Liebert EXL Installation Manual

Page 1
Liebert® EXL
Installation Manual — 625-1200kVA, 1.0PF, 60Hz, Three-Phase, Single-Module and Multi-Module
Page 2
CONTACTING VERTIV FOR SUPPORT
To contact Vertiv™ Services for information or repair service in the United States, call 800-543-2378. Vertiv Services offers a complete range of startup services, repair services, preventive maintenance plans and service contracts.
For repair or maintenance service outside the 48 contiguous United States, contact Vertiv Services, if available in your area. For areas not covered by Vertiv Services, the authorized distributor is responsible for providing qualified, factory-authorized service.
For Vertiv Services to assist you promptly, please have the following information available:
Part numbers: ___________________________________________________________________________________________________________
Serial numbers: __________________________________________________________________________________________________________
Rating:___________________________________________________________________________________________________________________
Date purchased: _________________________________________________________________________________________________________
Date installed: ___________________________________________________________________________________________________________
Location: ________________________________________________________________________________________________________________
Input voltage/frequency: ________________________________________________________________________________________________
Output voltage/frequency: ______________________________________________________________________________________________
Battery reserve time: ____________________________________________________________________________________________________
Product Warranty Registration
To register for warranty protection, visit the Service and Support section of our Web site at:
www.liebert.com
Click on Product Registration and fill out the form.
©2016 Vertiv Co. All rights reserved throughout the world
Verti vC o.co m | Vert iv Headq ua rter s
Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners.
While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.
This document may contain confidential and/or proprietary information of Liebert Corporation, and its receipt or possession does not convey any right to reproduce, disclose its contents, or to manufacture or sell anything that it may describe. Reproduction, disclosure, or use without specific authorization from Liebert Corporation is strictly prohibited.
, 1050 Dearborn Drive, Columbus, OH, 43085, USA
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev.3 | 02/17
Page 3
TABLE OF CONTENTS
CONTACTING VERTIV FOR SUPPORT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . INSIDE FRONT COVER
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.0 M
ECHANICAL INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Environmental Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
1.3.1 UPS Room. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3.2 Storing the UPS and Batteries for Delayed Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4 Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
1.4.1 Moving the Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.4.2 Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.4.3 Raised-Floor Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.4.4 Kick Plate Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.4.5 Special Considerations for 1+N Parallel Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
1.4.6 Special Considerations for Remote Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.5 System Composition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
1.6 Cable Entry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
1.7 Cable Routing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2.0 UPS ELECTRICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
2.1 External Protective Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
2.2 Power Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.3 Sizing the Input Breaker Feeding a Liebert EXL UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
2.3.1 Power Cable Connection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.4 Remote Breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
2.5 Control Cable and Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
2.5.1 Dry Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
2.5.2 Multi-Module Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
2.6 Digital LBS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.7 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.7.1 Three-Wire Input connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.7.2 High Resistance Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.7.3 Preferred Grounding Configuration, Battery Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
2.8 Internal Breaker Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
3.0 OPTIONAL EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.1 Single-Module System Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.1.1 Battery Temperature Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.1.2 Matching Liebert EXL Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.1.3 Remote Alarm Status Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.2 Remote Breaker UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.3 Rectifier Input Breaker (RIB). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.4 Remote Backfeed Breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 i
Page 4
3.5 Communication and Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.5.1 Alber® Monitoring System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.0 INSTALLATION DRAWINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.0 S
PPENDIX A-SHIPPING SPLITS, KICKPLATES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A53
A
PECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
FIGURES
Figure 1 Top-terminal battery system configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 2 Top-terminal stand-alone battery system configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 3 Top-terminal battery system configuration—Battery cabinets not attached to UPS or each
other . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Figure 4 Front-terminal battery system configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 5 Front-terminal stand-alone battery system configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Figure 6 Front-terminal battery system configuration—Battery cabinets not attached to UPS or each
other . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 7 Liebert EXL customer connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 8 UPS MMS/1+N connectivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Figure 9 LBS connectivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 10 Customer connections (remote breaker) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 11 Rectifier Input Breaker diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 12 Remote Backfeed Breaker diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 13 Terminal block locations—input cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 14 Typical main components, 625-800kVA Liebert EXL UPS, SMS and 1+N multi-module
unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Figure 15 Typical main components, 1000-1200kVA Liebert EXL, SMS and 1+N multi-module unit . . . . . . . 29
Figure 16 Main components for remote breaker configuration—Single module with static bypass
or 1+N multi-module; 625kVA-800kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Figure 17 Main components for remote breaker configuration—Single module with static bypass
or 1+N multi-module; 1000kVA-1200kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Figure 18 Outline Drawing, 625-800kVA Liebert EXL UPS, SMS and 1+N multi-module unit . . . . . . . . . . . . . . .31
Figure 19 Outline Drawing, 1000-1200kVA Liebert EXL UPS, SMS and 1+N multi-module unit . . . . . . . . . . . . 32
Figure 20 Base drawing, 625-800kVA Liebert EXL UPS, SMS and 1+N multi-module unit. . . . . . . . . . . . . . . . . 33
Figure 21 Base drawing, 1000-1200kVA Liebert EXL UPS, SMS and 1+N multi-module unit. . . . . . . . . . . . . . . 34
Figure 22 Input and battery terminal detail, 625-800kVA Liebert EXL UPS, SMS and 1+N
multi-module unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 23 Input and battery terminal detail, 1000-1200kVA Liebert EXL UPS, SMS and 1+N
multi-module unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 24 Output and bypass terminal detail, 625-800kVA Liebert EXL UPS, SMS and 1+N
multi-module unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 25 Output and bypass terminal detail, 1000-1200kVA Liebert EXL UPS, SMS and 1+N
multi-module unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Figure 26 Input, output and bypass terminal spacing details, 625-1200kVA Liebert EXL UPS, SMS
and 1+N multi-module unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Figure 27 Low-voltage cable routing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Figure 28 Cabling for single input configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 ii
Page 5
Figure 29 Optional Input Contact Isolator Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 30 Control wiring, Programmable Relay Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Figure 31 Inverter overload data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Figure 32 Rectifier overload data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Figure 33 Bypass overload data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Figure 34 Shipping split, 625-800kVA Liebert EXL UPS, SMS and 1+N multi-module unit . . . . . . . . . . . . . . . . 53
Figure 35 Shipping split, 625-800kVA Liebert EXL UPS, SMS and 1+N multi-module
unit, continued. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Figure 36 Shipping split, 1000-1200kVA Liebert EXL UPS, SMS and 1+N multi-module unit, Page 1 . . . . . . . 56
Figure 37 Shipping split, 1000-1200kVA Liebert EXL UPS, SMS and 1+N multi-module unit, Page 2. . . . . . . 57
Figure 38 Shipping split, 1000-1200kVA Liebert EXL UPS, SMS and 1+N multi-module unit, Page 3. . . . . . . 58
Figure 39 Kickplate installation—625-800kVA units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Figure 40 Kickplate installation—1000-1200kVA, single module units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Figure 41 Kickplate installation—1000-1200kVA, 1+N multi-module units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
TABLES
Table 1 Load distribution for various load cable differences for systems with and without
sharing inductor, 800kVA UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Table 2 UPS Digital Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Table 3 UPS Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Table 4 UPS control contacts to Remote Status Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Table 5 UPS control contacts to Battery Interface Boards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Table 6 Rectifier Input Breaker contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table 7 Rectifier Input Breaker specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table 8 Remote Backfeed Breaker contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Table 9 Remote Backfeed Breaker specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Table 10 Input Contact Isolator Board pre-assigned values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Table 11 Input Contact Isolator Board control wiring connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Table 12 Programmable Relay Board pinout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Table 13 Liebert EXL UPS specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Table 14 Current ratings—rectifier input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Table 15 Current ratings—bypass input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Table 16 Current ratings—output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Table 17 Current ratings—DC source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Table 18 Recommended conduit and cable sizes for use with 100% rated breakers . . . . . . . . . . . . . . . . . . . . . 50
Table 19 Recommended breakers, upstream and downstream . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Table 20 Recommended torque values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Table 21 Recommended lug sizes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Table 22 Connections associated with top-down view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Table 23 Section J-J connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Table 24 Connections associated with sections in “View” column . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 iii
Page 6
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 iv
Page 7
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation of your Liebert EXL UPS. Read this manual thoroughly, paying special attention to the sections that apply to your installation, before working with the UPS. Retain this manual for use by installing personnel.
WARNING
Risk of electrical shock. Can cause personal injury or death. This UPS has several circuits that are energized with high DC as well as AC voltages. Check for voltage
with both AC and DC voltmeters before working within the UPS. Check for voltage with both AC and DC voltmeters before making contact. Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should be involved in installing the UPS or preparing the UPS for installation. When performing maintenance with any part of the equipment under power, service personnel and test equipment should be standing on rubber mats.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or those approved for use in fighting electrical fires.
Extreme caution is required when performing installation and maintenance. Special safety precautions are required for procedures involving handling, installation and maintenance of
the UPS system. Observe all safety precautions in this manual before handling or installing the UPS system. Observe all precautions in the Operation and Maintenance Manual, SL-26030, before as well as during performance of all maintenance procedures. Observe all DC safety precautions before working on or near the DC system.
AVERTISSEMENT
Risque de décharge électrique pouvant causer des blessures graves, voire mortelles. Ce système ASC comporte plusieurs circuits à haute tension c.a et c.c. Vérifiez les tensions au moyen de voltmètres c.a. et c.c. avant d’utiliser le système ASC. Vérifiez les tensions avec des voltmètres c.a. et c.c. avant d’établir tout contact. Seuls des employés qualifiés et dûment formés portant un casque, des gants, des chaussures et des lunettes de sécurité adéquats doivent se charger d’installer le système ASC ou de le préparer pour l’installation.Les responsables de l’entretien et l’équipement d’essai doivent reposer sur des tapis de caoutchouc lors de toute intervention sur une pièce d’équipement sous tension. En cas d’incendie associé à du matériel électrique, n’utilisez que des extincteurs à dioxyde de carbone ou homologués pour la lutte contre les incendies d’origine électrique. Les opérations d’installation et d’entretien requièrent une extrême prudence. Des précautions de sécurité spéciales sont requises pour les procédures associées à la manutention, à l’installation et à l’entretien du système ASC. Observez toutes les précautions de sécurité décrites dans le présent manuel avant de manipuler ou d’installer le système ASC. Observez également toutes les précautions décrites dans le manuel d’utilisation et d’entretien, SL-26030, avant et pendant toutes les procédures d’entretien. Observez toutes les précautions de sécurité appropriées lorsque vous travaillez sur à proximité d’une source c.c. de sécurité appropriées dès que vous vous trouvez à proximité d’une source c.c.
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 1
Page 8
WARNING
Risk of heavy unit falling over. Improper handling can cause equipment damage, injury or death. Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel.
The UPS module weight is up to 8095 lb. (3672 kg).
Locate center of gravity symbols and determine unit weight before handling each cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times. Slots at the base of the module cabinets are intended for forklift use. Base slots will support the unit only if the forks are completely beneath the unit.
Read all of the following instructions before attempting to move, lift, or remove packaging from unit, or prepare unit for installation.
AVERTISSEMENT
Le centre de gravité élevé de l’appareil présente un risque de renversement. Une mauvaise manutention peut entraîner des dommages matériels, des blessures et même la mort. Faites preuve d’une extrême prudence lors de la manutention des armoires ASC afin d’éviter de les endommager ou de blesser le personnel. Le module ASC pèse jusqu’à 3 672 kg (8 095 lb).
Identifiez les symboles de centre de gravité et déterminez le poids de l’appareil avant de manipuler chaque armoire. Testez le levage et l’équilibre des armoires avant de transporter l’appareil. Maintenez en tout temps l'inclinaison verticale minimale.
Les fentes situées à la base des armoires du module sont conçues pour utiliser le chariot élévateur. Les fentes situées à la base peuvent soutenir le système seulement si les fourches se trouvent complètement sous le système.
Lisez toutes les instructions ci-dessous avant de tenter de déplacer, lever, déballer ou préparer le système en vue de son installation.
WARNING
Risk of electrical shock and fire. Can cause equipment damage, personal injury or death. Under typical operation and with all UPS doors closed, only normal safety precautions are necessary. The
area around the UPS system should be kept free of puddles of water, excess moisture and debris. Only test equipment designed for troubleshooting should be used. This is particularly true for oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when the power is turned Off, dangerously high potential electric charges may exist at the capacitor banks and at the DC connections. All wiring must be installed by a properly trained and qualified electrician. All power and control wiring must comply with all applicable national, state and local codes. One person should never work alone, even if all power is disconnected from the equipment. A second person should be standing by to assist and to summon help in case of an accident.
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 2
Page 9
AVERTISSEMENT
Risque de décharge électrique et d’incendie. pouvant entraîner des dommages matériels, des blessures et même la mort.
Les précautions de sécurité habituelles suffisent lorsque le système ASC est en mode de fonctionnement normal et que toutes les portes sont fermées. La zone entourant le système ASC doit être exempte de flaques d’eau, d’humidité excessive et de débris. Seuls des équipements d’essai conçus pour le dépannage doivent être utilisés. Cette mise en garde couvre notamment les oscilloscopes. Utilisez toujours un voltmètre c.a. et c.c. pour vérifier les tensions avant d’établir un contact ou d’utiliser des appareils. Des tensions dangereusement élevées peuvent demeurer dans les batteries de condensateurs et au niveau des raccords c.c., même une fois l’alimentation coupée.
