8 MED
3.1 LOW
282
(600)
TOTAL CURRENT DRAW (AMPS) @ 120 VAC
DIMENSIONS 500ERV
EXHAUST AIR
TO OUTSIDE
NOTE:  Service clearance is 30 in. (760 mm)
SUPPLY AIR
FROM OUTSIDE
DEFROST
ENTHALPIC CORE ALUMINUM CORE
49"
DRAIN CONNECTION
(1245 mm)
FRONT VIEW
OPTIONS
99-104 Digital Electronic Timer - 20/40/60 min. (3 wire) 99-105 Programmable Ventilation Control includes
Programmable Time Clock, Dehumidistat and Air Sentry™
99-109 Air Sentry™ Air Quality Monitor designed to
accept remotely mounted Control Pad
DATE: __________________________
PROJECT: ________________________________________
MECHANICAL CONTRACTOR: ________________________________
EXHAUST AIR
FROM BUILDING
18 3/4"
(475 mm)
SUPPLY AIR
TO BUILDING
10
1 1/4"
(32 mm
)
INTERIOR DUCT
All units conform to CSA and UL standards.
WARRANTY
Units carry a 5 year warranty on the energy recovery cores, a 15 year warranty on aluminum cores and a 2 year replacement parts warranty.
ERVs are not recommended for regions where the design temperature is below 25°F (-4°C)
inches (mm)
14"
(356 mm)
28 1/4 "
(717 mm)
CONNECTION SIDE
5 7/8"
(150 mm)
8"
(200 mm)
18 3/4"
(475 mm)
MOUNTING POINTS
5 7/8"
(150 mm)
1 3/8"
(35 mm)
EXTERIOR DUCT
14"
(356 mm)
28 1/4"
(717 mm)
CONNECTION SIDE
511 McCormick Blvd. London, Ontario
Ph: (519) 457-1904 Fx: (519) 457-1676 Email: nutech@lifebreath.com Website: www.lifebreath.com
8"
(200 mm)
N5W 4C8
TI-130
0105
Page 11
CLEAN • FRESH • AIR
®
Model 700ERV
SPECIFICATIONS
LATENT RECOVERY (MOISTURE) TRANSFER CORES
Modular (2 section) enthalpic (moisture) transfer cores arranged for efficient cross-flow ventilation.
MOTORS
Two PSC, 3 speed single shafted, 120 VAC, 2.75 Amps each (5.5 total on high speed). HP - 1/10, 1625 RPM. Watts - total on high speed - 648.
FILTERS
Washable air filters in exhaust and supply air streams.
BLOWERS
Centrifugal type rated at 700 CFM (329 L/s) free air delivery. Each air stream has one single shafted motor driving a centrifugal blower.
CONNECTION DUCT SIZES
Four - 14" x 8" (356 mm x 200 mm)
MOUNTING
Unit to be set on support brackets hung by threaded rod type apparatus (brackets and rods not provided).
CASE
20 gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated with foil faced insulation where required to prevent exterior condensation.
CONTROLS
Illuminated power switch, 3 speed blower control, low voltage (24 VAC) terminals for connection of remote controls.
WEIGHT 142 lbs (64.4 kg) SHIPPING WEIGHT 167 lbs. (75.8 kg)
PERFORMANCE
AIRFLOWS (Each Air Stream)
423 (900) 378 (800) 329 (700) 282 (600) 235 (500) 190 (400) 143 (300) 94 (200)
AIRFLOW L/s (CFM)
42 (100)
25 (.1) 50 (.2) 75 (.3) 100 (.4) 125 (.5) 150 (.6) 175 (.7)
EXTERNAL STATIC PRESSURE IN PASCALS (IN. W.C.)
TEMPERATURE EFFECTIVENESS
70%
60%
50%
EFFECTIVENESS
143
(300)
HIGH SPEED MED SPEED LOW SPEED
NOTE: Exhaust Relative Humidity (RH) at 40%
190
(400)
AIRFLOW IN L/s (CFM)
235
(500)
(600)
282
329
(700)
5.5 HIGH
5.0 MED
4.7 LOW
TOTAL CURRENT DRAW (AMPS) @ 120 VAC
DIMENSIONS 700ERV
SUPPLY AIR
FROM OUTSIDE
NOTE:  Service clearance is 30 in. (760 mm)
EXHAUST AIR
FROM BUILDING
ENTHALPIC CORE
29 5/8"
(753 mm)
HEAT RECOVERY VENTILATORS (HRVs)
EXHAUST AIR
TO OUTSIDE
¤
SUPPLY AIR
TO BUILDING
24 5/8 "
(625 mm)
FRONT VIEW
OPTIONS
99-101 Sixty Minute Remote Timer
All units conform to CSA and UL standards.
DATE: __________________________
PROJECT: ________________________________________
MECHANICAL CONTRACTOR: ________________________________
CONTROLS
DISCHARGE SIDE
WARRANTY
Units carry a 5 year warranty on the energy recovery cores and 2 year replacement parts warranty.
ERVs are not recommended for regions where the design temperature is below 25°F (-4°C)
11
inches (mm)
14"
(356 mm)
8"
(200 mm)
28 3/4"
(730 mm)
8 1/4"
(210 mm)
6 1/2"
(165 mm)
MOUNTING POINTS
6 1/2"
(165 mm)
14"
(356 mm)
6 1/4"
(159 mm)
8"
(200 mm)
28 3/4"
(730 mm)
INLET SIDE
511 McCormick Blvd. London, Ontario
Ph: (519) 457-1904 Fx: (519) 457-1676 Email: nutech@lifebreath.com Website: www.lifebreath.com
N5W 4C8
TI-131
0105
Page 12
®
CLEAN • FRESH • AIR
SPECIFICATIONS
LATENT RECOVERY (MOISTURE) TRANSFER CORES
Modular (3 section) latent recovery (moisture) transfer cores arranged for efficient cross-flow ventilation.
MOTORS
Two PSC, 3 speed double shafted, 120 VAC, 4 Amps each (8.1 total on high speed). HP - 1/4, 1625 RPM. Watts - total on high speed - 972.
FILTERS
Washable air filters in exhaust and supply air streams.
BLOWERS
Centrifugal type rated at 1200 cfm (566 L/s) free air delivery. Each air stream has one double shafted motor driving a centrifugal blower.
CONNECTION DUCT SIZES
Four - 20" x 8" (508 mm x 200 mm).
MOUNTING
Unit to be set on support brackets hung by threaded rod type apparatus. (brackets and rod not provided).
CASE
20 gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated with foil faced insulation where required to prevent exterior condensation.
