Liebert SiteScan Reference Manual

Page 1
Revision B.33 2/25/2011
Liebert Monitoring Group – Development
Liebert® SiteScan®
Protocol Reference Document for
Including Modbus and BACnet object
Listings
Reference document is based on the assumption that the
connecting module is of exec. 6 or exec. B firmware type unless
otherwise noted.
Page 1 of 149
Page 2
Liebert Monitoring Group – Development
Revision
Date
Description
B.5
11/8/00
Added: revision level update chart, HiPulse support, and NPower support
B.6
2/19/01
Revised NPower definition
B.7
4/4/02
Added support for HiMod LNA
B.8
5/3/02
Revised Modbus explanation (Hi Byte / Lo Byte)
B.9
10/1/02
Corrected NPower table (typing error)
B.10
1/22/03
Added support for DataMate
B.11
7/23/03
Added support for STS-2
B.12
4/19/04
Corrected ModBus register addressing for STS-2 alarms. PM2 – removed duplicate Output Voltage THD Alarm. Added XDP Unit. Added LDS5000 Unit. Added Universal Monitor. Added BACNet/IP for: WDU, MM4, SC4, PM2 & LAM. Added Run Hours for MM2
B.13
5/24/04
Removed non-existent alarms for MM2. Added BacNet/IP Point addresses for MM2.
B.14
8/19/200 4
Track issue 3576 – Make BacNet points consistent with Modbus Points.
B.15
11/22/20 04
Added ESP-2 based UPS Units that use OC485 card. Includes Nx, HiNet, PSI, and GXT
B.16
5/18/05
Added “High Water Humidifier Pan” alarm to L00. Corrected alarm points for BACNet and Modbus addressing on STS-2.
B.17
7/1/05
Added Remote shutdown alarm to LAM. Added Note about Alarms “BACNet auto
discovery” to CCM, L00, LAM, MMS, PM2, PMP, SCC. Added note to STS2 that it is
for units with or without PDU. Changed breaker status register for STS2 from bits1-8 to 0-7.
B.18
7/21/05
Added XDC Unit. Added control point note for units with on/off control as follows: Bit 0 on=unit off Bit 1 on=unit on. Removed cables 3 & 4 on LDS5000 and marked these registers as spares.
B.19
11/30/05
Corrected revision level and date in header on this document.
B.20
12/14/05
SMS – Added Scale factor for kVA & kW. Revised note on page 1 to state module type rather than “SS2000 Hardware”.
B.21
8/9/06
Series 610 UPS – added note that Series 610 is the same as series 600. SC4-SM4
changed “Bypass Breaker Closed” alarm from “Bypass Breaker Open”. Added note to
LAM that iCOM w/native IGM also applies.
B.22
8/10/06
Nfinity UPS (pnf), Nx (pnx), STS-2 (st2) – deleted status and setpoint points that are not displayed in SiteScan. XDC, XDP added scale factor notes for Ref, Fluid and CW temps.
B.23
3/16/07
PMP – Local Alarm #1 was Load Alarm, Added Local Alarm #2, Corrected Modbus addressing from 40290:04 to 40290:07
B.24
4/16/07
AC8 – Added Unit tables to reference library
B.25
4/30/07
MM2 – Corrected entire table due to MS Word problems.
B.26
5/2/07
Corrected major MS Word formatting problems throughout document.
B.27
11/15/07
Added iCOM DS unit for 2mb modules (small version), SM3 corrected reversed Modbus addressing for kW & kVA. Noted that pages for Series 600 UPS also apply to series 610.
B.28
6/24/08
Added iCOM-XDP unit
B.29
7/11/08
Corrected alarm info for Npower (IMP) unit.
B.30
5/13/09
Corrected revision number in page header B.30 from B.9. Changed XDP unit description on page 53 from XD. Corrected miscellaneous document formatting errors. Added WDU definition back in document from accifental deletion.
B.31
10/13/09
Added local Alarms 2,3 &4 for MM2, L00 & LSM. Local alrm 3=High Water for MM2
B.32
4/23/10
Clarified LAM/iCOM program usage and added iCOM 16mb version. Added examples and notes sections. Removed discontinued modules.
B.33
2/2/11
Removed General Alarm from iCOM_DS. Added Hi Water Humidifier Pan to L8T. Moved Generator Disconnected from Alarm to Status in NX unit.
Revision Level Updates:
Revision B.33 2/25/2011
Page 2 of 149
Page 3
Revision B.33 2/25/2011
Liebert Monitoring Group – Development

Table of Contents

Click on the desired page number for instant navigation. Use the back arrow on your toolbar to return to the table of contents.
TABLE OF CONTENTS.................................................................................................................................................. 3
OPEN COMMUNICATIONS .............................................. 7
DEFAULT MAPPING FOR MODBUS & BACNET OBJECTS ............................................................................................ 7
MODBUS COMMUNICATIONS ...................................................................................................................................... 9
Connectivity to SiteLink modules using Modbus ................................................................................................... 9
Implementation Basics ........................................................................................................................................... 9
Transmission Format ............................................................................................................................................. 9
Modbus Packet Format........................................................................................................................................ 10
RTU Framing ....................................................................................................................................................... 11
BACNET COMMUNICATIONS .................................................................................................................................... 12
BACnet Protocol Implementation Conformance Statement Rev. 2.1 .............................................................. 12
LIEBERT ENVIRONMENTAL UNITS ............................. 15
AIR UNIT - LEVEL 0 L00 ................................ ................................ ................................................................ ........ 16
AIR UNIT LEVEL 10 L10 ................................................................................................................................ ..... 18
AIR UNIT STANDARD MICROPROCESSOR LSM ................................................................................................... 20
AIR UNIT ADVANCED MICROPROCESSOR LAM .................................................................................................. 22
AIR UNIT SMALL SYSTEMS L0B ......................................................................................................................... 25
AIR UNIT MINI-MATE 2 MM2, DATAMATE ....................................................................................................... 27
AIR UNIT 8 TON MINIMATE L8T ........................................................................................................................ 29
ATLAS AIR UNIT C10 ............................................................................................................................................ 32
CHILLER UNIT CSU3000 CSU ............................................................................................................................ 35
CHILLER UNIT CSU 3000 W/ECONO CSE ........................................................................................................... 37
AIR UNIT - HIROSS MICROFACE ............................................................................................................................... 39
AIR UNIT X-TREME DENSITY COOLANT DISTRIBUTION UNIT CDU .................................................................... 43
AIR UNIT X-TREME DENSITY COOLANT PUMPING UNIT XDP ............................................................................ 45
AIR UNIT X-TREME DENSITY CHILLER UNIT XDC ................................................................ ............................. 47
AIR UNIT ICOM DS & RETROFIT (2MB VERSION SITELINK) ................................................................................. 50
AIR UNIT ICOM DS & RETROFIT (16MB VERSION SITELINK) ............................................................................... 53
AIR UNIT XDP REFRIGERANT PUMPING UNIT XDP W/ ICOM CONTROL .......................................................... 58
LIEBERT POWER UNITS ............................................... 60
POWER UNIT VOLTAGE- CURRENT MONITORING PANEL – VCM .......................................................................... 61
POWER UNIT POWER MONITORING PANEL PMP ................................................................................................ 63
POWER UNIT VOLTAGE-CURRENT-FREQ. MONITOR PANEL – VCF ....................................................................... 66
POWER UNIT POWER MONITORING PANEL (EXT. PROTOCOL– PM2) .................................................................... 68
POWER UNIT STATIC TRANSFER SWITCH PDU EDS ........................................................................................... 71
POWER UNIT STATIC TRANSFER SWITCH PDU DUAL OUTPUT STS ................................................................... 74
POWER UNIT STATIC TRANSFER SWITCH PDU DUAL OUTPUT STS-2 ................................................................ 77
LIEBERT UPS UNITS ..................................................... 81
UPS UNIT MULTI MODULE UPS S600/610 EXTENDED PROT. MM4 ............................................................... 82
UPS UNIT MULTI MODULE SERIES MMS ........................................................................................................... 85
UPS UNIT SYSTEM CONTROL CABINET S/610 EXT. PROT. SC4 ....................................................................... 87
UPS UNIT SYSTEM CONTROL CABINET SCC ...................................................................................................... 90
UPS UNIT SINGLE MODULE SERIES SMS ........................................................................................................... 92
UPS UNIT SINGLE MODULE UPS S/610 EXT. PROT. SM4 ............................................................................... 94
Page 3 of 149
Page 4
Revision B.33 2/25/2011
Liebert Monitoring Group – Development
UPS UNIT MULTI-MODULE SICE 7200 & HIPULSE UPS SMM ......................................................................... 98
UPS UNIT SYSTEMS CABINET SICE 7200 UPS SSC ......................................................................................... 103
UPS UNIT SINGLE MODULE SICE 7200 & HIPULSE UPS SSM ........................................................................ 106
UPS UNIT UPSTATION S3 US3......................................................................................................................... 111
UPS UNIT SINGLE MODULE SERIES AP301/302 SM3 ...................................................................................... 114
UPS UNIT SINGLE MODULE UPS NPOWER—IMP ........................................................................................... 117
UPS UNIT SINGLE MODULE UPS NX—PNX ................................................................................................... 120
UPS UNIT HINET PHN ..................................................................................................................................... 123
UPS UNIT NFINITY PNF ................................................................................................................................... 125
UPS UNIT GXT PGX........................................................................................................................................ 128
UPS UNIT PSI PPS ........................................................................................................................................... 132
LIEBERT MONITORING MODULES ............................ 135
CONTACT CLOSURE MODULE CCM .................................................................................................................... 136
WATER/LIQUID DETECTION UNIT WDU ............................................................................................................. 139
REMOTE AUTOCHANGEOVER RAC ...................................................................................................................... 140
TEMPERATURE/HUMIDITY MODULE THM .......................................................................................................... 141
WATER/LIQUID DETECTION UNIT LDS5000 WD5 .............................................................................................. 144
UNIVERSAL MONITOR UVM ............................................................................................................................... 145
AUTOCHANGEOVER CONTROLLER – AC8 .............................................................................................................. 148
Page 4 of 149
Page 5
Revision B.33 2/25/2011
Liebert Units
Indicates the Environmental, Power, UPS or Monitoring Module by model name that uses this controller.
SiteScan Interface Modules
Indicates which SiteScan Hardware Modules can be used with the controller. Take Special note of this box when adding new units to an existing SiteScan system, as some new controllers are only compatible with the new hardware (SiteLink).
BMS interface Modules
Indicates which SiteScan Hardware Modules can be used with the controller for interfacing with a third part using BACnet or Modbus protocol.
Status Points (View)
Status Information for the listed points that will be presented in SiteScan
Alarm Points
Alarms that are available to SiteScan
Setpoints (View)
Current settings of controllable Setpoints available to SiteScan
Control Points (Set)
Setpoints that can be changed with SiteScan
Trendable Points (Set)
Points that can be graphically trended within the SiteScan software
Reports
Reports that can be triggered within the SiteScan software
Liebert Monitoring Group – Development

How to use the Reference Library Charts

This document contains a dedicated sheet for each Liebert Unit and associated controller. The title of each chart contains the name of the Liebert Controller used such as L00 for a Level-0 Air unit or PMP for a Power Monitoring Panel for Power Center.
Every documented unit assumes the maximum possible optional points and configuratios of the specific unit family. The specific points that will be used depend on the unit being read as that unit will only report values and alarms that the specific unit supports.
The first section, Compatible Hardware, indicates the equipment associated with this particular controller as follows:
The next section, Available Points, contains six categories providing the following information:
Page 5 of 149
Page 6

Liebert Unit ID Chart

3-Letter ID
Environmental Products
3-Letter ID
UPS Products
L00
Level 00, Level 1
SMS
Single Module Series UPS - S300, S500, S600 (Prior to 1/98)
L10
Level 2, Level 3, and Level 10
SM3
Single Module Series 30x (latest version)
LAM
Level 15 and Level AM/AG, HiMod (LNA), iCOM control w/ native IGM terminal 77/78
SM4
Single Module Series 600/610 - Extended Protocol (1/98 or later)
LSM
Level SM and Level 0 w/ On/Off Control
US3
UPStation S3 UPS
L0B
Small Systems Controller
MMS
Multi Module Series 500-600 UPS (Prior to 1/98)
MM2
Small Systems Controller - Mini Mate II, DataMate
MM4
Multi Module Series 600/610 UPS ­Extended Protocol (1/98 or later)
C10
Atlas Air Environmental Control (LECS15)
SCC
System Control Cabinet Series 500-600 (Prior to 1/98)
CSE
Chiller w/ Econocoil
SC4
System Control Cabinet Series 600/610­Extended Protocol (1/98 or later)
CSU
Chiller
SSM
Single Module Series UPS - SICE 7200 & HiPulse
XDP
Xtreme Density Unit Environmental Control
SMM
Multi Module Series UPS - SICE 7200 & HiPulse
CDU
Xtreme Density Coolant Distribution Unit
SSC
System Control Cabinet - SICE 7200
iCOM
DS Unit with iCOM control or Deluxe System 3 with iCOM control retrofit using optional IS485 interface with 16mb SiteLink.
IMP
NPower (S300 Replacement)
iCOM-2mb
DS Unit with iCOM control or Deluxe System 3 with iCOM control retrofit using optional IS485 interface with 2mb SiteLink.
PNX
NX UPS – ESP2 Protocol
HIA
Hiross Hiromatic Air unit
PHN
HiNet UPS – ESP2 Protocol
Static Switch PDU
PNF
Nfinity UPS – ESP2 Protocol
EDS
Static Switch PDU (Single Output Breaker, Prior to 1/99)
PGX
GXT UPS – ESP2 Protocol
STS
Static Switch PDU (Dual Output Breaker Option, 1/99 or later)
PPS
PSI UPS – ESP2 Protocol
Miscellaneous
CCM
All IGM Contact Modules CM200 / RCM8 / VSM
RAC
Remote Autochangeover Module - RAC2-8
THM
Temperature / Humidity Module
Power Products PDU
WDU
Liquid Detection LDS750 or LDS1000
PMP
Precision Power & Datawave w/ PMP (latest LCD display)
WD5
Liquid Detection LDS5000
VCF
All Voltage-Current-Frequency Panels (Old Red LED Display)
UVM
Universal Monitor
VCM
All Voltage-Current Monitoring Panels (Old Red LED Display)
AC8
Autochangeover Controller
PM2
Precision Power & Datawave w/ PMP (latest LCD display and extended protocol EPROM version 3.290.0, manufactured and shipped after 4/99)
Revision B.33 2/25/2011
Liebert Monitoring Group – Development
Page 6 of 149
Page 7
Revision B.33 2/25/2011
Liebert Monitoring Group – Development

Open Communications

Default Mapping for Modbus & BACnet Objects

This model represents the standard configuration for a Liebert Sitelink-12 module. Consecutive register / object mapping is utilized, regardless of the SiteLink-12 population. All ports that do not have a Liebert IGM attached will be assigned null values (or zeros) for their corresponding registers. The default “slave ID” or “Device ID” follows the CMNet address of the unit. The address can be visually checked by looking at the address dip-switch or rotary switch settings. However, the address can be changed in software to suit specific needs.
Please note that the SiteLink hardware places a limit on the quantity of Modbus registers available. Therefore, it is possible there will be more data points available using BACnet than using Modbus.
How to use this table:
The unit or model specific reference sheets assume that the desired unit is attached to port 1 of the SiteLink module. If the desired unit is attached to a different port, the table below indicates the starting register or object number for the unit.
For example: The register for “temperature” for a L00 type unit attached to port 1 is identified as
40001. If an additional L00 type unit were attached to port 2, the “temperature” value would be located in
register 40025. The same type unit attached to port 3 = 40049…etc.
Modbus Notes:
Modbus Registers start at 40001. All registers are unsigned integers.
BACnet Notes:
BACnet Objects start at 1. All “Status” and “Alarm” objects are “AI’s” (analog inputs). The “Control” objects are “AO’s” (analog outputs)
Page 7 of 149
Page 8
Revision B.33 2/25/2011
Register Offset
Object Type
Port Assignment
1-24
Status
1
25-48
Status
2
49-72
Status
3
73-96
Status
4
97-120
Status
5
121-144
Status
6
145-168
Status
7
169-192
Status
8
193-216
Status
9
217-240
Status
10
241-264
Status
11
265-288
Status
12
289-293
Alarms
1
294-298
Alarms
2
299-303
Alarms
3
304-308
Alarms
4
309-313
Alarms
5
314-318
Alarms
6
319-323
Alarms
7
324-328
Alarms
8
329-333
Alarms
9
334-338
Alarms
10
339-343
Alarms
11
344-348
Alarms
12
349-351
Control
1
352-354
Control
2
355-357
Control
3
358-360
Control
4
361-363
Control
5
364-366
Control
6
367-369
Control
7
370-372
Control
8
373-375
Control
9
376-378
Control
10
379-381
Control
11
382-384
Control
12
Liebert Monitoring Group – Development
** See reference libraries for unit specific objects.
Page 8 of 149
Page 9
Revision B.33 2/25/2011
Physical
Port
Transmission
Mode
Baud Rate
Data Bits
Parity Bits
Stop Bits
Default
EIA-232 –
DB9 DCE
RTU
9600
8
None
1
Yes
EIA-232 –
DB9 DCE
ASCII
1200 –
38.4kbd
(19.2kbd omit)
Configurable
Configurable
Configurable
No
EIA-485 – 2
or 4 wire
RTU or ASCII
1200 –
38.4kbd
(19.2kbd omit)
Configurable
Configurable
Configurable
No
Liebert Monitoring Group – Development

Modbus Communications

Connectivity to SiteLink modules using Modbus

This design specification describes the Modbus communications protocol as supported by the SiteLink module. It includes information on how to pass information to and from the SiteLink module via Modbus. It is also intended to help facilitate answering questions regarding supported types, frame format, function code support etc.

Implementation Basics

Protocol controls the language structure or message format between devices in other words, the rules for communication. The rules for communication include how master and slave devices initiate communications, as well as unit identification, message handling and error checking. Modbus protocol simply refers to the control of the query and response cycles between master and slave devices.
The SiteLink module is configured to act as a slave device on a common network. The common network can be point-to-point over EIA-232, where one master communicates to one slave device or in a multi-drop configuration over EIA-485, where multiple slaves reside on a common wire or loop.
Documented write points can cause read errors if you attempt to read a write-only point. For example: an LAM air unit has separate Setpoint View and Setpoint Set registers and if you read a write-to register it can and most likely will result in a Modbus exception response. Do not include setpoint set registers in batch read commands as one point read error will result in an exception response for the entire batch read.