Tous les raccords doivent être effectués par un électricien dûment formé et qualifié. Tous les câbles d’alimentation et de commande doivent être conformes aux codes nationaux et locaux en vigueur.
Une personne ne devrait jamais travailler seule, même si toute l’alimentation d’entrée est coupée. Une deuxième personne devrait toujours être présente pour porter assistance ou chercher de l’aide en cas d’accident.
NOTE
Materials sold hereunder cannot be used in the patient vicinity (e.g., use where UL, cUL or IEC 60601-1 is required). Medical applications such as invasive procedures and electrical life support equipment are subject to additional terms and conditions.
NOTICE
If optional filtering is installed, this unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause harmful interference to radio communications. Operation of this unit in a residential area may cause harmful interference that the user must correct at his own expense.
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 3
Page 10
1.0 MECHANICAL INSTALLATION
1.1 INTRODUCTION
This section describes the requirements that must be taken into account when planning the positioning and cabling of the Liebert EXL uninterruptible power supply and related equipment.
This chapter is a guide to general procedures and practices that should be observed by the installing personnel. The particular conditions of each site will determine the applicability of such procedures.
WARNING
Risk of electrical shock. Can cause injury or death. Special care must be taken when working with the batteries associated with this equipment. When they are connected together, the battery terminal voltage will exceed 400VDC and is potentially lethal.
AVERTISSEMENT
Risque de décharge électrique pouvant causer des blessures graves, voire mortelles. Des précautions particulières doivent être prises lors de travaux touchant les batteries associées à cet
équipement. Lorsque les batteries sont branchées ensemble, la tension à la borne d’une batterie dépasse 400 V c.c. et
est potentiellement mortelle.
NOTE
All equipment not referred to in this manual is shipped with details of its own mechanical and electrical installation.
NOTICE
Three-phase input supply required. The standard Liebert EXL UPS is suitable for connection to three-phase, three-wire (+ Earth) TN-C and TN-S.
NOTICE
Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer.
1.2 PRELIMINARY CHECKS
Before installing the UPS, please carry out the following preliminary checks:
• Visually examine the UPS equipment for transit damage, both internally and externally. Report any damage to the shipper immediately.
• Verify that the correct equipment is being installed. The equipment supplied has an identification tag on the interior doors reporting the type, size and main calibration parameters of the UPS.
• Verify that the UPS room satisfies the environmental conditions stipulated in the equipment specification, paying particular attention to the ambient temperature and air exchange system.
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 4
Page 11
1.3 ENVIRONMENTAL CONSIDERATIONS
1.3.1 UPS Room
The UPS module is intended for indoor installation and should be located in a cool, dry, clean-air environment with adequate ventilation to keep the ambient temperature within the specified operating range (see Environmental Parameters in Tab le 1 3).
The Liebert EXL UPS is cooled with the aid of internal fans. To permit air to enter and exit and prevent overheating or malfunctioning, do not cover the ventilation openings.
The Liebert EXL UPS is equipped with air filters located behind the front doors. A schedule for inspection of the air filters is required. The period between inspections will depend upon environmental conditions.
When bottom entry is used, the conduit plate must be installed.
NOTE
The UPS is suitable for mounting on concrete or other non-combustible surface only.
1.3.2 Storing the UPS and Batteries for Delayed Installation
If the Liebert EXL system will not be installed immediately, it must be stored indoors in a clean, dry and cool location (see Environmental Parameters in Tab le 1 3). If the UPS includes batteries, either internally or in a battery cabinet, the batteries’ requirements will dictate the storage conditions. Batteries should be unpacked, installed and charged as soon as possible after delivery.
NOTICE
Risk of failure to properly charge batteries. Can cause permanent damage to batteries and void the warranty. Batteries will self-discharge during storage. Batteries must be recharged as recommended by the battery manufacturer. A notice of “Charge Before Date” is affixed to each unit that has batteries inside. The “Charge Before Date” is calculated
based on the batteries being stored at 77°F (25°C). Storage at a higher temperature will increase the rate of self-discharge, requiring earlier recharge. Consult the battery manufacturer on how to determine when the batteries need to be recharged.
1.4 POSITIONING
The cabinet is structurally designed to handle lifting from the base.
Access to the power terminals, auxiliary terminal blocks and power switches is from the front.
The door can be opened to give access to the power connection bars, auxiliary terminal blocks and power isolators. Front door can be opened to 90 degrees, and interior doors can be removed for more flexibility in installations.
NOTE
The UPS must be placed on a non-combustible surface suitable to support the weight of the unit.
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 5
Page 12
1.4.1 Moving the Cabinets
The route to be traveled between the point of arrival and the unit’s position must be planned to make sure that all passages are wide enough for the unit and that floors are capable of supporting its weight (for instance, check that doorways, lifts, ramps, etc. are adequate and that there are no impassable corners or changes in the level of corridors).
Ensure that the UPS weight is within the designated surface weight loading (lb/in2) of any handling equipment. For weight details, see Tab le 1 3.
The UPS can be handled with a forklift or similar equipment. Ensure any lifting equipment used in moving the UPS cabinet has sufficient lifting capacity. When moving the unit by forklift, care must be taken to protect the panels. Do not exceed a 15-degree tilt with the forklift. Bottom structure will support the unit only if the forks are completely beneath the unit.
Handling with straps is not authorized.
WARNING
Risk of heavy unit falling over. Improper handling can cause equipment damage, injury or death. Because the weight distribution in the cabinet is uneven, use extreme care while handling and
transporting. Take extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel.
The UPS module weighs up to 8095 lb. (3672 kg).
Locate center of gravity symbols and determine unit weight before handling each cabinet. Test lift
and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times.
AVERTISSEMENT
Le centre de gravité élevé de l’appareil présente un risque de renversement. Une mauvaise manutention peut entraîner des dommages matériels, des blessures et même la mort.
En raison de la distribution inégale du poids de l’armoire, vous devez faire preuve d’extrême prudence lors de sa manipulation et de son transport. Faites preuve d’une extrême prudence lors de la manutention des armoires ASC afin d’éviter de les endommager ou de blesser le personnel.
Le module ASC pèse jusqu’à 3 672 kg (8 095 lb).
Identifiez les symboles de centre de gravité et déterminez le poids de l’appareil avant de manipuler
chaque armoire. Testez le levage et l’équilibre les armoires avant de transporter l’appareil. Maintenez en
tout temps l'inclinaison verticale minimale.
1.4.2 Clearances
The Liebert EXL has no ventilation grilles at either side or at the rear of the UPS. Clearance around the front of the equipment should be sufficient to permit free passage of personnel with the doors fully opened. It is important to leave a distance of 24in. (610mm) between the top of the UPS and any overhead obstacles to allow the module to be serviced and to permit adequate circulation of air coming out of the unit.
1.4.3 Raised-Floor Installations
If the equipment is to be located on a raised floor, it should be mounted on a pedestal suitably designed to accept the equipment point loading. Refer to Figure 20 to design this pedestal.
1.4.4 Kick Plate Installation
If the unit is to be installed in a position that does not permit access to rear kick plates, then the kick plates should be installed before the unit is placed in its final position.
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 6
Page 13
1.4.5 Special Considerations for 1+N Parallel Systems
Design the grounding configuration of the system before finalizing module placement See 2.7 - Grounding.
The cabling impedance must be carefully controlled to ensure good load-sharing. Impedance mismatch may cause an overload on one module in a 1+N system, triggering a shutdown and loss of power to the connected load. Mismatched cable impedance is amplified when a 1+N system is operating on bypass because the power on the bypass path is not controlled.
The Liebert 1+N UPS module is supplied with a sharing inductor to minimize the impact of cable impedance mismatch. An impedance mismatch may be further minimized by controlling the wiring length of each unit. The design and the layout of the UPS system and associated panels and cabling must be designed to ensure that cable lengths and impedances are closely matched.
Tabl e 1 shows bypass load sharing when the cabling length is varied for three 800kVA UPS modules powering the load via their static bypass switches.
Table 1 Load distribution for various load cable differences for systems with and without sharing inductor, 800kVA UPS
With Share Inductor, 100% System Load
(4) 600kcmil per phase, 0.9 PF
% cable
Difference
01001001000100100100
10 99.5 99.5 101.1 10 96.4 96.4 107.2
25 98.6 98.6 102.8 25 90 90 120 *
50 97.2 97.2 105.8 50 75 75 150.1 *
01001001000100100100
10 99.2 99.2 101.6 10 96.4 96.4 107.1
25 98 98 104 25 90 90 120 *
50 96 96 108.3 50 75 75 150.1 *
01001001000100100100
10 99 99 102 10 96.4 96.4 107.2
25 97.5 97.5 105.1 25 90 90 120 *
50 94.9 94.9 110.6 * 50 75.1 75.1 150.1 *
01001001000100100100
10 98.9 98.9 102.3 10 96.4 96.4 107.2
25 97.1 97.1 1 06 2 5 90 90 120 *
50 93.8 93.8 112.8 * 50 75.1 75.1 150.1 *
* Overloaded unit, causing to breaker trip and load shutdown.
% Current
UPS #1
% Current
UPS #2
% Current
UPS #3
Bypass Cable Length 50ft. (15.3m)
Bypass Cable Length 75ft. (23m)
Bypass cable length 100ft. (30.5m)
Bypass Cable Length 125ft. (38m)
Without Share Inductor, 100% System Load
(4) 600kcmil per phase, 0.9 PF
% cable
Difference
% Current
UPS #1
% Current
UPS #2
% Current
UPS #3
For further information about matching cable impedances or refer to “Performance Improvements with Sharing Inductors in Distributed Static Switch UPS Systems” found at the Liebert EXL section of Liebert’s Web site,
www.liebert.com; or contact Vertiv® customer support.
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 7
Page 14
1.4.6 Special Considerations for Remote Breaker
The voltage sense cable for the rectifier input breaker must accommodate the pre-charge circuit for the UPS, sized to 60A fuses at the sense location (see Figure 11). Breakers must be sized appropriately for the overload curves as shown in the operation and maintenance manual, SL-26030, available at Liebert’s Web site,
www.liebert.com
1.5 SYSTEM COMPOSITION
A UPS system can include a number of equipment cabinets, depending on the system design: (e.g., UPS cabinet, battery cabinet, maintenance bypass cabinet). In general, all the cabinets used in a particular installation are of the same height. Refer to the drawings provided in 4.0 - Installation Drawings for the positioning of the cabinets as shown in Figures 1 through 6.
1.6 CABLE ENTRY
Cables can enter the UPS cabinet from bottom or top into the Input/Output (I/O) of the unit; see the figures in
4.0 - Installation Drawings.
1.7 CABLE ROUTING
Per NEC 300.20 (NEC 2014 or equivalent), all phase conductors and ground conductors must be grouped together when they are installed in ferrous enclosures or go through ferrous material. This is to avoid heating from induction currents.
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 8
Page 15
Figure 1 Top-terminal battery system configurations
47"
(1194mm)
Battery
Cabinet
47"
(1194mm)
Battery
Cabinet
47"
(1194mm)
Battery
Cabinet
15-½"
Junction
Cabinet
(May be on
either end or betw een any battery
cabinets)
625-750kVA Stand-Alone
Interconnected
Systems
47"
(1194mm)
Battery
Cabinet
47"
(1194mm)
Battery
Cabinet
47"
(1194mm)
Battery
Cabinet
S
p a c e
r
Liebert
UPS
625-1200kVA
One or more battery cabinets
bolted to the UPS
Battery cabinets must be on the
left side of the UPS.
47"
(1194mm)
Battery
Cabinet
47"
(1194mm)
Battery
Cabinet
47"
(1194mm)
Battery
Cabinet
17-½"
Junction
Cabinet
(May be on
either end or between any battery
cabinets )
800-1200kVA
Stand-Alone
Interconnected
Systems
55"
(1397mm)
Battery
Cabinet
55"
(1397mm)
Battery
Cabinet
55"
(1397mm)
Battery
Cabinet
55"
(1397mm)
Battery
Cabinet
Stand-Alone
Individual
Systems
Figure 2 Top-terminal stand-alone battery system configuration
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 9
Page 16
Figure 3 Top-terminal battery system configuration—Battery cabinets not attached to UPS or each other
Liebert
UPS
Detached
Junction
Cabinet
32"
(813mm)
55"
(1397mm)
Battery
Cabinet
55"
(1397mm)
Battery
Cabinet
Stand-Alone
Individual
Systems
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 10
Page 17
Figure 4 Front-terminal battery system configurations
62"
(1575mm)
Battery
Cabinet
62"
(1575mm)
Battery
Cabinet
62"
(1575mm)
Battery
Cabinet
15-½"
Junction
Cabinet
(May be on
either end or betw een any battery
cabinets)
625-750kVA Stand-Alone
Interconnected
Systems
625-1200kVA
One or more battery cabinets
bolted to the UPS
Battery cabinets must be on the
left side of the UPS.
