Liebert Integrated Secured Protection User Manual

Page 1
Little Glass House
Integrated Secured Protection
for Network Equipment
USER MANUAL
English
Page 2
SAFETY INSTRUCTIONS ...................................................................................................................................3
GLOSSARY OF SYMBOLS.................................................................................................................................3
INTRODUCTION .................................................................................................................................................4
UPS SUPPORT................................................................................................................................................5
INSTALLATION...................................................................................................................................................5
UNLOADING AND INSPECTION .....................................................................................................................5
LOCATION.......................................................................................................................................................5
INSTALLATION CONNECTIONS.....................................................................................................................6
INSTALLING CUSTOMER EQUIPMENT.......................................................................................................... 6
START-UP.......................................................................................................................................................7
OPERATION .......................................................................................................................................................8
ENVIRONMENTAL CONTROL MODULE (ECM) & UNINTERRUPTIBLE AIR SUPPLY™ (UAS)......................8
FORCED AIR COOLING (FAC)........................................................................................................................8
SITENET® INTEGRATOR®.............................................................................................................................8
SENSOR OPTIONS.........................................................................................................................................9
FILTER CLEANING ........................................................................................................................................10
ECM REPLACEMENT....................................................................................................................................10
UPS REPLACEMENT ....................................................................................................................................10
FORCED AIR COOLING (FAC) PERFORMANCE DATA (WITH 30PPI FILTER)............................................11
ENVIRONMENTAL COOLING MODULE (ECM) PERFORMANCE DATA.......................................................11
FIXED SERVICE CONNECTION (AMPS).......................................................................................................12
MAX. AVAILABLE CUSTOMER EQUIPMENT AMPS.....................................................................................12
FULL LOAD AMP DRAW (230V - 50HZ).........................................................................................................12
Model Number Breakdown
RD 78 38 M D E K
Enclosure
Rack Width RD=24" Rack HD=19" Rack
Enclosure
Height/ Depth
78" Height 72" Height
38" Depth 34" Depth (Nominal)
Main or
Cluster
M = Main
C = Cluster
Primary Cooling
System A = FAC-190 B = FAC-360 C = ECM-42 D = ECM-62 E = N/A F = ECM-80
UPS
Rack-Mount 0 = None A = N/A B = N/A C = GXT-1000 D = N/A E = GXT-1500 F = N/A G = GXT-2000
Input Power
K = 120V/60Hz/1PH S = 230V/50Hz/1PH
2
Page 3
SAVE THESE IMPORTANT SAFETY INSTRUCTIONS
WARNING: Do not attempt to service this product yourself. Opening or removing
covers will risk exposure to dangerous voltages. Refer all servicing to qualified service
personnel.
1. SAVE THESE INSTRUCTIONS. THIS MANUAL CONTAINS IMPORTANT SAFETY INSTRUCTIONS. Read all safety and operating instructions before operating the Little Glass House (LGH). Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions.
CONSERVER CES INSTRUCTIONS. CETTE NOTICE CONTIENT DES INSTRUCTIONS IMPORTANTES CONCERNANT LA SÉCURITÉ.
2. This product is designed for Commercial/Industrial use only. It is not intended for use with life support and other designated “critical” devices. Maximum load must not exceed that shown on the LGH rating label. If uncertain, consult your dealer. See Limited Warranty.
3. The LGH must be permanently connected to the input AC/mains supply and protected by a suitable circuit breaker or fuse.
4. The LGH must be powered from a suitable single phase supply rated in accordance with the equipment data plate, and must be suitably grounded/earthed.
5. The utility/mains supply socket or means of isolation must be within 2 meters of the equipment and accessible to the operator.
6. This equipment complies with the requirements of the EMC Directive 89/336/EEC and the published technical standards. Continued compliance requires installation in accordance with these instructions and the use of manufacturer approved accessories with output cables not exceeding 10 meters (30 ft.) in length. Use a shielded cable for the external communications interface.
7. Route power supply cords so they are not walked on or pinched.
8. Never block or insert any object into the ventilation holes or other openings. Maintain a minimum clearance of 305 mm (12 inches) in front and rear of the LGH for proper air flow and cooling.
9. Operate the LGH in an indoor environment only with an ambient temperature range of 0° C to +40° C (32° F to +104° F). Install it in a clean environment, free from moisture, flammable liquids, gasses, or corrosive substances.
10. Storing magnetic media on top of the LGH may result in data loss or corruption.
11. Do not stand beverage containers on the LGH.
12. This equipment can be operated by individuals without previous training.
13. Qualified Personnel should be consulted
for the following conditions:
- Power cable is damaged
- Liquid spilled into product
- LGH does not operate when operating instructions have been followed.

