To contact Liebert Global Services for information or repair service in the United States, call
1-800-LIEBERT (1-800-543-2378). Liebert Global Services offers a complete range of start-up
services, repair services, preventive maintenance plans and service contracts.
For repair or maintenance service outside the 48 contiguous United States, contact Liebert Global
Services, if available in your area. For areas not covered by Liebert Global Services, the
authorized distributor is responsible for providing qualified, factory-authorized service.
For Liebert Global Services to assist you promptly, please have the following information
available:
Part numbers: _________________________________________________________________
Serial numbers:________________________________________________________________
This manual contains important instructions that should be followed during the installation and
maintenance of the Liebert Static Transfer Switch 2 Power Distribution Unit (STS2/PDU).
Read this manual thoroughly, paying special attention to the sections that apply to your installation,
before working with the Static Transfer Switch 2 Power Distribution Unit. Retain this manual for use
by installing personnel.
Refer to 1.2.1 - Handling Considerations before attempting to move the unit.
WARNING
!
The unit is supplied by more than one power source. The unit contains hazardous voltages if
any of the input sources are on, even when the unit is in bypass. To isolate the unit, turn off
and lock out all input power sources.
Verify that all input power sources are de-energized and locked out before making connections
inside unit.
Lethal voltages exist inside the unit during normal operation. Only qualified service
personnel should perform maintenance on the STS2/PDU.
NOTE
Read the entire manual before installing or operating the system. Adhere to all operating
instructions and warnings on the unit and in this manual.
WARNING
!
Under typical operation and with all STS2/PDU doors closed, only normal safety precautions
are necessary. The area around the STS2/PDU should be kept free of puddles of water, excess
moisture and debris.
ONLY qualified service personnel should perform maintenance on the Static Transfer
Switch 2 Power Distribution Unit. When performing maintenance on any part of the
equipment under power, service personnel and test equipment should be located on rubber
mats. The service personnel should wear insulating shoes for isolation from direct contact
with the floor.
One person should never work alone, even if all power is removed from the equipment. A
second person should be standing by to assist and summon help in case an accident should
occur.
WARNING
!
The input sources to the STS2/PDU must be grounded-wye sources. Input sources other than
solidly grounded-wye sources may cause damage to the switch.
Liebert Corporation neither recommends nor knowingly sells this product for use with life support or
other FDA-designated “critical” devices.
The Static Transfer Switch 2 Power Distribution Unit is suitable for indoor use only. Protect the unit
from excessive moisture and install the unit in an area free from flammable liquids, gases and corrosive substances.
The unit is designed to operate from solidly grounded AC power sources only. Provide input over-current protection in accordance with the unit ratings. Wire and ground the unit according to national
and local electrical safety codes. All wiring should be installed by a qualified electrician.
1
A thorough equipment inspection and supervised start-up by qualified service personnel are strongly
recommended at these times:
1. Before unit is placed into service for the first time
2. After equipment relocation, and
3. After the unit has been de-energized for an extended period of time
CAUTION
!
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J
of the FCC rules and EN550022. These limits provide reasonable protection against harmful
interference in a commercial environment. This unit generates, uses and radiates radio
frequency energy and, if not installed and used in accordance with this instruction manual,
may cause harmful interference to radio communications. Operation of this unit in a
residential area may cause harmful interference that the user must correct at his own
expense.
WARNING
!
Locate the center of gravity symbols and determine the unit’s weight
before handling the cabinet.
2
1.0UNPACKINGAND INSPECTIONS
NOTE
Read the entire manual before beginning to install the STS2/PDU. Upon delivery of the
STS2/PDU, the installer should perform the following steps to ensure a high-quality
installation.
A high-quality installation begins on the receiving dock. The STS2/PDU and its packaging should be
inspected when the unit is delivered. If the packaging is not damaged, unpack the unit and conducting internal inspection before beginning the installation process. This section discusses inspecting
and unpacking the STS2/PDU.
1.1External Inspections
1. While the STS2/PDU is still on the truck, inspect the equipment and shipping container(s) for any
signs of damage or mishandling. Do not attempt to install the system if damage is apparent.