62"
(1575mm)
Battery
Cabinet
62"
(1575mm)
Battery
Cabinet
62"
(1575mm)
Battery
Cabinet
17-½"
Junction
Cabinet
(May be on
either end or between any battery
cabinets )
800-1200kVA
Stand-Alone
Interconnected
Systems
62"
(1575mm)
Battery
Cabinet
62"
(1575mm)
Battery
Cabinet
62"
(1575mm)
Battery
Cabinet
S
p a c e
r
Liebert
UPS
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 11
Page 18
Figure 5 Front-terminal stand-alone battery system configuration
62"
(1575mm)
Battery
Cabinet
62"
(1575mm)
Battery
Cabinet
62"
(1575 mm)
Battery
Cabinet
62"
(1575mm)
Battery
Cabinet
Stand-Alone
Individual
Systems
Liebert
UPS
Detached
Junction
Cabinet
32"
(813mm)
62"
(1575mm)
Battery
Cabinet
62"
(1575 mm)
Battery
Cabinet
Stand-Alone
Individual
Systems
Figure 6 Front-terminal battery system configuration—Battery cabinets not attached to UPS or each other
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 12
Page 19
2.0 UPS ELECTRICAL INSTALLATION
This chapter provides guidelines for qualified installers who must have knowledge of local wiring practices pertaining to the equipment to be installed.
WARNING
Risk of electrical shock. Can cause injury or death. The UPS contains high DC as well as AC voltages. Check for voltage with both AC and DC voltmeters before working within the UPS.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should be involved in installing the UPS or preparing the UPS for installation.
AVERTISSEMENT
Risque de décharge électrique pouvant causer des blessures graves, voire mortelles. Le système ASC contient des tensions c.c. et c.a. élevées. Vérifiez les tensions au moyen de voltmètres
c.a. et c.c. avant d’utiliser le système ASC. Seuls des employés qualifiés et dûment formés portant un casque, des gants, des chaussures et des
lunettes de sécurité adéquats doivent se charger d’installer le système ASC ou de le préparer pour l’installation.
2.1 EXTERNAL PROTECTIVE DEVICES
For safety, circuit breakers must be installed in the input AC supply and external battery system. Given that every installation has its own characteristics, this section provides guidelines for qualified installation personnel with knowledge of operating practices, regulatory standards and the equipment to be installed.
External overcurrent protection must be provided. See Figures 31, 32 and 33 for overload capacity.
2.2 POWER CABLES
The UPS requires both power and control cabling. All control cables, whether shielded or not, should be run separately from the power cables in metal conduits or metal ducts that are electrically bonded to the metalwork of the cabinets to which they are connected.
The cable design must comply with the voltages and currents in Ta bles 1 4 through 17, follow local wiring practices and take into consideration the environmental conditions (temperature and physical support media), room temperature and conditions of installation of the cable and system’s overload capacity (see 5.0 - Specifications).
WARNING
Risk of electrical shock. Can cause injury or death. Before cabling the UPS, ensure that you are aware of the location and operation of the external isolators that connect the UPS input/bypass supply to the power distribution panel. Check that these supplies are electrically isolated, and post any necessary warning signs to prevent their inadvertent operation.
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 13
Page 20
AVERTISSEMENT
Risque de décharge électrique pouvant causer des blessures graves, voire mortelles. Avant de procéder au câblage du système ASC, assurez-vous que vous êtes au courant de l’emplacement
et du fonctionnement des isolateurs externes qui raccordent l’alimentation d’entrée ou de dérivation au panneau de distribution électrique. Vérifiez que ces raccords sont isolés électriquement et installez tous les panneaux d’avertissement nécessaires pour empêcher leur utilisation accidentelle.
When sizing battery cables, a maximum voltage drop of 2VDC is permissible at the current ratings given in Tabl e 17 .
The following are guidelines only and are superseded by local regulations and codes of practice where applicable:
• The grounding conductor should be sized according to the fault rating, cable lengths, type of protection, etc. The grounding cable connecting the UPS to the main ground system must follow the most direct route possible.
• Consideration should be given to the use of paralleled smaller cables for heavy currents, as this can ease installation considerably.
• AC and DC cables must be run in conduits according to local codes, national codes and standard best practices. This will prevent creation of excess EMI fields.
2.3 SIZING THE INPUT BREAKER FEEDING A LIEBERT EXL UPS
Nominal input current (considered continuous) is based on full-rated output load. Maximum current includes nominal input current and maximum battery recharge current (considered noncontinuous). Continuous and noncontinuous current are defined in the NEC.
Maximum input current is controlled by the current limit setting, which is adjustable. Values shown are for default current limit of 125%. If a smaller input feed breaker is used, the input current limit can be adjusted; see your Vertiv representative for more information. The input current limit should not be set less than 105% of the current needed to support the inverter at full load for normal operation. This results in sufficient power to recharge the battery in a reasonable time and to operate over the published input voltage range.
2.3.1 Power Cable Connection Procedure
The rectifier input, bypass, output and battery power cables (all require lug-type terminations) are connected to busbars in the I/O sections (refer to 4.0 - Installation Drawings).
Equipment Ground
The equipment ground busbars are in the I/O sections (refer to 4.0 - Installation Drawings). The grounding conductor must be connected to the ground busbar and bonded to each cabinet in the system.
All cabinets and cabling should be grounded in accordance with local regulations.
NOTE
Proper grounding reduces problems in systems caused by electromagnetic interference.
WARNING
Failure to follow adequate grounding procedures can result in electric shock hazard to personnel, or the risk of fire, should a ground fault occur.
All operations described in this section must be performed by properly trained and qualified electricians or technical personnel. If any difficulties are encountered, contact Vertiv. See the back page of this manual for contact information.
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 14
Page 21
AVERTISSEMENT
Le non-respect des procédures de mise à la terre peut entraîner des risques d’électrocution du personnel, ou des risques d’incendie en cas de défectuosité de la mise à la terre.
Toutes les opérations décrites dans cette section ne doivent être effectuées que par des électriciens ou des techniciens professionnels dûment formés et qualifiés . En cas de difficultés, communiquez avec Vertiv. Pour obtenir les renseignements de contact, consultez la dernière page de ce manuel.
Once the equipment has been positioned and secured, connect the power cables as described below (refer to the appropriate cable connection drawing in 4.0 - Installation Drawings):
1. Verify that the UPS equipment is isolated from its external power source and all the UPS power isolators are open. Check
that these supplies are electrically isolated and post any necessary warning signs to prevent their inadvertent operation.
2. Open exterior and interior panels on the front of the I/O sections.
3. Connect the ground to the equipment ground busbar located in the I/O sections.
4. Make power connections and tighten the connections to the proper torque.
Ensure correct phase rotation.
WARNING
Risk of electrical shock. Can cause injury or death. If the load equipment will not be ready to accept power on the arrival of the commissioning engineer,
ensure that the system output cables are safely isolated at their termination.
AVERTISSEMENT
Risque de décharge électrique pouvant causer des blessures graves, voire mortelles. Si les équipements branchés ne sont pas prêts à être alimentés à l’arrivée de l'ingénieur de mise en
service, assurez-vous que les bornes des câbles de sortie du système soient isolées de façon sécuritaire.
WARNING
Risk of electrical shock. Can cause injury or death. When connecting the cables between the battery extremities to the circuit breaker, always connect the circuit breaker end of the cable first.
AVERTISSEMENT
Risque de décharge électrique pouvant causer des blessures graves, voire mortelles. Lors du raccordement de câbles entre des bornes de batterie et un disjoncteur, branchez toujours en
premier l’extrémité du câble qui se raccorde au disjoncteur.
5. For control connection details, see 2.5 - Control Cable and Communication.
NOTE
If any fault bracing brackets were removed during installation, they MUST be replaced.
6. Close and secure the interior and exterior doors.
7. Attach the kick plates to the bottom of the unit. See Figure 39.
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 15
Page 22
2.4 REMOTE BREAKER
The remote breaker option has remote circuit breakers for both CB1 and the BFB. These remote circuit breakers are referred to as the Rectifier Input Breaker (RIB) and Remote Backfeed Breaker (RBB). See 3.2 - Remote
Breaker UPS Installation.
2.5 CONTROL CABLE AND COMMUNICATION
Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery system (external battery circuit breaker), communicate with a building management system or provide alarm signaling to external devices, or for Remote Emergency Power Off (REPO). The external interface connections, arranged for this purpose, are next to the option box in the Rectifier section (refer to 4.0 - Installation Drawings).
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 16
Page 23
Figure 7 Liebert EXL customer connections
TB1154 – DC Communication
TB1- Remote St atus Panel
TB2 – Digital
Inputs
TB3-SKRU Enable
Liebert EXL Control Drawer
1
2
3
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
4
1
2
3
4
1
2
3
4
5
6
7
8
9
10
Remote BackFeed Breaker (RBB)
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
1
2
3
4
5
6
7
8
9
10
Rectifi er Input Breaker (RIB )
Not Used
Reserved
for LBS
Reserved for
MMS/1+N
J1
J9
J8
J7
J6
J5
J4
J3
J2
TB9
TB6
TB7
TB4
TB5
TB8
UPS Control Drawer
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 17
Page 24
2.5.1 Dry Contacts
Table 2 UPS Digital Inputs
Item
Maintenance Bypass Breaker (MBB)
Maintenance Isolation Breaker (MIB)
Bypass Isolation Breaker (BIB) - Dual Source Input None - Single Source Input
Rectifier Feed Breaker (RFB) - Dual Source Input UPS Input Breaker (UIB) - Single Source Input
Reserved for Internal Use (SMS)/ Module Output Breaker (1+N)
REPO/EPO (N.O.)
REPO/EPO (Form-C or N.C.)
Ter mi na l
Block Pin
(Description of External Item)
TB2 1 MBB Aux Contact, Closed = Circuit Breaker is Closed
TB2 2 MBB Aux Contact Common
TB2 3 MIB Aux Contact, Closed = Circuit Breaker is Closed
TB2 4 MIB Aux Contact Common
TB2 5 BIB Aux Contact, Closed = Circuit Breaker is Closed
TB2 6 BIB Aux Contact Common
TB2 7 RFB Aux Contact, Closed = Circuit Breaker is Closed
TB2 8 RFB Aux Contact Common
TB2 9
Reserved for Internal Use (SMS)/MOB Aux Contact, Closed = Circuit Breaker is Closed (1+N)
TB2 10 Reserved for Internal Use (SMS)/MOB Aux Contact Common (1+N)
TB2 11 REPO Switch, Normally Open Contact
TB2 12 REPO Switch, Normally Open Common
TB2 13 REPO Switch, Normally Closed Contact
TB2 14 REPO Switch, Normally Closed Common
REPO/EPO (Form-C) TB2 15 REPO Switch, Normally Open Contact
REPO/EPO Additional Common TB2 16 REPO Switch, Normally Closed Common
Key Status
On Generator
1. All contacts have: Maximum voltage: 24VDC
Maximum current: 10mA Wire range: #14-22AWG Maximum length: 500' (150m)
2. All external wire furnished by others
3. All wiring must be in accordance with national and local electrical codes
4. If using REPO/EPO with Form-C contacts, Pins 13-15 must be used
5. If using REPO/EPO with normally closed (N.C.) contacts only, a jumper must be placed across Pins 15 and 16
TB2 17 Key Status Switch, Closed = Key Released
TB2 18 Key Status Switch, Common
TB2 19 On Generator (NO)
TB2 20 On Generator (COM)
Connect to
Table 3 UPS Output
Item
SKRU Enable TB3
1. To prevent signal interference, low-voltage (<48V) and low-current (5A) cable groups should be run in separate, grounded conduit from high-voltage or high-current cable groups.
2. All external wire furnished by others.
3. All wiring must be in accordance with national and local electrical codes.
Ter mi nal
Block
Pin
1SKRU Enable Common
3 SKRU Enabled, Contact is Closed
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 18
Connects to
(Description of
External Item)
Maximum
Vol tag e
120VAC 1A #14-22 AWG 164ft. (50m)2 SKRU Enabled, Contact is Open
Maximum
Current
Wire
Range
Maximum
Length
Page 25
Table 4 UPS control contacts to Battery Interface Boards
Reserved
for LBS
Reserved for
MMS/1+N
J1
J9
J8
J7
J6
J5
J4
J3
J2
J1
J9
J8
J7
J6
J5
J4
J3
J2
UPS 1 UPS 2 UPS n
Cat 6 Cable
NC
NC
J1
J9
J8
J7
J6
J5
J4
J3
J2
Item
Ter mi nal
Block
Pin
(Description of
External Item)
Maximum
Vol tag e
Maximum
Current
Wire
Range
Maximum
Length
1CAN +24V
Connects to
Battery Cabinet Communication
TB1154
2CAN Common
3CANbus High
24VDC 2A 18AWG
1000ft
(305m)
4CANbus Low
1. To prevent signal interference, low voltage (<48V) and low current (5A) cable groups should be run in separate grounded conduit from high voltage or high current cable groups.
2. All external wire furnished by others.
3. All wiring must be in accordance with national and local electrical codes.
4. The maximum length must take into account all battery communications connections in the system.
Table 5 UPS control contacts to Remote Status Panel
Connects To
Item
Ter mi na l
Block
Pin
TB1
Remote Status Panel
TB1154
1. To prevent signal interference, low voltage (<48V) and low current (5A) cable groups should be run in separate grounded conduit from high voltage or high current cable groups.
2. All external wire furnished by others.
3. All wiring must be in accordance with national and local electrical codes.
(Description of
External Item)
1CAN +24V
2CAN Common
3CANbus High
4CANbus Low
Maximum
Vol tag e
Maximum
Current
Wire
Range
24VDC 150mA 18AWG
Maximum
Length
1000ft
(305m)
2.5.2 Multi-Module Communication
Paralleling cables that connect the module to other modules in the 1+N system are connected via Terminals J1­J6 customer connections on the control drawer. See Figure 8.