Transmission Format

The SiteLink module supports both Modbus RTU (Remote Terminal Unit) and ASCII (American Standard Code for Information Interchange) transmission modes. The SiteLink module has a choice of transmission medium, baud
rate, character parity and number of stop bits. See chart below.
Page 9 of 149
Page 10
Revision B.33 2/25/2011
Liebert Monitoring Group – Development

Modbus Packet Format

Each Modbus packet consists of the following fields:
Device Address Function Code Data Field(s) Error Check Field
Device Address:
The address field immediately follows the beginning of the frame and consists of 8-bits (RTU) or 2 characters (ASCII). These bits indicate the user assigned address of the slave device that is to receive the message sent by the attached master device.
Each slave must be assigned a unique address and only the addressed slave will respond to a query that contains its address.
Function Code:
The function code field tells the addressed slaves what function to perform. Function codes are specifically designed invoke a specific action by the slave device. The function code range is from 1 to 127. However, the
SiteLink module primarily uses Function Code 3 (Read Holding Registers), Function Code 6 (Preset Single Register) and Function Code 16 (Preset Multiple Registers).
Data Field(s):
The data field varies in length depending on whether the message is a request or a response to a packet. This field typically contains information required by the slave device to perform the command specified or to pass back data to the master device.
Error Check Field:
The Error Check Field consists of a 16-bit (2 byte) Cyclical Redundancy Check (CRC16). It allows the receiving device to detect a packet that has been corrupted with transmission errors.
Page 10 of 149
Page 11
Revision B.33 2/25/2011
Slave
Address
Function
Code
Starting
Register
―Hi Byte‖
Starting
Register
―Lo Byte‖
Number of
Registers
―Hi Byte‖
Number of
Registers ―Lo Byte‖
CRC16
―Hi Byte‖
CRC16
―Lo Byte‖
02
03
00
32
00
03
E5
FA
Slave
Address
Function
Code
Count:
Bytes of
Data
Register
40051 Data
Hi Lo
Register
40052 Data
Hi Lo
Register
40053 Data
Hi Lo
CRC16
―Hi Byte
CRC16
―Lo Byte‖
02
03
6
01 58
00 FA
00 54
1B
0D
Frame
Start
Slave
Address
Function
Code
Data
Error
Check
End of
Frame
CR
Ready for
Data
LF
:
2 Char 16-bits
2 Char 16-bits
N x 4 Char N x 16-bits
B3
0D
0A
Liebert Monitoring Group – Development

RTU Framing

The example below shows a typical Q/R from a SiteLink module. In common terms, the master device initiates a query asking slave device 2 for holding registers starting at holding register 40051 (decimal 50) and including next 2 Registers (3 total).
Query Sample
Response Sample
Slave address 2 responds to Function Code 3 with 6 bytes of hexadecimal data and ends with CRC16 checksum.
Register values: 40051 = 158(hex) = 344(decimal)
40052 = FA (hex) = 250 (decimal) 40053 = 54 (hex) = 84 (decimal)
ASCII Framing:
Framing in ASCII transmission mode is accomplished by the use of the unique colon (:) to indicate the beginning of the frame and a carriage return (CR) line feed (LF) to delineate the end of the frame. The line feed also serves as a synchronizing character which indicates that the transmitting station is ready to receive an immediate reply.
ASCII Example
Char = Character: 1 Character = 7 data bits, 1 start bit, 1 or 2 stop bits and 1 parity bit (optional)
Page 11 of 149
Page 12
Revision B.33 2/25/2011
Class 1
Class 4
Class 2
Class 5
Class 3
x
Class 6
Clock
Files
HHWS
Reinitialize
PCWS
Virtual Operator Interface
Event Initialization
Virtual Terminal
Event Response
Device Communications
COV Event Initiation
Time Master
COV Event Response
Liebert Monitoring Group – Development

BACnet Communications

BACnet Protocol Implementation Conformance Statement Rev. 2.1

Vendor Name: Liebert Corporation Product Name: SiteLink Module Product Model Number: SiteLink (All)
Point Documentation:
The points in this document are listed by object reference name and each exposed BACnet point has information in the description field detailing what the point is. Both of these BACnet properties can be read and discovered remotely in addition to the points present value property. This document is not able to define specific object instance numbers because they are dynamically assigned when the programming for the module is created and will vary from situation to situation. A report detailing reference name, description and object instance number can be requested from the startup engineer at the time of the modules commissioning.
If after startup if changes are made or new programs are added the dynamically built AV/BV points list will shift for all points.
Product Description:
The SiteLink module provides a BACnet Point-to-Point communication exchange between proprietary Liebert Environmental, Power, UPS units to other BACnet compliant devices. The connection to the SiteLink module is via EIA-232, 9600 baud, no parity, 8 data bits, 1 stop bit (9600,N,8,1 default.) The SiteLink modules are available in 12 port and 4 port configurations (i.e. 1 port per/ Liebert Unit, 12 Liebert units per/ SiteLink module maximum.)
BACnet Conformance Class Supported:
BACnet Functional Groups Supported:
Page 12 of 149
Page 13
Liebert Monitoring Group – Development
Application Service
Initiate
Requests
Execute Requests
AcknowledgeAlarm
ConfirmedCOVNotification
ConfirmedEventNotification
GetAlarmSummary
GetEnrollmentSummary
SubscribeCOV
UnconfirmedCOVNotification
UnconfirmedEventNotification
AtomicReadFile
AtomicWriteFile
AddListElement
RemoveListElement
CreateObject
DeleteObject
ReadProperty
X
X
ReadPropertyConditional
ReadPropertyMultiple
X
WriteProperty
X
X
WritePropertyMultiple
X DeviceCommunicationControl
ConfirmedPrivateTransfer
UnconfirmedPrivateTransfer
ReinitializeDevice
ConfirmedTextMessage
TimeSynchronization
Who-Has
X
I-Have
X
Who-Is
X
I-Am
X
VT-Open
VT-Closed
VT-Data
Authenticate
Request Key
BACnet Standard Application Services Supported:
Revision B.33 2/25/2011
Page 13 of 149
Page 14
Revision B.33 2/25/2011
Object Type
Supported
Dynamically
Creatable
Dynamically
Deleteable
Optional
Properties
Writable
Properties
Analog Input
X None
Analog Output
X
Present Value
Analog Value
Binary Input
Binary Output
Binary Value
Calendar
Command
Device
Event Enrollment
File
Group
Loop
Multi-State Input
Multi-State Output
Notification Class
Program
Schedule
Segmented Requests Supported
No
Segmented Responses Supported
No
Router
No
Liebert Monitoring Group – Development
BACnet Standard Application Services Supported (continued):
Data Link Layer:
Point-to-Point, EIA-232, baud rates: 9600 & 38,400
Character Set Supported:
ANSI X3.4
Special Functionality:
Page 14 of 149
Page 15
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Control Points (Set)
Unit On/Off
40349
349
BC01_x
Bit 0 on=unit off Bit 1 on=unit on
Temperature Setpoint
40350
350
BC02_x
Temperature Tolerance
40350
350
BC02_x
Multiply desired value by 1000
Humidity Setpoint
40351
351
BC03_x
Humidity Tolerance
40351
351
BC03_x
Multiply desired value by 1000
Reheat Lockout
40349
349
BC01_x
Bit 2 on=RH off Bit 3 on=RH on
Humidifier Lockout
40349
349
BC01_x
Bit 2 on=HL off Bit 3 on=HL on
Function
Command if
BIT=1
BIT
Number
Value sent from
BMS
Resulting Action
Unit On/Off
―Off‖
BIT 0 1 Units turns ―Off‖
Unit On/Off
―On‖
BIT 1 2 Unit turns ―On‖
Reheat Lockout
―Off‖
BIT 2 4 Reheat Lockout turns ―Off‖
Reheat Lockout
―On‖
BIT 3 8 Reheat Lockout turns ―On‖
Humidifier Lockout
―Off‖
BIT 4
16
Humidifier Lockout turns ―Off‖
Humidifier Lockout
―On‖
BIT 5
32
Humidifier Lockout turns ―On‖
Control Points (Set)
Temperature Setpoint
40350
350
BC02_x
Temperature Tolerance
40350
350
BC02_x
Multiply desired value by 100
Humidity Setpoint
40351
351
BC03_x
Humidity Tolerance
40351
351
BC03_x
Multiply desired value by 100
Liebert Monitoring Group – Development

Liebert Environmental Units

Using Unit Control Points
This section is an example of how to utilize Liebert environmental unit Setpoints Set registers. In all cases the Setpoints View section contains the value that the unit itself is reporting and can be used to confirm that the unit received the transmitted command.
Example table from this document:
The above notes in the document refer to binary bits. Notice that register 40349 is used more than once in the table. The table below shows the integer number in the value set from BMS column.
For the setpoint registers, the setpoint and tolerance are in the same register. Writing a zero to the field will result in no change.
Some examples of valid values to send:
To make the Temperature Setpoint “70”, send a “70” to the register. To make the Temperature Tolerance “+/- 2.5 degrees”, send “2500” to the register. To make the Temperature Tolerance “+/- 2.5 degrees” and Setpoint “70”, send “2570” to the register. To make the Humidity Setpoint “50%”, send a “50” to the register. To make the Humidity Tolerance “+/- 5%”, send “5000” to the register. To make the Humidity Tolerance “+/- 5%” and Setpoint “50%”, send “5050” to the register.
Page 15 of 149
Page 16
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Challenger 3, Logicool, Modular Plus, LS400, Mini-Tower, System 4
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Temperature
40001
1
BS01_x
Humidity
40002
2
BS02_x
Cooling
40003
3
BS03_x
1=on / 0=0ff
Heating
40004
4
BS04_x
1=on / 0=0ff
Humidification
40005
5
BS05_x
1=on / 0=0ff
Dehumidification
40006
6
BS06_x
1=on / 0=0ff
Econ-o-Cycle
40007
7
BS07_x
1=on / 0=0ff
Stages
40008
8
BS08_x
% Capacity
40009
9
BS09_x
Alarm Points
Discrete BACnet alarm objects available – use auto-discover for this unit
Communications
40289:0
289:0
BA01_x:00
High Head Pressure 1
40289:1
289:1
BA01_x:01
High Head Pressure 2
40289:2
289:2
BA01_x:02
Loss of Airflow
40289:3
289:3
BA01_x:03
Liquid Detected
40289:4
289:4
BA01_x:04
Change Filters
40289:5
289:5
BA01_x:05
High Temperature
40289:6
289:6
BA01_x:06
Low Temperature
40289:7
289:7
BA01_x:07
High Humidity
40289:8
289:8
BA01_x:08
Low Humidity
40289:9
289:9
BA01_x:09
Local Alarm 1
40289:10
289:10
BA01_x:10
High Water Humidifier Pan
40289:11
289:11
BA01_x:11
Local Alarm 2
40289:12
289:12
BA01_x:12
Local Alarm 3
40289:13
289:13
BA01_x:13
Local Alarm 4
40289:14
289:14
BA01_x:14
Liebert Monitoring Group – Development

Air Unit - Level 0 – L00

Page 16 of 149
Page 17
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Setpoints (View)
Temperature Setpoint
40010
10
BS10_x
Temperature Tolerance
40011
11
BS11_x
Humidity Setpoint
40012
12
BS12_x
Humidity Tolerance
40013
13
BS13_x
Control Points (Set)
Temperature Setpoint
40350
350
BC02_x
Temperature Tolerance
40350
350
BC02_x
Multiply desired value by 1000
Humidity Setpoint
40351
351
BC03_x
Humidity Tolerance
40351
351
BC03_x
Multiply desired value by 1000
Trendable points (Set)
Temperature
Humidity
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 17 of 149
Page 18
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Modular Plus, Deluxe System/3, Industrial Cooling Series
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Temperature
40001
1
BS01_x
Humidity
40002
2
BS02_x
Cooling
40003
3
BS03_x
1=on / 0=off
Heating
40004
4
BS04_x
1=on / 0=off
Humidification
40005
5
BS05_x
1=on / 0=off
Dehumidification
40006
6
BS06_x
1=on / 0=off
Econ-o-Cycle
40007
7
BS07_x
1=on / 0=off
Stages
40008
8
BS08_x
% Capacity
40009
9
BS09_x
Alarm Points
Communications
40289:0
289:0
BA01_x:00
High Head Pressure 1
40289:1
289:1
BA01_x:01
High Head Pressure 2
40289:2
289:2
BA01_x:02
Loss of Airflow
40289:3
289:3
BA01_x:03
Standby Glycol Unit On
40289:4
289:4
BA01_x:04
Liquid Detected
40289:5
289:5
BA01_x:05
Change Filters
40289:6
289:6
BA01_x:06
High Temperature
40289:7
289:7
BA01_x:07
Low Temperature
40289:8
289:8
BA01_x:08
High Humidity
40289:9
289:9
BA01_x:09
Low Humidity
40289:10
289:10
BA01_x:10
Humidifier Problem
40290:0
290:0
BA02_x:00
No Water in Humidifier Pan
40290:1
290:1
BA02_x:01
Compressor 1 Overload
40290:2
290:2
BA02_x:02
Compressor 2 Overload
40290:3
290:3
BA02_x:03
Main Fan Overload
40290:4
290:4
BA02_x:04
Liebert Monitoring Group – Development

Air Unit – Level 10 – L10

Page 18 of 149
Page 19
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Manual Override
40290:5
290:5
BA02_x:05
Smoke Detected
40290:6
290:6
BA02_x:06
Loss of Water
40290:7
290:7
BA02_x:07
Standby Unit On
40290:8
290:8
BA02_x:08
Low Suction
40290:9
290:9
BA02_x:09
Short Cycle
40290:10
290:10
BA02_x:10
Loss of Power
40291:0
291:0
BA03_x:00
Inverter Bypass
40291:1
291:1
BA03_x:01
Standby Fan On
40291:2
291:2
BA03_x:02
Loss of Emergency Power
40291:3
291:3
BA03_x:03
Local Alarm 1
40291:4
291:4
BA03_x:04
Local Alarm 2
40291:5
291:5
BA04_x:05
Setpoints (View)
Temperature Setpoint
40010
10
BS10_x
Temperature Tolerance
40011
11
BS11_x
Humidity Setpoint
40012
12
BS12_x
Humidity Tolerance
40013
13
BS13_x
High Temperature Setpoint
40014
14
BS14_x
Low Temperature Setpoint
40015
15
BS15_x
High Humidity Setpoint
40016
16
BS16_x
Low Humidity Setpoint
40017
17
BS17_x
Auto-Restart Delay
Control Points (Set)
Temperature Setpoint
40350
350
BC02_x
Temperature Tolerance
40350
350
BC02_x
Multiply desired value by 1000
Humidity Setpoint
40351
351
BC03_x
Humidity Tolerance
40351
351
BC03_x
Multiply desired value by 1000
Trendable Points (Set)
Temperature
Humidity
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 19 of 149
Page 20
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Challenger 3000. Deluxe System / 3, ICS , System 4 (Replaces L0A control)
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Temperature
40001
1
BS01_x
Humidity
40002
2
BS02_x
Cooling
40003
3
BS03_x
1=on / 0=off
Heating
40004
4
BS04_x
1=on / 0=off
Humidification
40005
5
BS05_x
1=on / 0=off
De-humidification
40006
6
BS06_x
1=on / 0=off
Econ-O-Cycle
40007
7
BS07_x
1=on / 0=off
Stages
40008
8
BS08_x
% Capacity
40009
9
BS09_x
Unit Status (On / Off)
40014
14
BS14_x
1=on / 0=off
Alarm Points
Communications
40289:0
289:0
BA01_x:00
Local Off
40289:1
289:1
BA01_x:01
Remote Off
40289:2
289:2
BA01_x:02
High Head Pressure 1
40289:3
289:3
BA01_x:03
High Head Pressure 2
40289:4
289:4
BA01_x:04
Loss of Airflow
40289:5
289:5
BA01_x:05
Liquid Detected
40289:6
289:6
BA01_x:06
Change Filters
40289:7
289:7
BA01_x:07
High Temperature
40289:8
289:8
BA01_x:08
Low Temperature
40289:9
289:9
BA01_x:09
High Humidity
40289:10
289:10
BA01_x:10
Low Humidity
40290:0
290:0
BA02_x:00
Local Alarm 1
40290:1
290:1
BA02_x:01
Local Alarm 2
40290:2
290:2
BA02_x:02
Local Alarm 3
40290:3
290:3
BA02_x:03
Local Alarm 4
40290:4
290:4
BA02_x:04
Liebert Monitoring Group – Development

Air Unit – Standard Microprocessor – LSM

Page 20 of 149
Page 21
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Setpoints (View)
Temperature Setpoint
40010
10
BS10_x
Temperature Tolerance
40011
11
BS11_x
Humidity Setpoint
40012
12
BS12_x
Humidity Tolerance
40013
13
BS13_x
Control Points (Set)
Unit On / Off
40349
349
BC01_x
Bit 0 on=unit off Bit 1 on=unit on
Temperature Setpoint
40350
350
BC02_x
Temperature Tolerance
40350
350
BC02_x
Multiply desired value by 1000
Humidity Setpoint
40351
351
BC03_x
Humidity Tolerance
40351
351
BC03_x
Multiply desired value by 1000
Trendable Points (Set)
Temperature
Humidity
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 21 of 149
Page 22
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Challenger 3000. Deluxe System / 3, ICS, System 4 (Replaces L15 & L1A) HiMod (LNA version) – iCOM control using native IGM terminal 77/78
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Temperature
40001
1
BS01_x
Humidity
40002
2
BS02_x
Cooling
40003
3
BS03_x
1=on / 0=off
Heating
40004
4
BS04_x
1=on / 0=off
Humidification
40005
5
BS05_x
1=on / 0=off
De-humidification
40006
6
BS06_x
1=on / 0=off
Econ-O-Cycle
40007
7
BS07_x
1=on / 0=off
Stages
40008
8
BS08_x
% Capacity
40009
9
BS09_x
Unit Status (On / Off)
40018
18
BS18_x
1=on / 0=off
Alarm Points
Discrete BACnet alarm objects available – use auto-discover for this unit
Communications
40289:0
289:0
BA01_x:00
Local Off
40289:1
289:1
BA01_x:01
Remote Off
40289:2
289:2
BA01_x:02
High Head Pressure 1
40289:3
289:3
BA01_x:03
High Head Pressure 2
40289:4
289:4
BA01_x:04
Loss of Airflow
40289:5
289:5
BA01_x:05
Standby Glycol Unit On
40289:6
289:6
BA01_x:06
Liquid Detected
40289:7
289:7
BA01_x:07
Change Filters
40289:8
289:8
BA01_x:08
High Temperature
40289:9
289:9
BA01_x:09
Low Temperature
40289:10
289:10
BA01_x:10
High Humidity
40290:0
290:0
BA02_x:00
Low Humidity
40290:1
290:1
BA02_x:01
Humidifier Problem
40290:2
290:2
BA02_x:02
No Water in Humidifier Pan
40290:3
290:3
BA02_x:03
Liebert Monitoring Group – Development

