Reference document is based on the assumption that the
connecting module is of exec. 6 or exec. B firmware type unless
otherwise noted.
Page 1 of 149
Liebert Monitoring Group – Development
Revision
Date
Description
B.5
11/8/00
Added: revision level update chart, HiPulse support, and NPower support
B.6
2/19/01
Revised NPower definition
B.7
4/4/02
Added support for HiMod LNA
B.8
5/3/02
Revised Modbus explanation (Hi Byte / Lo Byte)
B.9
10/1/02
Corrected NPower table (typing error)
B.10
1/22/03
Added support for DataMate
B.11
7/23/03
Added support for STS-2
B.12
4/19/04
Corrected ModBus register addressing for STS-2 alarms. PM2 – removed duplicate
Output Voltage THD Alarm. Added XDP Unit. Added LDS5000 Unit. Added Universal
Monitor. Added BACNet/IP for: WDU, MM4, SC4, PM2 & LAM. Added Run Hours for
MM2
B.13
5/24/04
Removed non-existent alarms for MM2. Added BacNet/IP Point addresses for MM2.
B.14
8/19/200
4
Track issue 3576 – Make BacNet points consistent with Modbus Points.
B.15
11/22/20
04
Added ESP-2 based UPS Units that use OC485 card. Includes Nx, HiNet, PSI, and
GXT
B.16
5/18/05
Added “High Water Humidifier Pan” alarm to L00. Corrected alarm points for BACNet
and Modbus addressing on STS-2.
B.17
7/1/05
Added Remote shutdown alarm to LAM. Added Note about Alarms “BACNet auto
discovery” to CCM, L00, LAM, MMS, PM2, PMP, SCC. Added note to STS2 that it is
for units with or without PDU. Changed breaker status register for STS2 from bits1-8
to 0-7.
B.18
7/21/05
Added XDC Unit. Added control point note for units with on/off control as follows: Bit
0 on=unit off Bit 1 on=unit on. Removed cables 3 & 4 on LDS5000 and marked these
registers as spares.
B.19
11/30/05
Corrected revision level and date in header on this document.
B.20
12/14/05
SMS – Added Scale factor for kVA & kW. Revised note on page 1 to state module
type rather than “SS2000 Hardware”.
B.21
8/9/06
Series 610 UPS – added note that Series 610 is the same as series 600. SC4-SM4
changed “Bypass Breaker Closed” alarm from “Bypass Breaker Open”. Added note to
LAM that iCOM w/native IGM also applies.
B.22
8/10/06
Nfinity UPS (pnf), Nx (pnx), STS-2 (st2) – deleted status and setpoint points that are
not displayed in SiteScan. XDC, XDP added scale factor notes for Ref, Fluid and CW
temps.
B.23
3/16/07
PMP – Local Alarm #1 was Load Alarm, Added Local Alarm #2, Corrected Modbus
addressing from 40290:04 to 40290:07
B.24
4/16/07
AC8 – Added Unit tables to reference library
B.25
4/30/07
MM2 – Corrected entire table due to MS Word problems.
B.26
5/2/07
Corrected major MS Word formatting problems throughout document.
B.27
11/15/07
Added iCOM DS unit for 2mb modules (small version), SM3 corrected reversed
Modbus addressing for kW & kVA. Noted that pages for Series 600 UPS also apply
to series 610.
B.28
6/24/08
Added iCOM-XDP unit
B.29
7/11/08
Corrected alarm info for Npower (IMP) unit.
B.30
5/13/09
Corrected revision number in page header B.30 from B.9. Changed XDP unit
description on page 53 from XD. Corrected miscellaneous document formatting
errors. Added WDU definition back in document from accifental deletion.
B.31
10/13/09
Added local Alarms 2,3 &4 for MM2, L00 & LSM. Local alrm 3=High Water for MM2
B.32
4/23/10
Clarified LAM/iCOM program usage and added iCOM 16mb version. Added
examples and notes sections. Removed discontinued modules.
B.33
2/2/11
Removed General Alarm from iCOM_DS. Added Hi Water Humidifier Pan to L8T.
Moved Generator Disconnected from Alarm to Status in NX unit.
Revision Level Updates:
Revision B.33 2/25/2011
Page 2 of 149
Revision B.33 2/25/2011
Liebert Monitoring Group – Development
Table of Contents
Click on the desired page number for instant navigation. Use the ―back‖ arrow on your toolbar to return to the table
of contents.