2. Upon receipt and before unpacking, inspect the shipping crate for damage or mishandling.
Check the Shock-Watch™ indicator.
• If the indicator is red, note on shipper’s receipt and check for concealed damage.
• If any damage as a result of shipping is observed, file a damage claim with the shipper within 24 hours
and contact your local Liebert representative or Liebert Global Services at 1-800-543-2378 to
inform them of the damage claim and the condition of the equipment.
3. Locate the bag containing the keys for the front access door. The bag is attached to the cabinet.
4. Compare the contents of the shipment with the bill of lading. Report any missing items to the
carrier and to Liebert Global Services immediately.
5. Check the nameplate on the cabinets to verify that the model numbers correspond with the one
specified. Record the model numbers and serial numbers in the front of this installation manual.
A record of this information is necessary should servicing be required.
6. If unit is to be stored before installation, it is recommended to store the unit in a dry environment
with temperatures in the range of -40 to 176°F (-40 to 80°C). Use original packing materials or
other suitable means to keep the unit clean. When opening the shipping crate, use care not to
puncture the container with sharp objects.
Unpacking and Inspections
1.2Unloading and Handling
CAUTION
!
When moving the unit by forklift, lift the unit from the rear so as to protect the front panel.
Do not exceed a 15 degree tilt with the forklift.
Also, if you are moving the unit by forklift or pallet jack after it has been removed from the
pallet, be aware of the location of the casters and leveling feet (if unit is so equipped) so as not
to damage them.
Most STS2/PDU models are contained in one cabinet. The 800 amp units are contained in two cabinets that shipped on two pallets and connected together in the field.
The unit can be moved by forklift or pallet jack. However, because the weight distribution in the cabinet is uneven, use extreme care during handling and transporting.
See 1.2.2 - Unit Preparation for instructions on removing the STS2/PDU from the pallet.
3
1.2.1Handling Considerations
The STS2/PDU is bolted to a wood shipping pallet to allow handling by forklift equipment or a pallet
jack.
WARNING
!
Exercise extreme care when handling STS2/PDU cabinets to avoid equipment damage or
injury to personnel.
The cabinet can be safely tilted 15 degrees in any direction by forklift.
If moving the unit up a ramp on its casters (if the unit is so equipped) or a pallet jack, ensure
that the incline does not exceed 15 degrees.
Locate the center of gravity symbols and determine the unit’s weight before handling
the cabinet.
Check the unit size and weight. Refer to the cabinet drawings furnished with the unit for size and
weight. Typical cabinet dimensions are shown in Figures 7 through 22. Typical unit crated weights
are:
Table 1Shipping weights (typical)
ModelWeight - lbs. (kg)
250A3730 lbs. (1692 kg)
400A4900 lbs. (2132 kg)
600A 5580 lbs. (2531 kg)
800A Module A*4052 lbs. (1838 kg)
800A Module B*4595 lbs. (2084 kg)
*800A ships on two separate pallets
Unpacking and Inspections
Plan the route. Review the route over which the unit will be transported to its installation location to
ensure that all passages are large enough to accommodate the unit and support the weight.
Check for any non-negotiable corners or offsets in hallways. Before moving the unit to the intended
location, review 2.0 - Location Considerations.
1.2.2Unit Preparation
The unit can be removed from the pallet before it is moved to its location.
Complete the following steps to properly remove the STS2/PDU from the shipping pallet:
1. Set the pallet in a level area with enough room to maneuver and remove the unit.
2. Remove the bolts holding the unit to the shipping pallet (located in the base of the unit).
3. Remove the shipping blocks from under the frame of the unit.
4. Use a forklift to raise the unit off the pallet and onto the floor. On the 250A unit ensure that the
forklift is clear of the unit's casters and leveling feet. Lift the unit from the rear.
5. Conduct an internal inspection of the unit. See the list in 1.3 - Internal Inspections.
1.3Internal Inspections
After the STS2/PDU has been unpacked, conduct an internal inspection:
1. Verify that all items have been received.
2. If spare parts were ordered, verify their arrival.
3. After the Static Transfer Switch 2 Power Distribution Unit has been removed from the pallet,
open the door and remove cabinet panels to check for shipping damage to internal components.