CONTROLS
Illuminated power switch, 3 speed blower control, low voltage (24 VAC) terminals for connection of remote controls. WEIGHT 191 lbs. (87 kg) SHIPPING WEIGHT 215 lbs. (98
kg)
Model 1200ERV
PERFORMANCE
AIRFLOWS (Each Air Stream)
613 (1300) 566 (1200) 518 (1100) 472 (1000) 423 (900) 378 (800) 329 (700)
AIRFLOW L/s (CFM)
282 (600) 235 (500)
25 (.1) 50 (.2) 75 (.3) 100 (.4) 125 (.5) 150 (.6) 175 (.7)
EXTERNAL STATIC PRESSURE IN PASCALS (in. W.C.)
TEMPERATURE EFFECTIVENESS
70%
60%
EFFECTIVENESS
50%
235
(500)
NOTE: Exhaust Relative Humidity (RH) at 40%
282
329
(700)
(800)
(600)
AIRFLOW IN L/s (CFM)
378
HIGH SPEED
MED SPEED
LOW SPEED
423
(900)
472
(1000)
518
(1100)
8.1 HIGH
7.8 MED
7.1 LOW
TOTAL CURRENT DRAW (AMPS) @ 120 VAC
566
(1200)
DIMENSIONS 1200ERV
EXHAUST AIR
HEAT RECOVERY VENTILATORS (HRVs)
TO OUTSIDE
¤
SUPPLY AIR
TO BUILDING
CONTROLS
(1055 mm)
DISCHARGE SIDE
20"
(508 mm)
41 1/2"
WARRANTY
SUPPLY AIR
FROM OUTSIDE
NOTE:
 Service clearance is 30 in. (760 mm) from front  access doors.
EXHAUST AIR
FROM BUILDING
OPTIONS
ENTHALPIC CORE
29 7/8"
(759 mm)
FRONT VIEW
Units carry a 5 year warranty on the energy recovery cores
99-101 Sixty Minute Remote Timer
and 2 year replacement parts warranty.
ERVs are not recommended for regions where the design
All units conform to CSA and UL standards.
temperature is below 25°F (-4°C)
DATE: __________________________
PROJECT: ________________________________________
MECHANICAL CONTRACTOR: ________________________________
12
inches (mm)
10 3/8"
(263 mm)
6 3/4"
(172 mm)
8"
(200 mm)
(625 mm)
24 5/8 "
10 3/8"
(263 mm)
20"
(508 mm)
5 7/8"
(149 mm)
8"
(200 mm)
41 1/2"
(1055 mm)
INLET SIDE
511 McCormick Blvd. London, Ontario
Ph: (519) 457-1904 Fx: (519) 457-1676 Email: nutech@lifebreath.com Website: www.lifebreath.com
N5W 4C8
TI-132
0105
Page 13
Location for Mounting
The Ductwork System
The HRV/ERV must be located in a conditioned space where the surrounding air temperature does not fall below 60˚F (16˚C). The unit must be mounted level (horizontal). The warranty will be void if these conditions are not met.
Typically the HRV/ERV is positioned close to an outside wall or the roof to simplify the connections and keep the length of insulated ducting required for the fresh air intake to a minimum.
A minimum clearance of 36 inches (90 cm) in front of the HRV/ERV is recommended to service the ventilator. The HRV/ERV may be mounted on an equipment platform providing the drain hoses are clear and there is sufficient space to open the doors for servicing.
Install the drain pans in the bottom of the HRV/ERV so the drain (not on all models) connections protrude through the holes provided. Use drain hoses with hose clamps to connect the drain pan outlets to a floor drain or standpipe. Make sure the drain line slopes down to the outlet. If this is not possible a condensate pump will be required for positive removal of the water. Protect the drain line from freezing.
A properly designed ducting system will allow the HRV/ERV to operate at its maximum efficiency. (Air flow will be restricted by undersized ducting, use of too many elbows, tees, bends, etc.). Always try to keep duct runs as short and straight as possible.
NOTE: Fully insulated ducting with an integral
vapour barrier must be used on all runs passing through unheated areas in order to avoid condensation problems and energy losses from the air steams.
All joints must be airtight, sealed and impervious to moisture. See specification sheets for each unit for exact duct sizes and location.
To minimize pressure drop and noise, galvanized metal ducts, properly sized, are recommended. Keep ducting as short as possible and use a minimum of elbows and tees. Connecting sections and shorter runs may be flexible ducting one size larger than the metal equivalent. Use flexible duct connectors at the transmission.
All duct joints must be secured with screws, rivets or duct sealant and sealed with aluminum duct tape to prevent leakage.
HRV/ERV
to avoid noise
DRAIN
SPOUT
Forming the “P” Trap
TAPE
HRV CABINET
DRAIN
SPOUT
TEE
CONNECTOR
TO DRAIN
13
Page 14
Outside Weatherhoods
The weatherhoods must have built-in “bird” screen with 1/4 in (63.5 mm) minimum mesh to prevent birds and rodents from entering into the ductwork. Do not smaller mesh as it will be very susceptible to plugging up. Gravity dampers at the vents must not be used as they will restrict air flow and often “seize up”. The preferred location of the outside weatherhoods is:
• no less than 10 ft. (3 m) apart from each other
• at least 18 in ( 46 cm) above snow line or ground level
• away from sources of contaminants, such as
automobile exhaust fumes, gas meters, garbage cans, containers, etc.
• not exposed to prevailing winds, whenever reasonable possible
The outside perimeter of the weatherhood must be caulked to prevent leakage into the building.
The design and size of the weatherhoods or louvres chosen by the installer must allow for adequate free area. Water and debris penetration of the system is minimized when the airflow does not exceed 1000 FPM (5.08 m/s) free area velocity.
use
Ducting from the Weatherhoods
All duct joints must be fastened with screws, rivets or duct sealant and wrapped with a quality duct tape to prevent leakage. We recommend aluminum foil tape.
Stale Air Return System
The stale air return system is used to draw air from the points in the building where the worst air quality problems occur. Balancing dampers and/or adjustable grilles are recommended on all return air lines which are used during installation to help balance the “draw” from different areas of the building.
Alternately, the stale air may be drawn directly from the return air duct. When this system is used, the air handler’s blower must constantly operate. The exhaust takeoff connection must be at least a 3 ft (1 m) from a directly connected HRV/ERV supply duct if both are connected to the same duct run. Static pressure of the air handlers return system should be noted and compensated for if, it is apparent that the static pressure of the return in the air handler will exceed .1 to .15” W.C.
A damper located just prior to the HRV/ERV is required to balance the stale air exhausted with the fresh air supply entering the building.
Galvanized sheet metal ducting with sufficient cross section with an integral single piece vapour barrier should be used to connect the HRV/ERV to the weatherhoods.
All ducting must meet UL Class 1 requirements.
A minimum R value of insulation should be equal to 4 (RSI 0.75)
A good bead of high quality caulking (preferably acousti­cal sealant) and taping with a high quality aluminum foil tape is recommended to seal the duct to both the HRV/ERV and the weatherhood.
Warmside Ducting - General
Ducting from the HRV/ERV to the different areas in the building should be galvanized metal whenever possible.