TABLE OF CONTENTS.................................................................................................................................................. 3
OPEN COMMUNICATIONS .............................................. 7
DEFAULT MAPPING FOR MODBUS &BACNET OBJECTS ............................................................................................ 7
Transmission Format ............................................................................................................................................. 9
LIEBERT ENVIRONMENTAL UNITS ............................. 15
AIR UNIT -LEVEL 0–L00 ................................ ................................ ................................................................ ........ 16
AIR UNIT –LEVEL 10–L10 ................................................................................................................................ ..... 18
AIR UNIT –STANDARD MICROPROCESSOR –LSM ................................................................................................... 20
AIR UNIT –ADVANCED MICROPROCESSOR –LAM .................................................................................................. 22
AIR UNIT –SMALL SYSTEMS –L0B ......................................................................................................................... 25
AIR UNIT –MINI-MATE 2–MM2,DATAMATE ....................................................................................................... 27
AIR UNIT –8TON MINIMATE –L8T ........................................................................................................................ 29
ATLAS AIR UNIT –C10 ............................................................................................................................................ 32
CHILLER UNIT –CSU3000–CSU ............................................................................................................................ 35
CHILLER UNIT –CSU3000 W/ECONO –CSE ........................................................................................................... 37
AIR UNIT -HIROSS MICROFACE ............................................................................................................................... 39
AIR UNIT –X-TREME DENSITY COOLANT DISTRIBUTION UNIT–CDU .................................................................... 43
AIR UNIT –X-TREME DENSITY COOLANT PUMPING UNIT–XDP ............................................................................ 45
AIR UNIT –X-TREME DENSITY CHILLER UNIT–XDC ................................................................ ............................. 47
AIR UNIT – ICOMDS&RETROFIT (2MB VERSION SITELINK) ................................................................................. 50
AIR UNIT – ICOMDS&RETROFIT (16MB VERSION SITELINK) ............................................................................... 53
AIR UNIT –XDPREFRIGERANT PUMPING UNIT –XDPW/ ICOMCONTROL .......................................................... 58
LIEBERT POWER UNITS ............................................... 60
POWER UNIT –VOLTAGE-CURRENT MONITORING PANEL – VCM .......................................................................... 61
POWER UNIT –POWER MONITORING PANEL –PMP ................................................................................................ 63
POWER UNIT –VOLTAGE-CURRENT-FREQ.MONITOR PANEL – VCF ....................................................................... 66
POWER UNIT –POWER MONITORING PANEL (EXT.PROTOCOL– PM2) .................................................................... 68
POWER UNIT –STATIC TRANSFER SWITCH PDU–EDS ........................................................................................... 71
POWER UNIT –STATIC TRANSFER SWITCH PDUDUAL OUTPUT –STS ................................................................... 74
POWER UNIT –STATIC TRANSFER SWITCH PDUDUAL OUTPUT –STS-2 ................................................................ 77
LIEBERT UPS UNITS ..................................................... 81
Indicates the Environmental, Power, UPS or Monitoring Module by model name that
uses this controller.
SiteScan Interface
Modules
Indicates which SiteScan Hardware Modules can be used with the controller. Take
Special note of this box when adding new units to an existing SiteScan system, as
some new controllers are only compatible with the new hardware (SiteLink).
BMS interface Modules
Indicates which SiteScan Hardware Modules can be used with the controller for
interfacing with a third part using BACnet or Modbus protocol.
Status Points (View)
Status Information for the listed points that will be presented in SiteScan
Alarm Points
Alarms that are available to SiteScan
Setpoints (View)
Current settings of controllable Setpoints available to SiteScan
Control Points (Set)
Setpoints that can be changed with SiteScan
Trendable Points (Set)
Points that can be graphically trended within the SiteScan software
Reports
Reports that can be triggered within the SiteScan software
Liebert Monitoring Group – Development
How to use the Reference Library Charts
This document contains a dedicated sheet for each Liebert Unit and associated controller. The title of each chart
contains the name of the Liebert Controller used such as L00 for a Level-0 Air unit or PMP for a Power Monitoring
Panel for Power Center.
Every documented unit assumes the maximum possible optional points and configuratios of the specific unit family.
The specific points that will be used depend on the unit being read as that unit will only report values and alarms
that the specific unit supports.
The first section, Compatible Hardware, indicates the equipment associated with this particular controller as follows:
The next section, Available Points, contains six categories providing the following information:
Page 5 of 149
Liebert Unit ID Chart
3-Letter ID
Environmental Products
3-Letter ID
UPS Products
L00
Level 00, Level 1
SMS
Single Module Series UPS - S300, S500,
S600 (Prior to 1/98)
L10
Level 2, Level 3, and Level 10
SM3
Single Module Series 30x (latest version)
LAM
Level 15 and Level AM/AG,
HiMod (LNA), iCOM control w/ native IGM
terminal 77/78
SM4
Single Module Series 600/610 - Extended
Protocol (1/98 or later)
LSM
Level SM and Level 0 w/ On/Off Control
US3
UPStation S3 UPS
L0B
Small Systems Controller
MMS
Multi Module Series 500-600 UPS (Prior to
1/98)
MM2
Small Systems Controller - Mini Mate II,
DataMate
MM4
Multi Module Series 600/610 UPS Extended Protocol (1/98 or later)
C10
Atlas Air Environmental Control (LECS15)
SCC
System Control Cabinet Series 500-600
(Prior to 1/98)
CSE
Chiller w/ Econocoil
SC4
System Control Cabinet Series 600/610Extended Protocol (1/98 or later)
CSU
Chiller
SSM
Single Module Series UPS - SICE 7200 &
HiPulse
XDP
Xtreme Density Unit Environmental Control
SMM
Multi Module Series UPS - SICE 7200 &
HiPulse
CDU
Xtreme Density Coolant Distribution Unit
SSC
System Control Cabinet - SICE 7200
iCOM
DS Unit with iCOM control or Deluxe
System 3 with iCOM control retrofit using
optional IS485 interface with 16mb
SiteLink.
IMP
NPower (S300 Replacement)
iCOM-2mb
DS Unit with iCOM control or Deluxe
System 3 with iCOM control retrofit using
optional IS485 interface with 2mb SiteLink.