Glossary of Symbols

Indicates weight
Indicates a Ground/Earth connection
Indicates a Warning - Hazardous Voltage Present
Consult the user’s manual for additional information
Indicates Caution: Note the accompanying instruction
Indicates alternating current
3
Page 4

INTRODUCTION

Your Liebert Little Glass House™ (LGH) will provide a secure controlled environment in a single factory assembled enclosure. The integrated/matched models are designed to control the environment and provide smooth reliable power so that your sensitive computer and network equipment will provide the reliable performance you depend upon for your business operations.
The Little Glass House is completely factory assembled and tested, ready for you to install your equipment and plug the unit into a 120 V~/ 60 Hz or 230 V~/ 50 Hz dedicated outlet. For 60 Hz models, the required power receptacle/socket may be 15, 20, or 30 Amps, depending on your selected LGH. Models with 60 Hz ECM-80 uses two input power connections, with one 20 Amp plug for the ECM­80 and the other plug either 15 or 20 Amps depending on the UPS model. For 50 Hz models, a power cord is included for connection to a customer supplied plug.
Refer to drawings and tables in this manual for dimensions, environmental performance data, and input power requirements. Refer to the separate UPS manual for UPS performance details.
ENCLOSURE
The enclosure can accommodate shelf mounted or rack mounted equipment, on either 19 or 24 inch punched rails (per EIA-310). The 19 inch rack cabinets are 25 inches (635 mm) wide. Cabinets with 24 inch racks are 30 inches (765 mm) wide. The enclosures can be nominal 72 or 78 inches (1830 or 1980 mm) high, and 34 or 38 inches (865 or 965 mm) deep. The unit is mounted on casters and leveling feet. Interior insulation is provided in models with Environmental Control Module (ECM) cooling.
A solid panel (metal) front door is standard. A smoked plastic front window is available to maintain enclosure security while allowing you to monitor equipment status. The rear door provides convenient access to customer wiring. Two horizontal cable entrance raceways are provided. An optional internal cable management raceway (vertical) is available. Both doors have a key lock and a four point latch.
ENVIRONMENTAL CONTROL
The Uninterruptible Air Supply™ (UAS) consists of an Environmental Control Module (ECM) and a Back-up Cooling Fan. The ECM is normally sized to match the capacity of the UPS module plus heat transmitted into the LGH. Three ECM modules, ECM-42, ECM-62, and ECM-80 are available. Air is controlled and circulated within the enclosure. Outside (ambient) air is used to remove heat from the enclosure through the air cooled condenser. Two-speed fans are used to provide quiet operation. At rated maximum ambient conditions, the temperature inside the enclosure will be from 70° to 95°F (21 to 35°C), depending on the electronics load. If the internal cabinet temperature reaches 100°F (38°C) -- for example, during a power failure -- the Back-up Cooling Fan operated on UPS battery power will flow filtered ambient air through the enclosure.
The Back-up Cooling Fan is standard on UAS models. All UAS or ECM models require a clearance of 12 inches (305 mm) both on top and rear of the LGH for proper airflow. The 50 Hz back-up cooling options have an On/Off (O/I) switch located in the inlet channel to the ECM condenser coil. This switch should be on during normal operation.
If environmental control as previously described is not required, Forced Air Cooling (FAC) is available. Filtered ambient air is drawn through the enclosure from the bottom front to the top rear. A two-speed fan is controlled by a thermostat factory set at 80°F (27°C), which measures air entering the unit. The two-speed fan design provides quiet low-speed operation below the thermostat set point. A single fan (nominally rated at 190 CFM - 323 CMH) or dual fans (nominally rated at 360 CFM - 611 CMH) can be provided. A clearance of 12 inches (305 mm) is required both on top and rear of the LGH for FAC models.
4
Page 5
UPS SUPPORT
The integrated/matched models include an uninterruptible power supply (UPS) module to provide surge suppression, regulated voltage and frequency, and battery backed operating time. This will allow you to perform a controlled computer shutdown in the event of a utility/mains power failure. The UPS supplied is a rackmount model factory installed in the rack rails and supported by brackets. UPS models available include the on-line Liebert UPStation GXT in 1000, 1500, or 2000 VA capacity. Refer to the separate UPS manual for more details.
EQUIPMENT MOUNTING OPTIONS
Optional equipment mounting hardware is available including a fixed shelf, a pullout shelf, 19 inch to 24 inch rack rail adapters, threaded adapters, adjustable position rack rails and Compaq® adapters. Each optional kit is supplied with installation hardware.
CLUSTERED CONFIGURATIONS
For applications requiring more than one enclosure, an optional Cluster Enclosure is available. In addition to providing more space for electronic equipment, this configuration allows cabinets to be connected side-by-side so that an ECM, FAC, or UPS can serve more than one cabinet. Refer to separate installation instructions provided with the cluster cabinet.
HEAT REJECTION DUCT
For applications in confined spaces (equipment rooms or closets), an optional Heat Rejection Duct is available to connect the Little Glass House to a ducted ventilation system. Refer to drawing on page 19 in this manual for details.