4. Check for loose connections or unsecured components in the cabinet(s).
5. Check for any unsafe condition that may be a potential safety hazard.
After the STS2/PDU has been inspected and no problems are found, the unit can be moved to its
installation location. If using a forklift, remember to lift the unit from the rear.
4
2.0LOCATION CONSIDERATIONS
The STS2/PDU should be placed in a clean, cool and dry location. The 250A unit without an output
cabinet requires only front access for installation and maintenance. Both front and side access are
required for installation and maintenance of 400-800A units and 250A units with output cabinet. The
output cabinet comes factory installed or either the right or left side depending on how it was ordered.
It cannot be moved from one side to the other in the field.
Adequate space is required above the unit for conduit (if configured as such) and cooling air flow. This
section provides specific information for these considerations.
The unit is designed with top and bottom cable terminations to allow maximum flexibility in its
installation. Units with output inline panelboards are bottom exit only. If bottom cable entry and exit
is used, sufficient cable bending space must be provided by a raised floor or a floor stand.
For dimensions of each unit, see Figures 7 through 22. If your unit is equipped with an optional key
lockout switch, see Figures 13 through 21 for the location of that switch.
2.1Recommended Minimum Service Clearances
The recommended service clearances are at the front and side, if equipped with output cabinet. The
minimum service clearance required by the National Electrical Code (NEC) Article 110-26 is
36 in. (91cm) for units with voltages up to 150V to ground and 42 in. (107cm) for units with voltages
over 150V to ground. Clearance of at least 18 in. (46cm) is required above the unit for cooling air flow.
Location Considerations
2.2Heat Output
The unit produces minimal heat during normal operation.
Table 2Heat output
Heat Output
Switch Size
250A12,590 (3.69)
400A20,140 (5.90)
600A30,200 (8.85)
800A40,270 (11.80)
BTU/Hr (kW)
2.3Operating Environment
The unit is designed to be installed indoors where the ambient air temperature is in the range of
32° to 104°F (0°C - 40°C) with a relative humidity of 0% to 95% non-condensing, up to an altitude of
4000 feet (1200 meters).
5
2.4Altitude
The standard units are designed for full load operation up to 4000 feet (1200m) above sea level. See
Figure 1 for recommended deratings for altitudes greater than 4000 feet (1200m).
Figure 1Recommended derating for high altitude operation
100
98
96
94
92
Rating (%)
90
88
86
0
7000
6500
6000
5500
5000
4500
4000
7500
8000
8500
9000
Location Considerations
9500
10000
Operation at full load at a higher altitude can be accommodated in ambient temperatures less than
104°F (40°C) ambient. Figure 2 shows the maximum allowable ambient temperature for full load
operation at altitudes above 4000 feet (1200m).
Figure 2Maximum ambient temperature for full load operation at higher altitudes
104.0 (40)
102.2 (39)
100.4 (38)
98.6 (37)
96.8 (36)
95.0 (35)
93.2 (34)
94.1 (33)
°F (°C)
89.6 (32)
87.8 (31)
86.0 (30)
0
4000
4500
5000
5500
6000
6500
7000
7500
8000
Max. Ambient Temperature
8500
Altitude—Feet
Table 3Altitude conversion—feet to meters
Feet = Meters
4000 = 12007500 = 2286
4500 = 13728000 = 2438
5000 = 15248500 = 2591
5500 = 16769000 = 2743
6000 = 18299500 = 2896
6500 = 198110000 = 3048
7000 = 2134
9000
9500
10000
6
3.0LOCATING THE STS2/PDU
This section provides instructions for leveling the STS2/PDU and anchoring the unit to the floor,
should that be required.
3.1Anchoring the Unit to the Floor
The STS2/PDU can be anchored to the concrete floor to ensure stability for the unit in the event of
seismic activity.