PNX
NX UPS – ESP2 Protocol
HIA
Hiross Hiromatic Air unit
PHN
HiNet UPS – ESP2 Protocol
Static Switch PDU
PNF
Nfinity UPS – ESP2 Protocol
EDS
Static Switch PDU (Single Output Breaker,
Prior to 1/99)
PGX
GXT UPS – ESP2 Protocol
STS
Static Switch PDU (Dual Output Breaker
Option, 1/99 or later)
PPS
PSI UPS – ESP2 Protocol
Miscellaneous
CCM
All IGM Contact Modules CM200 / RCM8 /
VSM
RAC
Remote Autochangeover Module - RAC2-8
THM
Temperature / Humidity Module
Power Products PDU
WDU
Liquid Detection LDS750 or LDS1000
PMP
Precision Power & Datawave w/ PMP
(latest LCD display)
WD5
Liquid Detection LDS5000
VCF
All Voltage-Current-Frequency Panels
(Old Red LED Display)
UVM
Universal Monitor
VCM
All Voltage-Current Monitoring Panels
(Old Red LED Display)
AC8
Autochangeover Controller
PM2
Precision Power & Datawave w/ PMP
(latest LCD display and extended protocol
EPROM version 3.290.0, manufactured
and shipped after 4/99)
Revision B.33 2/25/2011
Liebert Monitoring Group – Development
Page 6 of 149
Revision B.33 2/25/2011
Liebert Monitoring Group – Development
Open Communications
Default Mapping for Modbus & BACnet Objects
This model represents the standard configuration for a Liebert Sitelink-12 module. Consecutive register /
object mapping is utilized, regardless of the SiteLink-12 population. All ports that do not have a Liebert
IGM attached will be assigned “null values” (or zero’s) for their corresponding registers. The default
“slave ID” or “Device ID” follows the CMNet address of the unit. The address can be visually checked by
looking at the address dip-switch or rotary switch settings. However, the address can be changed in
software to suit specific needs.
Please note that the SiteLink hardware places a limit on the quantity of Modbus registers available.
Therefore, it is possible there will be more data points available using BACnet than using Modbus.
How to use this table:
The unit or model specific reference sheets assume that the desired unit is attached to port 1 of the
SiteLink module. If the desired unit is attached to a different port, the table below indicates the starting
register or object number for the unit.
For example: The register for “temperature” for a L00 type unit attached to port 1 is identified as
40001. If an additional L00 type unit were attached to port 2, the “temperature” value would be located in
register 40025. The same type unit attached to port 3 = 40049…etc.
Modbus Notes:
Modbus Registers start at 40001.
All registers are unsigned integers.
BACnet Notes:
BACnet Objects start at 1.
All “Status” and “Alarm” objects are “AI’s” (analog inputs).The “Control” objects are “AO’s” (analog outputs)
Page 7 of 149
Revision B.33 2/25/2011
Register Offset
Object Type
Port Assignment
1-24
Status
1
25-48
Status
2
49-72
Status
3
73-96
Status
4
97-120
Status
5
121-144
Status
6
145-168
Status
7
169-192
Status
8
193-216
Status
9
217-240
Status
10
241-264
Status
11
265-288
Status
12
289-293
Alarms
1
294-298
Alarms
2
299-303
Alarms
3
304-308
Alarms
4
309-313
Alarms
5
314-318
Alarms
6
319-323
Alarms
7
324-328
Alarms
8
329-333
Alarms
9
334-338
Alarms
10
339-343
Alarms
11
344-348
Alarms
12
349-351
Control
1
352-354
Control
2
355-357
Control
3
358-360
Control
4
361-363
Control
5
364-366
Control
6
367-369
Control
7
370-372
Control
8
373-375
Control
9
376-378
Control
10
379-381
Control
11
382-384
Control
12
Liebert Monitoring Group – Development
** See reference libraries for unit specific objects.
Page 8 of 149
Revision B.33 2/25/2011
Physical
Port
Transmission
Mode
Baud Rate
Data Bits
Parity Bits
Stop Bits
Default
EIA-232 –
DB9 DCE
RTU
9600
8
None
1
Yes
EIA-232 –
DB9 DCE
ASCII
1200 –
38.4kbd
(19.2kbd omit)
Configurable
Configurable
Configurable
No
EIA-485 – 2
or 4 wire
RTU or ASCII
1200 –
38.4kbd
(19.2kbd omit)
Configurable
Configurable
Configurable
No
Liebert Monitoring Group – Development
Modbus Communications
Connectivity to SiteLink modules using Modbus
This design specification describes the Modbus communications protocol as supported by the SiteLink module. It
includes information on how to pass information to and from the SiteLink module via Modbus. It is also intended to
help facilitate answering questions regarding supported types, frame format, function code support etc.
Implementation Basics
Protocol controls the language structure or message format between devices in other words, the rules for
communication. The rules for communication include how master and slave devices initiate communications, as
well as unit identification, message handling and error checking. Modbus protocol simply refers to the control of
the query and response cycles between master and slave devices.
The SiteLink module is configured to act as a slave device on a common network. The common network can be
point-to-point over EIA-232, where one master communicates to one slave device or in a multi-drop configuration
over EIA-485, where multiple slaves reside on a common wire or loop.
Documented write points can cause read errors if you attempt to read a write-only point. For example: an LAM air
unit has separate Setpoint View and Setpoint Set registers and if you read a write-to register it can and most likely
will result in a Modbus exception response. Do not include setpoint set registers in batch read commands as one
point read error will result in an exception response for the entire batch read.
Transmission Format
The SiteLink module supports both Modbus RTU (Remote Terminal Unit) and ASCII (American Standard Code for
Information Interchange) transmission modes. The SiteLink module has a choice of transmission medium, baud
rate, character parity and number of stop bits. See chart below.