To minimize airflow losses in the ductwork system, all ducts should be as short as possible and with as few bends or elbows as possible. 45° elbows are preferred to 90° elbows. Use “Wye” (Y) fittings instead of “Tees” (T) whenever possible.
Return air suction points should be located on the opposite side of the room from the fresh air inlet. The inlets may be located in the ceiling or high on the walls and fitted with inlet grilles.
Many commercial activities produce air contaminants in the form of dusts, fumes, mists, vapours and gases. Contaminants should be controlled at the source so that they are not dispersed through the building nor allowed to increase to toxic concentration levels. The ventilator allows for economical operation of the HVAC system while effectively removing contaminants from the space. In designing the exhaust portion of the system the exhaust grilles are placed so as to remove the contaminants while not allowing them to enter the breathing zone of the occupants.
For contaminants that are lighter than air, grilles should be located high on the wall. If contaminants are heavier than air, a lower placement of the grilles will be required. Information on a contaminants specific gravity and toxicity should be available from chemical data sheets.
14
Page 15
Fresh Air Supply System
The Integrated HVAC System
The fresh air supply ductwork from the HRV/ERV may be directly connected to the return air duct of the forced air system. Check the air flow balance of the HRV/ERV with the air handler blower both “ON” and “OFF” to determine that it does not imbalance the HRV/ERV more than 10%. Also, it is advisable to include a short length of flex duct or other non-metallic connector in this hard ducted line in order to keep the HRV/ERV acoustically isolated and separately grounded (electrically) from the air handler. This will avoid a possible shock hazard to service people if a short to ground develops in one of the devices.
It may be necessary to install a separate fresh air supply ductwork system if the heating is other than forced air.
When installing an HRV/ERV, the designer and installer should be aware of local codes that may require smoke detectors and/or firestats in the HVAC or HRV/ERV ductwork.
Because an HRV/ERV is designed to bring fresh air into the building, structures may require supply voltage interrupt when smoke or flame sensors are triggered, or when a central fire alarm system is activated.
Supply air grilles may be ceiling or high wall mounted. Avoid locating incoming fresh air grilles that could cause a direct draft on the occupants as the incoming air may be below room temperature. A reheat duct heater can be installed to improve occupant comfort.
The use of balancing dampers or adjustable grilles to balance the flow rates into various rooms is recommended.
The use of balancing dampers or adjustable grilles as supply air diffusers and air exhaust covers are recommended. TECHGRILLES™ are round, efficient, sound absorbing devices available in 4”, 5”, 6” and 8” (100, 125, 150, and 200 mm) models.
Figure A and B
The HRV/ERV has become an integral component of the HVAC system. Figure A shows an HRV/ERV unit providing fresh air directly to the return air plenum of a rooftop heat/cool unit.
In the balanced airflow system, the HRV/ERV exhaust removes stale room air (eg. from lunch room, storage or copy area) and returns to the space an equal amount of fresh outdoor air, making the use of an economizer obsolete in conjunction with an HRV/ERV.
Many buildings have ceiling return air plenum as in Figure B. Fresh air from the HRV/ERV can be introduced directly into the ceiling space but this should occur near the air handler’s intake.
By operating the HRV/ERV on a 24 hour/7 day battery backed timer, the unit can be set to operate only when occupancy or indoor conditions require the air exchange.
In installations where it is satisfactory to provide general exhaust from the space, the air to be exhausted may be taken directly from the return air plenum to the HRV/ERV as it is drawn back to the air handler. Fresh air supplied by the HRV/ERV is then introduced directly into the return air plenum but at a location closer to the air handler. The air handler would have a constant running blower to effectively distribute the fresh air and remove the stale air. Balancing dampers would be located in both the HRV/ERV supply and exhaust ducts between the return air plenum and the HRV/ERV.
NOTE: At no time should the air handler T.E.S.P. on the return duct exceed that of the HRV/ERV .
TECHGRILLE
(optional) schematic
AIR FLOW
SUPPLY
AIR FLOW
EXHAUST
15
Page 16
The Integrated HVAC System
ROOFTOP
ECONOMIZER
UNIT
FRESH AIR SUPPLY
STALE AIR EXHAUST
Figure A
HRV/ERV UNIT
RETURN AIR DUCT or
BREATHER T
B.D.
B.D.
HRV/ERV FRESH AIR SUPPLY
SUPPLY DUCT
STALE AIR EXHAUST TO HRV/ERV
Example only - Duct connections not typical
ECONOMIZER
FRESH AIR SUPPLY
STALE AIR EXHAUST
Figure B
ROOFTOP
ROOF DECK
CEILING RETURN AIR PLENUM
12" BREATHER
HRV/ERV UNIT
B.D.
HRV/ERV FRESH AIR SUPPLY
Example only - Duct connections not typical
16
UNIT
SPACE
B.D.
STALE AIR EXHAUST
SUPPLY DUCTWORK
Page 17
Figure 7A
Saddle Installation
Various Installation Types
NOTE: When installing your HRV/ERV
flexible duct connectors should be installed between the HRV/ERV and the galvanized duct work.
Vibration Isolators
Threaded  rod and U channel (Supplied by others)
(Supplied by others)
Hang unit with suspended rods and "U" channel members.
Figure 7C
Suspended
PVC Support Straps (Supplied by others)
Figure 7B
Curb Mounted
Curb is wood or metal (Supplied by others)
Mount unit on wooden or metal curb assembly. Unit must be raised an adequate height for installation  and slope of drain lines.
May be anchored to  floor,leaving space  for drain connections 
Vibration Isolators (Supplied by others)
Unit Suspended using  Polyester reinforced PVC support straps.
17
Page 18
Electrical Connections
It is recommended that a licensed electrician make all electrical connections. It is very important that the unit be properly grounded. It is recommended that a separate 15 amp/120 volt circuit be used.
accumulation. After the defrost period, the fresh air supply fan automatically returns to the normal speed and fresh outside air continues to be drawn into the building. Water from the melted frost collects in the bottom drip pans and drains out through the bottom
W
ARNING: In order to prevent electric shock when
cleaning or servicing the HRV/ERV, it is extremely important to confirm the polarity of the power line that is
drain connections. The defrost cycle repeats automatically until the air temperature rises above 27˚F(-3˚C).
switched by the safety (disconnect) switch whose control arm is located on the outside of the electrical control box area. The hot line (black) is the proper line to be switched.
DAMPER DEFROST
To confirm the proper polarity, use a voltmeter or test lamp to make sure there is no power after the switch when the
Models 700DD, 850DD, 1200DD
door is open. Check between that point and ground (on the cabinet). This must be done as occasionally some buildings are improperly wired. Always make sure the HRV/ERV is properly grounded.
These damper defrost HRV’s have an electronically controlled damper defrost mechanism. If the outside temperature drops below 27˚F(-3˚C ), the defrost timer is activated. A motor driven damper door mechanism opens the defrost port and at the same time closes off the supply air from outside. After approximately 3 minutes, the damper operates in the opposite direction to close off the defrost port and reopen the fresh air at the supply port. The 27.5 minute wait time and 3 minute defrost cycle repeat until the temperature again
Line
Black White
Power Supply
Cord
rises above 27˚F (-3˚C).