INSTALLATION

UNLOADING AND INSPECTION
Refer to drawing on page 13 for dimensions, weight, and connection locations for your model.
Carefully unload your new Little Glass House™ (LGH) from the box and from the pallet. Note the unit weight for your model. Use at least two people for safe handling.
Unloading Procedure:
1. Cut bands. Use caution.
2. Remove cardboard and plastic.
3. Remove two 2 X 4’s from sides of unit.
4. Remove one 2 X 6 from rear of unit.
5. Remove four lag bolts from front of skid.
6. Remove one 2 X 6 from front of unit.
7. Slide 4 X 4 runner from under front of skid.
8. Move unit forward until skid and unit tilt.
9. Roll unit off front of skid.
Open the doors and locate the keys, which are shipped inside the enclosure. The front and rear locks use the same key. To open either door, turn key clockwise 1/8 turn to unlock, lift bottom of handle, then turn handle away from unit 1/4 turn to open.
Inspect exterior and interior for shipping damage. If any damage is noted, file a claim with the shipper and inform your Liebert supplier.
LOCATION
The unit should be located in a room where the ambient air is adequately ventilated for the peripheral equipment (printers, etc.) outside the LGH. The maximum ambient operating condition for 60 Hz units is 105°F (40°C). For 50 Hz units, maximum ambient temperature is 100°F (38°C). Place unit on a level surface, or use leveling feet to level the unit.
Note the dimensions for your selected Little Glass House model to determine space required. Units with UAS or ECM require a clearance of 12 inches (305 mm) both on top and rear of the LGH. Units with Forced Air Cooling (FAC) require 12 inches (305 mm) of top and rear clearance. Air is drawn through the front intake louver and discharged at the rear. Do not block air flow at the front or the rear. The optional Heat Rejection Duct will require additional rear clearance.
5
Page 6
ALCOVE INSTALLATION
ECM ECM/UAS FAC
Rear 12" 12" 12"
Top 12" 12" 12"
Sides 0" 0" 0"
Bottom Non-Restricted
The unit can be rolled forward on casters for easy access to Liebert and customer wiring at the rear of the unit. To open the front door, clearance required depends on the size of your unit. No side clearance is needed.
For applications requiring more than one enclosure, an optional Cluster Enclosure is available. In addition to providing more space for electronic equipment, this configuration allows cabinets to be connected side-by-side so that an ECM, FAC, or UPS can serve more than one cabinet.
INSTALLATION CONNECTIONS
The Little Glass House is a self-contained unit. The only required connection is for electric power. For 60 Hz models, the power cord is 9 (2.7 m) feet long and has a NEMA 120 V~ plug, sized for current (Amps) based on equipment specified when ordered. For 50 Hz models, a power cord is included for connection to a customer supplied plug. The 60 Hz ECM-80 model uses two input power connections, with one 20 Amp plug for the ECM-80 and the other plug either 15 or 20 Amps depending on the UPS model. Refer to table on page 11. The LGH and its protected equipment should be on a dedicated circuit and circuit breaker.
Do not defeat ground/earth connections between the utility/mains outlet and the Little Glass House. All plug receptacles/sockets in the vicinity of where the LGH will be used must be a ground/earth type and grounded/earthed with an insulated ground/earth conductor of identical size, insulation material, and thickness to the grounded/earthed and ungrounded/earthed supply conductors which is grounded/earthed to ground/earth at the service equipment or separately derived source.
NOTE: The utility/mains output must have the neutral and ground/earth bonded, per the National Electrical Code, to prevent damage to the UPS. Damage related to faulty utility/mains wiring is not covered by Liebert warranty.
Contacts are provided to annunciate two alarms: High Temperature (100°F - 38°C internal, Back-
up Cooling Fan operating) and Dirty Air Filter (filter is clogged and requires cleaning). Customer connection is two compression lug terminals inside the rear of the unit. These normally open contacts are rated for 40 milliAmps at 30 volts maximum (Class 2 wiring).
A contact is provided on the rear of the ECM to indicate power to the compressor (Compressor on/off). This normally open contact is rated for
0.5 Amp at 120 V~.
A control contact is provided inside the ECM (under access plate at top left rear) for remote shutdown/ startup. To use, replace jumper on 37 and 38 with a normally open non-powered switch, rated for 5 Amps at 120 V~.
To allow communications between the UPS and a LAN server or other computer system, the available UPStation GXT is equipped with an RS-232 interface port. Other UPS communication options are available, including SNMP. Refer to the separate UPS manual for details.