Page 9 of 149
Revision B.33 2/25/2011
Liebert Monitoring Group – Development
Modbus Packet Format
Each Modbus packet consists of the following fields:
Device Address Function Code Data Field(s) Error Check Field
Device Address:
The address field immediately follows the beginning of the frame and consists of 8-bits (RTU) or 2 characters
(ASCII). These bits indicate the user assigned address of the slave device that is to receive the message sent by the
attached master device.
Each slave must be assigned a unique address and only the addressed slave will respond to a query that contains its
address.
Function Code:
The function code field tells the addressed slaves what function to perform. Function codes are specifically
designed invoke a specific action by the slave device. The function code range is from 1 to 127. However, the
SiteLink module primarily uses Function Code 3 (Read Holding Registers), Function Code 6 (Preset Single
Register) and Function Code 16 (Preset Multiple Registers).
Data Field(s):
The data field varies in length depending on whether the message is a request or a response to a packet.
This field typically contains information required by the slave device to perform the command specified or
to pass back data to the master device.
Error Check Field:
The Error Check Field consists of a 16-bit (2 byte) Cyclical Redundancy Check (CRC16). It allows the
receiving device to detect a packet that has been corrupted with transmission errors.
Page 10 of 149
Revision B.33 2/25/2011
Slave
Address
Function
Code
Starting
Register
―Hi Byte‖
Starting
Register
―Lo Byte‖
Number of
Registers
―Hi Byte‖
Number of
Registers
―Lo Byte‖
CRC16
―Hi Byte‖
CRC16
―Lo Byte‖
02
03
00
32
00
03
E5
FA
Slave
Address
Function
Code
Count:
Bytes of
Data
Register
40051 Data
Hi Lo
Register
40052 Data
Hi Lo
Register
40053 Data
Hi Lo
CRC16
―Hi Byte
CRC16
―Lo Byte‖
02
03
6
01 58
00 FA
00 54
1B
0D
Frame
Start
Slave
Address
Function
Code
Data
Error
Check
End of
Frame
CR
Ready for
Data
LF
:
2 Char
16-bits
2 Char
16-bits
N x 4 Char
N x 16-bits
B3
0D
0A
Liebert Monitoring Group – Development
RTU Framing
The example below shows a typical Q/R from a SiteLink module. In common terms, the master device initiates a
query asking slave device 2 for holding registers starting at holdingregister 40051 (decimal 50) and including
next 2Registers (3 total).
Query Sample
Response Sample
Slave address 2 responds to Function Code 3 with 6 bytes of hexadecimal data and ends with CRC16 checksum.
Framing in ASCII transmission mode is accomplished by the use of the unique colon (:) to indicate the beginning of the
frame and a carriage return (CR) line feed (LF) to delineate the end of the frame. The line feed also serves as a
synchronizing character which indicates that the transmitting station is ready to receive an immediate reply.
ASCII Example
Char = Character: 1 Character = 7 data bits, 1 start bit, 1 or 2 stop bits and 1 parity bit (optional)
The points in this document are listed by object reference name and each exposed BACnet point has information in
the description field detailing what the point is. Both of these BACnet properties can be read and discovered
remotely in addition to the points present value property. This document is not able to define specific object instance
numbers because they are dynamically assigned when the programming for the module is created and will vary from
situation to situation. A report detailing reference name, description and object instance number can be requested
from the startup engineer at the time of the modules commissioning.
If after startup if changes are made or new programs are added the dynamically built AV/BV points list will shift for
all points.
Product Description:
The SiteLink module provides a BACnet Point-to-Point communication exchange between proprietary Liebert
Environmental, Power, UPS units to other BACnet compliant devices. The connection to the SiteLink module is via
EIA-232, 9600 baud, no parity, 8 data bits, 1 stop bit (9600,N,8,1 default.) The SiteLink modules are available in 12
port and 4 port configurations (i.e. 1 port per/ Liebert Unit, 12 Liebert units per/ SiteLink module maximum.)
BACnet Conformance Class Supported:
BACnet Functional Groups Supported:
Page 12 of 149
Liebert Monitoring Group – Development
Application Service
Initiate
Requests
Execute Requests
AcknowledgeAlarm
ConfirmedCOVNotification
ConfirmedEventNotification
GetAlarmSummary
GetEnrollmentSummary
SubscribeCOV
UnconfirmedCOVNotification
UnconfirmedEventNotification
AtomicReadFile
AtomicWriteFile
AddListElement
RemoveListElement
CreateObject
DeleteObject
ReadProperty
X
X
ReadPropertyConditional
ReadPropertyMultiple
X
WriteProperty
X
X
WritePropertyMultiple
X DeviceCommunicationControl
ConfirmedPrivateTransfer
UnconfirmedPrivateTransfer
ReinitializeDevice
ConfirmedTextMessage
TimeSynchronization
Who-Has
X
I-Have
X
Who-Is
X
I-Am
X
VT-Open
VT-Closed
VT-Data
Authenticate
Request Key
BACnet Standard Application Services Supported:
Revision B.33 2/25/2011
Page 13 of 149
Revision B.33 2/25/2011
Object Type
Supported
Dynamically
Creatable
Dynamically
Deleteable
Optional
Properties
Writable
Properties
Analog Input
X None
Analog Output
X
Present Value
Analog Value
Binary Input
Binary Output
Binary Value
Calendar
Command
Device
Event Enrollment
File
Group
Loop
Multi-State Input
Multi-State Output
Notification Class
Program
Schedule
Segmented Requests Supported
No
Segmented Responses Supported
No
Router
No
Liebert Monitoring Group – Development
BACnet Standard Application Services Supported (continued):
This section is an example of how to utilize Liebert environmental unit Setpoints Set registers. In all cases the
Setpoints View section contains the value that the unit itself is reporting and can be used to confirm that the unit
received the transmitted command.