Figure 8 UPS MMS/1+N connectivity
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 19
Page 26
2.6 DIGITAL LBS
Reserved for LBS
Reserved for
MMS/1+N
J1
J9
J8
J7
J6
J5
J4
J3
J2
J1
J9
J8
J7
J6
J5
J4
J3
J2
UPS 1 UPS 2 UPS n
Cat 6 Cable
NC
NC
To next set of
modules, UPS1-J7
NC
NC
NC
NC
NC
NC
Cat 6 Cable
J1
J9
J8
J7
J6
J5
J4
J3
J2
The Load Bus Sync interface enables independent UPS units to remain in sync when operating on battery or when supplied by unsynchronized input sources.
Digital LBS cables that connect the module to the system are connected to Terminals J7-J9 customer connections on the control drawer. See Figure 9.
Figure 9 LBS connectivity
2.7 GROUNDING
2.7.1 Three-Wire Input connections
This module must NOT be used when single-phase loads are directly connected to the UPS. Note that whenever the UPS module transfers to or from bypass, two AC sources (UPS output and bypass) are briefly connected together and circulating current must flow. In this configuration, the current flows through the ground path and may trip ground fault interrupters (GFI’s), distorting the output voltage waveform. Proper adjustment of GFI’s is necessary to avoid unwanted tripping. The time delay should be set to at least 0.2 seconds to prevent tripping when the UPS performs a transfer or retransfer operation.
2.7.2 High Resistance Grounding
Contact your Vertiv® representative or the factory to determine whether the Liebert EXL is compatible with the specific type of HRG system involved.
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 20
NOTICE
Failure to set the ground fault interrupters properly could cause loss of power to the critical load.
Page 27
2.7.3 Preferred Grounding Configuration, Battery Systems
Open-rack battery systems, depending on local code requirements and customer preference, are normally:
• Floating (ungrounded) OR
• Center-tapped and floating
Battery cabinet systems must be connected as floating (ungrounded) systems.
Center-tapped or grounded battery systems are not possible with battery cabinet systems.
Whether the battery system is open-rack or cabinet, the metal rack parts or cabinet must be grounded to the UPS module ground bus.
2.8 INTERNAL BREAKER SETTINGS
All internal breakers—CB1, CB2 and BFB—were installed and set at the factory.
NOTICE
Risk of incorrect adjustment. Can cause equipment damage. Factory circuit breaker settings must not be altered without contacting Vertiv
®
customer support.
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 21
Page 28
3.0 OPTIONAL EQUIPMENT
3.1 SINGLE-MODULE SYSTEM OPTIONS
3.1.1 Battery Temperature Sensor
The optional external battery temperature sensor kit, supplied separately from the battery circuit breaker, contains one probe and one temperature transport board.
3.1.2 Matching Liebert EXL Battery Cabinet
The optional matching Liebert EXL Battery Cabinet can be used to obtain the desired autonomy time. The battery cabinets are designed to be either attached to the UPS or separate from the UPS (for details, see the Liebert EXL Battery Cabinet installation manual, SL-26035, available at Vertiv’s Liebert Web site:
www.liebert.com ).
3.1.3 Remote Alarm Status Panel
The remote alarm status panel has LED alarm lights. An audible alarm sounds upon any alarm condition. The surface- or flush-mounted NEMA 1 enclosed panel indicates: Load on UPS, Load on Bypass, Battery Discharging, Low Battery Warning, Overload Warning, Ambient Overtemp Warning, UPS Alarm Condition, New Alarm Condition (For a Second UPS Alarm Condition).
3.2 REMOTE BREAKER UPS INSTALLATION
The remote breaker option has remote circuit breakers for both CB1 and the BFB. These remote circuit breakers are referred to as the Rectifier Input Breaker (RIB) and Remote Backfeed Breaker (RBB).
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 22
Page 29
Figure 10 Customer connections (remote breaker)
TB1154 – DC Communication
TB1- Remote Status Panel
TB2 – Digital
Inputs
TB3-SKRU Enable
Liebert EXL Control Drawer
1
2
3
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
4
1
2
3
4
1
2
3
4
5
6
7
8
9
10
Remote BackFeed Breaker (RBB)
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
1
2
3
4
5
6
7
8
9
10
Rectifier Input Breaker (RIB)
Not Used
Reserved
for LBS
Reserved for
MMS/1+N
J1
J9
J8
J7
J6
J5
J4
J3
J2
TB9
TB6
TB7
TB4
TB5
TB8
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 23
Page 30
3.3 RECTIFIER INPUT BREAKER (RIB)
Unless noted other wise, wiring symbols used define t he followi ng:
Notes:
Twisted pair/triple control wiring.
Control wi ring by others.
A
B
C
E
RIBX
60A
IN_LINE_A
IN_LINE_B
IN_LINE _C
F23
F22
V_IN_R_A
V_IN_R_B
V_IN_R_C
K2
K2_4
K2_5
TB7
TB6
TB7-4 ( DRV)
TB7-3 (NO [C B CLOSED])
TB7-2 (NC [CB OPEN])
TB7-5 (+ 48V)
TB7-1 (CO M)
Inside UPS Cabinet
RIBX UVR Coil
(48VDC )
RIBX Stat us
Contacts
RIBX Form C
Contact ( Spare)
2x1
RIBX
240 VAC
(Supplied by
Switchgear Vendor )
TB6-10 (MT R_OP_ CLOSE)
TB6-08 (MT R_OP_ ENABLE)
Inside Switchgear
To Customer
Input Terminals
2x2
1x5 1x4
2x5
2x4 2x3
1 x 1
1 x 2
1 x 3
RIBX
2x6
2x8 2x7
1
1
Fuses should be 60A class CC or J type ti me delay fuse
Connects to P 101 on HV Attenuator Burden Bd 518691G1
Connects to Relay K 2 for Fan Power
TB10
TB10-1
TB10-2
TB10-3
Electri cal operator power provi ded by swit chgear vendor and shall be power ed fr om line side of RIBX
These are term inals numbers on t he switchgear where x designates t he unit number . Example, for x=1, RIBX woul d be RIB1.
F24
K2_6
F51
F50
P101
P101_5
P101_3
F52
P101_1
F29
F28
P3
P3_5
P3_1
Connects to P 3 on Power Oring Bd 418581 G1
F21
F20
K3
K3_1
K3_3
F46
F45
K4
K4_1
K4_3
Connects to Relay K 3 for DC bus precharge
Connects to Relay K 4 for DC bus precharge on 1200 kVA and above
TB11
PH A
TB12
PH B
TB13 PH C
EMIEMIEM I
EMI Cores
5 Turns
through Cor e
7
60A60A
12
12
12
8
12
12
12
12
12
12
12
12
12
12
12
12
2
3
4
5
6
7
8
Close
RIBX Electric al Operator
240 VAC
2
3
4
5
6
For systems that use a Rectifier Input Breaker (RIB), the controls for the Aux contact, UVR, Motor Operator and voltage sense will go between the remote breaker and the UPS input I/O section. See Figure 11.
Figure 11 Rectifier Input Breaker diagram
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 24
Page 31
Table 6 Rectifier Input Breaker specifications
Power
Class
625-
800kVA
1000-
1200kVA
kAIC
rating
65kA
Module
100kA
Module
65kA
Module
100kA
Module
RIB Specification
UL-Listed 489 (Molded Case Circuit Breaker) or UL 1066 (Low Voltage AC Power Circuit Breaker), which are required for use in UL-listed switchgear or switchboards. The circuit breaker must have a short-time rating of 65kA at a maximum voltage of 480V for three cycles.
UL-Listed 489 (Molded Case Circuit Breaker) or UL 1066 (Low Voltage AC Power Circuit Breaker), which are required for use in UL-listed switchgear or switchboards. The circuit breaker must have a short-time rating of 100kA at a maximum voltage of 480V for three cycles.
UL-Listed 489 (Molded Case Circuit Breaker) or UL 1066 (Low Voltage AC Power Circuit Breaker), which are required for use in UL-listed switchgear or switchboards. The circuit breaker must have a short-time rating of 65kA at a maximum voltage of 480V for three cycles.
UL-Listed 489 (Molded Case Circuit Breaker) or UL 1066 (Low Voltage AC Power Circuit Breaker), which are required for use in UL-listed switchgear or switchboards. The circuit breaker must have a short-time rating of 100kA at a maximum voltage of 480V for three cycles.
RIB General Specification
The remote breaker must be equipped with UVR and auxiliary contacts for proper operation with the UPS.
The remote breaker must be equipped with UVR and auxiliary contacts for proper operation with the UPS.
Comments
No UPS internal fuse protection on rectifier and bypass input.
No UPS internal fuse protection on the rectifier input. The bypass input has fuse protection.
No UPS internal fuse protection on rectifier and bypass input.
UPS internal fuse protection exists on rectifier and bypass input.
Table 7 Rectifier Input Breaker contacts
Item
Not Used
Not Used
Not Used
Ter mi nal
Block Pin
TB6 1 Not Used
TB6 2 Not Used
TB6 3 Not Used
TB6 4 Not Used
TB6 5 Not Used
TB6 6 Not Used
(Description of External Item)
Not Used TB6 7 Not Used
Breaker Motor Operation TB6 8 Motor Operation Enable (240VAC)
Not Used TB6 9 Not Used
Breaker Motor Operation TB6 10 Motor Operation Close Coil
TB7 1 RIB Aux Status Common
Breaker Auxiliary Status
TB7 2 RIB Aux Status, Normally Closed Contact, Closed = CB is Open
TB7 3 RIB Aux Status, Normally Open Contact, Open = CB is Open
Breaker UVR Control
1. For TB7, Pins 1-3, each contact has: Maximum voltage: 24VDC Maximum current: 10mA Wire range: #14-22AWG Maximum length: 500 ft. (150m)
2. All external wire field-supplied.
3. All wiring must be in accordance with national and local electrical codes.
TB7 4 RIB UVR Return
TB7 5 RIB UVR +48VDC
Connect to
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 25
Page 32
3.4 REMOTE BACKFEED BREAKER
Unless noted otherwise , wiring sy mbols used define the following :
Notes:
Twisted pair /triple contr ol wiring
Control wiri ng by others
A
B
C
E
RBBX
5A
BYP_LINE_A
BYP_LINE_B
BYP_LINE_C
V_BYP_R_A
V_BYP_R_B
V_BYP_R_C
Inside UPS Cabinet
RBFBX ST Coil
(48VDC)
RBFBX Status
Contacts
RBFBX Form C Contact ( Spare)
240 VAC
Close
4x1
RBFBX
RBFBX
Electric al
Operator
240 VAC
(Supplied by
Switchgear Vendor )
Inside Switchgear
To Customer
Bypass
Terminals
4x2
3x5
3x4
4x5
4x4
4x3
3X1
3X2
3X3
RBBX
4x6
4x8
4x7
1
Fuses s hould be 5A c lass CC or J ty pe time delay fuse
TB14
TB14-1
TB14-2
TB14-3
Electric al operator power provided by switchgear vendor and s hall be powered from line side of RBFB X
5
These are ter minals numbers on the sw itchgear where x des ignates the unit number . Ex ample, for x= 1, RBFBX would be R BFB1.
F64
F63
P300_3
P300_2
F65
P300_ 1
Connects to T4 Bypas s PS Transformer
F38
F37
T4
T4_H4
2
F35
F34
P300
P300_7
P300_6
Connects to P300 for B ypass Voltage Sens e on HV Attenuator Bd 518691 G1 and By pass Supply on Pow er Oring bd 418581G 1
R1
T4_H1
TB5
TB4
TB5-4 (DRV) TB5-3 (NO [CB CLOSED]) TB5-2 (NC [CB OPEN])
TB5-5 ( +48V)
TB5-1 (CO M)
TB4-10 (MTR_ OP_C LOSE) TB4-08 (MTR_OP_ENABLE)
EMIEMIEMI
EMI Cores
5 Turns thru Core
4
1
5A
5A
12
12
12
12
12
12
12
12
12
12
3
2
3
4
5
For systems that use a Remote Backfeed Breaker (RBB), the controls for the Aux contact, shunt trip and voltage sense will go between the remote breaker and the UPS output I/O section. See Figure 12.
Figure 12 Remote Backfeed Breaker diagram
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 26
Page 33
Table 8 Remote Backfeed Breaker specifications
Power
Class
625-
800kVA
1000-
1200kVA
kAIC
rating
65kA
Module
100kA
Module
65kA
Module
100kA
Module
RBB Specification
UL-Listed 489 (Molded Case Circuit Breaker) or UL 1066 (Low Voltage AC Power Circuit Breaker), which are required for use in UL-listed switchgear or switchboards. The circuit breaker must have a short-time rating of 65kA at a maximum voltage of 480V for three cycles.
UL-Listed 489 (Molded Case Circuit Breaker) or UL 1066 (Low Voltage AC Power Circuit Breaker), which are required for use in UL-listed switchgear or switchboards. The circuit breaker must have a short-time rating of 100kA at a maximum voltage of 480V for three cycles.
UL-Listed 489 (Molded Case Circuit Breaker) or UL 1066 (Low Voltage AC Power Circuit Breaker), which are required for use in UL-listed switchgear or switchboards. The circuit breaker must have a short-time rating of 65kA at a maximum voltage of 480V for three cycles.
