Liebert F277Y800-03 User Manual

E
Liebert Active Tracking Filter System
Operating Voltage Range.........................................+/-15%
Fault Current Rating (AIC)........................................ 200 kAIC
Operating Frequency Range.................................... 47 – 63 Hz
50  EMI/RFI Attenuation:
Normal Mode.............................................. 10 kHz-500MHz 60 dB
Common Mode........................................... 10 kHz-500MHz 50 dB
Response Time .........................................................<0.5 ns
Operating Humidity................................................... 0% to 95%
Status Indication.......................................................LEDs, Dry Contacts, Audible Alarm,
Surge Counter
Certifications.............................................................UL 1449 & 1283, CSA
Enclosure ..................................................................NEMA 12 standard
Warranty ....................................................................10-Years Parts / 5-Years Labor
Optional Equipment.................................................. Dual Surge Counter,
xample Part Number: F277Y800-03 = 277/480V, 3-Phase Wye, All Mode, 800 Amp Current Rating
LED’s, Alarm & Dual Counters, Form C Contacts
F__ __ __ __ __ __ __ __ - __ __
Nominal
Voltage Codes 120 120V 208 208V 220 220V 230 230V 240 240V 277 277V 480 480V 600 600V
Remote Monitor Panel
Option Code
01
03
06
LED, Form C
Contacts
LED, Alarm, Dual
Counters, Form C
Contacts
LED, Alarm, Counter,
Form C Contacts
Technical Specification
Life Cycle Surge Testing
10kA, 20kV, IEEE Cat. C3
Unit Per Mode (L-N/L-G/N-G) Per Phase
100 kA 12,000/12,000/12,000 24,000 150 kA 12,000/24,000/24,000 36,000 200 kA 24,000/24,000/24,000 48,000 300 kA 24,000/48,000/48,000 72,000
100-120V 400 400 800 400
208V 800 800
230-277V 800 800 1500 700
347V 1200 1000 2000 1000
400-480V 1500 1500
600V 2000 2000
Source configuration
N 1 Phase L-N 2w + gnd L 1 Phase L-L 2w + gnd S Split Phase 3w + gnd Y 3 Phase Wye 4w + gnd D 3 Phase Delta 3w + gnd H 3 Phase Delta Hi-leg 4w+ gnd
Current
Code
30 30A 100kA
60 60A 100kA 100 100A 150kA 225 225A 150kA 400 400A 150kA 800 800A 300kA*
1200 1200A 300kA* 2000 2000A 300kA* 4000 4000A 300kA
Current
Rating
* 200kA is available,
add –200 to part number.
Surge Current Capability
Per Phase
Job Name____________________________ Model# ______________________________ Date ________________________________ Qty _________________________________
Dimensional data in inches and shipping weight in pounds
Model/Configuration Dimensions in inches Wt
A B C D E F Lbs
30A Single Phase 20.0 16.0 9.0 21.25 10.0 .44 35 30A Split or Three Phase 24.0 20.0 9.0 25.25 14.0 .44 60 60A Single Phase 20.0 16.0 9.0 21.25 10.0 .44 35 60A Split or Three Phase 24.0 20.0 9.0 25.25 14.0 .44 60 100A Single Phase 24.0 20.0 9.0 25.25 14.0 .44 60 100A Split or Three Phase 30.0 24.0 9.0 31.25 18.0 .44 80 225A Single Phase 24.0 20.0 9.0 25.25 14.0 .44 60 225A Split or Three Phase 30.0 24.0 9.0 31.25 18.0 .44 80 400A Split or Three Phase 48.0 36.0 12.0 49.25 30.0 .44 300 800A Split or Three Phase 60.0 48.0 12.0 - - - 530 1200A Split or Three Phase 60.0 48.0 20.0 - - - 750 2000A Split or Three Phase 60.0 48.0 20.0 - - - 950 4000A Split or Three Phase 60.0 48.0 20.0 - - - 1300
Quote# ______________________________
Liebert Corporation • 1050 Dearborn Drive • PO Box 29186 • Columbus, OH 43229 Phone 607-724-2484 • Fax 607-722-8713 • US & Canada 800-288-6169 EMAIL: info@control-concepts.com • Web Site: www.Liebert.com 82245 Rev 0
Loading...