Liebert Type SS, SAD Hybrid Advantage, PanelGuard Extension, LPM, LM User Manual

...
Surge Protection For Business-Critical Continuity
Interceptor II, SAD Hybrid Advantage, Type SS, LM, AccuVar, PowerSure LPM/LPL Series, ATF Series, PanelGuard Extension, AccuGuide Products
Installation, Operation and Maintenance Manual
Surge Suppression Systems
LIEBERT SURGE PROTECTIVE DEVICE
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
TABLE OF CONTENTS
UNPACKING AND INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Unpacking and Preliminary Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Handling Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Storage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Location Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Door Closing Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Warnings Defi ned . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Voltage Ratings and Power Source Confi gurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Parallel Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Voltage Ratings and Power Source Confi gurations (Chart) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Typical Parallel Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
System Grounding and Bonding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
SPD Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
TROUBLESHOOTING / SERVICING / MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Corrective Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Preventative Maintenance (Inspection and Cleaning) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
PRODUCT INSTALLATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Typical Parallel Installation – Type SI, H, SS, LM, ACV, AII, LPM, & LPL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Active Tracking Filter – Type F Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
PanelGuard Series - Type LPGE Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
AccuGuide Series – Type ACG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
DIMENSIONAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Interceptor II Series – Type SI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Hybrid Advantage Series – Type H . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
AccuVar Series - Type ACV & AII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Active Tracking Filter Series – Type F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
SS Series – Type SS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
LM Series – Type LM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
PowerSure Medium Exposure Series – Type LPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
PowerSure Low Exposure Series – Type LPL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
PanelGuard Series - Type LPGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
EXAMPLE INSTALLATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
WARRANTY INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
10 Year Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5 Year Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Installation, Operation and Maintenance Manual 1 Liebert TVSS Units SL-22085 Rev 2, 11/2006
INSTALLATION INSTRUCTIONS
The Liebert Surge Protective Devices (SPDs) are high quality, high energy surge current diversion systems designed to protect sensitive equipment from damaging transient voltage surges. Proper installation is required for maximum system performance.
UNPACKING AND INSTALLATION
Unpacking and Preliminary Inspection
1. Inspect the shipping crate(s) for damage or signs of mishandling before unpacking the unit.
2. Remove any securing bands and cardboard packing and inspect the unit for any obvious shipping damages.
3. If any damage as a result of shipping is observed, immediately fi le a claim with the shipping agency and forward a copy to your local Liebert Sales Representative.
Handling Considerations
Larger units are bolted to a shipping pallet to facilitate handling by forklift or pallet jack. Check the size and weight. Refer to the cabinet data furnished with the unit.
Storage
The unit should be stored in a clean, dry environment. Storage temperature range is -55ºC (-67ºF) to +85ºC (+185ºF). Care should be taken to avoid condensation. All packing and shipping materials should be left intact until the unit is ready for fi nal installation. If the unit has been stored for an extended period of time, the unit should be cleaned and carefully inspected before placing into service.
Location Considerations Environment — The unit is designed for operation indoors in
ambient temperatures of -40ºC (-40ºF) to +60ºC (+140ºF) with a relative humidity of 0% to 95% (non-condensing).
The unit is provided in an industrial use enclosure, which is dust-tight and drip-tight and should not be installed in areas with excessive dust, corrosive vapors, fl ammable materials or explosive atmospheres.
Audible Noise — The audible noise of the unit is less than 40 dB at 5 feet, which allows its placement within almost any room if desired.
Service Clearances — Service clearance is needed for units with hinged doors on the front that are capable of being opened. Thirty-six inches (36 in/914 mm) minimum is recommended.
Surge Suppression Systems
The installer should perform the following steps to assure a quality installation. The entire installation manual should be read before starting installation. These instructions do not replace national or local electrical codes. Check applicable electrical codes to ensure compliance. Installation of the Liebert SPD system should only be performed by qualifi ed personnel.
EQUIPMENT PERFORMANCE!!
To maximize system performance locate unit as close as possible to protected circuit and keep inter­ connecting wiring less than 5 ft.