3.2Leveling of the 250A Only STS2/PDU Without Anchoring
The 250A Static Transfer Switch 2 Power Distribution Unit is furnished with casters and leveling
feet. After final positioning of the unit, adjust the leveling feet located in each corner of the frame base
to level and stabilize the unit.
For leveling feet details, see Figures 7 through 11.
Locating The STS2/PDU
7
4.0POWERAND CONTROL WIRING
All power and control wiring must be installed by a licensed, qualified electrician. All power and control wiring must comply with the National Electrical Code and all applicable local codes. Unless otherwise labeled, use the recommended tightening torque shown in Table 29.
The input power busbars are accessible through the front of the unit. Liebert’s 250A units have PEM
nut inserts designed to allow one-handed tightening. Busbars in the 400-800A units are supplied with
holes to accommodate two-hole lugs.
Cables can be installed through the top or bottom of the unit through removable conduits plates.
Units with output inline panelboards are bottom exit only for output cables.
See Figures 12 through 21 for wiring entrance locations.
4.1Input and Output Power Connections
The input power connections are made to the busbars provided inside the unit (see Figures 26
through 31). These busbars are accessible through the front of the unit.
Output power connections are handled two different ways, depending on the type of distribution used.
Power connections on standard units with an output breaker are made to the busbars inside the unit.
These busbars are accessible through the front on 250A units and on the side on 400-800A units. See
Figures 26 through 31 for details on the busbars. Power connections on units with panelboard distribution are made directly to the panelboard breakers. Busbars are provided in the output cabinet for
ground and neutral connections.
Power and Control Wiring
WARNING
!
Verify that all input power and control circuits are de-energized and locked out before making
connections inside unit.
The two input power feeds (sources) to the STS2/PDU should be from two independent sources to
avoid a common source failure.
To ensure proper operation of the STS2/PDU, the two input sources must be the same nominal voltage level and phase rotation.
For uninterrupted automatic transfer, the two input sources should be synchronized within
15 degrees.
CAUTION
!
The input sources to the STS2/PDU must be grounded-wye sources. Input sources other than
solidly grounded-wye sources may cause damage to the switch.
The STS2/PDU is designed for operation with 3-wire, solidly grounded sources only.
See Figures 3 through 6 for typical one-line diagrams. Refer to Figures 26 through 31 for electrical
field connections on all units.
The input and output power wire size should be based on the overcurrent protection device, observing
the NEC and local codes.
The STS2/PDU output power, ground and neutral busbars accommodate a wide range of wire sizes.
The STS2/PDU busbars accommodate standard two-hole lugs.
Table 4Input/output conduit plate specifications
Rating
250A
400-600A
800A
Maximum Number
of ConduitsSize, in.
12 2"
82-1/2"
63" or 3-1/2"
6 2"
42-1/2" or 3"
62-1/2"
53" or 3-1/2"
10
4.2System Grounding
Equipment grounding—Grounding is primarily for equipment and personnel safety, although proper
grounding also enhances equipment performance.
All input and output power feeds must include an equipment grounding means as required by the
NEC and local codes.
An insulated equipment ground conductor is recommended to run with each input and output power
feed. The equipment ground conductors should be at least the minimum size conductor per the NEC
based on the upstream overcurrent protection device.
WARNING
!
If conduit is used as a grounding means, adequate electrical continuity must be maintained at
all conduit connections. The use of isolating bushings with a metal conduit can be a safety
hazard and is not recommended.
4.3Control Wiring Connections
No control wiring is needed on the standard STS2/PDU. Certain options and remote monitoring configurations require external control wiring. See 6.0 - Options for details.
The customer must supply control wiring to the STS2/PDU for connection to any monitoring or communication options. Top and bottom removable conduit plates are provided for control wiring conduit.
Control cables can be installed through the top or bottom of the unit through removable control conduit plates. A top hat is provided on the 400-600A units for connecting the top entry control wiring
conduits (see Figures 13 through 21). The top hat is turned upside down and ships inside the unit. It
must be removed from the unit and flipped 180 degrees before being reinstalled (see Figure 49). The
control wiring top hat does NOT contain any knockouts for conduit. The installer must drill the
appropriate-sized holes for the conduit before attaching to the top of the STS2/PDU.