Example table from this document:
The above notes in the document refer to binary bits. Notice that register 40349 is used more than once in the table.
The table below shows the integer number in the value set from BMS column.
For the setpoint registers, the setpoint and tolerance are in the same register. Writing a zero to the field will result in
no change.
Some examples of valid values to send:
To make the Temperature Setpoint “70”, send a “70” to the register. To make the Temperature Tolerance “+/- 2.5 degrees”, send “2500” to the register. To make the Temperature Tolerance “+/- 2.5 degrees” and Setpoint “70”, send “2570” to the register. To make the Humidity Setpoint “50%”, send a “50” to the register. To make the Humidity Tolerance “+/- 5%”, send “5000” to the register. To make the Humidity Tolerance “+/- 5%” and Setpoint “50%”, send “5050” to the register.
Page 15 of 149
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Challenger 3, Logicool, Modular Plus, LS400, Mini-Tower, System 4
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Temperature
40001
1
BS01_x
Humidity
40002
2
BS02_x
Cooling
40003
3
BS03_x
1=on / 0=0ff
Heating
40004
4
BS04_x
1=on / 0=0ff
Humidification
40005
5
BS05_x
1=on / 0=0ff
Dehumidification
40006
6
BS06_x
1=on / 0=0ff
Econ-o-Cycle
40007
7
BS07_x
1=on / 0=0ff
Stages
40008
8
BS08_x
% Capacity
40009
9
BS09_x
Alarm Points
Discrete BACnet alarm objects available –
use auto-discover for this unit
Communications
40289:0
289:0
BA01_x:00
High Head Pressure 1
40289:1
289:1
BA01_x:01
High Head Pressure 2
40289:2
289:2
BA01_x:02
Loss of Airflow
40289:3
289:3
BA01_x:03
Liquid Detected
40289:4
289:4
BA01_x:04
Change Filters
40289:5
289:5
BA01_x:05
High Temperature
40289:6
289:6
BA01_x:06
Low Temperature
40289:7
289:7
BA01_x:07
High Humidity
40289:8
289:8
BA01_x:08
Low Humidity
40289:9
289:9
BA01_x:09
Local Alarm 1
40289:10
289:10
BA01_x:10
High Water Humidifier Pan
40289:11
289:11
BA01_x:11
Local Alarm 2
40289:12
289:12
BA01_x:12
Local Alarm 3
40289:13
289:13
BA01_x:13
Local Alarm 4
40289:14
289:14
BA01_x:14
Liebert Monitoring Group – Development
Air Unit - Level 0 – L00
Page 16 of 149
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Setpoints (View)
Temperature Setpoint
40010
10
BS10_x
Temperature Tolerance
40011
11
BS11_x
Humidity Setpoint
40012
12
BS12_x
Humidity Tolerance
40013
13
BS13_x
Control Points (Set)
Temperature Setpoint
40350
350
BC02_x
Temperature Tolerance
40350
350
BC02_x
Multiply desired value by 1000
Humidity Setpoint
40351
351
BC03_x
Humidity Tolerance
40351
351
BC03_x
Multiply desired value by 1000
Trendable points (Set)
Temperature
Humidity
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 17 of 149
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Modular Plus, Deluxe System/3, Industrial Cooling Series
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Temperature
40001
1
BS01_x
Humidity
40002
2
BS02_x
Cooling
40003
3
BS03_x
1=on / 0=off
Heating
40004
4
BS04_x
1=on / 0=off
Humidification
40005
5
BS05_x
1=on / 0=off
Dehumidification
40006
6
BS06_x
1=on / 0=off
Econ-o-Cycle
40007
7
BS07_x
1=on / 0=off
Stages
40008
8
BS08_x
% Capacity
40009
9
BS09_x
Alarm Points
Communications
40289:0
289:0
BA01_x:00
High Head Pressure 1
40289:1
289:1
BA01_x:01
High Head Pressure 2
40289:2
289:2
BA01_x:02
Loss of Airflow
40289:3
289:3
BA01_x:03
Standby Glycol Unit On
40289:4
289:4
BA01_x:04
Liquid Detected
40289:5
289:5
BA01_x:05
Change Filters
40289:6
289:6
BA01_x:06
High Temperature
40289:7
289:7
BA01_x:07
Low Temperature
40289:8
289:8
BA01_x:08
High Humidity
40289:9
289:9
BA01_x:09
Low Humidity
40289:10
289:10
BA01_x:10
Humidifier Problem
40290:0
290:0
BA02_x:00
No Water in Humidifier Pan
40290:1
290:1
BA02_x:01
Compressor 1 Overload
40290:2
290:2
BA02_x:02
Compressor 2 Overload
40290:3
290:3
BA02_x:03
Main Fan Overload
40290:4
290:4
BA02_x:04
Liebert Monitoring Group – Development
Air Unit – Level 10 – L10
Page 18 of 149
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Manual Override
40290:5
290:5
BA02_x:05
Smoke Detected
40290:6
290:6
BA02_x:06