Air Unit – Advanced Microprocessor – LAM

Page 22 of 149
Page 23
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Compressor 1 Overload
40290:4
290:4
BA02:04_x
Compressor 2 Overload
40290:5
290:5
BA02:05_x
Main Fan Overload
40290:6
290:6
BA02:06_x
Manual Override
40290:7
290:7
BA02:07_x
Smoke Detected
40290:8
290:8
BA02:08_x
Loss of Water
40290:9
290:9
BA02:09_x
Standby Unit On
40290:10
290:10
BA02:10_x
Low Suction
40291:0
291:0
BA03:00_x
Short Cycle
40291:1
291:1
BA03:01_x
Loss of Power
40291:2
291:2
BA03:02_x
Inverter on Bypass
40291:3
291:3
BA03:03_x
Standby Fan On
40291:4
291:4
BA03:04_x
Loss of Emergency Power
40291:5
291:5
BA03:05_x
Local Alarm 1
40291:6
291:6
BA03:06_x
Local Alarm 2
40291:7
291:7
BA03:07_x
Off by Remote Shutdown
40291:8
291:9
BA03:08_x
Runtimes (View)
Runtimes not available on iCOM control
Compressor 1 Run Hours
40019
19
BS19_x
Compressor 2 Run Hours
40020
20
BS20_x
Glycol Run Hours
Fan Motor Run Hours
40021
21
BS21_x
Humidifier Run Hours
40022
22
BS22_x
Reheat 1 Run Hours
Reheat 2 Run Hours
Reheat 3 Run Hours
Chilled Water Valve Run Hours
Setpoints (View)
Temperature Setpoint
40010
10
BS10_x
Temperature Tolerance
40011
11
BS11_x
Humidity Setpoint
40012
12
BS12_x
Humidity Tolerance
40013
13
BS13_x
High Temp Alarm Setpoint
40014
14
BS14_x
Low Temp Alarm Setpoint
40015
15
BS15_x
High Humd Alarm Setpoint
40016
16
BS16_x
Low Humidity Alarm Setpoint
40017
17
BS17_x
Liebert Monitoring Group – Development
Page 23 of 149
Page 24
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Control Points (Set)
Unit On / Off
40349
349
BC01_x
Bit 0 on=unit off Bit 1 on=unit on
Temperature Setpoint
40350
350
BC02_x
Temperature Tolerance
40350
350
BC02_x
Multiply desired value by 1000
Humidity Setpoint
40351
351
BC03_x
Humidity Tolerance
40351
351
BC03_x
Multiply desired value by 1000
Reheat Lockout
40349
349
BC01_x
Bit 2 on=RH off Bit 3 on=RH on
Humidifier Lockout
40349
349
BC01_x
Bit 4 on=HL off Bit 5 on=HL on
Trendable Points (Set)
Temperature
Humidity
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 24 of 149
Page 25
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
DataMate, Mini-Mate, Mini-Mate Plus
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Temperature
40001
1
BS01_x
Humidity
40002
2
BS02_x
Cooling
40003
3
BS03_x
1=on / 0=0ff
Heating
40004
4
BS04_x
1=on / 0=0ff
Humidification
40005
5
BS05_x
1=on / 0=0ff
Dehumidification
40006
6
BS06_x
1=on / 0=0ff
Econ-o-Cycle
40007
7
BS07_x
1=on / 0=0ff
Stages
40008
8
BS08_x
% Capacity
40009
9
BS09_x
Unit On/Off
40011
11
BS11_x
1=on / 0=0ff
Alarm Points
Communications
40289:0
289:0
BA01_x:00
Local Off
40289:1
289:1
BA01_x:01
Remote Off
40289:2
289:2
BA01_x:02
High Temperature
40289:3
289:3
BA01_x:03
Low Temperature
40289:4
289:4
BA01_x:04
High Humidity
40289:5
289:5
BA01_x:05
Low Humidity
40289:6
289:6
BA01_x:06
Setpoints (View)
None
Control Points (Set)
Remote On/Off
40349
349
BC01_x
Bit 0 on=unit off Bit 1 on=unit on
Liebert Monitoring Group – Development

Air Unit – Small Systems – L0B

Page 25 of 149
Page 26
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Trendable Points (Set)
Temperature
Humidity
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 26 of 149
Page 27
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Mini-Mate 2, DataMate
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Temperature
40001
1
BS01_x
Humidity
40002
2
BS02_x
Cooling
40003
3
BS03_x
1=on / 0=off
Heating
40004
4
BS04_x
1=on / 0=off
Humidification
40005
5
BS05_x
1=on / 0=off
Dehumidification
40006
6
BS06_x
1=on / 0=off
Econ-o-Cycle
40007
7
BS07_x
1=on / 0=off
Stages
40008
8
BS08_x
% Capacity
40009
9
BS09_x
Unit On/Off
40018
18
BS18_x
1=on / 0=off
Alarm Points
Communications
40289:0
289:0
BA01_x:00
Local Off
40289:1
289:1
BA01_x:01
Remote Off
40289:2
289:2
BA01_x:02
High Head Pressure 1
40289:3
289:3
BA01_x:03
Loss of Airflow
40289:5
289:5
BA01_x:05
Standby Glycol Unit On
40289:6
2896
BA01_x:06
Change Filters
40289:7
289:7
BA01_x:07
High Temperature
40289:8
289:8
BA01_x:08
Low Temperature
40289:9
289:9
BA01_x:09
High Humidity
40290:0
290:0
BA02_x:00
Low Humidity
40290:1
290:1
BA02_x:01
Humidifier Problem
40290:2
290:2
BA02_x:02
Smoke Detected
40290:8
290:8
BA02_x:08
Loss of Water Flow
40290:9
290:9
BA02_x:09
Standby Unit On
40290:10
290:10
BA02_x:10
Liebert Monitoring Group – Development

Air Unit – Mini-Mate 2 – MM2, DataMate

Page 27 of 149
Page 28
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Short Cycle
40291:1
291:1
BA03:01
Loss of Power
40291:2
291:2
BA03:02
Local Alarm 1
40291:6
291:6
BA03:06
Local Alarm 2
40291:7
291:7
BA03:07
High Water
40291:8
291:8
BA03:08
Local Alarm 4
40291:9
291:9
BA03:09
Run Hours (View)
Compressor 1
40019
19
BS19_x
Fan Motor
40020
20
BS20_x
Humidifier
40021
21
BS21_x
Reheat 1
Reheat 2
Reheat 3
Chilled Water Valve
Setpoints (View)
Temperature
40010
10
BS10_x
Temp Tolerance
40011
11
BS11_x
Humidity
40012
12
BS12_x
Humidity Tolerance
40013
13
BS13_x
High Temperature Alarm
40014
14
BS14_x
Low Temperature Alarm
40015
15
BS15_x
High Humidity Alarm
40016
16
BS16_x
Low Humidity Alarm
40017
17
BS17_x
Control Points (Set)
Remote On/Off
40349
349
BC01_x
Bit 0 on=unit off Bit 1 on=unit on
Temperature Setpoint
40350
350
BC02_x
Temperature Tolerance
40350
350
BC02_x
Multiply desired value by 1000
Humidity Setpoint
40351
351
BC03_x
Humidity Tolerance
40351
351
BC03_x
Multiply desired value by 1000
Trendable Points (Set)
Temperature
Humidity
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 28 of 149
Page 29
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
MiniMate - 8 Ton only
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Temperature
40001
1
BS01_x
Humidity
40002
2
BS02_x
Cooling
40003
3
BS03_x
1=on / 0=off
Heating
40004
4
BS04_x
1=on / 0=off
Humidification
40005
5
BS05_x
1=on / 0=off
De-humidification
40006
6
BS06_x
1=on / 0=off
Econ-O-Cycle
40007
7
BS07_x
1=on / 0=off
Stages
40008
8
BS08_x
% Capacity
40009
9
BS09_x
Unit Status (On / Off)
40018
18
BS18_x
1=on / 0=off
Alarm Points
Communications
40289:0
289:0
BA01_x:00
Local Off
40289:1
289:1
BA01_x:01
Remote Off
40289:2
289:2
BA01_x:02
High Head Pressure 1
40289:3
289:3
BA01_x:03
High Head Pressure 2
40289:4
289:4
BA01_x:04
Loss of Airflow
40289:5
289:5
BA01_x:05
Standby Glycol Unit On
40289:6
289:6
BA01_x:06
Not Used
40289:7
289:7
BA01_x:07
Change Filters
40289:8
289:8
BA01_x:08
High Temperature
40289:9
289:9
BA01_x:09
Low Temperature
40289:10
289:10
BA01_x:10
High Humidity
40290:0
290:0
BA02_x00
Low Humidity
40290:1
290:1
BA02_x01
Humidifier Problem
40290:2
290:2
BA02_x02
Not Used
40290:3
290:3
BA02_x03
Liebert Monitoring Group – Development

Air Unit – 8 Ton MiniMate – L8T

Page 29 of 149
Page 30
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Not Used
40290:4
290:4
Not Used
40290:5
290:5
Not Used
40290:6
290:6
Not Used
40290:7
290:7
Smoke Detected
40290:8
290:8
BA02_x:08
Loss of Water
40290:9
290:9
BA02_x:09
Standby Unit On
40290:10
290:10
BA02_x:10
Not Used
40291:0
291:0
BA03_x:00
Short Cycle
40291:1
291:1
BA03_x:01
Loss of Power
40291:2
291:2
BA03_x:02
Not Used
40291:3
291:3
BA03_x:03
Not Used
40291:4
291:4
BA03_x:04
Not Used
40291:5
291:5
BA03_x:05
Local Alarm 1
40291:6
291:6
BA03_x:06
Local Alarm 2
40291:7
291:7
BA03_x:07
High Water Humidifier Pan
40291:8
291:8
BA03_x:08
Run Times (View)
Compressor 1 Run Hours
40019
19
BS19_x
Compressor 2 Run Hours
40020
20
BS20_x
Glycol Run Hours
Fan Motor Run Hours
40021
21
BS21_x
Humidifier Run Hours
40022
22
BS22_x
Reheat 1 Run Hours
Reheat 2 Run Hours
Reheat 3 Run Hours
Chilled H2O Valve Run Hours
Setpoints (View)
Temperature Setpoint
40010
10
BS10_x
Temperature Tolerance
40011
11
BS11_x
Humidity Setpoint
40012
12
BS12_x
Humidity Tolerance
40013
13
BS13_x
High Temp Alarm Setpoint
40014
14
BS14_x
Low Temp Alarm Setpoint
40015
15
BS15_x
High Humidity Alarm Setpoint
40016
16
BS16_x
Low Humidity Alarm Setpoint
40017
17
BS17_x
Liebert Monitoring Group – Development
Page 30 of 149
Page 31
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Control Points (Set)
Unit On / Off
40349
349
BC01_x
Bit 0 on=unit off Bit 1 on=unit on
Temperature Setpoint
40350
350
BC02_x
Temperature Tolerance
40350
350
BC02_x
Multiply desired value by 1000
Humidity Setpoint
40351
351
BC03_x
Humidity Tolerance
40351
351
BC03_x
Multiply desired value by 1000
Reheat Lockout
40349
349
BC01_x
Bit 2 on=RH off Bit 3 on=RH on
Humidifier Lockout
40349
349
BC01_x
Bit 4 on=HL off Bit 5 on=HL on
Trendable Points (Set)
Temperature
Humidity
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 31 of 149
Page 32
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Atlas Air; LECS 15
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Unit Number
40001
1
BS01_x
Average Return Air Temp.
40002
2
BS02_x
Average Return Air Humidity
40003
3
BS03_x
Average Supply Air Temp.
40004
4
BS04_x
Average Supply Air Humidity
40005
5
BS05_x
Activation Mode
40006
6
BS06_x
Fan Status
40007
7
BS07_x Cool 1 Status
40008
8
BS08_x Cool 2 Status
40009
9
BS09_x Heat 1 Status
40010
10
BS10_x Heat 2 Status
40011
11
BS11_x Humidifier Status
40012
12
BS12_x
De-humidifier Status
40013
13
BS13_x
Cooling Capacity
40014
14
BS14_x
Heating Capacity
40015
15
BS15_x
Active Operation (Days)
Active Operation (Hours)
Cool Mode (Days)
Cool Mode (Hours)
Heat Mode (Days)
Heat Mode (Hours)
Humidifier Mode (Days)
Humidifier Mode (Hours)
De-humidifier Mode (Days)
De-humidifier Mode (Hours)
Cool 1 Operating Mode
(Days)
Cool 1 Operating Mode
(Hours)
Liebert Monitoring Group – Development

Atlas Air Unit – C10

Page 32 of 149
Page 33
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Cool 2 Operating Mode (Days)
Cool 2 Operating Mode (Hours)
Fan Operation (Days)
Fan Operation (Hours)
Heat 1Operating Mode (Days)
Heat 1Operating Mode (Hours)
Heat 2 Operating Mode (Days)
Heat 2 Operating Mode (Hours)
Humidify Operating Mode (Days)
Humidity Operating Mode (Hours)
Cool Service (Days)
Cool Service (Hours)
Filter Service (Days)
Filter Service (Hours)
Humidifier Service (Days)
Humidifier Service (Hours)
Temperature Control Status
40019
19
BS19_x
Battery Voltage Level
40020
20
BS20_x
Remote Shutdown Status
40021
21
BS21_x
General Alarm Status
40022
22
BS22_x
Audible Alarm Status
40023
23
BS23_x
Temperature Control Select
40024
24
BS24_x
Alarm Points
Communications
40289:00
289:00
BA01_x:00
Faulty Sensor
40289:01
289:01
BA01_x:01
High Temperature
40289:02
289:02
BA01_x:02
Low Temperature
40289:03
289:03
BA01_x:03
High Humidity
40289:04
289:04
BA01_x:04
Low Humidity
40289:05
289:05
BA01_x:05
Loss of Airflow
40289:06
289:06
BA01_x:06
Water Under Floor
40289:07
289:07
BA01_x:07
Cool 1 Low Pressure Alarm
40289:08
289:08
BA01_x:08
Cool 2 Low Pressure Alarm
40289:09
289:09
BA01_x:09
Cool 1 High Pressure Alarm
40289:10
289:10
BA01_x:10
Cool 2 High Pressure Alarm
40290:00
290:00
BA02_x:00
Cool Service
40290:01
290:01
BA02_x:01
Humidifier Service
40290:02
290:02
BA02_x:02
Liebert Monitoring Group – Development
Page 33 of 149
Page 34
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Filter Service
40290:3
290:3
BA02_x:03
Humidity Low Level
40290:4
290:4
BA02_x:04 Battery Level Low
40290:5
290:5
BA02_x:05
Loss of Power
40290:6
290:6
BA02_x:06
Spare 1
40290:7
290:7
BA02_x:07 Spare 2
40290:8
290:8
BA02_x:08
Setpoints (View)
Unit Status (On / Off)
Return Air Temperature
40016
16
BS16_x
Return Air Humidity
40017
17
BS17_x
Supply Air Temperature
40018
18
BS18_x
High Temperature Alarm
Low Temperature Alarm
High Humidity Alarm
Low Humidity Alarm
Start up Delay
Control Points (Set)
Unit Status (On / Off)
Return Air Temperature
40349
349
BC01_x Return Air Humidity
40350
350
BC02_x
Supply Air Temperature
40351
351
BC03_x
High Temperature Alarm
Low Temperature Alarm
High Humidity Alarm
Low Humidity Alarm
Start up Delay
Trendable Points (Set)
Average Return Air Temp.
Average Return Air Humidity
Average Supply Air Temp.
Average Supply Air Humidity
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 34 of 149
Page 35
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Chiller CSU-3000
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Number of Modules
40001
1
BS01_x
Module 1 Start
40002
2
BS02_x
1=START / 0=STOP
Module 1 Pump
40003
3
BS03_x
1=ON / 0=OFF
Module 1 Cool
40004
4
BS04_x
1=ON / 0=OFF
Module 2 Start
40005
5
BS05_x
Module 2 Pump
40006
6
BS06_x
1=ON / 0=OFF
Module 2 Cool
40007
7
BS07_x
1=ON / 0=OFF
Module 3 Start
40008
8
BS08_x
1=START / 0=STOP
Module 3 Pump
40009
9
BS09_x
1=ON / 0=OFF
Module 3 Cool
40010
10
BS10_x
1=ON / 0=OFF
Alarm Points
Communications
40289:0
289:0
BA01_x:00
Mod 1 High Head Pressure
40289:1
289:1
BA01_x:01
Mod 2 High Head Pressure
40289:2
289:2
BA01_x:02
Mod 3 High Head Pressure
40289:3
289:3
BA01_x:03
Module 1 No Water Flow
40289:4
289:4
BA01_x:04
Module 2 No Water Flow
40289:5
289:5
BA01_x:05
Module 3 No Water Flow
40289:6
289:6
BA01_x:06
Module 1 High Water Temp.
40289:7
289:7
BA01_x:07
Module 2 High Water Temp.
40289:8
289:8
BA01_x:08
Module 3 High Water Temp.
40289:9
289:9
BA01_x:09
Module 1 Low Water Temp.
40289:10
289:10
BA01_x:10
Module 2 Low Water Temp.
40290:0
290:0
BA02_x:00
Module 3 Low Water Temp.
40290:1
290:1
BA02_x:01
Module 1 No Power
40290:2
290:2
BA02_x:02
Module 2 No Power
40290:3
290:3
BA02_x:03
Liebert Monitoring Group – Development