The optional SiteNet™ Integrator is a separate rackmount unit which communicates status of the UPS and Little Glass House (including temperature/humidity and several contact closures) in SNMP protocol to a network management system.
No plumbing connections are required as ECM condensate is evaporated into the heat rejection airstream. A condensate drain tube (3/8 inch O.D. copper) is provided with ECM, but a customer connection is not necessary. The drain connection may need to be used in exceptional situations, such as if a door is left open for longer than 15 minutes while the ECM is operating.
INSTALLING CUSTOMER EQUIPMENT
The Little Glass House can accommodate rack mounted or freestanding computer and network equipment. The unit contains 19 or 24 inch punched rack rails (per EIA 310), depending on model selected. Rack rails are provided at the front and rear of the enclosure. Mounting hardware available from your Liebert representative includes a fixed shelf, a pullout shelf, 19 inch to 24 inch rack rail adapters, threaded adapters, adjustable position rack rails and Compaq® adapters. Each optional kit is supplied with installation hardware.
To maintain unit center of gravity as low as possible, install customer equipment from the
6
Page 7
bottom up, starting with the heavier units. Leave available space (if any) at the top of the enclosure.
CAUTION: To avoid tipping the unit when it is being moved, push slowly on the lower part of the enclosure. After customer equipment is installed, the Little Glass House may have a high center of gravity.
The LGH can support an electrical load based on the UPS capacity. For integrated/matched models, the Environmental Control Module is normally sized to match the capacity of the UPS plus heat transmitted into the enclosure. A larger UPS can be supplied for longer battery time. For 60 Hz units without a UPS, the customer specifies maximum Amp load to determine proper NEMA power plug rating.
NOTE: To charge the UPS batteries before using the unit, you can apply power to the UPS module while you are installing your equipment. Install your critical equipment in the Little Glass House. Use the two vertical channels at the rear of the unit for routing customer wiring. Power and communication wiring should be kept separate as much as possible.
The optional power strip includes a circuit breaker. The 60 Hz model includes 10 5-15R 15 Amp, 120 V~ receptacles/sockets. The 50 Hz model includes 10 CEE22 (IEC320) 10 Amp, 250 V~ receptacles/sockets. The power strip is protected by the UPS if a UPS is included. As viewed from the rear, the ten power outlets are on the right side. Power wiring is intended to be routed on the right. Communication and control wiring should be routed to the left side.
Provide enough length on customer supplied cables to allow unit to be rolled forward for rear access. Remember to connect a cable to the Little Glass House alarm contacts if required for your installation. Route customer wiring through the two horizontal cable entrance raceways. An optional internal cable management raceway (vertical) is available.
START-UP
Before applying power, make sure the computer equipment and power switches are in the OFF position. Plug the Little Glass House power cable into the customer provided receptacles/sockets. Be certain there are no obstructions (such as wires, conduit, or trash) to the front or sides of the ECM. Make sure all doors shut and seal properly. Roll the unit into final position according to the location section on page 4. If heat rejection duct option is included, be sure there are no loops or kinks in the duct.
Turn on the Environmental Control Module (ECM), or Forced Air Cooling system (FAC). Then turn on the UPS, if included. If UPS status indication is normal, turn on your computer and network equipment. The UPS will immediately supply regulated power. Battery back-up will be available after batteries are fully charged.
The 60Hz Environmental Control Module has a lighted power switch. The power switch for the 50 Hz models is the circuit breaker “B" on the electric service assembly. ECM temperature and capacity controls, including hot gas bypass, are factory set. The FAC models have a temperature switch factory set at 80°F (27°C), which measures air entering the unit. The front air filter requires periodic cleaning. CAUTION: To avoid excessive condensation, turn off the Environmental Control Module any time an LGH door will be open for more than 15 minutes.
The UPS module has user friendly controls and indicators. Refer to separate UPS manual for details of UPS operation and LED indicators. CAUTION: To maintain UPS battery capacity, do not store Little Glass House for more than 6 months without applying power.
Call your Liebert supplier if you have any questions or problems during the installation or operation of your Little Glass House.
7
Page 8