Black
Neut.
Power Terminal Block.
Green
Self Test of Defrost Systems
Models 700, 850, 1200
GND.
If confirmation of the defrost system is needed, complete the following steps.
1. Disconnect power to the unit and open access/
Electrical Connection
2. Locate the “snap disc” type temperature sensor
FAN DEFROST
3. Disconnect the two wires from the HRV to the
Models 700FD, 850FD, 1200FD
4. Using a jump wire with alligator clips, join two
Fan defrost HRV’s are equipped with an electronically controlled fan defrost system to remove frost that collects on the warm air side of the aluminum heat transfer surfaces of the heat exchanger core. When the outside air temperature drops below 27˚F(-3˚C), defrost is activated which provides for an automatic defrost cycle. During the automatic defrost cycle the fresh air supply is shut off while the exhaust fan contin ues to operate. This allows warm inside air to flow through the heat exchanger core melting frost
5. Close access doors and power the unit. This procedure will simulate a defrost that would occur
automatically in the field when the outside temperature drops below -3˚C (27˚F).
maintenance doors. mounted in the upper left hand corner (cold air
stream) of the HRV. sensor, at the sensor. wires from the HRV together.
18
Page 19
Speed Selection and Controls
Model 700, 850 and 1200 HRV/ERV only
These models are equipped with a 3 speed control, low medium and high, as well as a lighted on/off switch and a 4 screw terminal strip. The terminal strip can be used to connect any low voltage device which will then jump the unit to high speed from whatever setting the speed control was on. The terminal strip can also be wired to allow the unit to be turned off from a
ON
OFF
ON/OFF ONLY
LOW
HIGH
LOW/HIGH ONLY
SWITCHING FROM REMOTE LOCATION
*Supplied and Installed by Contractor*
remote location as well as from high to low from a remote location. To wire the unit in this configuration you would need two electrical on/off switches to be installed at the remote location into a double gang electrical enclosure or side by side. One should be labeled on/off and the other should be labeled high/low.
ON/OFF SWITCH
ON
OFF
LOW
HIGH
ON/OFF/LOW/HIGH
COMMON
3 SPEED CONTROL
HIGH
ON/OFF
Optional Remote Controls
RED BLACK ORANGE
DEHUMIDISTAT VENTILATION
CONTROL (DVC)
PART NO. 99-116
•Turns ERV ON/OFF
• Dehumidistat increases ventilation when required
DEHUMIDISTAT
PART NO. 99-130W
•Provides high speed
ventilation when humidity
level exceeds setting
Dehumidistat  Setting Relative to Outside Conditions
WINTER:
Set dehumidistat between 30% to 40%.
If home is too dry,
adjust to higher setting.
If home is too humid,
adjust to lower setting.
SUMMER:
Set dehumidistat 
to OFF.
Off
10
20
60
50
30
40
60 MINUTE CRANK TIMER
PART NO. 99-101
•Provides high speed
ventilation for 60 minutes
This style of remote switching began approximately July 1997
19
Page 20
ControlAir 15
OPTIONAL REMOTE CONTROLS Model 500 Only
PROGRAMMABLE VENTILATION CONTROLLER (PVC)
LOCATION: Hallway, kitchen, office
& work place
(connect 1/unit only)
• Advanced digital remote.
• Digital dehumidistat.
• Full fan speed control. AIR SENTRY™
• Recirculation mode (on compatible
Air Quality Sensor built-in.
HRV/ERVs).
• 7 day, 24 hour programmable timer.
• Digital display and status lights.
• 100' (30 m) maximum wire length.
PART NO. 99-105
Connects to RED, ORANGE, GREEN and YELLOW terminals.
*NOTE: This device is NOT compatible with the Air Sentry.
NEW! VENTILATION DEHUMIDISTAT
LOCATION: Central location in house.
• Dehumidistat activates high speed
VENTILATION
DEHUMIDISTAT
over-ride when humidity level in home exceeds setting.
• Knockout designed to accept Control
Pad when remotely mounted, giving full HRV/ERV functionality & control from remote location.
NEW!
AIR SENTRY™ AIR QUALITY SENSOR
LOCATION: Kitchen, basement,
work place
• Digital Air Quality Monitor.
ENTRY
S
IR
A
ENSOR
S
UALITY
Q
IR
A
IGITAL
D
• Status light indicates fan speed.
(connect 1/unit only).
• Increases ventilation to remove odours and contaminants.
• Among gases detected are
FAN SPEED INDICATOR
cigarette smoke and formaldehyde.
• 100' (30 m) maximum wire length.
• Knockout designed to accept Control Pad when remotely mounted.
PART NO. 99-109
Connects to RED, GREEN and YELLOW terminals.
*NOTE:
This device is NOT compatible with the PVC.
ControlAir 15
Control Module
Control Pad
• All controls wire to matching colour on the Control Module.
• Control Pad can be removed and mounted in a remote location.
PART NO. 99-250
Connects to BLACK, RED, GREEN and YELLOW terminals. *Replaces 99-116 DVC & 99-230 VRD.
*Only compatible with ControlAir 15 electronics.
DIGITAL ELECTRONIC TIMER (DET)
LOCATION: Bathrooms & kitchen
Connect up to 8 on 300
If a PVC or Air Sentry is used, connect
up to 5 on 300
' wire max.
• Touch pad operation.
• 20/40/60 minute status lights.
• Compact wall mount unit.
• Mounts in 2x4 box. Shown with “decora” cover plate
PART NO. 99-104
Connects to RED, GREEN and YELLOW terminals.
' (91 m) wire max.
(99-107W).
Control Pad mounts in a 2”x 4” box or can be mounted in the optional Ventilation Dehumidistat or Air Sentry.
• Full fan speed control.
Three Modes of Operation
- Standby/ON
- 20 ON / 40 OFF
-
Recirculation
(on compatible HRV/ERVs)
*See individual control instructions for more details.
20
0011
Page 21
FUNCTION & CONTROL
Model 500 Only
Operating the ControlAir 15
Plugging in the HRV/ERV energizes the unit. A self test function will be performed every time the HRV/ERV is energized (refer to “Self Test” for more details). After the self test has completed successfully the HRV/ERV will default to Speed 1. This is the factory default setting. Follow the instructions found on the HRV/ERV door to select desired mode and speed, or refer to the instructions found on the following page.
Control Module
Control Pad
ControlAir 15 Exploded view
Self Test
Each time the test function will automatically initiate. During the self test the available (1-5), test the damper motor operation and will default back to the previous mode/speed selection, (factory default is Speed 1). Total self test duration is approximately 1 min. 30 sec.