Chiller Unit – CSU3000 – CSU

Page 35 of 149
Page 36
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Module 3 No Power
40290:4
290:4
BA02_x:04
Module 1 Liquid Detected
40290:5
290:5
BA02_x:05
Module 2 Liquid Detected
40290:6
290:6
BA02_x:06
Module 3 Liquid Detected
40290:7
290:7
BA02_x:07
Local Alarm 1
40290:8
290:8
BA02_x:08
Local Alarm 2
40290:9
290:9
BA02_x:09
Setpoints (View)
None
Control Points (Set)
None
Trendable Points (Set)
None
Reports
Status
Liebert Monitoring Group – Development
Page 36 of 149
Page 37
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Chiller CSU-3000
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
System Econ-o-Cycle
40001
1
BS01_x
1=ON / 0=OFF
Number of Modules
40002
2
BS02_x
Module 1 Start
40003
3
BS03_x
1=START / 0=STOP
Module 1 Pump
40004
4
BS04_x
1=ON / 0=OFF
Module 1 Cool
40005
5
BS05_x
1=ON / 0=OFF
Module 2 Start
40006
6
BS06_x
1=START / 0=STOP
Module 2 Pump
40007
7
BS07_x
1=ON / 0=OFF
Module 2 Cool
40008
8
BS08_x
1=ON / 0=OFF
Module 3 Start
40009
9
BS09_x
1=START / 0=STOP
Module 3 Pump
40010
10
BS10_x
1=ON / 0=OFF
Module 3 Cool
40011
11
BS11_x
1=ON / 0=OFF
Module 1 Econ-o-Cycle
40012
12
BS12_x
1=ON / 0=OFF
Module 2 Econ-o-Cycle
40013
13
BS13_x
1=ON / 0=OFF
Module 3 Econ-o-Cycle
40014
14
BS14_x
1=ON / 0=OFF
Alarm Points
Communications
40289:00
289:00
BA01_x:00
Mod 1 High Head Pressure
40289:01
289:01
BA01_x:01
Mod 2 High Head Pressure
40289:02
289:02
BA01_x:02
Mod 3 High Head Pressure
40289:03
289:03
BA01_x:03
Module 1 No Water Flow
40289:04
289:04
BA01_x:04
Module 2 No Water Flow
40289:05
289:05
BA01_x:05
Module 3 No Water Flow
40289:06
289:06
BA01_x:06
Module 1 High Water Temp.
40289:07
289:07
BA01_x:07
Module 2 High Water Temp.
40289:08
289:08
BA01_x:08
Module 3 High Water Temp.
40289:09
289:09
BA01_x:09
Module 1 Low Water Temp.
40289:10
289:10
BA01_x:10
Liebert Monitoring Group – Development

Chiller Unit – CSU 3000 w/Econo – CSE

Page 37 of 149
Page 38
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Module 2 Low Water Temp.
40290:0
290:0
BA02_x:00
Module 3 Low Water Temp.
40290:1
290:1
BA02_x:01
Module 1 No Power
40290:2
290:2
BA02_x:02
Module 2 No Power
40290:3
290:3
BA02_x:03
Module 3 No Power
40290:4
290:4
BA02_x:04
Setpoints (Set)
None
Control Points (Set)
None
Trendable Points (Set)
None
Reports
Status
Liebert Monitoring Group – Development
Page 38 of 149
Page 39
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Liebert Hiross Microface
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
Liebert Hiross Hirolink
Available Points
SiteScan Availability
Modbus Register
BACnet Instance
Notes:
Status Points (View)
-
Unit On Off
-
G101
1=On / 0=Off
Heater Working Days
-
G102
Heater Working Hours
-
G103
Humidifier Working Days
-
G104
Humidifier Working Hours
-
G105
Compressor 1 Working Days
-
G106
Compressor 1 Working Hours
-
G107
Conditioner Working Days
G108
Conditioner Working Hours
-
G109
Low Humidity Warning
-
G110
High Humidity Warning
-
G110
Low Temperature Warning
-
G112
High Temperature Warning
-
G113
Humidity Proportional Band
-
G114
Temperature Proportional Band
-
G115
Room Humidity Setpoint
-
G116
Room Temperature Setpoint 1
-
G117
Compressor 2 Working Days
G118
Compressor 2 Working Hours
-
G119
Free-cooling Working Days
G120
Free-cooling Working Hours
-
G121
Cooling Ramp
-
G122
Status Dehumidification
-
G123
1=On / 0=Off
Status Electrical Heater 2
-
G124
1=On / 0=Off
Status Electrical Heater 1
-
G125
1=On / 0=Off
Status Compressor 1
-
G126
1=On / 0=Off
Humidifier Current
-
G127
Room Humidity
-
G128
Room Temperature
-
G129
Status Compressor 2
-
G130
1=On / 0=Off
Free-cooling Status
-
G131
Liebert Monitoring Group – Development

Air Unit - Hiross Microface

Page 39 of 149
Page 40
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet Instance
Notes:
Alarm Points
General Alarm
-
G200
Compressor 1 High Pressure
-
G201
Compressor 1 Low Pressure
-
G202
High Chiller Water Temp
-
G203
Low Chilled Water Flow
-
G204
Electric Heater Overheat
-
G205
Fan Failure Warning
-
G206
Fan Failure Alarm
-
G207
Clogged Filters
-
G208
Water Leak Detected Warning
-
G209
Water Leak Detected Alarm
-
G210
User Input Triggered Warning
-
G211
User Input Triggered Alarm
-
G212
EXT Humidifier Fail Warning
-
G213
Humidifier High Current
-
G214
Humidifier Failure Warning
-
G215
Humidifier Failure Alarm
-
G216
Humidifier Cylinder Warning
-
G217
High Room Temperature
-
G218
Low Room Temperature Warning
-
G219
High Room Humidity Warning
-
G220
Low Room Humidity Warning
-
G221
High Room Temp. (EEAP) Warning
-
G222
Low Room Temp. (EEAP) Warning
-
G223
High Room Humid (EEAP) Warning
-
G224
Low Room Humidity (EEAP)
-
G225
Conditioner Working Hours Exceeded
-
G226
Compressor 1 Working Hours Exceeded
-
G227
Humidifier Working Hours Exceeded
-
G228
PTC Sensor Failure
-
G229
Room Sensor Failure Warning
-
G230
Room Sensor Failure Alarm
-
G231
EEAP Sensor Failure Warning
-
G232
Water Presence Sensor Failure
-
G233
Network Failure
-
G234
Liebert Monitoring Group – Development
Page 40 of 149
Page 41
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet Instance
Notes:
Alarm Points (Continued)
Out Of Memory
-
G235
Unit On - G236
Unit Off - G237
Sleep Mode
-
G238
Standby Mode
-
G239
Power On - G240
Power Off - G241
Unit 1 Disconnected
-
G242
Unit 2 Disconnected
-
G243
Unit 3 Disconnected
-
G244
Unit 4 Disconnected
-
G245
Unit 5 Disconnected
-
G246
Unit 6 Disconnected
-
G247
Unit 7 Disconnected
-
G248
Unit 8 Disconnected
-
G249
Compressor 2 High Pressure
-
G258
Compressor 2 Low Pressure
-
G259
Compressor 2 Working Hours
-
G260
Outdoor Temperature Sensor Failure
-
G261
Glycol Temperature Sensor Failure
-
G262
Freecooling Stopped For 1 Hour
-
G263
On/Off By Hiromatic Not Enabled
-
G264
Smoke Alarm
-
G265
No Power (User Input)
-
G266
Power On (User Input)
-
G267
User Input 2 Triggered
-
G268
User Input 2 Alarm
-
G269
No Connection To Unit 1
-
G270
Compressor 1 Motor Protection
-
G271
Compressor 2 Motor Protection
-
G272
Fire Alarm - G273
Out Of Memory (Hiromatic)
-
G274
Condenser 1 Fan Failure
-
G275
Condenser 2 Fan Failure
-
G276
Network Ping
-
G277
Subgroup-ID Not Unique
-
G278
Subgroup-ID 1 Not Connected
-
G279
Liebert Monitoring Group – Development
Page 41 of 149
Page 42
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet Instance
Notes:
Alarm Points (Continued)
Subgroup-ID 2 Not Connected
-
G280
Share Room Sensor Failure
-
G281
Share Room Sensor Alarm
-
G282
Share Outdoor Temperature Sensor
-
G283
Share Glycol Temperature Sensor
-
G284
Unit Synchronization (Short Reset)
-
G285
Humidifier High Temperature
-
G286
Humidifier Overflow
-
G287
Unit Summary Alarm
-
STAT
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Liebert Monitoring Group – Development
Page 42 of 149
Page 43
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
X-Treme Density Coolant Distribution Unit
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Valve % Open
40001
1
BS01_x
Pump 1 Status
40002
2
BS02_x
1=On / 0=Off
Pump 2 Status
40003
3
BS03_x
1=On / 0=Off
Fluid Level
40004
4
BS04_x
Fluid Temperature
40005
5
BS05_x
Stop Valve
40006
6
BS06_x
1=On / 0=Off
Purge Valve
40007
7
BS07_x
43=C / 46=F
FMS Disable
40008
8
BS08_x
Rate Of Change
40009
9
BS09_x
Local Temp
40010
10
BS10_x
Local Humidity
40011
11
BS11_x
Local Dewpoint
40012
12
BS12_x
Remote Temp
40013
13
BS13_x
Remote Humidity
40014
14
BS14_x
Remote Dewpoint
40015
15
BS15_x
Unit Status
40016
16
BS16_x
Alarm Points
Communications
40289:00
289:0
BA01_x:00
Local Off
40289:01
289:1
BA01_x:01
Remote Off
40289:02
289:2
BA01_x:02
Loss Of Flow P1
40289:03
289:3
BA01_x:03
Loss Of Flow P2
40289:04
289:4
BA01_x:04
Pump Short Cycle
40289:05
289:5
BA01_x:05
Spare 5
40289:06
289:6
BA01_x:06
Leak Detected
40289:07
289:7
BA01_x:07
Valve Failure
40289:08
289:8
BA01_x:08
Customer Alarm 1
40289:09
289:9
BA01_x:09
Fan Fail
40289:10
289:10
BA01_x:10
High Fluid Temp
40290:00
290:0
BA02_x:00
Low Fluid Temp
40290:01
290:1
BA02_x:01
Liebert Monitoring Group – Development

Air Unit – X-Treme Density Coolant Distribution Unit– CDU

Page 43 of 149
Page 44
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Fluid Sensor Problem
40290:02
290:2
BA02_x:02
High Remote Temp
40290:03
290:3
BA02_x:03
Low Remote Temp
40290:04
290:4
BA02_x:04
Remote Sensor Problem
40290:05
290:5
BA02_x:05
High Local Temp
40290:06
290:6
BA02_x:06
Low Local Temp
40290:07
290:7
BA02_x:07
Local Sensor Problem
40290:08
290:8
BA02_x:08
Low Pressure
40290:09
290:9
BA02_x:09
High Fluid Level
40290:10
290:10
BA02_x:10
Low Fluid Level
40291:00
291:0
BA03_x:00
Low Low Level
40291:01
291:1
BA03_x:01
Fluid Level ROC
40291:02
291:2
BA03_x:02
System Purge P1
40291:03
291:3
BA03_x:03
Emergency Purge
40291:04
291:4
BA03_x:04
FMS Power Loss
40291:05
291:5
BA03_x:05
Loss Of Power
40291:06
291:6
BA03_x:06
Setpoints (View)
Temperature Setpoint
40017
17
BS17_x
High Fluid Temp Setpoint
40018
18
BS18_x
Temp Scale
High Air Temp
40019
19
BS19_x
Low Air Temp
40020
20
BS20_x
Dewpoint Margin
40021
21
BS21_x
Restart Delay
40022
22
BS22_x
Control Points (Set)
Unit On / Off
40349
49
BC01_x
Temperature Setpoint
40350
50
BC02_x
Dewpoint Margin
40351
51
BC03_x
Trendable Points (Set)
Temperature
Humidity
Dewpoint
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 44 of 149
Page 45
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
X-Treme Density Coolant Pumping Unit
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Valve % Open
40001
1
BS01_x
Pump 1 Status
40002
2
BS02_x
1=On / 0=Off
Pump 2 Status
40003
3
BS03_x
1=On / 0=Off
Fluid Temperature
40004
4
BS04_x
Divide by 10 for correct value
Chilled Water Temperature
40005
5
BS05_x
Divide by 10 for correct value
Unit Status
40006
6
BS06_x
1=On / 0=Off
Scale F or C
40007
7
BS07_x
43=C / 46=F
Local Temperature
40008
8
BS08_x
Local Humidity
40009
9
BS09_x
Local Dewpoint
40010
10
BS10_x
Remote Temperature
40011
11
BS11_x
Remote Humidity
40012
12
BS12_x
Remote Dewpoint
40013
13
BS13_x
Alarm Points
Communications
40289:00
289:0
BA01_x:00
Local Off
40289:01
289:1
BA01_x:01
Remote Off
40289:02
289:2
BA01_x:02
Loss Of Flow P1
40289:03
289:3
BA01_x:03
Loss Of Flow P2
40289:04
289:4
BA01_x:04
Pump Short Cycle
40289:05
289:5
BA01_x:05
Condensation
40289:06
289:6
BA01_x:06
Refrigerant Leak
40289:07
289:7
BA01_x:07
Valve Failure
40289:08
289:8
BA01_x:08
Customer Alarm 1
40289:09
289:9
BA01_x:09
Fan Failure Alarm
40289:10
289:10
BA01_x:10
High Chilled Water Temp
40290:00
290:0
BA02_x:00
Low Chilled Water Temp
40290:01
290:1
BA02_x:01
Failed Chilled Water Sensor
40290:02
290:2
BA02_x:02
High Remote Temp
40290:03
290:3
BA02_x:03
Low Remote Temp
40290:04
290:4
BA02_x:04
Liebert Monitoring Group – Development

Air Unit – X-Treme Density Coolant Pumping Unit– XDP

Page 45 of 149
Page 46
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Remote Sensor Problem
40290:05
290:5
BA02_x:05
High Local Temp
40290:06
290:6
BA02_x:06
Low Local Temp
40290:07
290:7
BA02_x:07
Local Sensor Problem
40290:08
290:8
BA02_x:08
Low Pressure
40290:09
290:9
BA02_x:09
High Refrigerant Temp
40290:10
290:10
BA02_x:10
Low Refrigerant Temp
40291:00
291:0
BA03_x:00
Failed Refrigerant Sensor
40291:01
291:1
BA03_x:01
Loss Of Power
40291:02
291:2
BA03_x:02
Setpoints (View)
Temperature Setpoint
40014
14
BS14_x
Temperature Scale
High Chilled Water Temp
40015
15
BS15_x
High Air Temp
40016
16
BS16_x
Low Air Temp
40017
17
BS17_x
Dewpoint Margin
40018
18
BS18_x
Restart Delay
40019
19
BS19_x
Control Points (Set)
Unit On / Off
40349
49
BC01_x
Temperature Setpoint
40350
50
BC02_x
Dewpoint Margin
40351
51
BC03_x
Trendable Points (Set)
Temperature
Humidity
Dewpoint
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 46 of 149
Page 47
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
X-Treme Density Chiller Unit
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Pump 1 Status
40001
N/A
BS01_x
1=On / 0=Off
Pump 2 Status
40002
N/A
BS02_x
1=On / 0=Off
Cooling %
40003
N/A
BS03_x
Compressor 1A status
40004
N/A
BS04_x
1=On / 0=Off
Compressor 1B status
40005
N/A
BS05_x
1=On / 0=Off
HG Valve1 %
40006
N/A
BS06_x
Compressor 2A status
40007
N/A
BS07_x
1=On / 0=Off
Compressor 2B status
40008
N/A
BS08_x
1=On / 0=Off
HG Valve2 %
40009
N/A
BS09_x
Refer Temp 1
40010
N/A
BS10_x
Divide by 10 for correct value
Refer Temp 2
40011
N/A
BS11_x
Divide by 10 for correct value
CW Temp
40012
N/A
BS12_x
Divide by 10 for correct value
Unit Status
40013
N/A
BS13_x
1=On / 0=Off
Scale F or C
40014
N/A
BS14_x
43=C / 46=F
Local Temp
40015
N/A
BS15_x
Local Humidity
40016
N/A
BS16_x
Local Dew Point
40017
N/A
BS17_x
Remote Temp
40018
N/A
BS18_x
Remote Humidity
40019
N/A
BS19_x
Remote Dew Point
40020
N/A
BS20_x
Alarm Points
Communications
40289:00
N/A
BA01_x:00
Local Off
40289:01
N/A
BA01_x:01
Remote Off
40289:02
N/A
BA01_x:02
Loss Of Flow Pump 1
40289:03
N/A
BA01_x:03
Loss Of Flow Pump 2
40289:04
N/A
BA01_x:04
Pump Short Cycle
40289:05
N/A
BA01_x:05
Customer Alarm 1
40289:06
N/A
BA01_x:06
Condensation
40289:07
N/A
BA01_x:07
Fan Failure Alarm
40289:08
N/A
BA01_x:08
Liebert Monitoring Group – Development