OPERATION

ENVIRONMENTAL CONTROL MODULE (ECM) & UNINTERRUPTIBLE AIR SUPPLY™ (UAS)
For integrated/matched models, the Environmental Control Module is normally sized to match the capacity of the UPS module and heat transmitted into the Little Glass House™. The module is located at the bottom of the enclosure. Internal air is conditioned and circulated within the enclosure. Outside (ambient) air is used to remove heat from the enclosure through the air cooled condenser. The outside air is drawn through a louver and filter at the bottom front of the unit and is discharged at the rear (near the bottom).
The lighted ON/OFF switch is located inside the front door, on the left side of the electrical panel on 60 Hz models. For 50 Hz models, use circuit breaker “B” of electrical service assembly for ECM On/Off.
At rated maximum ambient conditions, the temperature inside the enclosure will be from 70° to 95°F (21 to 35°C), depending on the electronics load. The two speed fans are factory set to operate at the lower speed for quiet operation when the outside air entering the condenser is below 80°F (27°C). The compressor in the Environmental Control Module will turn off if the internal cabinet temperature goes below 65°F (18°C).
The hot gas bypass valve is factory set so the compressor will operate nearly continuously for maximum compressor life. This valve modulates automatically to match compressor capacity to the present load. Consult factory if adjustment is desired.
In UAS systems, during an enclosure high temperature condition (100°F - 38°C) a separate Back-up Cooling Fan operated on UPS battery power (if included) will use filtered ambient air to cool the enclosure. This would occur only during a power failure or an Environmental Control Module failure. To annunciate a high temp condition, an alarm beeper sounds and the alarm contact closes (press Alarm Silence switch to turn off beeper). Outside air is drawn through a louver and filter at the bottom front of the unit and is discharged at the rear (near the top).
FORCED AIR COOLING (FAC)
Forced Air Cooling can be provided by a single fan (nominally rated at 190 CFM - 323 CMH), or by dual fans (nominally rated at 360 CFM - 611 CMH). The two-speed fans are activated by a temperature switch. Ambient air is drawn through the filter at the bottom front of the unit, and discharged at the top rear.
The ON/OFF control switch is located inside the front door, on the left side. The same control box includes the temperature switch factory set at 80°F (27°C), which measures air entering the unit. If the entering air temperature goes above 80°F (27°C), the fan speed switches from low to high.
UNINTERRUPTIBLE POWER SUPPLY (UPS)
The Little Glass House may be supplied with one of several Liebert UPS units, or with no UPS. For integrated/matched models, the UPS and ECM are normally sized with matched capacities. A larger UPS can be supplied for more battery time, but the connected electronics load should not exceed the ECM rating.
For LGH models supplied with a UPS, refer to the separate UPS manual for operation and specifications.
SITENET® INTEGRATOR®
Refer to the Integrator Electrical Connection Diagram on page 21 for specifics regarding installation.
The SiteNet Integrator is a separate rackmount unit that communicates status of the UPS and LGH. The option consists of a SiteNet Integrator module that is typically mounted in the top of the LGH cabinet.
The SiteNet Integrator is powered by one or two externally mounted power supplies. One is standard, the second is optional. These power supplies provide the 9VDC required to power the Integrator module. One supply will be plugged into the UPS or the UPS outlet strip located in the rear hinge side of the cabinet. The output cable is plugged into the SiteNet Integrator Power Supply Main input receptacle/socket. The (optional) second supply will be plugged into the electrical service power inlet in the lower rear of the LGH cabinet. The supply's output cable is plugged into the SiteNet Integrator Power Supply Aux input receptacle/socket.
8
Page 9
An optional UPS status communication cable is available that allows transmission of information between the UPS and the SiteNet Integrator. This cable will plug into the 25 pin D Type connector on the rear of the UPS marked DB­25P. The opposite end of the cable in plugged into the 9 pin D Type receptacle on the rear of the SiteNet Integrator marked UPS RS-232 DB­9P.
SENSOR OPTIONS
Door Ajar -- This option consists of two normally open switches that are mounted to the cabinet front and rear frame supports. The switches will indicate by the position of the doors (opened or closed) as determined by the status of the dry­contact inputs to which they are connected on the rear of the SiteNet Integrator.
Temperature and Humidity Sensors (Internal and External) -- The sensors allow monitoring
of temperature and humidity status by the SiteNet Integrator. The internal option is for installation inside the LGH cabinet and is supplied with a 12 foot (3.6 m) cord for connection between the temperature/humidity sensor and the SiteNet Integrator. Refer to the connection diagram for wiring specifics. The external option is supplied with a 30 foot (0.1 m) cord for monitoring of temperature humidity status outside the LGH cabinet. The sensor and connections for both options are identical.