UL-Listed 489 (Molded Case Circuit Breaker) or UL 1066 (Low Voltage AC Power Circuit Breaker), which are required for use in UL-listed switchgear or switchboards. The circuit breaker must have a short-time rating of 100kA at a maximum voltage of 480V for three cycles.
RBB General Specification
The remote breaker must be equipped with shunt trip and auxiliary contacts for proper operation with the UPS.
The remote breaker must be equipped with shunt trip and auxiliary contacts for proper operation with the UPS.
Comments
No UPS internal fuse protection on rectifier and bypass input
No UPS internal fuse protection on the rectifier input. The bypass input has fuse protection.
No UPS internal fuse protection on rectifier and bypass input
UPS internal fuse protection exists on rectifier and bypass input
Table 9 Remote Backfeed Breaker contacts
Item
Not Used
Not Used
Not Used
Not Used TB4 7 Not Used
Not Used TB4 8 Not Used
Not Used TB4 9 Not Used
Not Used TB4 10 Not Used
Breaker Auxiliary Status
Breaker ST Control
1. For TB7, Pins 1-3, each contact has:
Maximum voltage: 24VDC Maximum current: 10mA Wire range: #14-22AWG Maximum length: 500 ft. (150m)
2. All external wire field-supplied.
3. All wiring must be in accordance with national and local electrical codes.
Terminal Block Pin
Connect to (Description of External Item)
TB4 1 Not Used
TB4 2 Not Used
TB4 3 Not Used
TB4 4 Not Used
TB4 5 Not Used
TB4 6 Not Used
TB5 1 RBB Aux Status Common
TB5 2 RBB Aux Status, Normally Closed Contact, Closed = CB is Open
TB5 3 RBB Aux Status, Normally Open Contact, Open = CB is Open
TB5 4 RBB ST Return
TB5 5 RBB ST +48VDC
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 27
Page 34
3.5 COMMUNICATION AND MONITORING
Terminal blocks are inside the
control drawer in the
Liebert EXL’s input cabinet.
See Figure 14 or 15 for the
drawer’s location.
The Liebert EXL has these monitoring options:
• Liebert IntelliSlot® Unity-DP (Dual Protocol) Card The Liebert IntelliSlot Unity Card provides Web, embedded Vertiv
IP/MSTP, Modbus TCP/RTU, SMTP, SMS, and telnet communication and control capabilities in one unified communication platform. The platform supports 10/100 Mbit Ethernet, IPv4 and IPv6, HTTP/HTTPS for device Web page access, SMTP interface for e-mail, SMS interface for text messaging, Vertiv Protocol for communicating with Trellis software applications and LIFE technology for supporting Liebert Remote Service Delivery. SNMP v1/v2c/v3, Modbus TCP/IP, BACnet IP, Modbus RTU, BACnet MSTP and YDN23 third-party protocols are also supported for building management and network management applications. The Liebert IntelliSlot Unity card provides ground fault isolated 10/100 baseT Ethernet and RS-485 network connectivity.
• Programmable Relay Board
• Input Contact Isolator Board
Figure 13 Terminal block locations—input cabinet
®
LIFE™ Technology, Vertiv Protocol, SNMP, BACnet
and Liebert Nform®
3.5.1 Alber® Monitoring System
The matching Liebert EXL Battery Cabinet has space for an Alber battery monitoring system. The battery monitoring system can be factory-installed or field-installed later.
The Alber Battery Monitor by Vertiv continuously checks all critical battery parameters, such as cell voltage, overall string voltage, current and temperature. Automatic periodic tests of internal resistance of each battery will verify the battery’s operating integrity. Capabilities include automatic internal patented DC resistance tests and trend analysis, providing the ability to analyze performance, aid in troubleshooting and detect failing cells before they fail.
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 28
Page 35
4.0 INSTALLATION DRAWINGS
CORE
OUTPUT/BYPASS
CORE
U46-8C-2000 Rev. 5
DOORS AND INNER SKINS NOT SHOWN
Options Box (5 Slots)
Liebert IntelliSlot Housings
Motor Operated Circuit Breaker (CB1)
Module Output Circuit Breaker (CB2)
Backfeed Circuit Breaker (BFB)
Input Ground
Control Drawer
Input Busbars
DC Input
Output Busbars
Bypass Busbars
High-Voltage Sense Test Points
INPUT
Output Ground Busbar
Back Feed Circuit Breaker (BFB)
Module Output Circuit Breaker (CB2)
Bypass Busbars
Output Ground Busbar
Output Busbars
Liebert IntelliSlot Housings
Motor Operated Circuit Breaker (CB1)
Options Box (5 Slots)
High-Voltage
Sense
Test Points
DC Input
Input
Busbars
Input
Ground
Control Drawer
OUTPUT/BYPASSCORE CORE COREINPUT
U46-12C-2000 Rev. 3
DOORS AND INNER SKINS NOT SHOWN
The difference between an SMS and 1+N configuration is that the 1+N has sharing inductors present behind CB2 (not visible in drawing).
Figure 14 Typical main components, 625-800kVA Liebert EXL UPS, SMS and 1+N multi-module unit
Figure 15 Typical main components, 1000-1200kVA Liebert EXL, SMS and 1+N multi-module unit
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 29
Page 36
Figure 16 Main components for remote breaker configuration—Single module with static bypass or 1+N multi-module;
Module Output Circuit Breaker (CB2)
Bypass Busbars
Output Ground Busbar
Output Busbars
Liebert IntelliSlot Housings
Option Box
(5 Slots)
High-Voltage
Test Points
DC Input
Input
Busbars
Input Ground
Control Drawer
Output/BypassCore CoreInput
U46-8C-2002 Rev. 0
DOORS AND INNER SKINS NOT SHOWN
On Input/Output Cabinets
This illustration shows components based on remote installation of both the Rectifier Input Breaker (RIB) and Remote Backfeed Breaker (RBB).
Modul
O
C
B
(
)
By
B
p
G
B
O
Busb
S
g
H
Te s
s
D
B
G
C
D
O
SS
E
CORE
CORENPU
1
N
s
)
625kVA-800kVA
Figure 17 Main components for remote breaker configuration—Single module with static bypass or 1+N multi-module;
igh-Voltage
t Point
C Input
Input
usbars
Input
ontrol rawer
10 00 kVA- 120 0k VA
tions Box
5 Slots
round
T
Liebert Intelli Housin
lot
s
COR
DOORS AND INNER SKINS NOT SHOW
n Input/Output Cabinet
U46-12C-2002 Rev.
UTPUT/BYPA
utput ircuit reaker
CB2
pass
usbars
Out
round
usbar
utput
ars
e
ut
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 30
Page 37
Figure 18 Outline Drawing, 625-800kVA Liebert EXL UPS, SMS and 1+N multi-module unit
Notes
1. 24" (610mm) minimum clearance above unit required for air exhaust, and 36" (914mm) front access required for service.
2. Keep cabinet within 15 degrees of vertical while handling.
3. Top and bottom cable entry available through removable access plates. Remove punch to suit conduit size and replace.
4. Unit bottom is structurally adequate for forklift handling.
5. Control wiring and power wiring must be run in separate conduits.
6. All wiring is to be in accordance with national and local electrical codes.
7. Width dimension includes side panels. Subtract 1.4" (35mm) when removing both side panels.
8. See technical information drawing for shipping split weights.
To Frame
2.6" (65mm)
To
Frame
1.3"
(33mm)
U46-8C-2001 Rev. 3
RIGHT SIDE VIEW
33.5"
(851mm)
34.4"
(874mm)
77.5"
(1969mm)
With Accent Strip
See
Bottom
View
38.5"
(978mm)
51.2"
(1300mm)
123.6" (3140mm)
33.9"
(862mm)
To Frame
2.4" (60mm)
4" (101mm)
to Frame
Rectifier\DC
Cable Entry, Area
With Panel Removed
12.5" x 21.9"
(318mm x 556mm)
Rectifier\DC Cable Entry, Area With Panel Removed (23.5" x 21.8" (597mm) x 553mm)
Panel to Frame
Typical
Opposite
Side
To Frame
1.3" (33mm)
14.3" (363mm) to Frame
To Frame Typ
Opposite Side
1.6" (40mm)
Low-Voltage Cable Entry\Exit, Area With Panel Removed
4.9" x 21.8" (125mm x 553mm)
Bypass\ Output Cable Exit, Area With Panel Removed
10.9" x 28.4" (278mm x 722mm)
1.4" (37mm)
Section A - (Top Looking Down)
BOTTOM VIEW
Input Core Core Output/Bypass
TOP VIEW
FRONT VIEW
Low Voltage Cable Entry \ Exit, Area With Panel Removed
8.8" x 9.8" (224mm x 250mm)
Bypass\Output Cable Exit, Area With Panel Removed
12.5" x 23.2" (318mm x 590mm)
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 31
Page 38
Figure 19 Outline Drawing, 1000-1200kVA Liebert EXL UPS, SMS and 1+N multi-module unit
1.3" (33mm)
Typical Opp. Side
Low-Voltage Cable
Entry/Exit, Area
With Panel Removed
6.0" x 32.2"
(152 x 819mm)
Rectifier/DC
Cable Entry, Area
With Panel Removed
14.7" x 33.3"
(373 x 846mm)
Low-Voltage Cable
Entry/Exit, Area
With Panel Removed
10.6" x 7.9"
(269 x 7.9mm)
47"
(1193mm)
2.4" (60mm) To Frame
To Frame
(50mm)
1.3" (33mm)
2"
26.7" (679mm) To Frame
170.7" (4335mm)
To Frame
76.7" (1949mm)
Rectifier/DC Cable Entry, Area With Panel Removed
22.7" x 32.2" (577 x 819mm)
Section A (Top Looking Down)
BOTTOM VIEW
FRONT
TOP
47"
(1193mm)
Bypass/Output
Cable Exit, Area
With Panel Removed
28.7" x 14.3"
(730 x 364mm)
2.4" (60mm) To Frame
1.3" (33mm) To Frame
3" (77mm)
To Frame
Bypass/Output
Cable Exit, Area
With Panel Removed
25.4" x 15.7"
(645 x 399mm)
A
INPUT
NOTES
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit required for air exhaust; 36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical while handling.
4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in separate conduits.
7. All wiring is to be in accordance with national and local electrical codes.
8. Width dimension includes side panels. Subtract 1.4" (35mm) when removing both side panels.
9. See technical information drawing for shipping split weights.
CORE CORE CORE OUTPUT/BYPASS
FRONT
A
See Bottom View
33.5"
(850mm)
34.4"
(874mm)
RIGHT SIDE
U46-12C-2001 Rev. 2
77.5"
(1969mm)
With Accent Strip
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 32
Page 39
Figure 20 Base drawing, 625-800kVA Liebert EXL UPS, SMS and 1+N multi-module unit
1. All dimensions are in inches (mm).
2. Unit bottom is structurally adequate for forklift handling.
Forklift Openings
Forklift Openings
(Top Looking Down)
Front
Front
Conduit Plate Behind Support Rail
Input
Front
Core Output/BypassCore
Oppo. Side, Typ
U46-8l-1000 Rev. 0
Right Side
Lift Clearance
FRONT VIEW
27.8
(705)
16.4 (416)
12.8 (324)
BOTTOM VIEW Footprint Spacing
26.2
(665)
6.1 (155)
3.9 (99) Oppo. Side Typ
BOTTOM OUTPUT Right Side Bottom Cable Entry Panels
18.5
(470)
18.5
(470)
14.8
(376)
11. 2
(284)
7.1
(180)
3.5
(90)
7.1
(180)
7.1
(180)
4.7
(120)
3.5
(90)
20.5
(520)
20.5
(520)
23.8 (605)
Oppo. Side Typ.
25.6 (651) Pillar Spacing Inside
31.3 (795) Pillar Spacing Outside
23.8 (605)
Foot Spacing
Inside
30.8 (781)
Foot Spacing
Outside
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 33
Page 40
Figure 21 Base drawing, 1000-1200kVA Liebert EXL UPS, SMS and 1+N multi-module unit
23.8 (605)
Opposite Side
Typical
NOTES:
1. All dimensions are in inches (mm).
2. Unit bottom is structurally adequate for forklift handling.
Input
Core
Core
Core
Output/Bypass
18.8
(478)
18.8
(478)
18.8
(478)
18.8
(478)
18.5
(470)
18.5
(470)
18.5
(470)
40.7 (1035)
3 (99) Opposite Side Typical
FRONT VIEW
Forklift Openings Forklift Openings
20.5
(520)
20.5
(520)
20.5
(520)
31.3 (795)
Pillar Spacing
Outside
25.6 (651)
Pillar Spacing
Inside
30.8 (781)
Foot Spacing
Outside
23.8 (605)
Foot Spacing
Inside
Opposite
Side
BOTTOM OUTPUT
Right Side
Bottom Cable Entry Panels
BOTTOM VIEW
(Top Looking Down)
Footprint Spacing
2.8 (70)
Foot to Pillar
3.1
(80)
6.3
(160)
6.3
(160)
7.1
(180)
7.1
(180)
RIGHT SIDE
Lift Clearance
U46-12L-1000 Rev. 0
2.8 (70)
Foot to Pillar
Front
Front
6.1 (155)
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 34
Page 41
Figure 22 Input and battery terminal detail, 625-800kVA Liebert EXL UPS, SMS and 1+N multi-module unit
1.26 (32) Typ.
2.07 (53) Typ.
2.05 (52) Typ.
2.08 (53) Typ.
1.75 (44)
1.75 (44)
Ø.56 (14) Typ.