Air Unit – X-Treme Density Chiller Unit– XDC

Page 47 of 149
Page 48
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points (cont.)
High Local Temperature
40289:09
N/A
BA01_x:09
Low Local Temperature
40289:10
N/A
BA01_x:10
Local Sensor Problem
40290:00
N/A
BA02_x:00
High Remote Temperature
40290:01
N/A
BA02_x:01
Low Remote Temperature
40290:02
N/A
BA02_x:02
Remote Sensor Problem
40290:03
N/A
BA02_x:03
High Dewpoint
40290:04
N/A
BA02_x:04
High Head Compressor 1a
40290:05
N/A
BA02_x:05
High Head Compressor 1b
40290:06
N/A
BA02_x:06
High Head Compressor 2a
40290:07
N/A
BA02_x:07
High Head Compressor 2b
40290:08
N/A
BA02_x:08
Low Suction P Tandem 1
40290:09
N/A
BA02_x:09
Low Suction P Tandem 2
40290:10
N/A
BA02_x:10
Short Cycle Compressor 1a
40291:00
N/A
BA03_x:00
Short Cycle Compressor 1b
40291:01
N/A
BA03_x:01
Short Cycle Compressor 2a
40291:02
N/A
BA03_x:02
Short Cycle Compressor 2b
40291:03
N/A
BA03_x:03
High Refrigerant Temp 1
40291:04
N/A
BA03_x:04
Low Refrigerant Temp 1
40291:05
N/A
BA03_x:05
Failed Refrigerant Sensor 1
40291:06
N/A
BA03_x:06
High Refrigerant Temp 2
40291:07
N/A
BA03_x:07
Low Refrigerant Temp 2
40291:08
N/A
BA03_x:08
Failed Refrigerant Sensor 2
40291:09
N/A
BA03_x:09
High Chilled Water Temp
40291:10
N/A
BA03_x:10
Low Chilled Water Temp
40292:00
N/A
BA03_x:00
Failed Chilled Water Sensor
40292:01
N/A
BA03_x:01
Valve Failure
40292:02
N/A
BA03_x:02
Loss Of Power
40292:03
N/A
BA03_x:03
Setpoints (View)
Temp Setpoint
40021
N/A
BS21_x
High Temp Setpoint
40022
N/A
BS22_x
Low Temp Setpoint
40023
N/A
BS23_x
Liebert Monitoring Group – Development
Page 48 of 149
Page 49
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Control Points (Set)
Unit On / Off
40349
N/A
BC01_x
Temperature Setpoint
40350
N/A
BC02_x
Dewpoint Margin
-
N/A
-
Trendable Points
Temperature
Humidity
Dewpoint
Reports
Trend
Liebert Monitoring Group – Development
Page 49 of 149
Page 50
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
iCOM DS controls and iCOM retrofit using Optional IS485 interface card
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Unit On/Off Status
40001
BS01
Unit Standy Status
40002
BS02
Control Mode (Auto, Manual)
Control Reason
Fan Status
Cooling Status
40003
BS03
Freecooling Status
Hot Water State
Electric Heater State
40004
BS04
Humidifier State
40005
BS05
De-humidifier State
40006
BS06
Audible Alarm State
Cooling Ramp
40007
BS07
Heating Ramp
40008
BS08
Return Temp
40009
BS09
Return Humidity
40010
BS10
Run Hours (View)
Conditioner Run Hrs.
40011
BS11
Comp 1 Run Hrs.
40012
BS12
Comp 2 Run Hrs.
40013
BS13
Humidifier Run Hrs.
40014
BS14
Reheat 1 Run Hrs.
Reheat 2 Run Hrs.
Reheat 3 Run Hrs.
Setpoints (View)
Front Display Temp Scale
Humidifier Lockout Status
40015
BS15
Reheat Lockout Status
40016
BS16
Temperature Setpoint
40017
BS17
Temp Proportional Band
40018
BS18
Temp Deadband
Liebert Monitoring Group – Development

Air Unit – iCOM DS & Retrofit (2mb version SiteLink)

Page 50 of 149
Page 51
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Setpoints (View)
Humidity Setpoint
40019
BS19
Humd Proportional Band
40020
BS20
Humd Deadband
Autorestart Delay
IR Humidifier Flush Rate
High Temperature Alarm
40021
BS21
Low Temperature Alarm
40022
BS22
High Humidity Alarm
40023
BS23
Low Humidity Alarm
40024
BS24
Setpoints (Set)
Temperature Setpoint
40350
BC02_1
Temp Proportional Band
40350
BC02_2
Scale by 1000 (e.g. 2=2000 Modbus Only)
Temp Deadband
Humidity Setpoint
40351
BC03_1
Humd Proportional Band
40351
BC03_2
Scale by 1000 (e.g. 5=5000 Modbus Only)
Humd Deadband
Autorestart Delay
IR Humidifier Flush Rate
High Temperature Alarm
Low Temperature Alarm
High Humidity Alarm
Low Humidity Alarm
Commands (Set)
Unit On/Off
40349:0,1
BC01_1
Bit pair 0,1;1=off, 2=on (Modbus Only)
Humidifier Lockout
40349:2,3
BC01_2
Bit pair 2,3; 1=normal, 2=lckout (Modbus Only)
Reheat Lockout
40349:4,5
BC01_3
Bit pair 4,5; 1=normal, 2=lckout (Modbus Only)
Alarms
Discrete BACnet alarm objects available –use auto­discover for this unit
Loss Of Comm
40289:0
BA01_x:0
Main Fan Overload
40289:1
BA01_x:1
Loss of Airflow
40289:2
BA01_x:2
Loss of Water Flow
40289:3
BA01_x:3
Compressor 1 High Pressure
40289:4
BA01_x:4
Compressor 1 Overload
40289:5
BA01_x:5
Compressor 2 High Pressure
40289:6
BA01_x:6
Compressor 2 Overload
40289:7
BA01_x:7
Smoke Detected
40289:8
BA01_x:8
Water Detected
40289:9
BA01_x:9
Liebert Monitoring Group – Development
Page 51 of 149
Page 52
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarms (cont.)
Humidifier Problem
40289:10
BA01_x:10
Standby Unit On
40290:0
BA02_X:0
High Room Temp
40290:1
BA02_X:1
Low Room Temp
40290:2
BA02_X:2
High Room Humidity
40290:3
BA02_X:3
Low Room Humidity
40290:4
BA02_X:4
User Alarm #1
40290:5
BA02_X:5
User Alarm #2
40290:6
BA02_X:6
Unit On
40290:7
BA02_X:7
Unit Off
40290:8
BA02_X:8
Trends
Return Temperature
Return Humidity
Liebert Monitoring Group – Development
Page 52 of 149
Page 53
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
iCOM DS controls and retrofit using IS485 communication interface card
SiteScan Interface Modules:
SiteLink-E
BMS interface Modules:
SiteLink-E
Point Availability
SiteScan
Modbus
Register
BACnet
Object
Notes:
Status Points
Unit On/Off
40001
BS1
Unit Standby
40002
BS2
Cooling State
40003
BS03b1
Fan State
-
BS03b0
Free Cooling State
-
BS03b2
Hot Water State
-
BS03b3
Electrical Heater State
40004
BS03b4
Fan Ramp %
-
BS04
Cooling Ramp %
40007
BS05
Humidifier State
40005
BS03b5
Free Cooling Ramp %
-
BS06
Dehumidifier State
40006
BS03b6
Heating Ramp %
40008
BS07
Humidification Ramp %
-
BS08
De-humidification Ramp %
-
BS09
Free Cooling Status
-
BS0A
Return Temp
40009
BS0B
Return Temp Set-point
-
BS0D
Supply Temp
-
BS0F
FC Fluid Temp
-
BS15
Supply Temp SP
-
BS11
# Of Present Events
-
BS13
Humidity Lockout Active
40015
bs15
Reheat Lockout Active
40016
bs16
Sensor A Temp
-
BS17
Optional External Sensor
Sensor B Temp
-
BS19
Optional External Sensor
Sensor C Temp
-
BS1B
Optional External Sensor
Comp 1 Temp
-
BS1D
Comp 2 Temp
-
BS1F
Return Humidity
40010
BS21
Return Humidity Setpoint
-
BS22
Sensor A Humidity
-
BS23
Optional External Sensor
Sensor B Humidity
-
BS24
Optional External Sensor
Sensor C Humidity
-
BS25
Optional External Sensor
Conditioner Run Hours
40011
BS26
Compressor 1 Run Hrs
40012
BS28
Compressor 2 Run Hrs
40013
BS2A
Liebert Monitoring Group – Development

Air Unit – iCOM DS & Retrofit (16mb version SiteLink)

Page 53 of 149
Page 54
Revision B.33 2/25/2011
Point Availability
SiteScan
Modbus Register
BACnet
Object
Notes:
Status Points (cont.)
Humidifier Run Hrs
40014
BS2C
Dehumidifier Run Hrs
-
BS2E
FreeCool Run Hrs
-
BS30
Electric Heater #1 Run Hrs
-
BS32
Electric Heater #2 Run Hrs
-
BS32
Electric Heater #3 Run Hrs
-
BS36
Hot Water/Hot Gas Run Hrs
-
BS38
Daily High Temperature
-
BS3A
Daily Low Temperature
-
BS3E
Daily High Humidity
-
BS42
Daily Low Humidity
-
BS45
VFD Fan Speed Setpoint %
-
bs86
VFD Control Mode
-
bs87
Temperature Scale
-
BV09
0=Celcius, 1=Farenheit
Temperature Setpoint
40017
BV1C
Temp Prop. Band Setpoint
40018
BV1E
Temp Deadband Setpoint
-
BV20
Humidity Setpoint
40019
BV23
Humidity Prop. Band Setpoint
40020
BV24
Humidity Dead Band Setpoint
-
BV26
Auto-restart Delay Setpoint
-
BV27
IR Flush Rate % Setpoint
-
BV34
High Temp Alarm Setpoint
40021
BV36
Low Temp Alarm Setpoint
40022
BV38
Sensor A High Temp Alarm Sp
-
BV3A
Sensor A Low Temp Alarm Sp
-
BV3C
High Humidity Alarm Setpoint
40023
BV3E
Low Humidity Alarm Setpoint
40024
BV3F
Sensor A High Humd Alarm Sp
-
BV40
Sensor A Low Humd Alarm Sp
-
BV41
Alarm Points
Alarm I (Word)
40289
BA1
BacNet alarm points available as either bit
packed values in registers BA1-BA5 or
discrete points as documented.
Loss Of Comm
bit0
G701
Not Used
-
-
Main Fan Overload
bit2
BA02
Loss Of Airflow
bit3
BA03
Loss Of Waterflow
bit4
BA04
Compressor 1 High Pressure
bit5
BA05
Compressor 1 Low Pressure
bit6
BA06
Liebert Monitoring Group – Development
Page 54 of 149
Page 55
Revision B.33 2/25/2011
Point Availability
SiteScan
Modbus Register
BACnet
Object
Notes:
Alarm Points (cont.)
Alarm I (Word cont.)
40289
BA1
Compressor 1 Overload
bit7
BA07
Compressor 1 Pumpdown Fail
bit8
BA08
Compressor 2 High Pressure
bit5
BA09
Ored with bit5 (Comp 1 HP)
Compressor 2 Low Pressure
bit6
BA0A
Ored with bit6 (Comp 1 LP)
Compressor 2 Overload
bit7
BA0B
Ored with bit7 (Comp 1 OL)
Compressor 2 Pumpdown Fail
bit8
BA0C
Ored with bit8 (Comp 1 PF)
DigiScroll 1 High Temp
bit9
BA0D
DigiScroll 2 High Temp
bit9
BA0E
Ored with bit9 (DigiScroll 1 HT)
Smoke Detected
bit10
BA0F
Water Detected
bit11
ba10
Humidifier Problem
bit12
ba11
Standby Glycol Pump On
bit13
ba12
Standby Glycol Unit On
bit14
ba13
Condenser Pump High Water
bit15
ba14
Alarm II (Word)
40290
BA2
Room Sensor Fail
bit0
ba15
Compressor Loss Of Power
bit1
ba16
Blower Fail
bit2
ba17
Emergency Damper Fail
bit3
ba18
Internal High Temperature
bit4
ba19
Humidifier Water Low
bit5
ba1a
Humidifier High Current
bit6
ba1b
User High Temperature
bit7
ba1c
Loss Of Power
bit8
ba1d
High Chilled Water Temp
bit9
ba20
High Electric Heater Temp
bit10
ba21
High Room Temp
bit11
ba22
Low Room Temp
bit12
ba23
High Room Humidity
bit13
ba24
Low Room Humidity
bit14
ba25
Sensor A High Temp
bit15
ba26
Alarm III (Word)
40291
BA3
Sensor A Low Temp
bit0
ba27
Sensor A High Humidity
bit1
ba28
Sensor A Low Humidity
bit2
ba29
Loss Of Chilled Water Flow
bit3
ba2a
Clogged Air Filters
bit4
ba2b
Internal Low Temp
bit5
ba2c
High External Dewpoint
bit6
ba2d
Supply Sensor Fail
bit7
ba30
Liebert Monitoring Group – Development
Page 55 of 149
Page 56
Revision B.33 2/25/2011
Point Availability
SiteScan
Modbus Register
BACnet
Object
Notes:
Alarm Points (cont.)
Alarm III (Word cont.)
40291
BA3
Glycol Sensor Fail
bit8
ba31
Sensor A Fail
bit9
ba32
Digital Scroll 1 Sensor Fail
bit10
ba36
Digital Scroll 2 Sensor Fail
bit11
ba37
User Input Alarm #1
bit12
ba38
User Input Alarm #2
bit12
ba39
Ored with bit12 (User Input Alarm #1)
User Input Alarm #3
bit12
ba3a
Ored with bit12 (User Input Alarm #1
User Input Alarm #4
bit12
ba3b
Ored with bit12 (User Input Alarm #1
Unit Working Hours Exceeded
bit13
ba40
Comp1 Working Hours Exceeded
bit14
ba41
Comp2 Working Hours Exceeded
bit15
ba42
Alarm IV (Word)
40292
BA4
Free Cool Hours Exceeded
bit0
ba43
Electrical Heater 1 Hours Exceeded
bit1
ba44
Electrical Heater 2 Hours Exceeded
bit2
ba45
Electrical Heater 3 Hours Exceeded
bit3
ba46
Hot Water or Hot Gas Hours Exceeded
bit4
ba47
Humidifier Hours Exceeded
bit5
ba48
De-humidifier Hours Exceeded
bit6
ba49
Unit On/Off Key Disabled
bit7
ba4a
P2P Network Fail
bit8
ba4f
Master Station - P2P Network
bit9
ba50
Unit(s) Disconnected - P2P Network
bit10
ba51
P2P Network Unit Code Missing
bit11
ba52
P2P Network Unit Code Mismatch
bit12
ba53
Service Required
bit13
ba60
Control Board Memory Low
bit14
ba61
Alarm V (Word)
40293
BA5
Humidity Ctrl Board Not Connected
bit0
ba63
Parallel Flash Memory Test Fail
bit1
ba64
Serial Flash Memory Test Fail
bit2
ba65
Unit Front Access Open
bit3
ba66
Unit Rear Access Open
bit4
ba67
Unit Disabled By Alarm
bit5
ba70
Unit Shutdown By Alarm
bit6
ba71
Unit Synchronization
bit7
ba72
Compressor 1 Short Cycle
bit8
ba73
Unit On
-
ba74
Unit Off
-
ba75
Timer Off
bit9
ba76
Liebert Monitoring Group – Development
Page 56 of 149
Page 57
Revision B.33 2/25/2011
Point Availability
SiteScan
Modbus
Register
BACnet
Object
Notes:
Alarm Points (cont.)
Alarm V (Word cont.)
40293
BA5
Power On
-
ba77
Standby Mode
bit10
ba78
Power Off
bit11
ba79
Reheat Lockout
bit12
ba7a
Humidifier Lockout
bit13
ba7b
Compressor Lockout
bit14
ba7c
Compressor 2 Short Cycle
bit15
ba7d
Control Points (Write)
Unit On/Off
40349
bc01
Modbus - Set Bit0=off, Bit1=on
Humidifier Lockout
40349
bc01_2
Modbus - Set Bit4=off, Bit5=on
Reheat Lockout
40349
bc01_3
Modbus - Set Bit2=off, Bit3=on
Temp Setpoint
40350
bp1c
Temp Proportional Band
40350
bp1e
Scale *1000 (Modbus Only)
Temperature DeadBand
-
bp20
Humidity
40351
bp23
Humidity Proportional Band
40351
bp24
Scale *1000 (Modbus Only)
Humidity Dead Band
-
bp26
Auto-restart Delay Seconds
-
bp27
IR Flush Rate %
-
bp34
High Temp Setpoint
-
bp36
Low Temp Setpoint
-
bp38
High Temp Setpoint Sensor A
-
bp3a
Low Temp Setpoint Sensor A
-
bp3c
High Humidity Setpoint
-
bp3e
Low Humidity Setpoint
-
bp3f
High Humidity Setpoint Sens A
-
bp40
Low Humidity Setpoint Sens A
-
bp41
VFD Control Speed
40349
bp86
Modbus - Set Bits8-15=speed 50-100%
VFD Control Mode
40349
bp87
Modbus - Set Bit6=auto, Bit7=manual
Liebert Monitoring Group – Development
Page 57 of 149
Page 58
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
XDP Unit w/ iCOM Control
SiteScan Interface Modules:
SiteLink-E (Exec. B Modules)
SiteScan Availability
Modbus
Register
BACnet
Instance
Notes:
Status Points (View)
Valve % Open
40001
BS01_x
Pump 1 Status
40002
BS02_x
1=On / 0=Off
Pump 2 Status
40003
BS03_x
1=On / 0=Off
Supply Temperature
40004
BS04_x
Divide by 10 for correct value
Chilled Water Temperature
40005
BS05_x
Divide by 10 for correct value
Unit Status
40006
BS06_x
Off:1=Rmt, 3=Lcl, 4=Restart, 5=Epo; On=2
Scale F or C
40007
BS07_x
43=C / 46=F
Sensor A Temperature
40008
BS08_x
Sensor A Humidity
40009
BS09_x
Sensor A Dewpoint
40010
BS10_x
Sensor B Temperature
40011
BS11_x
Sensor B Humidity
40012
BS12_x
Sensor B Dewpoint
40013
BS13_x
Run Hours (View)
Pump 1 Run Hours
40014
BS14_x
Pump 2 Run Hours
40015
BS15_x
Setpoints (View)
Temperature Setpoint
40016
BS16_x
High Temp Alarm Setpoint
40017
BS17_x
Low Temp Alarm Setpoint
40018
BS18_x
Dewpoint Alarm Setpoint
40019
BS19_x
Refrigerant Temp Alarm Setpoint
40020
BS20_x
Chilled Water Temp Alarm Setpoint
40021
BS21_x
Dewpoint Margin Setpoint
40022
BS22_x
Temperature Scale F or C
0=F 1=C
Auto-restart Delay Setpoint
40023
BS23_x
Unit Status
1=On / 0=Off
Maintenance Mode Status
40024
BS24_x
On=All alarms disabled
Setpoints (Set)
Temperature Setpoint
40350
BC02_x
High Temp Alarm Setpoint
Low Temp Alarm Setpoint
Dewpoint Alarm Setpoint
40351
BC02_x
Liebert Monitoring Group – Development