Water Detect -- The water detect option includes a Liquitect (LT-400S) dry contact sensor mounted in the bottom of the LGH cabinet. The sensor is powered by a 24 VDC power supply mounted in the frame channel of the LGH cabinet. (Multiple options may share this same general power supply. The supply is rated for 1.6 Amps at 24 VDC). The water detector is connected to the dry-contact input on the rear of the SiteNet Integrator by a 30 foot two-conductor cable. The detector may be relocated outside the LGH cabinet by user discretion for external water detection.
Remote ECM On-Off Control -- This option allows on-off control of the ECM by the SiteNet Integrator. It consists of a 24 VDC Power Supply with Control Relay that is mounted in the frame channel of the LGH cabinet. The 24 VDC power supply may also be used to power other options. A black SJ two-conductor (black & red) cable is connected between the power supply relay normally open contacts and the ECM power terminal strip (terminals 37 & 38) in the
rear of the ECM. A two-conductor control cable is connected between the power supply terminal strips marked "Close to Energize Relay R1" and the Relay Output K1 terminal strip on the rear of the SiteNet Integrator. When the relay output contacts on the SiteNet Integrator close, the relay in the power supply is energized closing the normally open contacts and shorting between terminals 37 & 38 in the rear of the ECM. This will allow power to be applied to the ECM and cause the ECM to begin operation if the ECM On/Off switch is in the On position. Consequently, de-energizing the relay will allow the ECM to be turned off remotely by the SiteNet Integrator.
Smoke Detector Option -- A four-wire smoke detector with normally open contacts, heat sensor and sounder alarm is mounted in the top of the LGH cabinet. The smoke detector is power by a 24VDC power supply (*) mounted in the frame channel of the LGH cabinet. The power supply is normally powered from the UPS (if available), but may be powered from utility/mains by customer discretion. Power to the smoke detector is supplied by a two­conductor cable between the power supply and the smoke detector. A second two-conductor cable connects between the smoke detector and the Integrator dry-contact inputs. If smoke, flame, or high temperature change are detected, the normally open contacts of the smoke detector will close to provide alarm status to the Integrator. The smoke detector sounder alarm will also activate. This alarm can be silenced only by removing power from the smoke detector. This is accomplished by unplugging the smoke detector power supply. *The smoke detector power supply is a general purpose
supply that may be used to power any option requiring 24 VDC. Multiple options may share the same supply. The supply is rated for 1.6 Amps at 24 VDC.
All the above options are available factory installed with the order. The options are also available for field installation. Field installed options are shipped as kits containing the sensors with appropriate mounting hardware, cable, and cable restraint fixtures. Field installation requires hand tools for termination of control cables and routing of the cables.
All other standard alarm signals provided by the LGH (High Temp, Clogged Filter, Cooling Status) are also pre-wired for monitoring by the SiteNet Integrator.
9
Page 10
MAINTENANCE
CAUTION: To avoid tipping the unit when it is
being moved, push slowly on the lower part of the enclosure. After customer equipment is installed, the Little Glass House™ may have a high center of gravIty.
FILTER CLEANING NOTE: Inspect the air filter periodically to
determine the necessary cleaning interval based on conditions at your installation.
If the air filter becomes dirty and clogged, the alarm contact closes (no beeper alarm is sounded). The filter is behind the louver at the bottom of the front door. Remove two screws, pull up the filter, clean with mild soapy water, rinse, dry, and replace.
ECM REPLACEMENT
TO REMOVE THE ECM FOR FACTORY REPAIRS:
-Turn off power. Unplug Environmental Control Module from receptacle inside rear of the Little Glass House.
-Remove the screws retaining the access plate at top left rear of ECM. Remove the plate and tuck the ECM power cord and plug inside the opening to allow the ECM to pass beneath the UPS or mounted shelves. For models including a UPS, do not replace this access panel until after ECM has been removed.
-Models containing a 60 Hz ECM80 require the removal of the plug from the ECM power cord. Once removed the power cord strain relief may be loosened to allow the power cord to slide through when the ECM is withdrawn from the cabinet. Observe wiring polarity when reinstalling the plug on the replacement unit.
-If connected, remove customer wiring to ECM compressor power contact and/or remote shutdown/startup contact.
-Remove four screws retaining the front electrical panel. Pivot panel to the left. Cables are long enough to move the box out of the way so the Environmental Control Module can be pulled forward after removing four rack mount screws.
-Replace cable access cover on ECM. Package unit for return to Liebert.
-Install the replacement ECM.
UPS REPLACEMENT
To remove the UPS for factory repairs:
-Turn off power. Unplug UPS from receptacle
inside rear of the Little Glass House.
-Unplug the power strip, ECM or FAC controls,
and any other equipment plugged into the UPS.
-Disconnect any optional communication cables.
-Remove screws retaining the UPS.
-Remove the UPS from the front of the LGH.
-Install the replacement UPS.
PLUG WIRING
50 Hz 60 Hz
Line (L) Brown Black
Neutral (N) Blue White
Ground/Earth (G) Gold Gold
10
Page 11
FORCED AIR COOLING (FAC) PERFORMANCE DATA (WITH 30PPI FILTER)
# FANS
MODEL #
FAC-190 1 FAC-360 2