HRV/ERV
HRV/ERV
is powered/energized the self
will cycle through all the speeds
Automatic Defrost Operation
(Not on all models)
The advanced technology of the digital microprocessor automatically activates the defrost system only as it is needed. To be an efficient heat recovery device, the HRV/ERV must effectively provide for core defrost as well as providing efficient heat exchange. As outdoor conditions cool, the temperature sensor (thermistor) tracks the supply air temperature. The thermistor then sends its signal to the microprocessor (circuit board) which initiates only the defrost cycle time required to clear the core. On recirculating defrost models, the core is defrosted when the supply air port is automatically blocked off and exhaust air is redirected back through the HRV/ERV. On damper defrost models, the core is defrosted when the supply air port is automatically blocked off and the warm air surrounding the HRV/ERV is drawn in through the defrost port. The mode indicator will flash RED during the defrost cycle. This dramatic advance makes more energy available for recovery as the unit spends less time in defrost mode. By optimizing the defrost cycle, the HRV/ERV combines money saving performance with a well designed and reliable control system.
Removing and relocating the Control Pad
The Control Pad can be removed and installed in a remote location (100’ wire length max). The Control Pad can be installed in a 2x4 box with a “Decora” type cover plate or can be installed in the optional “Ventilation Dehumidistat” or “Air Sentry”. When the Control Pad is installed in a remote location, all optional controls will still be wired to the Control Module on the remotely mounted on its own, the Control Pad is wired to the Control Module by 3 wire (min. 20 gauge). Connect the colour coded terminals to the corresponding terminals on the Control Module. When the Control Pad is remotely mounted in the Ventilation Dehumidistat or Air Sentry, refer to optional controls page for wiring requirements.
HRV/ERV
. When
21
Glossary
DEFROST MODE - to ensure reliable operation during cold
weather, the HRV/ERV will automatically cycle through its defrost mode as needed. (not on all models)
DEHUMIDISTAT - a control device that senses the amount of moisture in the air and will activate high speed fan operation when the air moisture level exceeds the control setting. The optimum air moisture level (or relative humidity [Rh]) in the typical home is in the range of 30 to 40% Rh.
RESET - whenever resetting of the HRV/ERV is required, simply disconnect power for 30 seconds.
STANDBY MODE - the HRV/ERV is energized and waiting for fan operation to be initiated by a remote device or manual override.
THERMISTOR
measures electrical resistance in a known manner, as outdoor temperatures fluctuate.
- the
HRV/ERV
's temperature sensor which
Page 22
To select mode of operation for ControlAir 15
Model 500 Only
Press and hold the fan selection button on the Control Pad. After 5 seconds the control will begin to cycle each mode holding each for 2 seconds. Release the button when the desired mode of operation is reached.
Modes of Operation LED Indication
OFF No LED’s illuminated HRV/ERV is off, no controls will
initiate operation.
Standby / On Steady Green LED and Yellow LED to indicate speed
HRV/ERV will run at speed selected in ventilation mode. Standby mode is indicated by no speed indicator illuminated. Optional remote controls will override standby or selected speed into high speed.
20 On / 40 Off Flashing Green LED and Yellow LED to indicate speed
HRV/ERV will operate in ventilation mode at speed selected for 20 minutes and OFF for 40 minutes.
To select speed
Momentarily press fan selection button and release. HRV/ERV will move into next speed. OFF is indicated by no yellow LED illuminated. Speed 1 is the first yellow LED. Speed five is indicated by a flashing speed 4 LED.
Automatic Defrost
During cold outdoor conditions the function, which will prevent ice from forming on the core. Defrost is indicated by a flashing Red LED indicator.
HRV/ERV
will occasionally go into an automatic defrost
22
Page 23
PITOT TUBE AIR FLOW BALANCING
It is necessary to have balanced air flows in an HRV/ERV. The volume of air brought in from the outside must equal the volume of air exhausted by the unit. If the air flows are not properly balanced, then;
• The HRV/ERV may not operate at its maximum efficiency
• A negative or positive air pressure may occur in the house
• The unit may not defrost properly
• Failure to balance HRV/ERV properly may void warranty
For general balancing it is sufficient to move the pitot tube around in the duct and take an average or typical reading. Repeat this procedure in the other (supply or return) duct. Determine which duct has the high­est airflow (highest reading on the gauge). Then damper that airflow back to match the lower reading from the other duct. The flows should now be balanced. Actual airflow can be determined from the gauge reading. The value read on the gauge is called the velocity pressure. The Pitot tube comes with a chart that will give the air flow velocity
Excessive
walls of the building where it may condense (in cold weather) and degrade structural components. May also cause key holes to freeze up.
positive pressure may drive moist indoor air into the external
based on the velocity pressure indicated by the gauge. This velocity will be in either feet per minute or metres per second. To determine the actual airflow, the velocity is multiplied by the cross sectional area of the duct being measured.
Excessive
In some geographic locations, soil gases such as methane and radon gas may be drawn into the home through basement/ground contact areas. Excessive negative pressure may also cause the backdrafting of vented combustion equipment.
Read the Application Warning on the front of this manual!
Prior to balancing, ensure that:
1. All sealing of the ductwork system has been completed. All of the HRV/ERV's components are in place and functioning properly.
2.
3. Balancing dampers are fully open.
4. Unit is on HIGH speed.
5. Air flows in branch lines to specific areas of the house should be
negative pressure may have several undesirable effects.
This is an example for determining the airflow in a 6" duct. The Pitot tube reading was 0.025 inches of water. From the chart, this is 640 feet per minute.
The 6" duct has a cross sectional area of = The airflow is then:
640 ft./min. For your convenience, the cross sectional area of some common
round duct is listed below:
DUCT DIAM. (inches) CROSS SECTION AREA (sq. ft.)
adjusted first prior to balancing the unit. A smoke pencil used at the grilles is a good indicator of each branch line's relative air flow.
6. After taking readings of both the stale air to the
HRV/ERV
duct and fresh air to the house duct, the duct with the lower CFM ([L/s] velocity) reading should be left alone, while the duct with the higher reading should be dampered back to match the lower reading.
7. Return unit to appropriate fan speed for normal operation
The accuracy of the air flow reading will be affected by how close to any elbows or bends the readings are taken. Accuracy can be increased by taking an average of multiple readings as outlined in the literature supplied with the Pitot tube.
[
3.14 x(6"÷12)
= 0.2 square feet
X
0.2 square feet = 128 cfm
5 0.14 6 0.20 7 0.27
2
]
÷4
BALANCING PROCEDURE
The following is a method of field balancing an
HRV/ERV
using a Pitot tube,
Pitot tube and gauge
advantageous in situations when flow stations are not installed in the duct­work. Procedure should be performed with the
HRV/ERV
The first step is to operate all mechanical systems on high speed, have an influence on the ventilation system, i.e. the
on high speed.