Air Unit – XDP Refrigerant Pumping Unit – XDP W/ iCOM Control

Page 58 of 149
Page 59
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
Notes:
Setpoints (Set)
Refrigerant Temp Alarm Setpoint
Chilled Water Temp Alarm Setpoint
Temperature Scale F or C
Auto-restart Delay
Unit Run
40349
BC01_x
Alarms (View)
Loss Of Comm
40289:0
BA01_x:0
Loss Of Flow Pump 1
40289:1
BA01_x:1
Loss Of Flow Pump 2
40289:2
BA01_x:2
Fan Failure
40289:3
BA01_x:3
Condensation Alarm
40289:4
BA01_x:4
Customer Alarm
40289:5
BA01_x:5
High Chilled Water Temp
40289:6
BA01_x:6
Chilled Water Sensor Fail
40289:7
BA01_x:7
High Refrigerant Temp
40289:8
BA01_x:8
Low Refrigerant Temp
40289:9
BA01_x:9
Refrigerant Sensor Fail
40289:10
BA01_x:10
High Temp Sensor A
40289:11
BA01_x:11
Low Temp Sensor A
40289:12
BA01_x:12
Sensor A Fail
40289:13
BA01_x:13
High Temp Sensor B
40289:14
BA01_x:14
Low Temp Sensor B
40289:15
BA01_x:15
Sensor B Fail
40290:0
BA02_x:0
High Dewpoint
40290:1
BA02_x:1
Pump Short Cycle
40290:2
BA02_x:2
Control Valve Fail
40290:3
BA02_x:3
Loss Of Power
40290:4
BA02_x4 Trends (View)
Valve % Open
Refrigerant Supply Temp
Chilled Water Temp
Sensor A Temp
Sensor A Humidity
Sensor A Dewpoint
Sensor B Temp
Sensor B Humidity
Sensor B Dewpoint
Liebert Monitoring Group – Development
Page 59 of 149
Page 60
Liebert Monitoring Group – Development

Liebert Power Units

Revision B.33 2/25/2011
Page 60 of 149
Page 61
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Datawave, Precision Power Center
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Voltage Out X-Y
40001
1
BS01_x
Voltage Out Y-Z
40002
2
BS02_x
Voltage Out Z-X
40003
3
BS03_x
Voltage Out X-N
40004
4
BS04_x
Voltage Out Y-N
40005
5
BS05_x
Voltage Out Z-N
40006
6
BS06_x
Current Out A
40007
7
BS07_x
Current Out B
40008
8
BS08_x
Current Out C
40009
9
BS09_x
Ground Current
40010
10
BS10_x
Neutral Current
40011
11
BS11_x
KVA
40012
12
BS12_x
Alarm Points
Communications
40289:0
289:0
BA01_x:00
Output Undervoltage
40289:1
289:1
BA01_x:05
Output Overvoltage
40289:2
289:2
BA01_x:06
Transformer Overtemp
40289:3
289:3
BA01_x:07
Local Alarm #1
40289:4
289:4
BA01_x:08
Local Alarm #2
40289:5
289:5
BA01_x:09
Liebert Monitoring Group – Development

Power Unit – Voltage- Current Monitoring Panel – VCM

Page 61 of 149
Page 62
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Trendable Points (Set)
Voltage Out X-Y
Voltage Out Y-Z
Voltage Out Z-X
Voltage Out X-N
Voltage Out Y-N
Voltage Out Z-N
Current Out A
Current Out B
Current Out C
Ground Current
Neutral Current
kVA
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 62 of 149
Page 63
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Datawave, Precision Power Center
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Voltage In A-B
40001
1
BS01_x
Voltage In B-C
40002
2
BS02_x
Voltage In C-A
40003
3
BS03_x
Voltage Out A-B
40004
4
BS04_x
Voltage Out B-C
40005
5
BS05_x
Voltage Out C-A
40006
6
BS06_x
Voltage Out A-N
40007
7
BS07_x
Voltage Out B-N
40008
8
BS08_x
Voltage Out C-N
40009
9
BS09_x
Current Out A
40010
10
BS10_x
Current Out B
40011
11
BS11_x
Current Out C
40012
12
BS12_x
Ground Current
40013
13
BS13_x
Divide by 10 for correct value
Neutral Current
40014
14
BS14_x
KVA
40015
15
BS15_x
KW
40016
16
BS16_x
Frequency
40017
17
BS17_x
Divide by 10 for correct value
% Capacity A
40018
18
BS18_x
% Capacity B
40019
19
BS19_x
% Capacity C
40020
20
BS20_x
Alarm Points
Discrete BACnet alarm objects available –use auto-discover for this unit
Communications
40289:00
289:00
BA01_x:00
Output Undervoltage
40289:01
289:01
BA01_x:01
Output Overvoltage
40289:02
289:02
BA01_x:02
Output Overcurrent
40289:03
289:03
BA01_x:03
Frequency Deviation
40289:04
289:04
BA01_x:04
Liebert Monitoring Group – Development

Power Unit – Power Monitoring Panel – PMP

Page 63 of 149
Page 64
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Ground Overcurrent
40289:05
289:05
BA01_x:05
Transformer Overtemp
40289:06
289:06
BA01_x:06
Ground Fault
40289:07
289:07
BA01_x:07
Ground Failure
40289:08
289:08
BA01_x:08
Liquid Detected
40289:09
289:09
BA01_x:09
Security Alarm
40289:10
289:10
BA01_x:10
Phase Rotation/Loss
40290:00
290:00
BA02_x:00
Datawave Overtemperature
40290:01
290:01
BA02_x:01
Emergency Shutdown
40290:02
290:02
BA02_x:02
Load On Bypass
40290:03
290:03
BA02_x:03
Local Alarm #1
40290:04
290:04
BA02_x:04
Local Alarm #2
40290:05
290:05
BA02_x:05
Custom Alarm #1
40290:06
290:06
BA02_x:06
Custom Alarm #2
40290:07
290:07
BA02_x:07
Setpoints (View)
None
Control Points (Set)
None
Trendable Points (Set)
Voltage In A-B
Voltage In B-C
Voltage In C-A
Voltage Out A-B
Voltage Out B-C
Voltage Out C-A
Voltage In A-N
Voltage In B-N
Voltage In C-N
Liebert Monitoring Group – Development
Page 64 of 149
Page 65
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Trendable Points (Set)
Current Out A
Current Out B
Current Out C
% Capacity A
% Capacity B
% Capacity C
Ground Current
Neutral Current
KW
KVA
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 65 of 149
Page 66
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
MPU4000, Datawave, Precision Power Center
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Voltage Out X-Y
40001
1
BS01_x
Voltage Out Y-Z
40002
2
BS02_x
Voltage Out Z-X
40003
3
BS03_x
Voltage Out X-N
40004
4
BS04_x
Voltage Out Y-N
40005
5
BS05_x
Voltage Out Z-N
40006
6
BS06_x
Current Out A
40007
7
BS07_x
Current Out B
40008
8
BS08_x
Current Out C
40009
9
BS09_x
Ground Current
40010
10
BS10_x
Neutral Current
40011
11
BS11_x
KVA
40012
12
BS12_x
Frequency
40013
13
BS13_x
Divide by 10 for correct value
Alarm Points
Communications
40289:0
289:0
BA01_x:00
Output Undervoltage
40289:1
289:1
BA01_x:01
Output Overvoltage
40289:2
289:2
BA01_x:02
Transformer Overtemp
40289:3
289:3
BA01_x:03
Local Alarm #1
40289:4
289:4
BA01_x:04
Local Alarm #2
40289:5
289:5
BA01_x:05
Setpoints (View)
None
Control Points (Set)
None
Liebert Monitoring Group – Development

Power Unit – Voltage-Current-Freq. Monitor Panel – VCF

Page 66 of 149
Page 67
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Trendable Points (Set)
Voltage Out X-Y
Voltage Out Y-Z
Voltage Out Z-X
Voltage Out X-N
Voltage Out Y-N
Voltage Out Z-N
Current Out A
Current Out B
Current Out C
Ground Current
Neutral Current
kVA
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 67 of 149
Page 68
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Datawave, Precision Power Center
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet Instance (Exec. B
Modules)
Notes:
Status Points (View)
Voltage In X-Y
40001
1
BS01_x
Voltage In Y-Z
40002
2
BS02_x
Voltage In Z-X
40003
3
BS03_x
Voltage Out A-B
40004
4
BS04_x
Voltage Out B-C
40005
5
BS05_x
Voltage Out C-A
40006
6
BS06_x
Voltage Out A-N
40007
7
BS07_x
Voltage Out B-N
40008
8
BS08_x
Voltage Out C-N
40009
9
BS09_x
Current Out A
40010
10
BS10_x
Current Out B
40011
11
BS11_x
Current Out C
40012
12
BS12_x
Ground Current
40013
13
BS13_x
Divide by 10 for correct value
Neutral Current
40014
14
BS14_x
KVA
40015
15
BS15_x
KW
40016
16
BS16_x
Frequency
40017
17
BS17_X
Divide by 10 for correct value
% Capacity A
40018
18
BS18_x
% Capacity B
40019
19
BS19_x
% Capacity C
40020
20
BS20_x
Power Factor
40021
21
BS21_x
Divide by 100 for correct value
Kilowatt Hours
THD Voltage X
THD Voltage Y
THD Voltage Z
THD Current X
THD Current Y
Liebert Monitoring Group – Development

Power Unit – Power Monitoring Panel (Ext. Protocol– PM2)

Page 68 of 149
Page 69
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
THD Current Z
K Factor Current X
K Factor Current Y
K Factor Current Z
CREST Factor Current X
CREST Factor Current Y
CREST Factor Current Z
Alarm Points
Discrete BACnet alarm objects available –use auto-discover for this unit
Communications
40289:00
289:00
BA01_x:00
Output Undervoltage
40289:01
289:01
BA01_x:01
Output Overvoltage
40289:02
289:02
BA01_x:02
Output Overcurrent
40289:03
289:03
BA01_x:03
Frequency Deviation
40289:04
289:04
BA01_x:04
Ground Overcurrent
40289:05
289:05
BA01_x:05
Transformer Overtemp
40289:06
289:06
BA01_x:06
Ground Fault
40289:07
289:07
BA01_x:07
Ground Failure
40289:08
289:08
BA01_x:08
Liquid Detected
40289:09
289:09
BA01_x:09
Security Alarm
40289:10
289:10
BA01_x:10
Phase Rotation/Loss
40290:00
290:00
BA02_x:00
Datawave Overtemperature
40290:01
290:01
BA02_x:01
Emergency Shutdown
40290:02
290:02
BA02_x:02
Load On Bypass
40290:03
290:03
BA02_x:03
Local Alarm #1
40290:04
290:04
BA02_x:04
Local Alarm #2
40290:05
290:05
BA02_x:05
Output Voltage THD
40290:06
290:06
BA02_x:06
Custom Alarm #1
40290:07
290:07
BA02_x:07
Custom Alarm #2
40290:08
290:08
BA02_x:08
Setpoints (View)
None
Control Points (Set)
None
Liebert Monitoring Group – Development
Page 69 of 149
Page 70
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Trendable Points (Set)
Voltage In A-B
Voltage In B-C
Voltage In C-A
Voltage Out A-B
Voltage Out B-C
Voltage Out C-A
Voltage In A-N
Voltage In B-N
Voltage In C-N
Current Out A
Current Out B
Current Out C
% Capacity A
% Capacity B
% Capacity C
Ground Current
Neutral Current
KW
KVA
Power Factor
THD Voltage X
THD Voltage Y
THD Voltage Z
THD Current X
THD Current Y
THD Current Z
K Factor Current X
K Factor Current Y
K Factor Current Z
CREST Factor Current X
CREST Factor Current Y
CREST Factor Current Z
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 70 of 149
Page 71
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Static Transfer Switch
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Transfer Count
40001
1
BS01_x
Preferred Source
40002
2
BS02_x
1=Source 1 / 0=Source 2
Load On Source 1or 2
40003
3
BS03_x
1=Source 1 / 2=Source 2
Source 1 Voltage A-B
40004
4
BS04_x
Source 1 Voltage B-C
40005
5
BS05_x
Source 1 Voltage C-A
40006
6
BS06_x
Source 1 Current A
40007
7
BS07_x
Source 1 Current B
40008
8
BS08_x
Source 1 Current C
40009
9
BS09_x
Source 1 Frequency
40010
10
BS10_x
Divide by 10 for correct value
Source 2 Voltage A-B
40011
11
BS11_x
Source 2 Voltage B-C
40012
12
BS12_x
Source 2 Voltage C-A
40013
13
BS13_x
Source 2 Current A
40014
14
BS14_x
Source 2 Current B
40015
15
BS15_x
Source 2 Current C
40016
16
BS16_x
Source 2 Frequency
40017
17
BS17_x
Divide by 10 for correct value
KW
40018
18
BS18_x
KVA
40019
19
BS19_x
Auto Transfer Timer
40020
20
BS20_x
Nominal Voltage Deviation
40021
21
BS21_x
Phase Differential Limit
40022
22
BS22_x
Frequency Deviation
40023
23
BS23_x
Divide by 10 for correct value
Auto Transfer Enabled
40024
24
BS24_x
1=Enabled / 0=Disabled
Liebert Monitoring Group – Development

Power Unit – Static Transfer Switch PDU – EDS

Page 71 of 149
Page 72
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Communications
40289:00
289:00
BA01_x:00
Logic Failure
40289:01
289:01
BA01_x:01
Equipment Overtemp
40289:02
289:02
BA01_x:02
Power Supply 1 Fault
40289:03
289:03
BA01_x:03
Source 1 Overvoltage
40289:04
289:04
BA01_x:04
Source 1 Undervoltage
40289:05
289:05
BA01_x:05
Source 2 Overvoltage
40289:06
289:06
BA01_x:06
Source 2 Undervoltage
40289:07
289:07
BA01_x:07
Source 1 Overload
40289:08
289:08
BA01_x:08
Shorted SCR1
40289:09
289:09
BA01_x:09
Shorted SCR2
40289:10
289:10
BA01_x:10
Open SCR1
40290:00
290:00
BA02_x:00
Open SCR2
40290:01
290:01
BA02_x:01
Fan Failure
40290:02
290:02
BA02_x:02
Source 2 Overload
40290:03
290:03
BA02_x:03
Power Supply 2 Fault
40290:04
290:04
BA02_x:04
Frequency Deviation
40290:05
290:05
BA02_x:05
Transfer Inhibit
40290:06
290:06
BA02_x:06
Auto Retransfer Primed
40290:07
290:07
BA02_x:07
Out of Synchronization
40290:08
290:08
BA02_x:08
Source 1 Failure
40290:09
290:09
BA02_x:09
Source 2 Failure
40290:10
290:10
BA02_x:10
Auto Retransfer Failed
40291:00
291:00
BA03_x:00
Overload
40291:01
291:01
BA03_x:01
Control Fuse 1 Blown
40291:02
291:02
BA03_x:02
Control Fuse 2 Blown
40291:03
291:03
BA03_x:03
Source 1 CB1 Open
40291:04
291:04
BA03_x:04
Source 2 CB2 Open
40291:05
291:05
BA03_x:05
Output CB3 Open
40291:06
291:06
BA03_x:06
Custom Alarm 1
40291:07
291:07
BA03_x:07
Custom Alarm 2
40291:08
291:08
BA03_x:08
Bypass CB4 Closed
40291:09
291:09
BA03_x:09
Bypass CB5 Closed
40291:10
291:10
BA03_x:10
Custom Alarm 3
40292:00
292:00
BA04_x:00
Custom Alarm 4
40292:01
292:01
BA04_x:01
Liebert Monitoring Group – Development
Page 72 of 149
Page 73
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Custom Alarm 5
40292:2
292:2
BA04_x:02
Custom Alarm 6
40292:3
292:3
BA04_x:03
Custom Alarm 7
40292:4
292:4
BA04_x:04
Custom Alarm 8
40292:5
292:5
BA04_x:05
Setpoints (View)
None
Control Points (Set)
None
Trendable Points (Set)
Source 1 Voltage A-B
Source 1 Voltage B-C
Source 1 Voltage C-A
Source 1 Current A
Source 1 Current B
Source 1 Current C
Source 2 Voltage A-B
Source 2 Voltage B-C
Source 2 Voltage C-A
Source 2 Current A
Source 2 Current B
Source 2 Current C
KW
KVA
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 73 of 149
Page 74
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Static Transfer Switch with w/ & w/o PDU
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Transfer Count
40001
1
BS01_x
Preferred Source
40002
2
BS02_x
1=Source 1 / 0=Source 2
Load On Source 1 or 2
40003
3
BS03_x
1=Source 1 / 2=Source 2
Source 1 Voltage A-B
40004
4
BS04_x
Source 1 Voltage B-C
40005
5
BS05_x
Source 1 Voltage C-A
40006
6
BS06_x
Source 1 Current A
40007
7
BS07_x
Source 1 Current B
40008
8
BS08_x
Source 1 Current C
40009
9
BS09_x
Source 1 Frequency
40010
10
BS10_x
Divide by 10 for correct value
Source 2 Voltage A-B
40011
11
BS11_x
Source 2 Voltage B-C
40012
12
BS12_x
Source 2 Voltage C-A
40013
13
BS13_x
Source 2 Current A
40014
14
BS14_x
Source 2 Current B
40015
15
BS15_x
Source 2 Current C
40016
16
BS16_x
Source 2 Frequency
40017
17
BS17_x
Divide by 10 for correct value
KW
40018
18
BS18_x
KVA
40019
19
BS19_x
Auto Transfer Timer
40020
20
BS20_x
Nominal Voltage Deviation
40021
21
BS21_x
Phase Differential Limit
40022
22
BS22_x
Frequency Deviation
40023
23
BS23_x
Divide by 10 for correct value
Auto Transfer Enabled
40024
24
BS24_x
1=Enabled / 0=Disabled
Dual Output Breaker Status
1=Enabled / 0=Disabled
Liebert Monitoring Group – Development