For optimum transient surge protection, coordinated surge suppression should be applied at the service entrance and all other electrical connections to the building (telephone, CATV, etc.), at known surge generating loads within the building (large motors, arc welders, switched capacitors, etc.), as well as at sensitive electronic loads (such as computers, electronic appliances, solid state motor drives, etc.). For interconnected electronic loads (such as by way of data cabling), transient surge suppression should also be applied to the interconnecting wiring (data cables).
Mounting — Unit is intended to be wall mounted. Refer to individual instruction sheet or unit submittal drawings for typical mounting dimensions and weight.
Warnings Defi ned
Danger: Indicates an imminently
hazardous situation that, if not avoided, will result in death or serious injury. This signal word is to be limited to the most extreme situations.
Warning: Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.
Caution: Indicates a potentially hazardous situation that, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
Installation, Operation and Maintenance Manual 2 Liebert TVSS Units SL-22085 Rev 2, 11/2006
ELECTRICAL CONNECTIONS
Surge Suppression Systems
All electrical connections should be installed by a qualifi ed (licensed) electrician only. All wiring must comply with the National Electrical Code (NEC) and applicable local codes.
VERIFY THAT ALL POWER CIRCUITS ARE
DE-ENERGIZED AND LOCKED OUT BEFORE
MAKING ELECTRICAL CONNECTIONS.
Voltage Ratings and Power Source Confi gurations
Before making connections to the unit, verify that the unit model number and nameplate voltage rating are appropriate for connection to the intended power source. See the chart on page 4 for voltage rating applications with typical power source confi gurations.
Parallel Connection (see Figures on page 5)
EQUIPMENT PERFORMANCE!!
For maximum system performance, the unit must be located as close to the protected circuit as practical to minimize interconnecting wiring length.
To reduce the wiring impedance to surge currents, it is recommended that the phase, neutral (if required), and ground conductors are twisted together and routed in the same raceway (conduit). Avoid any sharp bends in the conductors.
Wire Sizing — With parallel connection, the size of the wiring to the SPD unit is independent of the protected circuit’s ampacity. For suggested wire size refer to individual product sheet.
NEC Article 285-21(B) requires surge suppressor connecting conductors to be at least #14 copper or #12 aluminum.
Overcurrent Protection — The SPD unit conducts practically no current under normal operation and only conducts very short duration transient surge currents.
The following is from the National Electric Code 2002 Edition.
285.21 Connection. Where a TVSS is installed, it shall be connected as follows:
(A) Location.
(1) Service Supplied Building or Structure. The transient
voltage surge suppressor shall be connected on the load side of a service disconnect overcurrent device required in 230.91.
(2) Feeder Supplied Building or Structure. The transient
voltage surge suppressor shall be connected on the load side of the fi rst overcurrent device at the building or structure.
Exception to (1) and (2): Where the TVSS is also listed as a surge arrestor, the connection shall be as permitted by Article 280.
(3) Separately Derived System. The TVSS shall be
connected on the load side of the fi rst overcurrent device in a separately derived system.
Disconnect Switch (If Provided) — All SPD units must still be connected to the load side of the main service disconnect, or load side of a protected circuit’s disconnecting means.
Surge Voltage Ratings — To obtain the suppression voltage ratings (SVRs), as obtained by Underwriters Laboratory, Incorporated, in accordance with the Standard for Safety, Transient Voltage Surge Suppressors (TVSS), Standard 1449, Second Edition, dated August 15, 1996, marked on this product, the wire size listed for each product must be utilized to connect the unit to your facilities’ power grid. Connections made with conductors other than the wire size listed may result in different SVRs.
Circuit Ampacity Limitations — Representative samples of these products have been investigated by Underwriters Laboratories, Incorporated to withstand, without exposing live circuits or components at system voltages and fault currents ranging from 14,000 AIC up to 200,000 AIC, as described in the Standard for Safety, Transient Voltage Surge Suppressor (TVSS), Standard 1449, Second Edition, dated August 15, 1996. Verify each products fault current rating on the individual installation pages that follow.