See Figures 47 and 48 for arrangement of optional cards.
Power and Control Wiring
4.4Remote Source Selection Wiring
An optional Remote Source Selection board may be installed in your STS2/PDU. This board is installed
in the same bay as the communications options. See Figures 47 and 48 for the location of these
options. See Figure 56 for information on the control wiring for the Remote Source Selection option.
The Remote Source Selection allows you choose the preferred input source from a remote location.
Terminal connections allow the customer to remotely select a source to be the preferred source in the
same process as the local source transfer selection.
If both the input contacts are closed, the current selected preferred source shall be retained. If the
unit’s preferred source selection and Remote Source Selection are active at the same time,
the STS2/PDU follows the last request for a preferred source change, regardless of whether it was
from the local or Remote Source Selection controls.
A six pin terminal block provides the Remote Source Selection connections. Two pairs of wires are
used from the switch to trigger the source selection. You can select the type of switch used for this
remote control. Connections are made to four of the connections, using Form A dry contacts. The contacts are numbered left to right:
Table 5Remote source selection terminal block
ContactConnection
1Source 1
2Isolated ground
3Source 2
4Isolated Ground
5DO NOT USE
6DO NOT USE
See 10.3 - Enabling Remote Source Selection for instructions on enabling the Remote Source
Selection option.
11
4.5Power Supply
The STS2/PDU is supplied with redundant power supplies that are designed to operate from a voltage
range of 200V to 600V. The unit is set at the factory to match the nameplate voltage. Field adjustments are not necessary. If the unit needs to operate at a voltage other than what is listed on the
nameplate, contact Liebert Global Services or your local Liebert representative. Table 6 provides
transformer tap information.
Table 6Terminal block 1 and terminal block 2 wire connections
Using Table 6, ensure that the wiring for the control transformers matches the input voltage
for the unit.
Improper wiring could result in blown fuses.
12
5.0OUTPUT POWER WIRING
The STS2/PDU standard model is provided with a circuit breaker for connecting to the load or a
remote distribution cabinet. Other distribution configurations are available.
The three main types of distributions available for the STS2/PDU are:
• Output Breaker
• Inline Panelboards—two panelboards (84 poles) on 250A units and four panelboards (168 poles)
on 400-800A units. Square D
bolt-in or plug-in breakers.
• Square D I-Line
to 250A. Additionally, 300A to 400A breakers are available on 800A units.
For other optional distribution methods, contact your local Liebert representative or call
1-800-LIEBERT.
The STS2/PDU distribution may be mounted on either the right or left side at the customer’s option.
Location of output conduit connections is affected by the location of the output cabinet. See
Figures 8, 9, 12, 13, 16 and 17 for wiring a right-side distribution configuration and
Figures 10, 11, 14, 15, 18 and 19 for wiring a left-side distribution configuration. See Figures 23
through 44 for wiring.
See Table 7 for wiring the various output options.
®
Panelboard—designed to accommodate up to 10 plug-in breakers from 100A
Output Power Wiring
®
and General Electric panelboards are available to accommodate
5.1Customer Connections
The customer is responsible for connections from the STS2/PDU distribution to the connected load,
either directly or through remote distribution cabinets.
Table 7Distribution configurations
For Details See
Distribution Type
Output Breaker
250AFigure 23
400-600AFigure 33
800AFigure 35
Inline Panelboards
250AFigure 30
400-800AFigure 31
I-Line (Square D)Figure 32
Electrical Output
Field Connections
13
6.0OPTIONS
This section discusses the options available for the STS2/PDU. The communications options are also
discussed in 12.0 - Communication Interfaces.
WARNING
!
All options must be installed by Liebert Global Services or Liebert factory-authorized service
provided by a Liebert distributor. The option area and customer control cable area contain
hazardous voltages if any of the input sources are on, even when the unit is in bypass. Turn
OFF all power sources before installing customer control cables to any option.