TABLES

AIRFLOW (w/Filter) SOUND LEVEL INPUT POWER (1PH)
HIGH
SPEED
190 CMF 112 CMH 360 CMF 212 CMH
LOW
SPEED
90 CMF
53 CMH 175 CMF 103 CMH
HIGH
SPEED
LOW
SPEED
61 dBa 47 dBa 0.5/15/15 0.5/15/15 59 dBa 49 dBa 1.0/15/15 1.0/15/15
FLA / WSA / OPD
120V/60Hz 220V/50Hz
ENVIRONMENTAL COOLING MODULE (ECM) PERFORMANCE DATA
RATED
NUMBER
ECM-42 4200/1230 2730/800 105F ECM-62 6200/1815 4095/1200 105F ECM-80 8000/2345 5800/1700 105F
CAPACITY BTUH/Watt BTUH/Watt 60Hz 50Hz U
SUPPORT
LOAD
RATED/MAX
41C 41C 41C
AMBIENT
100F 100F 100F
38C 38C 38C
HEIGHT
6 10.5/ 7 12.3/ 9 15.8/
DIMENSIONS
17.5/ 445
22/
560
22/
560
WIDTH
In/mm In/mm Rack In/mm
265 310 400
DEPTH
19 27/
685
24 27/
685
24 29/
735
TOTAL
HEAT REJ. BTUH/Watt
7625/
2235
11310/
3315
14605/
4280
INPUT POWER (1PH) WEIGHTMODEL
120V/60Hz 220V/50Hz
8/15/15 7/15/15 95/43 12/20/20 9/15/15 115/52 16/20/20
16/20/20
(lbs/Kg)
167/76
ECM Notes: Standard Offerings - All Systems
1. 60Hz: R-22 refrigerant / 50Hz: R-134A refrigerant
2. Two-Speed Operation - Switch low-high speed on ambient temperature external to LGH enclosure
3. Automatic Load Matching: Hot gas by-pass factor set for minimum capacity; by-pass will adjust to match supported loads
4. Condensate Re-evaporation & Removal: Drain connection only required if enclosure seal is violated.
11
Page 12
Electrical Service / Connection
The 60 Hz LGH is provided with a single NEMA plug and cord input power connection (except for ECM­80 systems).
60 Hz Systems with UPS - Service Connection
If a UPS is supplied, the system power rating and plug connection are fixed.
FIXED SERVICE CONNECTION (AMPS)
UPS-GXT (VA)Cooling
System
FAC-190 15 15 20 FAC-360 15 15 20 UAS/ECM-42 20 -- -­UAS/ECM-62 30 30 -­UAS/ECM-80* ECM-80 - 20 Amp / UPS-Load - 20 Amp
*LGH ECM-80 systems provided with separate
ECM & UPS power connections.
1000 1500 2000
60 Hz Systems with NO UPS - Service Connection Selection
If a UPS is not supplied, the system power rating and plug connection are customer selected based on the Cooling System and customer Amp load.
MAX. AVAILABLE CUSTOMER EQUIPMENT AMPS
(based on customer selected Service Connection)
SERVICE CONNECTIONCooling System
15 Amp 20 Amp 30 Amp FAC-190 11.5 15.5 23.5 FAC-360 11 15 23 ECM-42 only -- 8 16 UAS-42 -- 7 15 ECM-62 only -- -- 12 UAS-62 -- -- 10 UAS/ECM-80* -- -- --
*Power strip is rated for 15 Amp service
50 Hz Systems with NO UPS or WITH UPS - Full Load Amp Draw
The 50 Hz LGH is provided with a cord for input power connection; an appropriate plug is to be field supplied. Selection charts below are to be used to determine plug requirements per local codes.
FULL LOAD AMP DRAW (230V - 50Hz)
UPS-G (VA)Cooling System UPS
1000 1500 2000 FAC-190 .5 4.5 6.5 8.7 FAC-360 1 5 7 9.2 UAS/ECM-42E only 7 11 -- -­UAS/ECM-42E 7.5 11 -- -­UAS/ECM-62E only 9 13 15 -­UAS/ECM-62E 9 13 15 -­UAS/ECM-80E 9 13 15 17
Note: Power strip is rated for 10 Amp service
12
Page 13

DRAWINGS

13
Page 14
14151617181920
Page 15
Page 16
Page 17
Page 18
Page 19
Page 20
Page 21
200
400
600
800
1400
INTERNAL LOAD PER CABINET, WATTS
MINIMUM SPEED SET AT 2000 RPM
LGH RD/HD FORCED AIR CABINET TEMP. RISE
AT STANDARD AIR CONDITIONS
TEMP. RISE PER CABINET, DEG. F
40
30
FAC-360(2 FAN) HIGH SPEED FAC-190(1 FAN) HIGH SPEED FAC-360(2 FAN) LOW SPEED FAC-190(1 FAN) LOW SPEED
20
10
0
10001200
21
Page 22
INTEGRATOR POWER, UPS, & TERMINAL CONNECTIONS
22
Page 23