Installation, Operation and Maintenance Manual 3 Liebert TVSS Units SL-22085 Rev 2, 11/2006
Source Confi gurations
Single Phase L-N, 2 W + G
Single Phase L-L, 2 W + G
Single Phase, 3 W + G
Three Phase Delta, 3 W + G
Three Phase Delta Hi Leg, 4 W + G
L
N
G
L1
L2
G
L1
N
L2
G
Surge Suppression Systems
VOLTAGE RATINGS AND POWER SOURCE CONFIGURATIONS
Nominal Operating Voltage
L-N L-G L-L
100 100 N/A
L
110 110 N/A
120 120 N/A
N
230 230 N/A
277 277 N/A
G
347 347 N/A
N/A 208 208
L1
N/A 240 240
N/A 400 400
L2
N/A 480 480
G
N/A 600 600
120 120 208, 240
L1
240, 277 240, 277 480
N
L2
347 347 600
G
N/A 208 208
A
B
C
GG
B
N/A 240 240
N/A 380 380
N/A 400 400
N/A 415 415
N/A 480 480
N/A 600 600 580 L-L
120/240/120 120/240/120 240 150 L-N 240N
Maximum Continuous
150 L-N
150 L-N
150 L-N
275 L-N
320 L-N
420 L-N
130 L-L
150 L-L
275 L-L
275 L-L
420 L-L
150 L-N 120S
320 L-N
420 L-N
250 L-L 208D
320 L-L
580 L-L
580 L-L
580 L-L
580 L-L
Model Voltage Code
(Found in part number)
120 N or 120-
120 N or 120-
120 N or 120-
230 N or 230-
277 N or 277-
347 N or 347-
208L or 208-
240L or 240-
400L or 400-
480L or 480-
600L or 600-
240S
347S
240D
400D
400D
400D
480D
600D
A N G
Three Phase Wye, 4 W + G
C
A
N
B C
G
Three Phase Wye, 3 W + G No Neutral
A
B C G
240/480/240 240/480/240 480 250 L-N
120 120 208
127 127 220
220 220 380
230 230 400
254 254 440
277 277 480
347 347 600
N/A 120 208
N/A 127 220
N/A 220 380
N/A 230 400
N/A 254 440
N/A 277 480
N/A 347 600
150 L-N
150 L-N
320 L-N
320 L-N
320 L-N
320 L-N
420 L-N
150 L-G
150 L-G
320 L-G
320 L-G
320 L-G
320 L-G
420 L-G
480H
120Y
127Y
230Y
230Y
254Y
277Y
347Y
120X
127X
230X
230X
254X
277X
347X
Installation, Operation and Maintenance Manual 4 Liebert TVSS Units SL-22085 Rev 2, 11/2006
Note 1: For other voltages or source confi gurations, consult factory.
Surge Suppression Systems
Typical Parallel Connections (without Internal Rotary Disconnect)
Ground
Phases
Neutral
To
Protected
Loads
Protected
Panel
Wire should be less than 5 feet
and straight
as possible
Neutral
Phase(s)
Transient
Ground
Safety
Ground
Liebert
Surge
Protective
Device
Typical Parallel Connections (with Internal Rotary Disconnect)
Ground
Protected
Panel
Phases
Neutral
Wire should be
less than 5 feet
and straight
as possible
Rotar y
Disconnect
Neutral
Phase(s)
Transient
Ground
Safety
Ground
Liebert
Surge
Protective
Device
To
Protected
Loads
Installation, Operation and Maintenance Manual 5 Liebert TVSS Units SL-22085 Rev 2, 11/2006
System Grounding and Bonding
The performance and safety of any SPD system is dependent on proper grounding and bonding. Grounding is required for safety. Correct implementation also enhances equipment performance. Incorrect grounding can reduce or impede the SPD’s operation.
All electrical circuits to the SPD must include an equipment­grounding conductor as required by the NEC and local codes.
An insulated grounding conductor is required in addition to any metallic raceway, which may be used as a grounding conductor. For parallel-connected SPDs, the grounding conductor should be the same wire size as the associated power conductors. Grounding conductors must be routed with the associated power conductors in the same raceway (conduit).
When metallic raceways are used, adequate electrical continuity must be maintained at all raceway connections, particularly raceway terminations to the electrical enclosures.