Loss of Water
40290:7
290:7
BA02_x:07
Standby Unit On
40290:8
290:8
BA02_x:08
Low Suction
40290:9
290:9
BA02_x:09
Short Cycle
40290:10
290:10
BA02_x:10
Loss of Power
40291:0
291:0
BA03_x:00
Inverter Bypass
40291:1
291:1
BA03_x:01
Standby Fan On
40291:2
291:2
BA03_x:02
Loss of Emergency Power
40291:3
291:3
BA03_x:03
Local Alarm 1
40291:4
291:4
BA03_x:04
Local Alarm 2
40291:5
291:5
BA04_x:05
Setpoints (View)
Temperature Setpoint
40010
10
BS10_x
Temperature Tolerance
40011
11
BS11_x
Humidity Setpoint
40012
12
BS12_x
Humidity Tolerance
40013
13
BS13_x
High Temperature Setpoint
40014
14
BS14_x
Low Temperature Setpoint
40015
15
BS15_x
High Humidity Setpoint
40016
16
BS16_x
Low Humidity Setpoint
40017
17
BS17_x
Auto-Restart Delay
Control Points (Set)
Temperature Setpoint
40350
350
BC02_x
Temperature Tolerance
40350
350
BC02_x
Multiply desired value by 1000
Humidity Setpoint
40351
351
BC03_x
Humidity Tolerance
40351
351
BC03_x
Multiply desired value by 1000
Trendable Points (Set)
Temperature
Humidity
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 19 of 149
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Challenger 3000. Deluxe System / 3, ICS , System 4 (Replaces L0A control)
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Temperature
40001
1
BS01_x
Humidity
40002
2
BS02_x
Cooling
40003
3
BS03_x
1=on / 0=off
Heating
40004
4
BS04_x
1=on / 0=off
Humidification
40005
5
BS05_x
1=on / 0=off
De-humidification
40006
6
BS06_x
1=on / 0=off
Econ-O-Cycle
40007
7
BS07_x
1=on / 0=off
Stages
40008
8
BS08_x
% Capacity
40009
9
BS09_x
Unit Status (On / Off)
40014
14
BS14_x
1=on / 0=off
Alarm Points
Communications
40289:0
289:0
BA01_x:00
Local Off
40289:1
289:1
BA01_x:01
Remote Off
40289:2
289:2
BA01_x:02
High Head Pressure 1
40289:3
289:3
BA01_x:03
High Head Pressure 2
40289:4
289:4
BA01_x:04
Loss of Airflow
40289:5
289:5
BA01_x:05
Liquid Detected
40289:6
289:6
BA01_x:06
Change Filters
40289:7
289:7
BA01_x:07
High Temperature
40289:8
289:8
BA01_x:08
Low Temperature
40289:9
289:9
BA01_x:09
High Humidity
40289:10
289:10
BA01_x:10
Low Humidity
40290:0
290:0
BA02_x:00
Local Alarm 1
40290:1
290:1
BA02_x:01
Local Alarm 2
40290:2
290:2
BA02_x:02
Local Alarm 3
40290:3
290:3
BA02_x:03
Local Alarm 4
40290:4
290:4
BA02_x:04
Liebert Monitoring Group – Development
Air Unit – Standard Microprocessor – LSM
Page 20 of 149
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Setpoints (View)
Temperature Setpoint
40010
10
BS10_x
Temperature Tolerance
40011
11
BS11_x
Humidity Setpoint
40012
12
BS12_x
Humidity Tolerance
40013
13
BS13_x
Control Points (Set)
Unit On / Off
40349
349
BC01_x
Bit 0 on=unit off Bit 1 on=unit on
Temperature Setpoint
40350
350
BC02_x
Temperature Tolerance
40350
350
BC02_x
Multiply desired value by 1000
Humidity Setpoint
40351
351
BC03_x
Humidity Tolerance
40351
351
BC03_x
Multiply desired value by 1000
Trendable Points (Set)
Temperature
Humidity
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 21 of 149
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Challenger 3000. Deluxe System / 3, ICS, System 4 (Replaces L15 & L1A)
HiMod (LNA version) – iCOM control using native IGM terminal 77/78
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Temperature
40001
1
BS01_x
Humidity
40002
2
BS02_x
Cooling
40003
3
BS03_x
1=on / 0=off
Heating
40004
4
BS04_x
1=on / 0=off
Humidification
40005
5
BS05_x
1=on / 0=off
De-humidification
40006
6
BS06_x
1=on / 0=off
Econ-O-Cycle
40007
7
BS07_x
1=on / 0=off
Stages
40008
8
BS08_x
% Capacity
40009
9
BS09_x
Unit Status (On / Off)
40018
18
BS18_x
1=on / 0=off
Alarm Points
Discrete BACnet alarm objects available –
use auto-discover for this unit
Communications
40289:0
289:0
BA01_x:00
Local Off
40289:1
289:1
BA01_x:01
Remote Off
40289:2
289:2
BA01_x:02
High Head Pressure 1
40289:3
289:3
BA01_x:03
High Head Pressure 2
40289:4
289:4
BA01_x:04
Loss of Airflow
40289:5
289:5
BA01_x:05
Standby Glycol Unit On
40289:6
289:6
BA01_x:06
Liquid Detected
40289:7
289:7
BA01_x:07
Change Filters
40289:8
289:8
BA01_x:08
High Temperature
40289:9
289:9
BA01_x:09
Low Temperature
40289:10