TROUBLESHOOTING

PROBLEM CAUSE SOLUTION
ECM Not Cooling
Fans blowing warm air
Condensate draining continuously
noise Cabinet is excessively
hot
No Power 60 HZ: Verify F2 fuse not blown by
checking on/off switch. If not lit, fuse is
50Hz: Verify breaker has not tripped. Filter Clogged Clean, or replace filter Refrigerant loss Verify leak. If refrigerant system needs
repaired, replace ECM. Hot Gas Bypass Valve set incorrectly Squirrel cage free spinning on evaporator or condenser blowers Clogged Condenser coil Clean coil Compressor trips on thermal overload.
Faulty Compressor Verify Compressor has failed. Replace
Excessive opening of doors Reduce the amount of opening. Suggest
Enclosure not properly sealed Verify leak and fix or replace gasket Evaporator drain kinked or clogged
Defective motor in blower Replace motorExcessive vibration or Defective squirrel cage in blower Replace squirrel cage, or reattach and
ECM is overloaded Verify the correct UPS and load on UPS. If
Heat not rejected from room Verify LGH is located in room with air
ECM not cooling See above UAS operation Verify UAS operation by jumpering
Set valve correctly per LGH handbook
Reattach and tighten squirrel cage to
Open LGH doors and let compressor cool. Turn ECM on and verify compressor is energized (humming). Verify cold air is being discharged from evaporator discharge (right side of ECM).
ECM. If electrical component has failed causing compressor not to run, replace component.
external keyboard tray. Turn ECM off when opening door.
Remove ECM and verify plastic tubing is attached to drain and not kinked or clogged.
tighten to blower shaft. no UPS; verify watt load of equipment
does not exceed ECM rating. circulation and heat rejected from ECM is
sufficiently removed from room.
terminals on high temperature stat
blown
blower shaft
23
Page 24
Limited Warranty
(for U.S. Sales and Installations)
We are pleased that you have purchased the Little Glass House™ product to enhance the environment and the reliability of the available AC power for your sensitive electronic equipment. Liebert Corporation warrants to the original user all parts that make up the Little Glass House for a period of thirteen (13) months from the factory ship date or proof of purchase date, including the LGH enclosure and the Environmental Control Module (ECM). The UPS module and batteries have a parts warranty of twenty-four (24) months from factory ship date or proof of purchase date. Complete removal of the UPS and Environmental Control Module is required for warranty field replacement. Extended warranty contracts are available for the Little Glass House. Note that the limited warranty for the Little Glass House is for parts only. NOTE: UPS Warranty is void if the battery is allowed to discharge below the minimum battery voltage cutoff point. CAUTION: To prevent excessive battery discharge. DO NOT leave the UPS POWER switch ON for more than 2 days without AC/mains power being supplied to the UPS. The battery must be recharged every 4 to 6 months if not in use. Circuit breaker resetting is not covered by this warranty and may indicate use beyond capability of the product. No warranty applies to products which have been abused, mishandled, modified, damaged by act of God or source external to the product, repaired by others, or which have product serial numbers removed or altered. There are no warranties other than that described herein. In no event will Liebert be responsible beyond the purchase price of the product. SELLER DISCLAIMS ANY IMPLIED WARRANTY OF MERCHANTABILITY OF THE GOODS OR THE FITNESS OF THE GOODS FOR ANY INTENDED PURPOSES. LIEBERT ASSUMES NO RESPONSIBILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES, INCLUDING WITHOUT LIMITATION, LOSS OF USE, PROFIT, OR INCOME. To make a warranty claim for replacement of a part/module, first call your Liebert supplier with the unit model number and serial number. He will obtain the required warranty return authorization from Liebert Corporation. Customer is to package and ship the defective module or part to Liebert as outlined on the Warranty Return Tag. The Warranty Return Tag needs to be completed with description of defect, installer's name and telephone number, and must accompany the defective module or part back to Liebert. The Warranty Return Tag is included with the packing of the new or reconditioned part from Liebert.
24
Page 25
1050 Dearborn Drive  Columbus, OH 43229  614-888-0246
Little Glass House
Integrated Secured Protection
for Network Equipment
Outside the U.S.A. 614-841-6755
Germany +49 89 99 19 220
Netherlands +31 (0) 475 503333
Worldwide FAX tech support +614-841-5471
The Company Behind The Products

Technical Support

U.S.A. 1-800-222-5877
U.K. +44 (0) 1793 553355
France +33 (0) 1 43 60 01 77
Italy +39 2 98250 1
E-mail upstech@liebert.com
Web site http://www.liebert.com
With more than 500,000 installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics:
§ Environmental systems: close-control air conditioning from 1.5 to 60 tons.
§ Power conditioning and UPS with power ranges from 250 VA to more than 1000 kVA.
§ Integrated systems that provide both environmental and power protection in a single, flexible package.
§ Monitoring and control — on-site or remote — from systems of any size or location.
§ Service and support, through more than 100 service centers around the world, and a 24­hour Customer Response Center.
While every precaution has been taken to ensure accuracy and completeness of this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
©1997 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-15050 (5/97) Rev. 4
25
Loading...