The use of isolating bushings or other means to interrupt a metallic conduit run is a potential safety hazard and is not recommended.
Grounding Electrode — Surge protective devices do not
discharge all surges to ground (earth). Surge protective devices divert the surge current back to its source to complete the electrical circuit.
In the case of lightning whose potential is developed with respect to the earth, the SPD diverts the surge current to the grounding electrode (earth connection). However, for most transient surges that are developed by switching loads, the SPD diverts the surge current back to its source without involving the grounding electrode.
For proper SPD performance, the service entrance grounding electrode system must comply with the NEC by having all available electrodes (building steel, metal water pipe, driven rods, concrete encased electrodes, etc.) properly bonded together and connected to the power system grounding.
The use of a separate grounding electrode to ground the SPD defeats the effectiveness of the SPD, is a potential safety hazard, may cause equipment damage, is an NEC violation (reference NEC 250-51 and 250-54), and is not recommended.
Surge Suppression Systems
FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IF PROVIDED), MUST BE RELIABLY CONNECTED TO THE NEUTRAL OF THE SOURCE. FAILURE TO PROVIDE A RELIABLE NEUTRAL CONNECTION MAY RESULT IN MODULE FAILURE!
SPD Monitoring External Status Indicators — These indicators provide a
summary of the status of the surge SPD module. For normal conditions, the green “OK” LED is illuminated and the red “Service” LED is extinguished. If the surge SPD module requires replacement, the green “OK” LED is turned off and the red “Service” LED illuminated.
Summary Alarm Contact (if applicable) — Summary alarm Form C (1 N.O. and 1 N.C.) relay contacts may be provided for remote indication of the failed surge SPD module.
Contacts are rated 5 amps at 250 VAC maximum with a power factor of 1.0. For units with Summary Alarm Contacts, access to the contacts are typically provided via contact terminals located on the printed circuit board mounted on the inside of the unit’s cover.
Transient Counter (if applicable) – Transient counters are provided for transient voltage surge monitoring. The counter totalizes surges monitored since the last counter reset.
The transient counter monitors line transient voltages. The circuit counts all surges that deviate from the line sine wave. The factory setting is 30% over nominal line voltage. Other settings include 50%, 70%, and 100%.
Swell Counter (if applicable) — The swell counter monitors line to line & line to neutral voltages. It is factory set to record whenever the peak voltage on any normal mode exceeds the nominal voltage of the TVSS for more than 10ms. This counter records temporary line over voltages that may result from utility switching, line regulation problems, etc.
Audible Alarm (if applicable) — If the surge SPD module requires replacement, an audible alarm is activated to draw attention to the fact that repair service is required to restore the system to normal operation. An audible alarm disable is provided to silence the alarm. The system will automatically reset itself after repair. The audible alarm switch and “Service” LED can be tested by activating the “Test” switch on the system monitor panel. For information on the AccuVar Series Alarm, see page 16.
Installation, Operation and Maintenance Manual 6 Liebert TVSS Units SL-22085 Rev 2, 11/2006
Surge Suppression Systems
Troubleshooting / Servicing / Maintenance
Troubleshooting
If status failure indication occurs or Form C relay has changed states, a qualifi ed electrician shall fi rst determine if the systems voltage and proper phasing exists.
If the SPD remains in an alarm condition once the electrician is satisfi ed that the electrical system and its connections are normal, the unit should be repaired. At this point consult the factory, having available the following information:
• Unit identifi cation number – (refers to the model and serial numbers detailed on the data label and is located on the front or upper left [hinge] side of the enclosure.)
• Nature of problem – (including status of all status indicators and alarms).
Servicing
ONLY QUALIFIED PERSONNEL SHOULD PERFORM MAINTENANCE ON THE SYSTEM.
HAZARDOUS VOLTAGES ARE PRESENT INSIDE THE UNIT DURING NORMAL OPERATIONS.
ELECTRICAL SAFETY PRE-CAUTIONS MUST BE FOLLOWED WHEN SERVICING THIS UNIT.
TO PREVENT RISK OF ELECTRICAL SHOCK, TURN OFF AND LOCK OUT ALL POWER SOURCES TO THE UNIT BEFORE SERVICING UNIT.