Ø.56 (14) Typ.
Ø.56 (14) Typ.
Ø.56 (14) Typ.
Notes
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduits.
3. All wiring is to be in accordance with national and local electrical codes.
4. Based on NEC 408.56 minimum spacing, all live parts, including lugs, must be at least 1" (25mm) from any other live part from a different phase or the chassis frame. If lug stacking is required, the method of stacking and required minimum spacing are the responsibility of the installing contractor and authority having jurisdiction.
LEFT SIDE VIEW
INPUT
ISOMETRIC
VIEW
LEFT SIDE VIEW
TILTED DOWN
TO SHOW BUSBARS
U46-8E-3200B Rev. 3
#1 Input Phase Busbar 20.5 x 4 x .38
#3
#3
#2 DC Pos. / Neg. Busbar 20.1 x 4 x .5
#3 Input Ground Busbar 25.4 x 3 x .25
(See Isometric View)
23
(584)
42.8
(1088)
#1 #1
#2
1.75 (44)
1.75 (44)
SE-556101
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 35
Page 42
Figure 23 Input and battery terminal detail, 1000-1200kVA Liebert EXL UPS, SMS and 1+N multi-module unit
NOTES
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduits
3. All wiring is to be in accordance with national and local electrical codes.
4. See Page 1, Drawing U46-12E-3200A and Page 3, Drawing U46-12E-3200C.
5. Based on NEC 408.56 minimum spacing, all live parts, including lugs, need to be at least 1 inch (25.4mm) from any other live part from a different phase or the chassis frame. If lug stacking is required, the method of stacking and required minimum spacing is the responsibility of the installing contractor and authority having jurisdiction (AHJ).
1.75 (44)
Ø 0.563 (14) Typical
U46-12E-3200B Rev. 0
2.06 (52.4) Typical
SECTION OF
LEFT SIDE VIEW
Tilted Down to Show Busbars
LEFT SIDE VIEW
Input
1
1
2
3
4
FRONT
43.7
(1109)
1. Input Ground Busbar 29.5 x 5 x .25
Ø 0.624 x 1 (16 x 25.4) 2 Places
2.2 (56)
2.5 (64)
1.97 (50)
1.97 (50)
2.09 (5.3)
1.75 (44)
Ø 0.563 x .875 (14x22) Typical
3. Input Phase Busbar 18.6 x 3.5 x .5
1.75 (44)
Ø 0.563 (14) Typical
2.04 (52) Typical
4. DC Pos. / Neg. Busbar 18.7 x 6 x .5
2.04 (52) Typ.
1.75 (44)
Ø 0.563 x .875 (14x22) Typical
2. Input Aux. Ground Busbar 21.6 x 5 x .25
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 36
Page 43
Figure 24 Output and bypass terminal detail, 625-800kVA Liebert EXL UPS, SMS and 1+N multi-module unit
2.36" (60mm) Typ.
#6 Output Ground Busbar 25.4 x 3 x .25
2.36" (60mm) Typ.
#5 Phase Output Busbar 17.7 X 4 X .25
2.36"
(60mm)
Typ.
1.97"
(50mm)
Typ.
2.36"
(60mm)
Typ.
#4 Bypass Input Busbar 38.2 x 4 x .25
Ø .56" (14mm) Typ.
1.44" (37mm)
1.0" (25mm) Typ.
Ø .56" (14mm) Typ.
1.75" (44mm)
Ø .56" (14mm) Typ.
1.43" (36mm)
4
6
5
58.4"
(1484mm)
30.3"
(770mm)
18.5"
(469mm)
Notes:
1. Control wiring and power wiring must be run in separate conduits
2. All wiring is to be in accordance with national and local electrical codes.
3. See Page 1, Drawing U46-8E-3200A and Page 2, Drawing U46-8E-3200B.
4. Based on NEC 408.56 minimum spacing, all live parts, including lugs, must be at least 1" (25mm) from any other live part from a different phase or the chassis frame. If lug stacking is required, the method of stacking and required minimum spacing is the responsibility of the installing contractor and authority having jurisdiction.
Dual Hole Lug Pad Width (Max.)
1.75" (44mm)
RIGHT SIDE VIEW OUTPUT/BYPASS
U46-8E-3200C Rev. 3
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 37
Page 44
Figure 25 Output and bypass terminal detail, 1000-1200kVA Liebert EXL UPS, SMS and 1+N multi-module unit
5. Bypass Input Busbar 44.3" x 3.5" x .5" (1125 x 89 x 13mm)
1.75" (44mm) Typical
6. Output Ground Busbar 28.4" x 5" x .25"
(722 x 127 x 7mm)
1.97" (50mm)
2.63"
(67mm)
Ø 0.563" x 1.375" (14 x 35mm) Typical
7. Output Phase Busbar 29.5" x 4" x .375"
(749 x 102 x 10mm)
Ø 0.563" (14mm), Typical
Ø 0.563" (14mm), Typical
1.56" (39.6mm)
Ø 0.563" x 1.375" (14 x 35mm) Typical
5
1.75" (44mm)
6
7
1.56" (39.6mm)
1.75"
(44mm)
Typical
Notes:
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduits
3. All wiring is to be in accordance with national and local electrical codes.
4. See Page 1, Drawing U46-12E-3200A and Page 2, Drawing U46-12E-3200B.
5. Based on NEC 408.56 minimum spacing, all live parts, including lugs, must be at least 1 inch (25.4mm) from any other live part from a different phase or the chassis frame. If lug stacking is required, the method of stacking and required minimum spacing is the responsibility of the installing contractor and authority having jurisdiction (AHJ).
Ø 0.563" x 1.375" (14 x 35mm) Typical
Dual Hole Lug Pad Width (Max.)
1.75" (44mm)
20.9"
(531mm)
RIGHT SIDE
Output/Bypass
U46-12E-3200C Rev. 0
54.4"
(1381mm)
23"
(585mm)
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 38
Page 45
Figure 26 Input, output and bypass terminal spacing details, 625-1200kVA Liebert EXL UPS, SMS and 1+N multi-module unit
U46-8E-3200A Rev. 0
3
[75]
Typ.
3 (75) Typ.
Between Busbars
TOP VIEW
#1 Input Phase Busbar #2 DC Positive / Negative Busbar #3 Input Ground Busbar #4 Bypass Input Busbar #5 Phase Output Busbar #6 Output Ground Busbar
SEE BUSBAR DETAIL PAGES 2 & 3
1. All dimensions are in inches [mm].
2. Control wiring and power wiring must be run in separate conduits.
3. All wiring is to be in accordance with national and local electrical codes.
4. See Page 2, Drawing U46-8E-3200B and Page 3, Drawing U46-8E-3200C.
Input Output/Bypass
#2#1
#3
BCA
+
-
#6
#4
A B C
#5
A B C
(Front)
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 39
Page 46
Figure 27 Low-voltage cable routing
Use these entry holes for Liebert IntelliSlot Unity card cables only
Use these entry holes for Liebert IntelliSlot
®
Unity™ card
cables only
DOORS AND INNER SKINS REMOVED
INPUT
Low Voltage Control Cable
Top Entry
Low Voltage Wire Way
Low-Voltage Control Cable
Bottom Entry
Provide at least 18" (457mm) of service loop to all control connections to permit opening the service drawer without removing the connections. The extra service loop can either be left hanging or loosely attached to the corner post.
Service Drawer
Openings to Control Wire Way
To Ensure Isolation:
A
g
.
k
y
.
ll wiring must have insulation rated
for 600V or hi
her
•All cables not rated Class 1 must be ept separated and secured awa
from high-voltage Class 1 cables
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 40
Page 47
Figure 28 Cabling for single input configuration
NOTES
1. 24" (610) minimum clearance above the unit is required for air exhaust.
2. Top and bottom cable entry is available through removable access plates. Remove, punch to suit conduit size and replace.
3. All wiring is to be in accordance with national and local electrical codes.
4. See Ta bl e 1 8 for cable sizing
5. Connections between the rectifier and bypass busbars are supplied by others.
6. Based on NEC 408.56 minimum spacing, all live parts, including lugs, must be at least 1 inch (25.4mm) from any other live part from a different phase or the chassis frame. If lug stacking is required, the method of stacking and required minimum spacing is the responsibility of the installing contractor and the authority having jurisdiction. See Figures 22 - 26 for busbar details.
625-800kVA unit
shown, similar
configuration for
1000-1200kVA unit
Output/Bypass
Core
Input
Core
Output/Bypass
Core
Input
Core
Note 1
1. Customer control wiring connection points are Terminals 1 through 16 (see Ta ble 11 ).
2. Customer-provided, normally open dry contacts for user alarm messages.
3. All control wiring (by others) must be run separate from power wiring.
4. Signal voltage: 100mA @ 12VDC.
5. Maximum cable length is 500 ft. (152m) with #16AWG and flexible stranded cable.
6. All wiring must be in accordance with national and local electrical codes.
Figure 29 Optional Input Contact Isolator Board
P99
P66
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 41
12345678910111213141516
J51
Page 48
Table 10 Input Contact Isolator Board pre-assigned values
ICI #1 ICI #2
Channel #
1 Reduced Rect ILimit None
2 Reduced Batt ILimit None
3 Stop Battery Charge None
4— None
5 EcoMode Suspended None
6— None
7— None
8— None
Pre-Assigned Label Pre-Assigned Label
Table 11 Input Contact Isolator Board control wiring connections
Input Contact Pin No.
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 42
Page 49
Figure 30 Control wiring, Programmable Relay Board
1. Customer control wiring connection points are Terminals 1 through 12.
2. Programmable Relay Board option includes eight signal channels with one Form-C dry contact per channel (see Ta bl e 1 2).
3. All control wiring (by others) must be run separate from power wiring.
4. Contact ratings: 1A @ 30VDC or 125VAC @ 0.45A
5. Maximum cable length is 500 ft. (152m) with #16AWG and flexible stranded cable.
6. All wiring must be in accordance with national and local electrical codes.
P99
P66
Table 12 Programmable Relay Board pinout
Ter mi na l
Block Channel Pin No. Common
CH1 1-3 1 2 3
J71
J72
CH2 4-6 4 5 6
CH3 7-9 7 8 9
CH4 10-12 10 11 12
CH5 1-3 1 2 3
CH6 4-6 4 5 6
CH7 7-9 7 8 9
CH8 10-12 10 11 12
Normally
Closed
J71
123456 789101112
123456 789101112
J72
Normally
Open
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 43
Page 50
5.0 SPECIFICATIONS
Table 13 Liebert EXL UPS specifications
Model Size
Input Parameters
Input Voltage to Rectifier, VAC 480V 3-phase, 3-wire 480V 3-phase, 3-wire
Input Voltage to Bypass, VAC 480V 3-phase, 3-wire 480V 3-phase, 3-wire
Input Voltage Range, VAC +10% to -30% +10% to -30%
Input Frequency, Hz 60 60
Permissible Input Frequency Range, Hz 55 to 65 55 to 65
Reflected Input THDi, Nominal Voltage, Full
Load, %
Power Walk-In, sec 1 to 30 (selectable) in 1 sec. Increments 1 to 30 (selectable) in 1 sec. Increments
Battery & DC Parameters
Battery Type
Nominal Battery Bus, VDC 480V 480V
Battery Float Voltage, VDC 540V 540V
Minimum End of Discharge Voltage, VDC 384V (for VRLA / Flooded Lead Acid) 384V (for VRLA / Flooded Lead Acid)
DC Ripple Voltage in Float & Const V Ch.