Power Unit – Static Transfer Switch PDU Dual Output – STS

Page 74 of 149
Page 75
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Communications
40289:00
289:00
BA01_x:00
Logic Failure
40289:01
289:01
BA01_x:01
Equipment Overtemp
40289:02
289:02
BA01_x:02
Power Supply 1 Fault
40289:03
289:03
BA01_x:03
Source 1 Overvoltage
40289:04
289:04
BA01_x:04
Source 1 Undervoltage
40289:05
289:05
BA01_x:05
Source 2 Overvoltage
40289:06
289:06
BA01_x:06
Source 2 Undervoltage
40289:07
289:07
BA01_x:07
Source 1 Overload
40289:08
289:08
BA01_x:08
Shorted SCR1
40289:09
289:09
BA01_x:09
Shorted SCR2
40289:10
289:10
BA01_x:10
Open SCR1
40290:00
290:00
BA02_x:00
Open SCR2
40290:01
290:01
BA02_x:01
Fan Failure
40290:02
290:02
BA02_x:02
Source 2 Overload
40290:03
290:03
BA02_x:03
Power Supply 2 Fault
40290:04
290:04
BA02_x:04
Frequency Deviation
40290:05
290:05
BA02_x:05
Transfer Inhibit
40290:06
290:06
BA02_x:06
Auto Retransfer Primed
40290:07
290:07
BA02_x:07
Out of Synchronization
40290:08
290:08
BA02_x:08
Source 1 Failure
40290:09
290:09
BA02_x:09
Source 2 Failure
40290:10
290:10
BA02_x:10
Auto Retransfer Failed
40291:00
291:00
BA03_x:00
Overload
40291:01
291:01
BA03_x:01
Control Fuse 1 Blown
40291:02
291:02
BA03_x:02
Control Fuse 2 Blown
40291:03
291:03
BA03_x:03
Source 1 CB1 Open
40291:04
291:04
BA03_x:04
Source 2 CB2 Open
40291:05
291:05
BA03_x:05
Output CB3 Open
40291:06
291:06
BA03_x:06
Custom Alarm 1
40291:07
291:07
BA03_x:07
Custom Alarm 2
40291:08
291:08
BA03_x:08
Bypass CB4 Closed
40291:09
291:09
BA03_x:09
Bypass CB5 Closed
40291:10
291:10
BA03_x:10
Output CB 3B Open
40292:00
292:00
BA04_x:00
Custom Alarm 4
40292:01
292:01
BA04_x:01
Custom Alarm 5
40292:02
292:02
BA01_x:02
Custom Alarm 6
40292:03
292:03
BA01_x:03
Liebert Monitoring Group – Development
Page 75 of 149
Page 76
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Custom Alarm 7
40292:4
292:4
BA01_x:04
Custom Alarm 8
40292:5
292:5
BA01_x:05
Setpoints (View)
Auto Transfer Timer
Nominal Voltage Deviation
Phase Differential Limit
Frequency Deviation
Auto Transfer Enabled
Control Points (Set)
None
Trendable Points (Set)
Source 1 Voltage A-B
Source 1 Voltage B-C
Source 1 Voltage C-A
Source 1 Current A
Source 1 Current B
Source 1 Current C
Source 2 Voltage A-B
Source 2 Voltage B-C
Source 2 Voltage C-A
Source 2 Current A
Source 2 Current B
Source 2 Current C
KW
KVA
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 76 of 149
Page 77
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Static Transfer Switch Extended Protocol w/ & w/o PDU
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Total Transfer Count
40001
1
BS01_x
Preferred Source
40002
2
BS02_x
0=Source 1, 255=Source 2
Active Source
40003
3
BS03_x
1=Source 1, 2=Source 2
Source 1 Volts A-B
40004
4
BS04_x
Source 1 Volts B-C
40005
5
BS05_x
Source 1 Volts C-A
40006
6
BS06_x
Source 1 Current A
40007
7
BS07_x
Source 1 Current B
40008
8
BS08_x
Source 1 Current C
40009
9
BS09_x
Source 1 Frequency
40010
10
BS10_x
Divide by 10 for correct value
Source 2 Volts A-B
40011
11
BS11_x
Source 2 Volts B-C
40012
12
BS12_x
Source 2 Volts C-A
40013
13
BS13_x
Source 2 Current A
40014
14
BS14_x
Source 2 Current B
40015
15
BS15_x
Source 2 Current C
40016
16
BS16_x
Source 2 Frequency
40017
17
BS17_x
Divide by 10 for correct value
Output KW
40018
18
BS18_x
Output KVA
40019
19
BS19_x
Sync Phase Angle
Total Operating Hours
CB1 Status
40024:0
24:0
BS24_x:00
CB2 Status
40024:1
24:1
BS24_x:01
CB3 Status
40024:2
24:2
BS24_x:02
CB3A Status
40024:3
24:3
BS24_x:03
CB4 Status
40024:4
24:4
BS24_x:04
CB5 Status
40024:5
24:5
BS24_x:05
CB7 Status
40024:6
24:6
BS24_x:06
CB8 Status
40024:7
24:7
BS24_x:07
Setpoints (View)
Retransefer Delay
40020
20
BS20_x
Liebert Monitoring Group – Development

Power Unit – Static Transfer Switch PDU Dual Output – STS-2

Page 77 of 149
Page 78
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Setpoints (Cont)
STS2 Voltage Rating
40021
21
BS21_x
Max Xfer Phase Angle
40022
22
BS22_x
Freq. Deviation Trip Point
40023
23
BS23_x
Alarm Points
Discrete BACnet alarm objects available – use auto­discover for this unit
Communications Lost
40289:00
289:00
BA01_x:00
S1 SCR Short
40289:01
289:01
BA01_x:01
S2 SCR Short
40289:02
289:02
BA01_x:02
S1 SCR Open
40289:03
289:03
BA01_x:03
S2 SCR Open
40289:04
289:04
BA01_x:04
Primary Fan Fail
40289:05
289:05
BA01_x:05
Control Module Fail
40289:06
289:06
BA01_x:06
PWR Supply DC A Fail
40289:07
289:07
BA01_x:07
PWR Supply DC B Fail
40289:08
289:08
BA01_x:08
PWR Supply SRC 1 AC Fail
40289:09
289:09
BA01_x:09
PWR Supply SRC 2 AC Fail
40289:10
289:10
BA01_x:10
PWR Supply Logic Fail
40289:11
289:11
BA01_x:11
Output Voltage Sense Fail
40289:12
289:12
BA01_x:12
S1 Voltage Sense Fail
40289:13
289:13
BA01_x:13
S2 Voltage Sense Fail
40289:14
289:14
BA01_x:14
S1 SCR Sense Fail
40289:15
289:15
BA01_x:15
S2 SCR Sense Fail
40290:00
290:00
BA02_x:00
S1 Current Sense Fail
40290:01
290:01
BA02_x:01
S2 Current Sense Fail
40290:02
290:02
BA02_x:02
S1 Gate Drive Fail
40290:03
290:03
BA02_x:03
S2 Gate Drive Fail
40290:04
290:04
BA02_x:04
Internal Comm Fail
40290:05
290:05
BA02_x:05
External Comm Fail
40290:06
290:06
BA02_x:06
CB1 Shunt Trip Fail
40290:07
290:07
BA02_x:07
CB2 Shunt Trip Fail
40290:08
290:08
BA02_x:08
CB6 Neutral Open
40290:09
290:09
BA02_x:09
Contactor Neutral Fail
40290:10
290:10
BA02_x:10
Heatsink Overtemp
40290:11
290:11
BA02_x:11
Equipment Overtemp
40290:12
290:12
BA02_x:12
Ambient Overtemp
40290:13
290:13
BA02_x:13
S1 Undervolts
40290:14
290:14
BA02_x:14
S1 Undervolts (RMS)
40290:15
290:15
BA02_x:15
S1 Overvolts
40291:00
291:00
BA03_x:00
S1 Over/Under Freq
40291:01
291:01
BA03_x:01
Liebert Monitoring Group – Development
Page 78 of 149
Page 79
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points (cont.)
Discrete BACnet alarm objects available – use auto-discover for this unit
S1 Fail
40291:02
291:02
BA03_x:02
S2 Undervolts
40291:03
291:03
BA03_x:03
S2 Undervolts (RMS)
40291:04
291:04
BA03_x:04
S2 Overvolts
40291:05
291:05
BA03_x:05
S2 Over/Under Frequency
40291:06
291:06
BA03_x:06
S2 Fail
40291:07
291:07
BA03_x:07
S1 Overcurrent
40291:08
291:08
BA03_x:08
S2 Overcurrent
40291:09
291:09
BA03_x:09
S1 I-Peak
40291:10
291:10
BA03_x:10
S2 I-Peak
40291:11
291:11
BA03_x:11
Sources Out of Sync
40291:12
291:12
BA03_x:12
Load On Alternate Source
40291:13
291:13
BA03_x:13
Auto Retransfer Inhibit
40291:14
291:14
BA03_x:14
CB1 (S1) Open
40292:00
292:00
BA04_x:00
CB2 (S2) Open
40292:01
292:01
BA04_x:01
CB4 (S1 BYP) Closed
40292:02
292:02
BA04_x:02
CB5 (S2 BYP) Closed
40292:03
292:03
BA04_x:03
CB3 Output Bkr Open
40292:04
292:04
BA04_x:04
CB3A Output Bkr Open
40292:05
292:05
BA04_x:05
S1 Phase Rotation Error
40292:06
292:06
BA04_x:06
S2 Phase Rotation Error
40292:07
292:07
BA04_x:07
Transfer Inhibited
40292:08
292:08
BA04_x:08
Output Undervoltage
40292:09
292:09
BA04_x:09
History Logs Full
40292:10
292:10
BA04_x:10
Input Contact #1
40292:11
292:11
BA04_x:11
Input Contact #2
40292:12
292:12
BA04_x:12
Input Contact #3
40292:13
292:13
BA04_x:13
Input Contact #4
40292:14
292:14
BA04_x:14
Input Contact #5
40293:00
293:00
BA05_x:00
Input Contact #6
40293:01
293:01
BA05_x:01
Input Contact #7
40293:02
293:02
BA05_x:02
Input Contact #8
40293:03
293:03
BA05_x:03
Liebert Monitoring Group – Development
Page 79 of 149
Page 80
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Trendable Points (Set)
S1 Amps A
S1 Amps B
S1 Amps C
S2 Amps A
S2 Amps B
S2 Amps C
kVA
kW
Liebert Monitoring Group – Development
Page 80 of 149
Page 81
Liebert Monitoring Group – Development

Liebert UPS Units

Revision B.33 2/25/2011
Page 81 of 149
Page 82
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Series 600/610 MMS
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Input Voltage A-B
40001
1
BS01_x
Input Voltage B-C
40002
2
BS02_x
Input Voltage C-A
40003
3
BS03_x
Output Voltage A-B
40004
4
BS04_x
Output Voltage B-C
40005
5
BS05_x
Output Voltage C-A
40006
6
BS06_x
Output Voltage A-N
Output Voltage B-N
Output Voltage C-N
Output Amps Phase A
40007
7
BS07_x
Output Amps Phase B
40008
8
BS08_x
Output Amps Phase C
40009
9
BS09_x
DC Bus Voltage
40010
10
BS10_x
Battery Current
40011
11
BS11_x
KVA
40012
12
BS12_x
KW
40013
13
BS13_x
Critical Bus Frequency
40014
14
BS14_x
Divide by 10 for correct value
% Capacity Phase A
40015
15
BS15_x
% Capacity Phase B
40016
16
BS16_x
% Capacity Phase C
40017
17
BS17_x
Input Amps Phase A
40018
18
BS18_x
Input Amps Phase B
40019
19
BS19_x
Input Amps Phase C
40020
20
BS20_x
Total Operating Hours
Module Number
Total # Battery Discharge
Accumulated Battery Time
Liebert Monitoring Group – Development

UPS Unit – Multi Module UPS – S600/610 Extended Prot. – MM4

Page 82 of 149
Page 83
Revision B.33 2/25/2011
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet Instance (Exec. B
Modules)
Notes:
Status Points (View)
Accumulated Battery Amp/Hr
Accumulated Battery kw/Hr
Battery Charge Percent
Battery Time Remaining
Battery Temperature
Alarm Points
Communications
40289:00
289:00
BA01_x:00
Battery Discharge
40289:01
289:01
BA01_x:01
Input Failure
40289:02
289:02
BA01_x:02
Hardware Shutdown
40289:03
289:03
BA01_x:03
DC Ground Fault
40289:04
289:04
BA01_x:04
Input CB Open
40289:05
289:05
BA01_x:05
Output CB Open
40289:06
289:06
BA01_x:06
DC Cap Fuse Blown
40289:07
289:07
BA01_x:07
Low Battery Reserve
40289:08
289:08
BA01_x:08
Output Overload
40289:09
289:09
BA01_x:09
Rectifier Fuse Blown
40289:10
289:10
BA01_x:10
Emergency Power Off
40290:00
290:00
BA02_x:00
Ambient Overtemperature
40290:01
290:01
BA02_x:01
Battery Disconnected
40290:02
290:02
BA02_x:02
Control Power Failure
40290:03
290:03
BA02_x:03
Overload Shutdown
40290:04
290:04
BA02_x:04
Inverter Fault
40290:05
290:05
BA02_x:05
Input Current Unbalanced
40290:06
290:06
BA02_x:06
Inverter Out of Sync
40290:07
290:07
BA02_x:07
Reverse Power
40290:08
290:08
BA02_x:08
Low Battery Shutdown
40290:09
290:09
BA02_x:09
DC Overvoltage Shutdown
40290:10
290:10
BA02_x:10
Battery Cycle Buffer Full
40291:00
291:00
BA03_x:00
Equipment Overtemp
40291:01
291:01
BA03_x:01
Blower/Fan Failure
40291:02
291:02
BA03_x:02
Overtemperature Shutdown
40291:03
291:03
BA03_x:03
Battery Room Overtemp
40291:04
291:04
BA03_x:04
Battery Test Running
40291:05
291:05
BA03_x:05
Liebert Monitoring Group – Development
Page 83 of 149
Page 84
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet Instance (Exec. B
Modules)
Notes:
Setpoints (View)
Overload Alarm
DC Overvoltage Alarm
Battery Discharging Alarm
Low Battery Alarm
Battery Shutdown 1 Alarm
Battery Shutdown 2 Alarm
Control Points (Set)
None
Trendable Points (Set)
Input Voltage A-B
Input Voltage B-C
Input Voltage C-A
Output Voltage A-B
Output Voltage B-C
Output Voltage C-A
Output Voltage A-N
Output Voltage B-N
Output Voltage C-N
Output Amps Phase A
Output Amps Phase B
Output Amps Phase C
DC Bus Voltage
KVA
KW
% Capacity Phase A
% Capacity Phase B
% Capacity Phase C
Input Amps Phase A
Input Amps Phase B
Input Amps Phase C
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 84 of 149
Page 85
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Series /610MMS, Series 600T MS
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink
Available Points
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Voltage In A-B
40001
1
BS01_x
Voltage In B-C
40002
2
BS02_x
Voltage In C-A
40003
3
BS03_x
Voltage Out A-B
40004
4
BS04_x
Voltage Out B-C
40005
5
BS05_x
Voltage Out C-A
40006
6
BS06_x
Voltage Out A-N
40007
7
BS07_x
Voltage Out B-N
40008
8
BS08_x
Voltage Out C-N
40009
9
BS09_x
Current Out A
40010
10
BS10_x
Current Out B
40011
11
BS11_x
Current Out C
40012
12
BS12_x
DC Bus Voltage
40013
13
BS13_x
Battery Current
40014
14
BS14_x
KVA
40015
15
BS15_x
KW
40016
16
BS16_x
Frequency
40017
17
BS17_x
Divide by 10 for correct value
% Capacity A
40018
18
BS18_x
% Capacity B
40019
19
BS19_x
% Capacity C
40020
20
BS20_x
Alarm Points
Discrete BACnet alarm objects available – use auto-discover for this unit
Communications
40289:00
289:00
BA01_x:00
Battery Discharge
40289:01
289:01
BA01_x:01
Low Battery Reserve
40289:02
289:02
BA01_x:02
Output Overload
40289:03
289:03
BA01_x:03
Fuse Cleared
40289:04
289:04
BA01_x:04
Ambient Overtemperature
40289:05
289:05
BA01_x:05
Liebert Monitoring Group – Development

UPS Unit – Multi Module Series – MMS

Page 85 of 149
Page 86
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Battery Grounded
40289:06
289:06
BA01_x:06
Battery Disconnected
40289:07
289:07
BA01_x:07
Module Cooling Failure
40289:08
289:08
BA01_x:08
Control Power Failure
40289:09
289:09
BA01_x:09
Overload Shutdown
40289:10
289:10
BA01_x:10
Setpoints (View)
None
Control Points (Set)
None
Trendable Points (Set)
Voltage In A-B
Voltage In B-C
Voltage In C-A
Voltage Out A-B
Voltage Out B-C
Voltage Out C-A
Voltage Out A-N
Voltage Out B-N
Voltage Out C-N
Current Out A
Current Out B
Current Out C
% Capacity A
% Capacity B
% Capacity C
DC Bus Voltage
DC Bus Current
kW
kVA
Reports
Trend
Liebert Monitoring Group – Development
Page 86 of 149
Page 87
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Series /610 SCC
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance (Exec. B
Modules)
Notes:
Status Points (View)
Input Voltage A-B
40001
1
BS01_x
Input Voltage B-C
40002
2
BS02_x
Input Voltage C-A
40003
3
BS03_x
Output Voltage A-B
40004
4
BS04_x
Output Voltage B-C
40005
5
BS05_x
Output Voltage C-A
40006
6
BS06_x
Output Voltage A-N
Output Voltage B-N
Output Voltage C-N
Output Amps Phase A
40007
7
BS07_x
Output Amps Phase B
40008
8
BS08_x
Output Amps Phase C
40009
9
BS09_x
KVA
40010
10
BS10_x
KW
40011
11
BS11_x
Critical Bus Frequency
40012
12
BS12_x
Divide by 10 for correct value
% Capacity Phase A
40013
13
BS13_x
% Capacity Phase B
40014
14
BS14_x
% Capacity Phase C
40015
15
BS15_x
Bypass Voltage A-B
40016
16
BS16_x
Bypass Voltage B-C
40017
17
BS17_x
Bypass Voltage C-A
40018
18
BS18_x
Output Frequency
40019
19
BS19_x
Divide by 10 for correct value
Bypass Frequency
40020
20
BS20_x
Divide by 10 for correct value
Total Operating Hours
Number of Modules in System
System Number
Liebert Monitoring Group – Development