(For servicing assistance, contact your local Liebert Sales Representative or Liebert at 800-288-6169 or 607-724-2484.)
Corrective Maintenance
The Liebert SPD is designed for years of trouble-free operation. However, even the most reliable equipment may fail under abnormal conditions.
Diagnostic indicators are provided to indicate when the unit needs replacement (see individual SPD operation of this manual for details). To ensure continuity of surge protection, failed units should be replaced at the earliest convenient service opportunity.
When replacing surge modules, other components should be inspected for damage and replaced if necessary. Standard electrical troubleshooting procedures should be used to isolate problems other than failed surge current diverter modules.
When replacing components, for continued proper operation and safety, replace only with identically rated components. Please contact factory for information on replacement parts.
Preventative Maintenance (Inspection and Cleaning)
Periodic system inspections, cleaning, and connection checks are recommended to ensure reliable system performance and continued surge transient protection.
It is diffi cult to establish a schedule for preventative maintenance since conditions vary from site to site. Inspections for failed surge modules using available diagnostics should be done routinely (weekly or monthly).
Installation, Operation and Maintenance Manual 7 Liebert TVSS Units SL-22085 Rev 2, 11/2006
Interceptor II Series
Type SI
Typical Parallel Installations
Surge Protective Devices (SPD)
Hybrid Advantage Series
Typ e H
Surge Suppression Systems
Type SS Series Type LM Series
PowerSure Medium Exposure Series AccuVar Series PowerSure Low Exposure Series
Type LPM Type ACV & AII Type LPL
Installation Instructions
1. Insure that all power is removed before beginning installation. A qualifi ed licensed electrician shall install all electrical connections.
2. The SPD is provided in the enclosure type listed below. NEMA 12 enclosures are suitable for use in indoor installations. NEMA 3R, NEMA 4 or NEMA 4X enclosures are suitable for use in indoor or outdoor installations.
SPD Standard Enclosure Optional Enclosures SPD Standard Enclosure Optional Enclosures Type SI NEMA 4 NEMA 4X Type ACV/AII NEMA 4X N/A Type H NEMA 12 NEMA 3R, 4, 4X Type LPM NEMA 12 NEMA 3R, 4, 4X Type SS NEMA 4X N/A Type LPL ABS Plastic 94V-0 NEMA 1 Type LM NEMA 12 NEMA 3R, 4, 4X
3. Determine where the SPD is to be mounted, allowing for minimum length of wire between itself and the input power terminals of the service panel. Punch or cut the proper hole size in the side of the SPD closest to the knockout to be utilized in the service panel. Drill mounting holes in wall at location picked for SPD next to service panel using mounting dimensions shown in the tables on the “Dimensional Information” pages in this manual. Mount surge suppressor using the hardware listed.
SPD Mounting Hardware SPD Mounting Hardware
Type SI (Page 15) 3/8" Type ACV/AII (Page 16) #8 Type H (Page 16) 3/8" Type LPM (Page 20) #10 Type SS (Page 18) 1/4" Type LPL (Page 21) #6 Type LM (Page 19) 1/4"
4. The SPD has obtained the short circuit current rating shown below.
SPD Short Circuit Current Rating SPD Short Circuit Current Rating
Type SI 200,000 Symmetrical Amperes Type ACV/AII 200,000 Symmetrical Amperes Type H 200,000 Symmetrical Amperes Type LPM 65,000 Symmetrical Amperes Type SS 65,000 Symmetrical Amperes Type LPL 14,000 Symmetrical Amperes Type LM 200,000 Symmetrical Amperes
Circuit Ampacity Limitations. Representative samples of these products have been investigated by Underwriters Laboratories, Incorporated to withstand, without exposing live circuits or components at system voltages and fault currents of up to the rating shown above, as described in the Standard for Safety, Transient Voltage Surge Suppressor (TVSS), Standard 1449, Second Edition, dated August 15, 1996.
Installation, Operation and Maintenance Manual 8 Liebert TVSS Units SL-22085 Rev 2, 11/2006
Loading...
+ 21 hidden pages