HRV/ERV
itself and
which
the forced air furnace or air handler if applicable. This will provide the maximum pressure that the
HRV/ERV
will need to overcome, and allow
for a more accurate balance of the unit. Drill a small hole in the duct (about 3/16"), three feet downstream of
any elbows or bends, and one foot upstream of any elbows or bends. These are recommended distances but the actual installation may limit the
Place pitot tube a minimum of 18" from blower or elbows
amount of straight duct. The Pitot tube should be connected to a
magnehelic gauge or other manometer capable of reading from 0 to 0.25 in. (0­62 Pa) of water, preferably to 3 digits of resolution. The tube coming out of the top of the pitot is connected to the high pressure side of the gauge. The tube coming out of the side of the pitot is con­nected to the low pressure or reference side of the gauge.
Insert the Pitot tube into the duct; point-
Magnehelic
gauge
MAGNEHELIC
Pitot tube
ing the tip into the airflow.
AIR FLOW
Pitot tube
Magnehelic gauge
Magnehelic
gauge
MAGNEHELIC
MAGNEHELIC
DUCT
Pitot Tube Air Flow Balancing Kit
c/w magnehelic gauge, Pitot tube, hose and carry case. PART NO. 99-167
Outdoors
Pitot
tube
Note: Duct connections may vary,  depending on model.
23
TI-74-2C
0105
Page 24
SERVICE/MAINTENANCE
Servicing your HRV/ERV on a regular schedule will result in optimum operating efficiencies and prolonged life of the equipment.
Due to numerous applications in which this equipment can be installed, it is difficult to predict servicing intervals. In certain situations where there is heavy smoke, servicing the equipment every one ­two months may be needed; whereas ventilating a meeting room for example for carbon dioxide may only need service every six months to a year.
MOTOR
Access to the motor is through the front service doors. Note heat exchanger core can be removed to provide more room. See CORE in this section.
The motor is a permanent split capacitor type (PSC) which uses a sleeve mechanism to steady the shaft. There is an oil wick beside the sleeve which supplies oil to it on a continuous basis.
If the motor does not have oil tubes, no maintenance is required.
Access to the wick is through oil tubes, (two per motor) located in the motor case itself. These oil tubes are either capped with yellow plugs, (which need to be removed for oiling) or have clear tubes protruding from them.
In either case an oiling device such as an “Oil Telespout” filled with 20 S.A.E. non-detergent electric motor oil should be used to put oil inside the tubes. A couple of drops of oil once a year will do.
DO NOT OVER OIL!
HRV CORE (HRV only)
The heat exchange core is accessible through the front service door. Special care and attention should be given to this component as the edges may be
sharp, and the core itself susceptible to damage if dropped.
When removing the core, the location it is removed from should be noted.
The core is removed by carefully pulling the core outward from the unit, sliding it evenly along its “H channel” supports found in each corner of the core. Note the core may have some resistance when sliding out. Avoid tilting the core as this will result in its edges catching the H channel and temporarily preventing its removal.
In most cases, washing the core in a mild detergent and warm water will be all that is needed to completely clean them. Do not use harsh chemicals as this may cause corrosion in the HRV. The time between core service will depend on the application the HRV has been installed in. It can be as often as one - two months or at the very least, cleaned every six months. When reinstalling
the core you must note foam location and drip edge location for proper core placement.
See diagram below.
ERV CORE (ERV only)
Remove core and vacuum or use low pressurized clean core. Do not wash or submerse in water.
With the core in its proper position, place the bottom flange, (approximately 1/4”) into its H channel support, then place the left side, the right side and finally the top flange into place in the same fashion. Once all four corners are in place, push the core evenly into the cabinet until it reaches the back. Be sure the drip edges are overlapping the drip trays.
Note the core will protrude slightly out from the front of the cabinet, this is so the access door, when closed, ensures a tight fit.
air to
FRONT VIEW
Models 700, 1200 Model 500
FILTER
DOUBLE
DRIP EDGE
CORE
FILTER
DRAIN PANS (not on all models) DRAIN PANS (not on all models)
Note location and arrangement of cores and filters when removing.
DOUBLE DRIP EDGES
FILTER
SINGLE
DRIP EDGE
CORE
Model 850
DOUBLE
DRIP EDGE
CORE
24
FILTER
DOUBLE DRIP EDGES
FILTER
LEFT DRIP
EDGE
SINGLE DRIP
EDGE CORE
DRAIN
PAN
RIGHT DRIP EDGE
FILTER
Page 25
FILTERS
Open front service door to access the filters located in both supply and exhaust air streams. Note to remove and install filters, it may be easier to first remove the core(s). See CORE.
The filters are designed to stop large particles from entering in the core. The filters are fastened in place by a metal spring rod. To remove filters from core(s) simply pull the rod from one end, outward until free from core lip, and remove.
Only use warm water with a mild detergent to wash the filters. Do not use harsh chemicals.
The time between filter service will depend on the application the HRV/ERV has been installed in. It can be as often as one - two months or at the very least, cleaned every six months.
CONDENSATE DRAINS
The condensate drains consist of two drain pans which may collect water after the HRV/ERV initiates a defrost cycle, and a drain line to remove the condensate.
Maintenance on this portion of the system should be done as often as possible and should not exceed six months. Note bacterial growth in standing water is a major concern to healthy indoor air quality, and should be avoided whenever possible.
To clean these components, open the front service door and flush the pans with water. Ensure that the pans drain completely and in a reasonable amount of time. Note if the water does not drain right away, check for blockage in the drain line, also check that the drain line has a good slope to it. (1/8 - 1/4” per foot)
DUCT WORK
It is a good idea to inspect ducting, outside weather hoods (wall caps), and grilles for blockage and dirt buildup, at least every six months.
Outside weather hoods should be protected by a rodent screen which can plug up with debris. Also, it is a good idea to visually confirm that the fresh air supply is free from any sources of contamination, such as other vented combustion equipment added after the fact.
DAMPER MOTOR
The damper motor, (if applicable) is a self contained motor and does not require service. The damper door attached to the motor could use a little lithium grease on the shaft opposite the motor, where it enters its holder, once every two - three years.
General Maintenance
As a final step in a routine maintenance schedule, it is a good idea to confirm operation of the system, checking speed control functions and remote control operation, if applicable.
Wipe the inside of the cabinet to remove dust and cob webs as needed.
It is a good idea to keep a service/maintenance log of the unit.
The drain line itself should have a “P” trap in it below the HRV/ERV which is to be filled with water to prevent odours or gases from entering back into the unit. When flushing out the drain pans, this too will be flushed out, and the water that was there will be replaced with clean water.
25
Page 26
TROUBLESHOOTING YOUR HRV/ERV SYSTEM
SYMPTOM CAUSE SOLUTION
Poor Air Flows
Supply air feels cold
Dehumidistat is not Operating
Humidity Levels are too High Condensation is appearing on the windows
• 1/4” (6 mm) mesh on the outside hoods is plugged
• filters plugged
• core obstructed
• house grilles closed or blocked
• dampers are closed if installed
• poor power supply at site
• ductwork is restricting HRV/ERV
• improper speed control setting
• HRV/ERV airflow improperly balanced
• poor location of supply grilles, the airflow may irritate the occupant
• outdoor temperature extremely cold
• improper low voltage connection
• external low voltage is shortened out by a staple or nail
• check dehumidistat setting it may be on OFF
• dehumidistat is set too high
• HRV/ERV is undersized to handle a hot tub, indoor pool, etc.