289:10
BA01_x:10
High Humidity
40290:0
290:0
BA02_x:00
Low Humidity
40290:1
290:1
BA02_x:01
Humidifier Problem
40290:2
290:2
BA02_x:02
No Water in Humidifier Pan
40290:3
290:3
BA02_x:03
Liebert Monitoring Group – Development
Air Unit – Advanced Microprocessor – LAM
Page 22 of 149
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Compressor 1 Overload
40290:4
290:4
BA02:04_x
Compressor 2 Overload
40290:5
290:5
BA02:05_x
Main Fan Overload
40290:6
290:6
BA02:06_x
Manual Override
40290:7
290:7
BA02:07_x
Smoke Detected
40290:8
290:8
BA02:08_x
Loss of Water
40290:9
290:9
BA02:09_x
Standby Unit On
40290:10
290:10
BA02:10_x
Low Suction
40291:0
291:0
BA03:00_x
Short Cycle
40291:1
291:1
BA03:01_x
Loss of Power
40291:2
291:2
BA03:02_x
Inverter on Bypass
40291:3
291:3
BA03:03_x
Standby Fan On
40291:4
291:4
BA03:04_x
Loss of Emergency Power
40291:5
291:5
BA03:05_x
Local Alarm 1
40291:6
291:6
BA03:06_x
Local Alarm 2
40291:7
291:7
BA03:07_x
Off by Remote Shutdown
40291:8
291:9
BA03:08_x
Runtimes (View)
Runtimes not available on iCOM control
Compressor 1 Run Hours
40019
19
BS19_x
Compressor 2 Run Hours
40020
20
BS20_x
Glycol Run Hours
Fan Motor Run Hours
40021
21
BS21_x
Humidifier Run Hours
40022
22
BS22_x
Reheat 1 Run Hours
Reheat 2 Run Hours
Reheat 3 Run Hours
Chilled Water Valve Run
Hours
Setpoints (View)
Temperature Setpoint
40010
10
BS10_x
Temperature Tolerance
40011
11
BS11_x
Humidity Setpoint
40012
12
BS12_x
Humidity Tolerance
40013
13
BS13_x
High Temp Alarm Setpoint
40014
14
BS14_x
Low Temp Alarm Setpoint
40015
15
BS15_x
High Humd Alarm Setpoint
40016
16
BS16_x
Low Humidity Alarm Setpoint
40017
17
BS17_x
Liebert Monitoring Group – Development
Page 23 of 149
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Control Points (Set)
Unit On / Off
40349
349
BC01_x
Bit 0 on=unit off Bit 1 on=unit on
Temperature Setpoint
40350
350
BC02_x
Temperature Tolerance
40350
350
BC02_x
Multiply desired value by 1000
Humidity Setpoint
40351
351
BC03_x
Humidity Tolerance
40351
351
BC03_x
Multiply desired value by 1000
Reheat Lockout
40349
349
BC01_x
Bit 2 on=RH off Bit 3 on=RH on
Humidifier Lockout
40349
349
BC01_x
Bit 4 on=HL off Bit 5 on=HL on
Trendable Points (Set)
Temperature
Humidity
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 24 of 149
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
DataMate, Mini-Mate, Mini-Mate Plus
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Temperature
40001
1
BS01_x
Humidity
40002
2
BS02_x
Cooling
40003
3
BS03_x
1=on / 0=0ff
Heating
40004
4
BS04_x
1=on / 0=0ff
Humidification
40005
5
BS05_x
1=on / 0=0ff
Dehumidification
40006
6
BS06_x
1=on / 0=0ff
Econ-o-Cycle
40007
7
BS07_x
1=on / 0=0ff
Stages
40008
8
BS08_x
% Capacity
40009
9
BS09_x
Unit On/Off
40011
11
BS11_x
1=on / 0=0ff
Alarm Points
Communications
40289:0
289:0
BA01_x:00
Local Off
40289:1
289:1
BA01_x:01
Remote Off
40289:2
289:2
BA01_x:02
High Temperature
40289:3
289:3
BA01_x:03
Low Temperature
40289:4
289:4
BA01_x:04
High Humidity
40289:5
289:5
BA01_x:05
Low Humidity
40289:6
289:6
BA01_x:06
Setpoints (View)
None
Control Points (Set)
Remote On/Off
40349
349
BC01_x
Bit 0 on=unit off Bit 1 on=unit on
Liebert Monitoring Group – Development
Air Unit – Small Systems – L0B
Page 25 of 149
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Trendable Points (Set)
Temperature
Humidity
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 26 of 149
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Mini-Mate 2, DataMate
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available
Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Temperature
40001
1
BS01_x
Humidity
40002
2
BS02_x
Cooling
40003
3
BS03_x
1=on / 0=off
Heating
40004
4
BS04_x
1=on / 0=off
Humidification
40005
5
BS05_x
1=on / 0=off
Dehumidification
40006
6
BS06_x
1=on / 0=off
Econ-o-Cycle
40007
7
BS07_x
1=on / 0=off
Stages
40008
8
BS08_x
% Capacity
40009
9
BS09_x
Unit On/Off
40018
18
BS18_x
1=on / 0=off
Alarm Points
Communications
40289:0
289:0
BA01_x:00
Local Off
40289:1
289:1
BA01_x:01
Remote Off
40289:2
289:2
BA01_x:02
High Head Pressure 1
40289:3
289:3