6.1Programmable Relay Board
The programmable relay board (PRB) provides a means to trigger an external device when an event
occurs in the STS2/PDU. Each PRB has 8 channels. Each channel has two sets of Form-C dry contacts, rated 1A @ 30VDC or 250mA @ 125VAC.
Any alarm or event may be programmed to any channel or channels. Up to ten (10) events may be
programmed to a relay. If multiple events are grouped to one relay, group the events logically to simplify troubleshooting when an event is triggered. The same alarm or event may be programmed to
more than one channel. Up to two programmable relay boards can be installed in the STS2/PDU for a
total of 16 channels. Programming is performed through the touch screen display.
See Configuring the Programmable Relay Board Settings on page 109 for default settings and
instructions for reconfiguring the relays. See Figures 47 and 48 for the location of the PRB. See
Figure 50 for wiring details. Table 8 provides the PRB pinout.
Table 8Programmable relay board pinout
ChannelPin No.CN.C.N.O.
CH1
TB1
TB2
TB3
TB4
Key: N.O. = Normally Open; N/C. = Normally Closed; C = Common
Note: Pin 16 not used on TB1, TB2 and TB3.
CH2
CH3
CH4
CH5
CH6
CH7
CH8
A1-3 12 3
B4-6 45 6
A7-9 78 9
B10-12101112
A13-15131415
B1-3 12 3
A4-6 45 6
B7-9 78 9
A10-12101112
B13-15131415
A1-3 12 3
B4-6 45 6
A7-9 78 9
B10-12101112
A13-15131415
B1-3 12 3
Options
6.2Input Contact Isolator Board
The Input Contact Isolator Board (ICI) provides an STS2/PDU module interface for up to eight external user alarm or message inputs to be routed through the Static Transfer Switch 2 Power Distribution Unit’s alarm network. The eight contacts are normally open dry contacts. When a contact closes,
an event is triggered.
The Input Contact Isolator options are configured through the Input Contact Isolator dialog box,
which is accessed from the Comm Option dialog box on the touch screen display. You also can program the alarm messages through this dialog box. See Configuring the Input Contact Isolator Settings on page 108 for instructions on configuring the connections.
See Figures 47 and 48 for the location of the ICI. See Figure 51 for wiring details.
14
6.3Comms Board
The Comms Board provides a communication interface to Liebert SiteScan, site monitoring product
and/or an external or internal modem. SiteLink-12 or SiteLink-4 is required for SiteScan to communicate with the STS2/PDU.
The Comms Board is equipped with an RS-422 communication port for communication to a Liebert
SiteScan monitoring system using a 2-wire twisted pair for reliable communication up to 1000 meters
(3281 feet). Information available from the RS-422 port includes the present switch status information, all monitoring parameters and all active alarms.
The Comms Board is equipped with a modem interface for remote reporting of the present switch status information, alarm history information and the history of status screens that are triggered upon a
major alarm event. The monitoring system software also supports an auto-dial feature that allows the
system to automatically dial programmed phone numbers by way of the modem to report designated
alarm conditions.
Programming the Comms Board is performed through the touch screen display. See Comm Options on page 105 for details.
See Figures 47 and 48 for the location of the Comms Board. See Figure 52 for information on the
control wiring.
6.4Internal Modem
The Internal Modem is an option that must be ordered separately. An external modem is available
from third party sources. The Internal Modem is capable of dialing out from the STS2/PDU or accepting incoming calls and connecting to a remote terminal or computer. Using an ASCII Query and
Answer format the modem connection can be used to view system status and alarms. The modem provides all information normally available on the LCD of the STS2/PDU. No control functions are available via the modem, such as making transfers, selecting a preferred source or changing
configurations.
Options
The modem can also be configured to dial out two different telephone numbers (any combination of
modem or pager numbers).
The connection to this modem is through a standard RJ-11 port.
See Figures 47 and 48 for the location of the internal modem. See Figure 53 for more information on
the internal modem.
Programming the modem is performed through the touch screen display, see Configuring the Modem on page 105 for details.
The modem commands are shown in Table 13.