Mode, %
Temperature Compensated Battery Charging Optional (with temperature probe) Optional (with temperature probe)
Output Parameters
Inverter Type IGBT-based Sine Wave PWM Controlled IGBT-based Sine Wave PWM Controlled
Output Power, kW 625 | 750 | 800 1000 | 1100 | 1200
Output Voltage, VAC 480V 3-ph, 3-wire 480V 3-ph, 3-wire
Output Voltage Regulation, % < 1% (3-phase RMS average) < 1% (3-phase RMS average)
Output Voltage Regulation (50% Unbalanced
Load)
Output Frequency, Hz 60 60
Output Frequency Regulation, % ± 0.1 ± 0.1
Output THDv Linear Load at Nominal Voltage,
Output THDv at Nominal Voltage Including a
100kVA Non-Linear Load per EN 62040-3, %
Capacity to Handle High Crest Factor Load 3:1 3:1
Capacity to handle Step Load, % 0-100 or 100-0 0-100 or 100-0
Step Load Transient Recovery (linear loads),
Unbalance Loads Current Capacity 100% of nominal phase current 100% of nominal phase current
Load Power Factor Supported (Without
Derating)
Voltage Displacement, ° (Electrical Degree) 120° ±1° (with 50% unbalanced load) 120° ±1° (with 50% unbalanced load)
Overload Conditions, % FL See Figures 31, 32 and 33
Physical Parameters and Standards
Width, in (mm), With Static Bypass 123.6 (3140) 170.7 (4335)
Depth, in (mm) 34.4 (874) 34.4 (874)
VRLA (Valve Regulated Lead Acid) or FLA
%
%
IEC 62040-3, Section 5.3.1 Figure 1 IEC 62040-3, Section 5.3.1 Figure 1
625-800kVA 1000-1200kVA
<5% <5%
VRLA (Valve Regulated Lead Acid) or FLA
(Flooded Lead Acid)
<1 (RMS value) < 3,4% Vpp <1 (RMS value) < 3,4% Vpp
< 2% (3-phase RMS average) < 2% (3-phase RMS average)
<3% <3%
6% (max) 6% (max)
0.7 Leading to 0.7 Lagging 0.7 Leading to 0.7 Lagging
(Flooded Lead Acid)
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 44
Page 51
Table 13 Liebert EXL UPS specifications (continued)
Model Size
Height, in (mm) 77.5 (1969) 77.5 (1969)
Weight, Unpackaged, lb. (kg)
approximate with Static Bypass (1+N)
Maximum Heat Dissipation, Full Load, BTU/hr (kW)
Cooling Air, CFM ≤4,600 ≤6,700
Color Black (ZP-7021) Black (ZP-7021)
Front Door Opening (for serviceability) 90° 90°
Degree of Protection for UPS Enclosure IP 20 (with and without front door open) IP 20 (with and without front door open)
Minimum Clearance, Top, in (mm) 24 (610) 24 (610)
Minimum Clearance, Back, in (mm) 0 0
Minimum Clearance, Sides, in (mm) 0 0
Location of Cable Entrance Top or Bottom Top or Bottom
Standards and Conformities
IEC62040-2, Level 4, Criteria A
Environmental Parameters
Storage Temperature Range, °F (°C) -4 to 104 (-20 to 40)
Operating Temperature Range, °F (°C)
1.5% maximum kW / degrees C derating up
122°F (50°C) absolute maximum with
Relative Humidity
(Operating and Non-Operating)
3300 ft.(1000m) (per IEC 62040/3) - 1%
Maximum Altitude Above MSL
1. Width dimensions are with side panels attached. Subtract 1.4" (35mm) for dimensions without side panels.
2. Depth dimensions include the front door and rear panel.
3. Contact the factory before storing at temperatures exceeding 104°F (40°C)
Maximum kW derating / 1000 ft. rise
between 3300 and 10,000 ft. (305m rise
625-800kVA 1000-1200kVA
5687 (2580) 8095 (3672)
625kVA UPS: 77,417 (22.7) 1000kVA UPS: 123,867 (36.3)
750kVA UPS: 95,653 (28.0) 1100kVA UPS: 136,253 (39.9)
800kVA UPS: 102,030 (29.9) 1200kVA UPS: 148,640 (43.5)
UL 1778, 5th Ed.
CSA 22.2 107.3
FCC Part 15, Class A
(with optional filters installed)
UL 1778, 5th Ed.
CSA 22.2 107.3
FCC Part 15, Class A
(with optional filters installed)
IEC62040-2, Level 4, Criteria A
ANSI C62.41, Category A3 &B3
ISTA
WEEE
3
32°F to 95°F (0°C to 35°C) at
full rated load
ANSI C62.41, Category A3 &B3
ISTA
WEEE
-4 to 104 (-20 to 40)
32°F to 95°F (0°C to 35°C) at
full rated load
1.5% maximum kW / degrees C derating up
to 50°C
to 50°C
122°F (50°C) absolute maximum with
derating
95% or less Non-Condensing
95% or less Non-Condensing
derating
(Operating and Non-Operating)
3300 ft. (1000m) (per IEC 62040/3) - 1%
Maximum kW derating / 1000 ft. rise
between 3300 and 10,000 ft. (305m rise
between 1000 and 3000m)
between 1000 and 3000m)
3
Table 14 Current ratings—rectifier input
UPS Rating
625 625 480 779 818
Vol tag e
VAC
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 45
Nominal
Current
Maximum
CurrentkVA kW
Page 52
Table 14 Current ratings—rectifier input
UPS Rating
750 750 480 935 982
800 800 480 995 1044
1000 1000 480 1244 1308
1100 1100 480 1368 1438
1200 1200 480 1493 1569
Vol tag e
VAC
Nominal
Current
Table 15 Current ratings—bypass input
UPS Rating
625 625 480 752
750 750
800 800 480 962
1000 1000
1100 1100
1200 1200 480 1443
Vol tag e
VAC
Nominal
CurrentkVA kW
480 902
480 1203
480 1323
Table 16 Current ratings—output
UPS Rating
625 625 480 752
750 750
800 800 480 962
1000 1000 480 1203
1100 1100
1200 1200 480 1443
Vol tag e
VAC
Nominal
CurrentkVA kW
480 902
480 1323
Table 17 Current ratings—DC source
UPS Rating
Vol tag e
kVA kW
625 625 480 1601
750 750 480 1923
800 800 480 2051
1000 1000 480 2591
1100 1100 480 2850
1200 1200 480 3109
VAC
Maximum
Current
at EOD
Notes on Tables 14 through 17
1.Nominal rectifier AC input current (considered continuous) is based on full
rated output load. Maximum current
includes nominal input current and maximum battery recharge current (considered non-continuous).
2.The rectifier overload current is controlled by the input current limit setting,
which is adjustable from 25 to 200% (default:125%).
3.For breaker coordination while the module is overloaded, see the current
versus time values on the overload curves.
4.Nominal battery voltage is shown at 2.0 volts/cell.
5.DC Source current based at 401VDC.
Maximum
CurrentkVA kW
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 46
Page 53
Figure 31 Inverter overload data
631.1
324.8
194.7
120.0
75.9
49.0
32.4
21.8
14.9
10.4
7.3
5.2
3.8
2.8
2.1
1.5
1.2
0.9
0.2
0.0
100.0
200.0
300.0
400.0
500.0
600.0
700.0
100% 110% 120% 130% 140% 150% 160% 170% 180% 190% 200%
% Load
Time (sec)
Continuous
106%: 15005 secs
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 47
Page 54
Figure 32 Rectifier overload data
341.0
204.5
126.0
79.6
51.5
34.0
22.9
15.6
10.9
7.7
5.5
4.0
3.1
2.3
1.7
1.3
1.0
0.2
694.2
0.0
100.0
200.0
300.0
400.0
500.0
600.0
700.0
100% 110% 120% 130% 140% 150% 160% 170% 180% 190% 200%
% Load
Time (sec)
Continuous
106%: 16506 secs
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 48
Page 55
Figure 33 Bypass overload data
0.2
0.9
1.2
1.5
2.1
2.8
3.8
5.2
7.3
10.4
500.0
500.0
450.0
400.0
324.8
350.0
300.0
250.0
Time (sec)
194.7
200.0
14.9
21.8
32.4
49.0
75.9
120.0
Continuous
150.0
100.0
50.0
% Load
100% 110% 120% 130% 140% 150% 160% 170% 180% 190% 200%
0.0
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 49
Page 56
Table 18 Recommended conduit and cable sizes for use with 100% rated breakers
Rectifier Input
UPS Rating
kVA kW Copper Conductors Aluminum Conductors
625 625
750 750
800 800
1000 1000
1100 1100
1200 1200
Bypass Input
UPS Rating
kVA kW Copper Conductors Aluminum Conductors
625 625
750 750
800 800
1000 1000
1100 1100
1200 1200
Output
UPS Rating
kVA kW Copper Conductors Aluminum Conductors
625 625
750 750
800 800
1000 1000
1100 1100
1200 1200
Vol tage
VAC
480
480
Vol tage
VAC
480
480
Vol tage
VAC
480
480
Cable Entry
Top (3) 2.5"C 3-350kcmil; #2/0AWG (3) 3"C 3-500kcmil; #4/0AWG
Bottom (3) 3"C 3-350kcmil; #2/0AWG (3) 3.5"C 3-500kcmil; #4/0AWG
Top (3) 3"C 3-500kcmil; #2/0AWG (3) 3"C 3-600kcmil; #4/0AWG
Bottom (3) 3.5"C 3-500kcmil; #2/0AWG (3) 3.5"C 3-600kcmil; #4/0AWG
Top (4) 2.5"C 3-350kcmil; #3/0AWG (4) 3"C 3-500kcmil; 250kcmil
Bottom (4) 3"C 3-350kcmil; #3/0AWG (4) 3.5"C 3-500kcmil; 250kcmil
Top (4) 3"C 3-500kcmil; #4/0AWG (5) 3"C 3-500kcmil; 350kcmil
Bottom (4) 3.5"C 3-500kcmil; #4/0AWG (5) 3.5"C 3-500kcmil; 350kcmil
Top (5) 3"C 3-500kcmil; #4/0AWG (5) 3"C 3-600kcmil; 350kcmil
Bottom (5) 3.5"C 3-500kcmil; #4/0AWG (5) 4"C 3-600kcmil; 350kcmil
Top (5) 3"C 3-500kcmil; #4/0AWG (5) 3"C 3-600kcmil; 350kcmil
Bottom (5) 3.5"C 3-500kcmil; #4/0AWG (5) 4"C 3-600kcmil; 350kcmil
Cable Entry
Top (3) 2.5"C 3-350kcmil; #1/0AWG (3) 3"C 3-500kcmil; #3/0AWG
Bottom (3) 3"C 3-350kcmil; #1/0AWG (3) 3.5"C 3-500kcmil; #3/0AWG
Top (3) 3"C 3-500kcmil; #2/0AWG (3) 3"C 3-600kcmil; #4/0AWG
Bottom (3) 3.5"C 3-500kcmil; #2/0AWG (3) 3.5"C 3-600kcmil; #4/0AWG
Top (3) 3"C 3-500kcmil; #2/0AWG (3) 3"C 3-600kcmil; #4/0AWG
Bottom (3) 3.5"C 3-500kcmil; #2/0AWG (3) 3.5"C 3-600kcmil; #4/0AWG
Top (4) 3"C 3-500kcmil; #4/0AWG (5) 3"C 3-500kcmil; 350kcmil
Bottom (4) 3.5"C 3-500kcmil; #4/0AWG (5) 3.5"C 3-500kcmil; 350kcmil
Top (4) 3"C 3-500kcmil; #4/0AWG (5) 3"C 3-500kcmil; 350kcmil
Bottom (4) 3.5"C 3-500kcmil; #4/0AWG (5) 3.5"C 3-500kcmil; 350kcmil
Top (5) 3"C 3-500kcmil; #4/0AWG (5) 3"C 3-600kcmil; 350kcmil
Bottom (5) 3.5"C 3-500kcmil; #4/0AWG (5) 4"C 3-600kcmil; 350kcmil
Cable Entry
Top (3) 2.5"C 3-350kcmil; #1/0AWG (3) 3"C 3-500kcmil; #3/0AWG
Bottom (3) 3"C 3-350kcmil; #1/0AWG (3) 3.5"C 3-500kcmil; #3/0AWG
Top (3) 3"C 3-500kcmil; #2/0AWG (3) 3"C 3-600kcmil; #4/0AWG
Bottom (3) 3.5"C 3-500kcmil; #2/0AWG (3) 3.5"C 3-600kcmil; #4/0AWG
Top (3) 3"C 3-500kcmil; #2/0AWG (3) 3"C 3-600kcmil; #4/0AWG
Bottom (3) 3.5"C 3-500kcmil; #2/0AWG (3) 3.5"C 3-600kcmil; #4/0AWG
Top (4) 3"C 3-500kcmil; #4/0AWG (5) 3"C 3-500kcmil; 350kcmil
Bottom (4) 3.5"C 3-500kcmil; #4/0AWG (5) 3.5"C 3-500kcmil; 350kcmil
Top (4) 3"C 3-500kcmil; #4/0AWG (5) 3"C 3-500kcmil; 350kcmil
Bottom (4) 3.5"C 3-500kcmil; #4/0AWG (5) 3.5"C 3-500kcmil; 350kcmil
Top (5) 3"C 3-500kcmil; #4/0AWG (5) 3"C 3-600kcmil; 350kcmil
Bottom (5) 3.5"C 3-500kcmil; #4/0AWG (5) 4"C 3-600kcmil; 350kcmil
(# of conduits); size of conduits; # -size of phase cables per conduit;
size of cable for ground per conduit
(# of conduits); size of conduits; # - size of phase cables per conduit;
size of cable for ground per conduit
(# of conduits); size of conduits; # -size of phase cables per conduit;
size of cable for ground per conduit
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 50
Page 57
Table 18 Recommended conduit and cable sizes for use with 100% rated breakers (continued)
Battery
UPS Rating
kVA kW Copper Conductors Aluminum Conductors
625 625
750 750
800 800
1000 1000
1100 1100
1200 1200
1. Recommended cable sizes are 167°F (75°C) (THW) wire at 86°F (30°C) ambient.
2. Refer to NEC recommendations for 104°F (40°C) ambient rated conductors.
3. Unless otherwise noted, use copper or aluminum conductors suitable for at least 75°C.
4. Recommended cables and conduits are based on breaker trip setting sized for the maximum continuous rated current for the rectifier input and the nominal current for the bypass and output listed in Tab les 14 through 17.
5. Conduit size is based on RNC type conduit for bottom input and EMT-type conduit for top input.
6. Vertiv® recommends that the site planner choose the appropriate cable type based on the particular installation requirements.
7. These recommendations are for use with 100% rated breakers. For 125% rated breakers, refer to the NEC recommended conduit and cable sizes.
8. Upstream and downstream non-standard recommended breaker settings have their trip adjustment behind a suitable cover in accordance with
240.6(c) of the NEC.