BA01_x:03
Loss of Airflow
40289:5
289:5
BA01_x:05
Standby Glycol Unit On
40289:6
2896
BA01_x:06
Change Filters
40289:7
289:7
BA01_x:07
High Temperature
40289:8
289:8
BA01_x:08
Low Temperature
40289:9
289:9
BA01_x:09
High Humidity
40290:0
290:0
BA02_x:00
Low Humidity
40290:1
290:1
BA02_x:01
Humidifier Problem
40290:2
290:2
BA02_x:02
Smoke Detected
40290:8
290:8
BA02_x:08
Loss of Water Flow
40290:9
290:9
BA02_x:09
Standby Unit On
40290:10
290:10
BA02_x:10
Liebert Monitoring Group – Development
Air Unit – Mini-Mate 2 – MM2, DataMate
Page 27 of 149
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Short Cycle
40291:1
291:1
BA03:01
Loss of Power
40291:2
291:2
BA03:02
Local Alarm 1
40291:6
291:6
BA03:06
Local Alarm 2
40291:7
291:7
BA03:07
High Water
40291:8
291:8
BA03:08
Local Alarm 4
40291:9
291:9
BA03:09
Run Hours (View)
Compressor 1
40019
19
BS19_x
Fan Motor
40020
20
BS20_x
Humidifier
40021
21
BS21_x
Reheat 1
Reheat 2
Reheat 3
Chilled Water Valve
Setpoints (View)
Temperature
40010
10
BS10_x
Temp Tolerance
40011
11
BS11_x
Humidity
40012
12
BS12_x
Humidity Tolerance
40013
13
BS13_x
High Temperature Alarm
40014
14
BS14_x
Low Temperature Alarm
40015
15
BS15_x
High Humidity Alarm
40016
16
BS16_x
Low Humidity Alarm
40017
17
BS17_x
Control Points (Set)
Remote On/Off
40349
349
BC01_x
Bit 0 on=unit off Bit 1 on=unit on
Temperature Setpoint
40350
350
BC02_x
Temperature Tolerance
40350
350
BC02_x
Multiply desired value by 1000
Humidity Setpoint
40351
351
BC03_x
Humidity Tolerance
40351
351
BC03_x
Multiply desired value by 1000
Trendable Points (Set)
Temperature
Humidity
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 28 of 149
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
MiniMate - 8 Ton only
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Temperature
40001
1
BS01_x
Humidity
40002
2
BS02_x
Cooling
40003
3
BS03_x
1=on / 0=off
Heating
40004
4
BS04_x
1=on / 0=off
Humidification
40005
5
BS05_x
1=on / 0=off
De-humidification
40006
6
BS06_x
1=on / 0=off
Econ-O-Cycle
40007
7
BS07_x
1=on / 0=off
Stages
40008
8
BS08_x
% Capacity
40009
9
BS09_x
Unit Status (On / Off)
40018
18
BS18_x
1=on / 0=off
Alarm Points
Communications
40289:0
289:0
BA01_x:00
Local Off
40289:1
289:1
BA01_x:01
Remote Off
40289:2
289:2
BA01_x:02
High Head Pressure 1
40289:3
289:3
BA01_x:03
High Head Pressure 2
40289:4
289:4
BA01_x:04
Loss of Airflow
40289:5
289:5
BA01_x:05
Standby Glycol Unit On
40289:6
289:6
BA01_x:06
Not Used
40289:7
289:7
BA01_x:07
Change Filters
40289:8
289:8
BA01_x:08
High Temperature
40289:9
289:9
BA01_x:09
Low Temperature
40289:10
289:10
BA01_x:10
High Humidity
40290:0
290:0
BA02_x00
Low Humidity
40290:1
290:1
BA02_x01
Humidifier Problem
40290:2
290:2
BA02_x02
Not Used
40290:3
290:3
BA02_x03
Liebert Monitoring Group – Development
Air Unit – 8 Ton MiniMate – L8T
Page 29 of 149
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Not Used
40290:4
290:4
Not Used
40290:5
290:5
Not Used
40290:6
290:6
Not Used
40290:7
290:7
Smoke Detected
40290:8
290:8
BA02_x:08
Loss of Water
40290:9
290:9
BA02_x:09
Standby Unit On
40290:10
290:10
BA02_x:10
Not Used
40291:0
291:0
BA03_x:00
Short Cycle
40291:1
291:1
BA03_x:01
Loss of Power
40291:2
291:2
BA03_x:02
Not Used
40291:3
291:3
BA03_x:03
Not Used
40291:4
291:4
BA03_x:04
Not Used
40291:5
291:5
BA03_x:05
Local Alarm 1
40291:6
291:6
BA03_x:06
Local Alarm 2
40291:7
291:7
BA03_x:07
High Water Humidifier Pan
40291:8
291:8
BA03_x:08
Run Times (View)
Compressor 1 Run Hours
40019
19
BS19_x
Compressor 2 Run Hours
40020
20
BS20_x
Glycol Run Hours
Fan Motor Run Hours
40021
21
BS21_x
Humidifier Run Hours
40022
22
BS22_x
Reheat 1 Run Hours
Reheat 2 Run Hours
Reheat 3 Run Hours
Chilled H2O Valve Run Hours
Setpoints (View)
Temperature Setpoint
40010
10
BS10_x
Temperature Tolerance
40011
11
BS11_x
Humidity Setpoint
40012
12
BS12_x
Humidity Tolerance
40013
13
BS13_x
High Temp Alarm Setpoint
40014
14
BS14_x
Low Temp Alarm Setpoint
40015
15
BS15_x
High Humidity Alarm Setpoint
40016
16
BS16_x
Low Humidity Alarm Setpoint
40017
17
BS17_x
Liebert Monitoring Group – Development
Page 30 of 149