6.5Network Interface Card (NIC)
An OpenComms Network Interface Card (NIC) enables the STS2/PDU to communicate to a network
management system (NMS). The NIC provides the internal hardware and software to communicate,
via SNMP, to any I.P.-based Ethernet network through an RJ-45 connector using Category 5 cabling.
The NIC provides redundant paths for communications that make it possible to connect to a Building
Management System (BMS) using Modbus, while simultaneously communicating to a NMS through
SNMP. A terminal block provides the connection to Modbus.
See Figures 47 and 48 for the location of the NIC. See Figure 54 for control wiring information.
If you have questions about the NIC, refer to the OpenComms Network Interface Card Installation
and Users Guide.
15
6.6Remote Source Selection
The Remote Source Selection allows the preferred input source to be chosen from a remote location. A
user supplied normally open dry contact allows the user to remotely select a source to be the preferred
source in the same process as the local source transfer selection.
If both the input contacts are closed, the current selected preferred source shall be retained. If the
unit’s preferred source selection and Remote Source Selection are active at the same time,
the STS2/PDU follows the last request for a preferred source change, regardless of whether it was
from the local or Remote Source Selection controls.
See 10.3 - Enabling Remote Source Selection for instructions on enabling the Remote Source
Selection.
See Figures 47 and 48 for the location of the Remote Source Selection option.
See 4.4 - Remote Source Selection Wiring and Figure 56 for information on the control wiring.
6.7Key Lockout Switch
The key lockout switch activates a software lockout of the touch screen display to prevent manual
transfers and configuration changes. When locked out, the touch screen becomes a read-only display.
A key is needed to do manual transfers or change settings.
The alarm silence button is not disabled when in the lockout position.
The switch is located on the front of the unit next to the display; it is behind the front door but can be
operated without opening the front door. See Figures 20 through 22 for the key lockout switch location on each unit.
See 13.2.1 - Security and Figure 65 for instructions on using the key lockout switch.
Options
6.8Static Switch Redundant Output Breaker
A plug-in, non-automatic circuit breaker is provided which allows redundancy in the static switch output power path. The breaker is connected in parallel with the static switch output plug-in non-automatic circuit breaker.
6.9Inline Panelboards
An output distribution cabinet with either Square D or General Electric inline panelboards with copper bus to accept bolt-in or plug-in circuit breakers. Each panelboard is individually protected by a
225A, 240V, 3-pole panelboard main circuit breaker.
Each panelboard includes a separate isolated neutral bus bar and a safety-ground bus bar for the neutral and safety-ground connections for at least 42 output circuits.
6.10I-Line Panelboards
An output distribution cabinet with one vertically mounted Square D I-Line panelboard with copper
bus to accept Square D three phase plug-in circuit breakers. The panelboard shall be totally enclosed
with an accent cover.
6.11Subfeed Breakers
Breakers for feeding remote panelboard(s) or other loads. Available in ratings of 225A or 400A.
NOTE
Only available on units with inline panelboards. 400A breaker not available on 250A units.
6.12K-Factor Transformers
K20-rated double-shielded copper isolation transformer specially designed to accommodate highly
nonlinear leads in accordance with UL 1561 (in place of standard isolation transformer).
6.13Surge Suppression System
A fused and monitored high-energy, 80 kAmp/phase surge suppression system by Control Concepts
connected to each input of the unit for superior surge suppression.
16
7.0INSTALLATION DRAWINGS
Figure 7Outline drawing, 250A STS2/PDU
Installation Drawings
17
Figure 8Outline drawing, 250A STS2/PDU with right side I-Line distribution
Installation Drawings
18
Figure 9Outline drawing, 250A STS2/PDU with right side inline distribution
Installation Drawings
19
Figure 10 Outline drawing, 250A STS2/PDU with left side I-Line distribution
Installation Drawings
20
Figure 11 Outline drawing, 250A STS2/PDU with left side Inline distribution
Installation Drawings
21
Figure 12 Outline drawing,400-600A STS2/PDU with right side inline distribution
Installation Drawings
22
Loading...
+ 126 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.