• lifestyle of the occupants
• moisture coming into the home from an unvented or unheated crawl space
• moisture is remaining in the washroom and kitchen areas
• condensation seems to form in the spring and fall
• HRV/ERV is set at too low a speed
• clean exterior hoods or vents
• remove and clean filter
• remove and clean core
• check and open grilles
• open and adjust dampers
• have electrician check supply voltage at house
• check duct installation
• increase the speed of the HRV/ERV
• have contractor balance HRV/ERV
• locate the grilles high on the walls or under the baseboards, install ceiling mounted diffuser or grilles so as not to directly spill the supply air on the occupant (eg. over a sofa)
• turn down the HRV/ERV supply speed. A small duct heater (1kw) could be used to temper the supply air
• placement of furniture or closed doors is restricting the
movement of air in the home
• if supply air is ducted into furnace return, the furnace fan may need to run continuously to distribute ventilation air comfortably
• check that the correct terminals have been used
• check external wiring for a short
• set the dehumidistat at the desired setting
• set dehumidistat lower
• cover pools, hot tubs when they are not in use
• avoid hanging clothes to dry, storing wood and venting clothes dryer inside. Heating wood may have to be moved outside
• vent crawl space and place a vapour barrier on the floor of the crawl space
• ducts from the washroom should be sized to remove moist air as effectively as possible, use of a bathroom fan for short periods will remove additional moisture
• on humid days, as the seasons change, some condensation may appear but the homes air quality will remain high with some HRV/ERV use
• increase speed of the HRV/ERV
Humidity Levels are too Low
HRV/ERV and / or Ducts Frosting up
Condensation or Ice Build Up in Insulated Duct to the Outside
Water in the bottom of the HRV/ERV
• dehumidistat control set too low
• blower speed of HRV/ERV is too high
• lifestyle of occupants
• HRV/ERV air flows may be improperly balanced
• HRV/ERV air flows are improperly balanced
• malfunction of the HRV/ERV defrost system
• incomplete vapour barrier around insulated duct
• a hole or tear in outer duct covering
• drain pans plugged
• improper connection of HRV/ERVs drain lines
• HRV/ERV is not level
• drain lines are obstructed
• HRV/ERV heat exchange core is not properly installed
• set dehumidistat higher
• decrease HRV/ERV blower speed
• humidity may have to be added through the use of humidifiers
• have a contractor balance HRV/ERV airflows
• Note: minimal frost build-up is expected on cores before unit initiates defrost cycle functions
• have HVAC contractor balance the HRV/ERV
• using the self-test feature at the Base Module, press the fan control symbol, the damper defrost unit should cycle its full travel when working properly.
• tape and seal all joints
• tape any holes or tears made in the outer duct covering
• ensure that the vapour barrier is completely sealed
• ensure O-Ring on drain nozzle sits properly
• look for kinks in line
• check water drain connections
• make sure water drains properly from pan
26
Page 27
WIRING DIAGRAM 500 (DAMPER DEFROST)
MICRO PROCESSOR BOARD
TO DISABLE
RECIRCULATION
REMOVE SEL2
REMOVE SEL1
WARNING
750 ma
MAX FUSE
P6
1 2
T5 T4 T3
FOR R-2000
GROUND
SEL2
SEL1
DRY
CONTACT
CHASSIS
FAN O/P
P1
LINE
P3
NEUTRAL
P4
P2
P5
T1
N/C
T2
COMMON
T6
N/O
SEE
DEFROST
DETAIL
T7
T8
T15
T9
THERMIST0R
INTERNAL
DEHUMIDISTAT
DOOR SWITCH
AUTO­TRANS FORMER
BLK
CONTROLAIR 15
120V POWER SUPPLY CORD
YEL GRN ORN RED BLK
Note: All control connections are labeled by colour. Connect to corresponding colour with low voltage wire ( 20 gauge minimum).
A dry contact closure between red & black will initiate high speed override.
FAN MOTOR DETAILS
T13
T11
BLK
GRN
WHITE
YEL
ORG
CAPACITOR
T10
WHITE
T11 T12
T13 T14
WHITE
BLACK
BLACK
GRN
FAN MOTOR
SEE MOTOR DETAIL
LEGEND
HIGH VOLTAGE 12V LOW VOLTAGE FIELD INSTALLED
12V LOW VOLTAGE
IMPORTANT: Control Low Voltage is 12VAC DO NOT CONNECT EXTERNAL POWER SOURCES TO UNIT
DEFROST DETAILS
24VAC
transformer
WHITE
PCB PLUG - IN
34
P1
12
RED
CCW
WHITE
COM
YELLOW
CW
DAMPER MOTOR
24VAC WIRING
DAMPER DEFROST
WIRE CONNECTOR
120V
WHITE
N/C
RELAY COM
N/O
BLACK
BLACK
PIN 1 - SPARE PIN 2 - BLACK PIN 3 - WHITE PIN 4 - SPARE
Note: If any of the original wire as supplied with the unit must be replaced, use only TEW certified wire
AUTO-TRANSFORMER DETAIL
T 7
T 10
PLUG IN CONNECTOR
P5 4 5 6
P6
P5
PIN 1 - BLUE PIN 4 - RED PIN 2 - YELLOW PIN 5 - WHITE PIN 3 - BROWN PIN 6 - BLACK
T14
T12
BLK
GRN
WHITE
YEL
ORG
CAPACITOR
FAN MOTOR
1 2 3
1 2
P6
PIN 1 - GREEN PIN 2 - GREEN
AUTO
TRANSFORMER
TI-126-NE
0102
27
Page 28
110 VAC
POWER SUPPLY
BLACK
WHITE
LINE
NEUT
ON/OFF
GREEN
GND.
WHITE
HIGH
TERMINAL
BLOCK
COMMON
24V
TERMINAL BOARD
3
2
WHITE
BLACK
Defond Switch
BROWN
1
3
BLACK
ON/OFF
SWITCH
YELLOW
2
BROWN
1
Carling Switch
WHITE
WHITE
1
RED
2
BLUE
3
BLACK
L
3 SPEED CONTROL
BLACK
INTAKE
(CCW)
PURPLE
700 STYLE
UNITS ONLY
YELLOW
YELLOW
PURPLE
TI-107
GND.