UPS Unit – System Control Cabinet – S/610 Ext. Prot. – SC4

Page 87 of 149
Page 88
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Communications
40289:00
289:00
BA01_x:00
Output Undervoltage
40289:01
289:01
BA01_x:01
Output Overvoltage
40289:02
289:02
BA01_x:02
Frequency Deviation
40289:03
289:03
BA01_x:03
Bypass CB Closed
40289:04
289:04
BA01_x:04
Output CB Open
40289:05
289:05
BA01_x:05
Static Switch Disconnected
40289:06
289:06
BA01_x:06
Output Overload
40289:07
289:07
BA01_x:07
Emergency Power Off
40289:08
289:08
BA01_x:08
Load On Bypass
40289:09
289:09
BA01_x:09
Static Switch Disabled
40289:10
289:10
BA01_x:10
Control Power Failure
40290:00
290:00
BA02_x:00
Module #1 Summary Alarm
40290:01
290:01
BA02_x:01
Module #2 Summary Alarm
40290:02
290:02
BA02_x:02
Module #3 Summary Alarm
40290:03
290:03
BA02_x:03
Module #4 Summary Alarm
40290:04
290:04
BA02_x:04
Module #5 Summary Alarm
40290:05
290:05
BA02_x:05
Module #6 Summary Alarm
40290:06
290:06
BA02_x:06
Bypass Not Available
40290:07
290:07
BA02_x:07
Not OK to Transfer
40290:08
290:08
BA02_x:08
Bypass Ph Rotation Error
40290:09
290:09
BA02_x:09
Manual Reset/Transfer
40290:10
290:10
BA02_x:10
Auto Re-Transfer Primed
40291:00
291:00
BA03_x:00
Overload Transfer
40291:01
291:01
BA03_x:01
Module #1 Offline
40291:02
291:02
BA03_x:02
Module #2 Offline
40291:03
291:03
BA03_x:03
Module #3 Offline
40291:04
291:04
BA03_x:04
Module #4 Offline
40291:05
291:05
BA03_x:05
Module #5 Offline
40291:06
291:06
BA03_x:06
Module #6 Offline
40291:07
291:07
BA03_x:07
Custom Alarm #1
40291:08
291:08
BA03_x:08
Custom Alarm #2
40291:09
291:09
BA03_x:09
Custom Alarm #3
40291:10
291:10
BA03_x:10
Custom Alarm #4
40292:00
292:00
BA04_x:00
Custom Alarm #5
40292:01
292:01
BA04_x:01
Liebert Monitoring Group – Development
Page 88 of 149
Page 89
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Custom Alarm #6
40292:02
292:02
BA04_x:02
Custom Alarm #7
40292:03
292:03
BA04_x:03
Custom Alarm #8
40292:04
292:04
BA04_x:04
Setpoints (View)
Overload Alarm
Control Points (Set)
None
Trendable Points (Set)
Input Voltage A-B
Input Voltage B-C
Input Voltage C-A
Output Voltage A-B
Output Voltage B-C
Output Voltage C-A
Output Voltage A-N
Output Voltage B-N
Output Voltage C-N
Output Amps Phase A
Output Amps Phase B
Output Amps Phase C
kVA
KW
% Capacity Phase A
% Capacity Phase B
% Capacity Phase C
Bypass Voltage A-B
Bypass Voltage B-C
Bypass Voltage C-A
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 89 of 149
Page 90
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Series 600/610 SCC
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Voltage In A-B
40001
1
BS01_x
Voltage In B-C
40002
2
BS02_x
Voltage In C-A
40003
3
BS03_x
Voltage Out A-B
40004
4
BS04_x
Voltage Out B-C
40005
5
BS05_x
Voltage Out C-A
40006
6
BS06_x
Voltage In A-N
40007
7
BS07_x
Voltage In B-N
40008
8
BS08_x
Voltage In C-N
40009
9
BS09_x
Current Out A
40010
10
BS10_x
Current Out B
40011
11
BS11_x
Current Out C
40012
12
BS12_x
KVA
40013
13
BS13_x
KW
40014
14
BS14_x
Frequency
40015
15
BS15_x
Divide by 10 for correct value
% Capacity Phase A
40016
16
BS16_x
% Capacity Phase B
40017
17
BS17_x
% Capacity Phase C
40018
18
BS18_x
Alarm Points
Discrete BACnet alarm objects available – use auto-discover for this unit
Communications
40289:00
289:00
BA01_x:00
Output Overload
40289:01
289:01
BA01_x:01
Emergency Power Off
40289:02
289:02
BA01_x:02
Load On Bypass
40289:03
289:03
BA01_x:03
Static Switch Disabled
40289:04
289:04
BA01_x:04
Output Out of Limits
40289:05
289:05
BA01_x:05
Module #1 Summary
40289:06
289:06
BA01_x:06
Liebert Monitoring Group – Development

UPS Unit – System Control Cabinet – SCC

Page 90 of 149
Page 91
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Module #2 Summary
40289:07
289:07
BA01_x:07
Module #3 Summary
40289:08
289:08
BA01_x:08
Module #4 Summary
40289:09
289:09
BA01_x:09
Module #5 Summary
40289:10
289:10
BA01_x:10
Module #6 Summary
40290:00
290:00
BA02_x:00
Setpoints (View)
None
Control Points (Set)
None
Trendable Points (Set)
Voltage In A-B
Voltage In B-C
Voltage In C-A
Voltage Out A-B
Voltage Out B-C
Voltage Out C-A
Voltage In A-N
Voltage In B-N
Voltage In C-N
Current Out A
Current Out B
Current Out C
% Capacity Phase A
% Capacity Phase B
% Capacity Phase C
KW
KVA
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 91 of 149
Page 92
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Series 300/500/600 Single Module UPS
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Voltage In A-B
40001
1
BS01_x
Voltage In B-C
40002
2
BS02_x
Voltage In C-A
40003
3
BS03_x
Voltage Out A-B
40004
4
BS04_x
Voltage Out B-C
40005
5
BS05_x
Voltage Out C-A
40006
6
BS06_x
Voltage Out A-N
40007
7
BS07_x
Voltage Out B-N
40008
8
BS08_x
Voltage Out C-N
40009
9
BS09_x
Current Out A
40010
10
BS10_x
Current Out B
40011
11
BS11_x
Current Out C
40012
12
BS12_x
DC Bus Voltage
40013
13
BS13_x
DC Bus Current
40014
14
BS14_x
KVA
40015
15
BS15_x
Divide by 10 for correct value
Modbus Only
KW
40016
16
BS16_x
Divide by 10 for correct value
Modbus Only
Frequency
40017
17
BS17_x
Divide by 10 for correct value
Modbus Only
% Capacity Phase A
40018
18
BS18_x
% Capacity Phase B
40019
19
BS19_x
% Capacity Phase C
40020
20
BS20_x
Alarm Points
Communications
40289:00
289:00
BA01_x:00
Battery Discharge
40289:01
289:01
BA01_x:01
Low Battery Reserve
40289:02
289:02
BA01_x:02
Output Overload
40289:03
289:03
BA01_x:03
Fuse Cleared
40289:04
289:04
BA01_x:04
Emergency Power Off
40289:05
289:05
BA01_x:05
Ambient Overtemperature
40289:06
289:06
BA01_x:06
Load On Bypass
40289:07
289:07
BA01_x:07
Static Switch Disabled
40289:08
289:08
BA01_x:08
Battery Disconnected
40289:09
289:09
BA01_x:09
Module Cooling Failure
40289:10
289:10
BA01_x:10
Liebert Monitoring Group – Development

UPS Unit – Single Module Series – SMS

Page 92 of 149
Page 93
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Control Power Failure
40290:00
290:00
BA02_x:00
Overload Shutdown
40290:01
290:01
BA02_x:01
Setpoints (View)
None
Control Points (Set)
None
Trendable Points (Set)
Voltage In A-B
Voltage In B-C
Voltage In C-A
Voltage Out A-B
Voltage Out B-C
Voltage Out C-A
Voltage Out A-N
Voltage Out B-N
Voltage Out C-N
Current Out A
Current Out B
Current Out C
% Capacity Phase A
% Capacity Phase B
% Capacity Phase C
DC Bus Voltage
DC Bus Current
KW
KVA
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 93 of 149
Page 94
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
Series /610 SMS
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Input Voltage A-B
40001
1
BS01_x
Input Voltage B-C
40002
2
BS02_x
Input Voltage C-A
40003
3
BS03_x
Output Voltage A-B
40004
4
BS04_x
Output Voltage B-C
40005
5
BS05_x
Output Voltage C-A
40006
6
BS06_x
Output Voltage A-N
Output Voltage B-N
Output Voltage C-N
Output Amps Phase A
40007
7
BS07_x
Output Amps Phase B
40008
8
BS08_x
Output Amps Phase C
40009
9
BS09_x
DC Bus Voltage
40010
10
BS10_x
Battery Current
40011
11
BS11_x
KVA
40012
12
BS12_x
KW
40013
13
BS13_x
Critical Bus Frequency
40014
14
BS14_x
Divide by 10 for correct value
% Capacity Phase A
40015
15
BS15_x
% Capacity Phase B
40016
16
BS16_x
% Capacity Phase C
40017
17
BS17_x
Bypass Voltage A-B
40018
18
BS18_x
Bypass Voltage B-C
40019
19
BS19_x
Bypass Voltage C-A
40020
20
BS20_x
Input Amps Phase A
40021
21
BS21_x
Input Amps Phase B
40022
22
BS22_x
Input Amps Phase C
40023
23
BS23_x
Bypass Frequency
40024
24
BS24_x
Divide by 10 for correct value
Liebert Monitoring Group – Development

UPS Unit – Single Module UPS – S/610 Ext. Prot. – SM4

Page 94 of 149
Page 95
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Bypass Frequency
Total Operating Hours
Module Number
Total # Battery Discharge
Accumulated Battery Time
Accumulated Battery Amp/Hr
Accumulated Battery kW/Hr
Battery Charge Percent
Battery Time Remaining
Battery Temperature
Alarm Points
Communications
40289:00
289:00
BA01_x:00
Output Undervoltage
40289:01
289:01
BA01_x:01
Output Overvoltage
40289:02
289:02
BA01_x:02
Battery Discharge
40289:03
289:03
BA01_x:03
Frequency Deviation
40289:04
289:04
BA01_x:04
Input Failure
40289:05
289:05
BA01_x:05
Hardware Shutdown
40289:06
289:06
BA01_x:06
DC Ground Fault
40289:07
289:07
BA01_x:07
Input CB Open
40289:08
289:08
BA01_x:08
Bypass CB Closed
40289:09
289:09
BA01_x:09
Output CB Open
40289:10
289:10
BA01_x:10
Static Switch Disconnected
40290:00
290:00
BA02_x:00
DC Cap Fuse Blown
40290:01
290:01
BA02_x:01
Low Battery Reserve
40290:02
290:02
BA02_x:02
Output Overload
40290:03
290:03
BA02_x:03
Rectifier Fuse Blown
40290:04
290:04
BA02_x:04
Emergency Power Off
40290:05
290:05
BA02_x:05
Ambient Overtemperature
40290:06
290:06
BA02_x:06
Load On Bypass
40290:07
290:07
BA02_x:07
Static Switch Disabled
40290:08
290:08
BA02_x:08
Battery Disconnected
40290:09
290:09
BA02_x:09
Control Power Failure
40290:10
290:10
BA02_x:10
Inverter Fault
40291:00
291:00
BA03_x:01
Input Current Unbalanced
40291:01
291:01
BA03_x:02
Liebert Monitoring Group – Development
Page 95 of 149
Page 96
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Bypass Not Available
40291:02
291:02
BA03_x:02
Not OK to Transfer
40291:03
291:03
BA03_x:03
Bypass Ph Rotation Error
40291:04
291:04
BA03_x:04
Manual Reset/Transfer
40291:05
291:05
BA03_x:05
Auto Re-Transfer Primed
40291:06
291:06
BA03_x:06
Overload Transfer
40291:07
291:07
BA03_x:07
Reserve Power
40291:08
291:08
BA03_x:08
Low Battery Shutdown
40291:09
291:09
BA03_x:09
DC Overvoltage Shutdown
40291:10
291:10
BA03_x:10
Battery Cycle Buffer Full
40292:00
292:00
BA04_x:00
Equipment Overtemp
40292:01
292:01
BA04_x:01
Blower/Fan Failure
40292:02
292:02
BA04_x:02
Overtemperature Shutdown
40292:03
292:03
BA04_x:03
Custom Alarm #1
40292:04
292:04
BA04_x:04
Custom Alarm #2
40292:05
292:05
BA04_x:05
Custom Alarm #3
40292:06
292:06
BA04_x:06
Custom Alarm #4
40292:07
292:07
BA04_x:07
Custom Alarm #5
40292:08
292:08
BA04_x:08
Custom Alarm #6
40292:09
292:09
BA04_x:09
Custom Alarm #7
40292:10
292:10
BA04_x:10
Custom Alarm #8
40292:00
292:00
BA05_x:00
Battery Room Overtemp
40293:01
293:01
BA05_x:01
Battery Test Running
40293:02
293:02
BA05_x:02
Auto-restart Initiated
40293:03
293:03
BA05_x:03
Auto-restart Failed
40293:04
293:04
BA05_x:04
Setpoints (View)
Overload Alarm
DC Overvoltage Alarm
Battery Discharging Alarm
Low Battery Alarm
Battery Shutdown 1 Alarm
Battery Shutdown 2 Alarm
Control Points (Set)
None
Liebert Monitoring Group – Development
Page 96 of 149
Page 97
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Trendable Points (Set)
Input Voltage A-B
Input Voltage B-C
Input Voltage C-A
Output Voltage A-B
Output Voltage B-C
Output Voltage C-A
Output Voltage A-N
Output Voltage B-N
Output Voltage C-N
Output Amps Phase A
Output Amps Phase B
Output Amps Phase C
DC Bus Voltage
Battery Current
KVA
KW
% Capacity Phase A
% Capacity Phase B
% Capacity Phase C
Bypass Voltage A-B
Bypass Voltage B-C
Bypass Voltage C-A
Input Amps Phase A
Input Amps Phase B
Input Amps Phase C
Reports
Trend
Status
Liebert Monitoring Group – Development
Page 97 of 149
Page 98
Revision B.33 2/25/2011
Hardware Compatibility
Liebert Units:
SICE 7200
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Output Voltage L1-L2
40001
1
BS01_x
Output Voltage L2-L3
40002
2
BS02_x
Output Voltage L3-L1
40003
3
BS03_x
Output Voltage L1-N
Output Voltage L2-N
Output Voltage L3-N
Output Amps L1
40004
4
BS04_x
Output Amps L2
40005
5
BS05_x
Output Amps L3
40006
6
BS06_x
Output Amps Neutral
Power L1
40007
7
BS07_x
Power L2
40008
8
BS08_x
Power L3
40009
9
BS09_x
Bypass Frequency
40010
10
BS10_x
Divide by 10 for correct value
Inverter Frequency
40011
11
BS11_x
Divide by 10 for correct value
Input Voltage L1-L2
Input Voltage L2-L3
Input Voltage L3-L1
Battery Voltage
40012
12
BS12_x
Battery Amperage
40013
13
BS13_x
Apparent Power L1
40014
14
BS14_x
Apparent Power L2
40015
15
BS15_x
Apparent Power L3
40016
16
BS16_x
% Load L1
40017
17
BS17_x
% Load L2
40018
18
BS18_x
% Load L3
40019
19
BS19_x
Module Number
Liebert Monitoring Group – Development

UPS Unit – Multi-Module SICE 7200 & HiPulse UPS – SMM

Page 98 of 149
Page 99
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
% Battery Charge
40020
20
BS20_x
Battery Temperature
40021
21
BS21_x
Battery Time Remaining
40022
22
BS22_x
Alarm Points
Communications
40289:00
289:00
BA01_x:00
Bypass Switch Open
40289:01
289:01
BA01_x:01
Output Switch Open
40289:02
289:02
BA01_x:02
Rectifier Switch Open
40289:03
289:03
BA01_x:03
Battery CB Open
40289:04
289:04
BA01_x:04
Manual Bypass Closed
40289:05
289:05
BA01_x:05
Bypass Absent
40289:06
289:06
BA01_x:06
Bypass Overvoltage
40289:07
289:07
BA01_x:07
Bypass Undervoltage
40289:08
289:08
BA01_x:08
Bypass Frequency Error
40289:09
289:09
BA01_x:09
Byp Phase Rotation Error
40289:10
289:10
BA01_x:10
Bypass SCR Failure
40290:00
290:00
BA02_x:00
Bypass Off
40290:01
290:01
BA02_x:01
Bypass Off Via Display
40290:02
290:02
BA02_x:02
Load On Bypass
40290:03
290:03
BA02_x:03
Bypass Overtemperature
40290:04
290:04
BA02_x:04
Rectifier Off
40290:05
290:05
BA02_x:05
Rectifier Off Via Display
40290:06
290:06
BA02_x:06
Rectifier Block
40290:07
290:07
BA02_x:07
Rectifier Current Limit
40290:08
290:08
BA02_x:08
Rectifier Overtemperature
40290:09
290:09
BA02_x:09
Rectifier Fuse Failure
40290:10
290:10
BA02_x:10
Inverter Off
40291:00
291:00
BA03_x:00
Inverter Off Via Display
40291:01
291:01
BA03_x:01
Inverter Block
40291:02
291:02
BA03_x:02
Inverter Current Limit
40291:03
291:03
BA03_x:03
Inverter Overtemperature
40291:04
291:04
BA03_x:04
Inverter Non Sync
40291:05
291:05
BA03_x:05
Inverter Overvoltage
40291:06
291:06
BA03_x:06
Inverter Undervoltage
40291:07
291:07
BA03_x:07
Liebert Monitoring Group – Development
Page 99 of 149
Page 100
Revision B.33 2/25/2011
SiteScan Availability
Modbus Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Inverter Fuse Failure
40291:08
291:08
BA03_x:08
Output Overvoltage
40291:09
291:09
BA03_x:09
Output Undervoltage
40291:10
291:10
BA03_x:10
Output No Voltage
40292:00
292:00
BA04_x:00
Output Waveform Error
40292:01
292:01
BA04_x:01
Inverter Frequency Error
40292:02
292:02
BA04_x:02
Inverter Parallel Error
40292:03
292:03
BA04_x:03
Contactor Failure
40292:04
292:04
BA04_x:04
Battery Test
40292:05
292:05
BA04_x:05
Battery Test Failed
40292:06
292:06
BA04_x:06
Battery On Load
40292:07
292:07
BA04_x:07
Battery End of Discharge
40292:08
292:08
BA04_x:08
Boost Time Expired
40292:09
292:09
BA04_x:09
DC Slow Overvoltage
40292:10
292:10
BA04_x:10
DC Undervoltage
40293:00
293:00
BA05_x:00
Battery Fuse Failure
40293:01
293:01
BA05_x:01
DC Fast Overvoltage
40293:02
293:02
BA05_x:02
Transfer Count Block
40293:03
293:03
BA05_x:03
Overload Shutdown
40293:04
293:04
BA05_x:04
Overtemperature SD
40293:05
293:05
BA05_x:05
Emergency Stop
40293:06
293:06
BA05_x:06
Overload Present
40293:07
293:07
BA05_x:07
Overload Shutdown TO
40293:08
293:08
BA05_x:08
Bad EEPROM
40293:09
293:09
BA05_x:09
Error LRC Par P1
40293:10
293:10
BA05_x:10
Error LRC Par P2
Error LRC Par P3
Error LRC Alarm History
Error LRC Event History
Internal Battery Low
Error LRC Table
Error LRC Panel
Can Bus No Response
Battery Ground Fault
Back Feed Fault
Liebert Monitoring Group – Development
Page 100 of 149
Loading...