1. Check packing slip to ensure ALL material has
been delivered.
2. All material shortages are to be reported to
Liebert within 48 hours from receipt of goods.
Liebert assumes no responsibility for any
material shortages beyond this period.
3. Inspect shipping boxes for damage and note
on shipping waybill accordingly.
4. After unpacking, inspect equipment for
damage and if damage is found, notify the
shipper promptly.
5. All Liebert products are shipped on an F.O.B.
factory basis. Any and all damage, breakage
or loss claims are to be made directly to the
shipping company.
PRE-INSTALLATION CHECKPOINT
1. Ensure that available voltage and phase
corresponds with humidifier voltage and phase
as indicated on humidifier’s nameplate label
(see Figure #1).
Figure #1
SGH Series Humidifier
Condensate
Return
Steam
Outlet
BASIC HUMIDIFIER CONFIGURATION
Liebert humidifier model SGH has a right side
electrical compartment. Each electrical compartment
has a hinge-down front door which is removable from
any partially or fully opened position. Each electrical
compartment has a screw-mounted right side cover
which can also be removed for ease of electrical
connection. For safety, the door when closed keeps
the side cover from being removed.
Single units have a plumbing compartment
attached to the left side of the electrical. Double units
have a second plumbing compartment. Each
plumbing compartment has a hinge-down front door
which is not intended to be removed. For safety, the
door must be closed in order to engage the lock. To
avoid any danger, never operate the humidifier with a
door off. For safety, each door when closed engages
its own safety interlock switch. All switches must be
engaged before the unit will operate.
To open the doors, unlock key, lift door up slightly
and pull top of door forward. Door will hinge 180
degrees and hang straight down. To remove door,
swing door parallel to floor. Then lift up slightly and
out. To reinstall door, hold parallel to floor and insert
hinge pins at bottom. The door can then be closed.
Figure #2
Clearance Requirements
WALL
WITHOUT BLOWER PACK
TOP VIEW
Power And
Control
Drain
Water
Su
Nameplate
Label
Wiring
2. Ensure that the dedicated external disconnect
is of sufficient size to handle the rated amps
as indicated on the nameplate label. Refer to
local codes.
NOTE: LOCAL AND NATIONAL
CODES MAY DEVIATE. PLEASE
CONSULT APPLICABLE CODES
FOR CLEARANCE REQUIREMENTS
IN ALL CASES.
MIN. 36"
FRONTAL
CLEARANCE.
LOCATION & MOUNTING
HUMIDIFIERS
SGH humidifiers are designed to mount on a
suitable wall or vertical surface. Do not sit on floor due
-1-
MIN. 36"SIDE
CLEARANCE
RECOMMENDED.
SEE NOTE.
to clearances required for plumbing, electrical, and
control entrances. The clearance dimensions shown
in this manual are for reference only and are the
minimum required for maintenance of the humidifier.
Local and National Codes should be consulted prior to
final location and installation of the humidifier. Liebert
can not accept responsibility for installation code
violations.
In addition, install a minimum of 2 field
supplied fasteners in the holes provided in the
back of the unit to prevent the unit from being
bumped off the wall bracket.
6. Make sure humidifier is level.
7. DO NOT mount humidifier on hot surfaces.
1. Location of the humidifier should be below and
as close as possible to the steam distributor
location as possible.
2. For front and side clearance requirements (for
access during installation, maintenance and
troubleshooting), see Figure #2.
3. If possible, DO NOT locate humidifier any
further than absolutely necessary from steam
distributor location, as net output will be
reduced as a result of heat loss through steam
hose. Also, increased static pressure may
cause operational problems and necessitate
use of the fill cup extension kit and other
components.
4. Where possible, mount humidifier at a height
convenient for servicing.
5. Wall mounting bracket provided should be
securely attached horizontally and open edge
upwards, using field-supplied fasteners. Use
a minimum of 3 - #12 x 3" long wood screws,
or better, into a vertical structural surface. If
any spacer material is used between the
bracket and the structural material such as
drywall, increase fastener length accordingly.
8. If humidifiers are mounted on roof, a
thermostatically ventilated weatherproof
cabinet by others should be used. Consult
factory.
9. DO NOT mount humidifiers in an area where
freezing may occur.
10. DO NOT mount humidifiers on vibrating
surface.
BLOWER PACKS
1. Blower packs are an optional accessory used
to directly distribute steam to localized areas
(such as computer rooms) or in structures that
do not have a built-in air distribution system.
2. Blower packs are available integrally-mounted
on humidifier (built-on blower pack, BOBP,
see Figure #4) or detached and field-piped
and wired to humidifier (remote mounted
blower pack RMBP, see Figure #5).
-2-
Figure #5
Remote Mounted Blower Packs (SGBP)
WALL
FRONT
CONDENSATE
See Figure #6 for mounting clearances.
STEAM
005-030
10-20
3.2" (8.0cm)
3. All SGH blower packs consist of a steel
cabinet containing: blower/motor powered by
voltage directly from the humidifier, fuse, relay,
speed select switch, stainless steel steam
distributor, supply air grille with adjustable
louvers, and built-in manual reset safety
thermostat to turn off the humidifier if the
blower pack gets overheated. Control
thermostat, mounted on the steam distributor,
starts the fan when steam is generated. When
supply voltage differs from voltage required to
run blower motor, blower pack will contain a
proper transformer. All blower packs provide
intake air filters.
4. Refer to Figure #6 for overhead and frontal
clearances required for blower packs.
Minimum clearance for the sides of the
Blower Pack unit is 12 inches. Dimensions
apply to both built-on and remote-mounted
versions of blower packs.
5. Mount remote blower pack(s) using factory
supplied wall mounting bracket, see Figure #5,
with clearance as recommended in Figure #6.
6. Steam distributor on the built-on and remote
blower packs have a hot surface that could
result in burns if touched. If space allows, we
recommend mounting at least 8 feet above the
floor.
7. Do not use blower packs as ducted blowers.
The air volume from a blower pack is not
sufficient to absorb the steam generated.
8.8. Pipe the steam line as stated in the STEAM
LINE section on page 6.
and at least one distributor (do not join two
or more cylinders to one larger steam line).
Any cylinder’s steam line may be divided into
multiple branches to feed more than one
distributor. Steam supply line “tees” are
common copper fittings that are available for
this purpose.
2. Steam distributor locations are typically as
follows: supply air duct, return air duct, air
handling unit. Proper location should
consider: air temperature, relative humidity
before the distributor, air velocity, dimensions
of the location, amount of steam being
introduced into the duct, downstream
obstructions, and surfaces vulnerable to
wetting.
3. When steam distributors are located in a duct,
they should be in a straight section of duct at
least 6 feet (2 meters) from any elbow or
obstruction. If the duct or plenum conditions
result in poor absorption distance
characteristics, please consult your local
representative or the factory. See Figure #7.
4. Steam distributors should always span the
width of the air stream. Multiple steam
distributors, arranged in a bank, can
minimize absorption distance.
-3-
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.