0002
SWITCH
BLACK
DOOR
INTERLOCK
32
TRANS-
FORMER
DEFROST
LIGHT
INDICATOR
ORANGE
1
ORANGE
2
3
BLACK
BLACK
BLACK WHITE WHITE
WHITE
WHITE
WHITE
WHITE
BLACK
BLACK WHITE
WHITE
WHITE
COM
120V RELAY
ORANGE
COM
N/C N/O
BLACK
N/C N/O
WHITE
WHITE
WHITE
24V RELAY
WHITE
ORANGE
COM
BLACK
N/C N/O
BROWN
BLUE
TERMINAL
BLOCK
WHITE WHITE
WHITE
BROWN
BLUE
TERMINAL
BLOCK
WHITE
BLACK BLACK BLACK
WHITE
BLUE
BLUE
BLACK
RED
RED
RED
WHITE
YELLOW
BLACK
BLACK
BLUE
BLACK
WHITE
RED
BLACK
YELLOW
EXHAUST
PURPLE
YELLOW
(CW)
CAPACITORS FAN MOTOR
CAPACITORS FAN MOTOR
PURPLE
LOWER
FAN MOTOR GREEN
UPPER
FAN MOTOR
GND. GREEN
BLACK
5
4
DEFROST
TIMER
700 STYLE
UNITS ONLY
BLACK
Remote Switching
Analogue Style
Controls
Wiring Diagram
TEMPERATURE SENSOR
FAN DEFROST
For Models:
700, 850,1200
28
Page 29
POWER SUPPLY
110 VAC
ORANGE
BLACK
WHITE
LINE
NEUT
ON/OFF
GND.
GREEN
HIGH
BLACK
COMMON
24V TERMINAL BOARD
RED
TERMINAL
BLOCK
3
2
Defond Switch
WHITE
BLACK
BROWN
1
3
BLACK
ON/OFF
SWITCH
POWER
2
BROWN
1
RED
Carling Switch
WHITE
WHITE
1
2
BLUE
3
BLACK
L
3 SPEED CONTROL
BLACK
INTAKE
(CCW)
PURPLE
0002
TI-108
700 STYLE
UNITS ONLY
GND.
YELLOW
YELLOW
PURPLE
GREEN
DOOR
INTERLOCK
SWITCH
23
TRANS-
FORMER
DEFROST
LIGHT
INDICATOR
ORANGE
BLACK
ORANGE
BLACK
BLACK BLACK WHITE WHITE
RED
WHITE
RED
WHITE
COM
120V RELAY
WHITE
BLACK
YELLOW
BLACK WHITE
WHITE
COM
RED
N/C N/O
WHITE
BLACK
N/C N/O
BLACK
WHITE
24V RELAY
BLACK
WHITE
COM
BLACK
N/C N/O
BROWN
TERMINAL
BLACK BLACK
WHITE
TERMINAL
BLUE
BLOCK
WHITE
BLACK
BLUE
BLOCK
BLUE
BLACK
WHITE
WHITE
ORANGE
BROWN
BLUE
RED
YELLOW
RED
WHITE
RED
BLACK
BLACK
WHITE
BLUE
BLACK
WHITE
BLACK
RED
YELLOW
PURPLE
YELLOW
PURPLE
LOWER
FAN MOTOR
CAPACITORS FAN MOTOR
CAPACITORS FAN MOTOR
UPPER
FAN MOTOR
GND. GREEN
BLACK
1
2
3
4
5
DEFROST
BLACK
TIMER
TEMPERATURE SENSOR
COM
CW CCW
RED
WHITE
YELLOW
DAMPER MOTOR
Remote Switching
Analogue Style
Controls
Wiring Diagram
For Models:
DAMPER DEFROST
700, 850, 1200
EXHAUST
(CW)
700 STYLE
UNITS ONLY
29
Page 30
COMMERCIAL LIFEBREATH
®
HEAT/ENERGY RECOVERY VENTILATORS
• 2 Year Limited Warranty • 15 Year Aluminum Core Warranty
• 5 Year Paper Core Warranty
NUTECH ENERGY SYSTEMS INC.®(NUTECH) warrants to the purchaser of the Commercial
LIFEBREATH®model and accessories referred to below, to be free from manufacturing defects.
This Warranty is personal to NUTECH®and is in effect from the date of the original purchase for a period of two years, save and except that a 15 YEAR WARRANTY is given to the LIFEBREATH®Aluminum core & a 5 YEAR WARRANTY is given to the LIFEBREATH®Paper core should they develop a condensation leak or become damaged during normal use.
Damage resulting from all other causes, including but not limited to: lighting, hurricane, tornado of the LIFEBREATH®or its operation in a manner contrary to the instructions accompanying the unit at the time of sale; accidental or intentional damage, neglect, improper care, or other failure by the owner to provide reasonable and necessary maintenance of the product; any attempt at repair by an unauthorized service representative or not in accordance with this warranty; or any other causes beyond the control of NUTECH®, are excluded from this warranty.
, earthquake or any other acts of God; improper installation, modification, alteration or misuse
If you feel that the LIFEBREATH®you purchased is not free from manufacturing defects, please contact NUTECH ENERGY SYSTEMS INC.®, 511 McCormick Blvd., London, Ontario N5W 4C8, 519-457-1904 or fax 519-457-1676 to find the name of your nearest dealer in order to repair the product. The labour required to install any replacement part(s) shall be dealt with at the option of the customer in either of the following ways:
(a) the customer may supply labour at their own expense: or (b) if the product was purchased from a dealer, then the dealer
will supply labour at cost to the customer.
NUTECH®reserves the right to replace the entire unit or to refund the original purchase price in lieu of repair.
NUTECH®MAKES NO EXPRESS WARRANTIES, EXCEPT FOR THOSE THAT ARE SET FORTH HEREIN AND SHALL NOT BE LIABLE FOR ANY INCIDENTAL, SPECIAL OR CONSEQUENTIAL DAMAGES WITH RESPECT TO LIFEBREATH®COVERED BY THIS WARRANTY. NUTECH’S COMPLETE LIABILITY AND THE OWNER’S EXCLUSIVE REMEDY BEING LIMITED TO REPAIR OR REPLACEMENT ON THE TERMS STATED HEREIN. ANY IMPLIED WARRANTIES, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTY OF MERCHANTABILITY AND OF FITNESS FOR ANY PARTICULAR PURPOSE, ARE EXPRESSLY EXCLUDED.
NO PERSON IS AUTHORIZED TO CHANGE THE WARRANTY IN ANY WAY OR GRANT ANY OTHER WARRANTY UNLESS SUCH CHANGES ARE MADE IN WRITING AND SIGNED BY AN OFFICER OF NUTECH®.
MODEL NO.: _____________________________________________________ UNIT SERIAL NO.: ______________________________________________________________ INSTALLED BY: ________________________________________________________________ DATE: _________________________________________________
30
_____
__________________
_____________
TI-38HRV/ERV
Page 31
511 McCormick Blvd. London, Ontario
Ph: (519) 457-1904 Fx: (519) 457-1676 Email: nutech@lifebreath.com Website: www.lifebreath.com
N5W 4C8
Loading...