Vol tage
VAC
480
480
Cable Entry
Top (5)3"C 2-600kcmil; 250kcmil (6) 3"C 2-600kcmil; 400kcmil
Bottom (5)3"C 2-600kcmil; 250kcmil (6) 3.5"C 2-600kcmil; 400kcmil
Top (5)3"C 2-600kcmil; 250kcmil (6) 3"C 2-600kcmil; 400kcmil
Bottom (5)3"C 2-600kcmil; 250kcmil (6) 3.5"C 2-600kcmil; 400kcmil
Top (6)3"C 2-600kcmil; 350kcmil (7) 3"C 2-700kcmil; 600kcmil
Bottom (6)3"C 2-600kcmil; 350kcmil (7) 3.5"C 2-700kcmil; 600kcmil
Top (8)3"C 2-600kcmil; 500kcmil (8) 3"C 2-700kcmil; 600kcmil
Bottom (8) 3.5"C 2-600kcmil; 500kcmil (8) 3.5"C 2-700kcmil; 600kcmil
Top (8)3"C 2-600kcmil; 500kcmil (8) 3"C 2-700kcmil; 600kcmil
Bottom (8) 3.5"C 2-600kcmil; 500kcmil (8) 3.5"C 2-700kcmil; 600kcmil
Top (9)3"C 2-750kcmil; 500kcmil (11) 3"C 2-700kcmil; 750kcmil
Bottom (9) 3.5"C 2-750kcmil; 500kcmil (11) 3.5"C 2-700kcmil; 750kcmil
(# of conduits); size of conduits; # -size of phase cables per conduit;
size of cable for ground per conduit
Table 19 Recommended breakers, upstream and downstream
UPS Rating
kVA
Upstream Breakers
625 777 900
750 933 1000
800 995 1200
1000 1246 1400
1100 1371 1600
1200 1496 1600
Downstream Breakers
625 752 800
750 902 1000
800 962 1000
1000 1203 1400
1100 1323 1400
1200 1443 1600
System Input
Nominal Current
Recommended External
Breaker Trip, Amps
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 51
Page 58
Table 20 Recommended lug sizes
Cable Size
#8AWG 54930BE 54850BE 60104-TB
#6AWG 54905BE 256-30695-868 60109-TB
#4AWG 54906BE 256-30695-733 60114-TB
#2-3AWG 54942BE 54811BE 60120
#1AWG 54947BE 54857BE 60126
#1/0AWG 54950BE 256-30695-593 60132
#2/0AWG 54951BE 54862BE 60138 60238
#3/0AWG 54965BE 54864BE 60144 60244
#4/0AWG 54970BE 54866BE 60150 60250
250kcmil 54913BE 54868BE 60156 60256
300kcmil 54914BE 54870BE 60162 60262
350kcmil 54915BE 54872BE 60165 60267
400kcmil 54916BE 54874BE 60168 60269
500kcmil 54918BE 54876BE 60171 60273
600kcmil 54920BE 54878BE 60176 60275
750kcmil 54922BE 54880BE 60178 60277 (750kcmil)
One Hole
T&B Copper
T&B Copp er Two
Hole
T&B Aluminum
One Hole
T&B Aluminum
Two Hole
Table 21 Recommended torque values
Grade 5 Steel: Unified Thread System Torque, lbf.*in. Class 8.8 Steel: Metric Thread System Torque, N*m
Fastener Finish Plain Steel Zinc Plating Fastener Finish Plain Steel Zinc Plating
Size
1/4
5/16
3/8
7/1 6
1/2
9/16
Threads/
Inch, Tpi
20 101 91
28 116 104 0.5 6.9 6.2
18 209 188
24 231 208 0.75 11 10
16 370 333
24 420 378 1 27 24
14 593 534
20 662 596 1.25 53 47
13 904 814
20 1,020 918 1.25 95 86
12 1305 1,175
18 1456 1310 1.5 151 136
No Washer/ Flat Washer
No Washer/
Flat Washer Size
M5
M6
M8
M10
M12
M14
Thread
Pitch, Tp
0.8 6.1 5.5
110 9
1.25 25 23
1.5 50 45
1.75 87 78
2139125
No Washer/
Flat Washer
No Washer/
Flat Washer
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 52
Page 59
APPENDIX A-SHIPPING SPLITS, KICKPLATES
553028P1 Pg. 1, Rev. 6
A
A
B
B
DETAIL D
SECTION A-A
DETAIL C
G
G
H
F
F
SHIPPING SPLIT INPUT
EMI Plates (3) {PN: 5533579P1} M6 Large Flat Washer (6) {PN: 09-43B00Z-00} M6 Split Lock Washer (6) {PN: 09-36B00Z-00} M6 x 25 Bolt (6) {PN: 09-02BL0Z-11}
See Detail C
See Detail D
See Detail E
Shipping Split Core 1 & 2
Shipping Split Bypass & Output
PH B - Flex from Input Cabinet M8 Large Flat Washer (2) {PN: 09-43E00Z-00} M8 Belleville Washer (4) {PN: 09-39D00Z-A7} M8 x 40 Bolt (2) {PN: 09-02EL0Z-14} Torque 180 in-lb (20 Nm)
Install MH From Core 1
Batt +
Batt -
Input Ph A
Input Ph B
Input Ph C
Install MH From Core 1
Install MH From Core 1
Install MH From Input
Install MH From Input
Install MH From Input
Install MH From Bypass
Install MH From Bypass
Install MH From Bypass
Install MH From Bypass
Install MH From Core 2
Install MH From Core 2
FRONT
FRONT
Output A
Output B
Output C
PH A - Flex from Bypass Cabinet M8 Large Flat Washer (2) {PN: 09-43E00Z-00} M8 Belleville Washer (4) {PN: 09-39D00Z-A7} M8 x 40 Bolt (2) {PN: 09-02EL0Z-14} Torque 180 in-lb (20 Nm)
PH B - Flex from Bypass Cabinet M8 Large Flat Washer (2) {PN: 09-43E00Z-00} M8 Belleville Washer (4) {PN: 09-39D00Z-A7} M8 x 40 Bolt (2) {PN: 09-02EL0Z-14} Torque 180 in-lb (20 Nm)
Cabinet-to-Cabinet Mounting Hardware M10 Large Flat Washer (1) {PN: 09-43G00Z-00} M10 Split Lock Washer (1) {PN: 09-36G00Z-00} M10 X 30 Bolt (1) {PN: 09-02GL0Z-12} (Typically 12 Places) (Labeled “MH”) Torque 240 in-lb (27 Nm)
Bend flex to 90° position before pushing the bypass and core together. Monitor flex to avoid pinching between cabinets or busbars.
Batt Pos (+) Flex from Input Cabinet M8 Large Flat Washer (4) {PN: 09-43E00Z-00} M8 Belleville Washer (8) {PN: 09-39D00Z-A7} M8 x 40 Bolt (4) {PN: 09-02EL0Z-14} Torque 180 in-lb (20 Nm)
Batt Neg (-) Flex from Input Cabinet M8 Large Flat Washer (4) {PN: 09-43E00Z-00} M8 Belleville Washer (8) {PN: 09-39D00Z-A7} M8 x 40 Bolt (4) {PN: 09-02EL0Z-14} Torque 180 in-lb (20 Nm)
PH A - Flex from Input Cabinet M8 Large Flat Washer (2) {PN: 09-43E00Z-00} M8 Belleville Washer (4) {PN: 09-39D00Z-A7} M8 X 40 Bolt (2) {PN: 09-02EL0Z-14} Torque 180 in-lb (20 Nm)
PH C - Flex from Input Cabinet M8 Large Flat Washer (2) {PN: 09-43E00Z-00} M8 Belleville Washer (4) {PN: 09-39D00Z-A7} M8 x 40 Bolt (2) {PN: 09-02EL0Z-14} Torque 180 in-lb (20 Nm)
Ph C - Flex from Bypass Cabinet M8 Large Flat Washer (2) {PN: 09-43E00Z-00} M8 Belleville Washer (4) {PN: 09-39D00Z-A7} M8 x 40 Bolt (2) {PN: 09-02EL0Z-14} Torque 180 in-lb (20 Nm)
SECTION B-B
Figure 34 Shipping split, 625-800kVA Liebert EXL UPS, SMS and 1+N multi-module unit
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 53
Page 60
Figure 35 Shipping split, 625-800kVA Liebert EXL UPS, SMS and 1+N multi-module unit, continued
J J
P1
P2
P3
P66
P1
P2
P3
P99
DETAIL E
DETAIL H
553028P1 Pg. 2, Rev. 6
CORE 1 FIB 1
P20
P1
SECTION G-G
SECTION J-J
SECTION F-F
Route harness from input in duct to Core 1 (Connectors - J400, J11) Bypass (Connectors - J13, J100, J200, J300) Core 1 & 2 Prechg (See Section J-J)
Connect to input harness (Connectors P400, P11
Rear Wiring Duct
Route harness from bypass in duct to input (Connectors - P13, P100, P200, P300)
Input (Connector HVAB P20) See Section F-F
Route harness from input in duct to Core 1 (Connectors - P1, P2, P3, P66) Core 2 (Connectors - P1, P2, P3) Bypass (Connectors - P99A, P1)
Core 1 (Connectors - P1, P2, P3) See Detail E
Core 1 (Connectors - P66) See Detail E
Core 2 (Connectors - P1, P2, P3) See Detail E
Bypass (Connectors - P1) See Section G-G
Bypass (Connector - CB2 I/F BD P99) See Detail H
From Input
Core 1 Prechr PhA (Brown Wire)
Core 1 Prechr PhB (Orange Wire)
Core 2 Prechr PhA (Brown Wire)
Core 2 Prechr PhB (Orange Wire)
Route harness from bypass in duct to input (Connector - P20)
FRONT WIRING DUCT
From Input
From Input
From Input
From Input
From Input
From Bypass
From Bypass
Input Cabinet HVAB
Core 1 Connector Board
Core 2 Connector Board
Wire Duct
Bypass Cabinet CB2 I/F Board
Bypass Cabinet Bypass Connector Board
See connection details in
Tables 22, 23 and 24.
Table 22 Connections associated with top-down view
Cabinet Start Connector Label Cabinet Finish Connector Label Duct
Connected together in the rear duct.
Table 23 Section J-J connections
Cabinet Start Connector Label Cabinet Finish Cabinet Finish Duct
Input J100 Bypass P100 Rear
Input J13 Bypass P13 Rear
Input J200 Bypass P200 Rear
Input J300 Bypass P300 Rear
Input J11 Core 1 P11 Rear
Input J400 Core 1 P400 Rear
Input Core Prechg Ph A Core 1 Prechg Ph A Core 2 Prechg Ph A Rear
Input Core Prechg Ph B Core 1 Prechg Ph A Core 2 Prechg Ph A Rear
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 54
Page 61
Table 24 Connections associated with sections in “View” column
Cabinet
Start
Bypass CT7-CT9 Input P20 HVAB Front Section F-F
Input P50 Bypass P1 Bypass Connector Board Front Section G-G
Input P66A Bypass P99A CB2 I/F BD Front Detail H
Input P11 Core 1 P1 Core Connector Board Front Detail E
Input P12 Core 1 P2 Core Connector Board Front Detail E
Input P1 Core 1 P3 Core Connector Board Front Detail E
Input P99 Core 1 P66 FIB 1 Front Detail E
Input P21 Core 2 P1 Core Connector Board Front Detail E
Input P22 Core 2 P2 Core Connector Board Front Detail E
Input P2 Core 2 P3 Core Connector Board Front Detail E
Bypass P66 Core 1 P99 FIB 1 Front Detail E
Connector
Label
Cabinet
Finish
Connector Label
(Connect This End) Duct View
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 55
Page 62
Figure 36 Shipping split, 1000-1200kVA Liebert EXL UPS, SMS and 1+N multi-module unit, Page 1
See Detail E
(Sheet 3)
Shipping Split Bypass & Output
B
Shipping Split Core 3
See Detail D
(Sheet 3)
Typical Cabinet To Cabinet Mounting Hardware
M10 Large Flat Washer (1) {PN: 09-43G00Z-00}
M10 Split Lock Washer (1) {PN: 09-36G00Z-00}
1
Shipping Split Core 1 & 2
M10 x 30 Bolt (1) {PN: 09-02GL0Z-12}
Torque 240 in-lb (27 Nm)
A
Bypass Cabinet
E
Core 3
B
1
Core 3 to bypass
cabinet mounting
hardware; see
Section BB
Install 6 places
C
Core 2Core 1
See cabinet-to-cabinet
power connections detail
(Sheet 2)
A
1
Core 2 to Core 3 mounting
hardware; install 6 places from Core 2
1
Input cabinet to Core 1 mounting
hardware; see Section A-A
Install 6 places
Route wires through
bushing between cores
DETAIL C
Shipping Split Input
HV Attenuator Burden Board
(Sheet 3)
1
Install
1
from Input
Install
from Core
1
1
Install
from Input
Install
from Core
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 56
Input Cabinet
EMI Plates (3) {PN: 553579P1}
M6 Large Flat Washer (6) {PN: 09-43B00Z-00}
1
Install
from Input
Input Ph C
1
Install
from Core 3
1
Install
from Core 3
SECTION A-A
BATT +
1
BATT -
Install
Output Ph A
FRONT
from Core
Input Ph B
1
Install
from Core 3
DC Pos (+) CORE 2
Remove hardware, install wires
from Core 3, then reuse hardware
Torque 180 in-lb (20.0 Nm)
M6 Split Lock Washer (6) {PN: 09-36B00Z-00}
M6 x 25 Bolt (6) {PN: 09-02BL0Z-11}
1
Install
Output Ph C
Output Ph B
Output Ph A
1
Install
from Core 3
from Core 3
1
Install
from Core 3
FRONT
DC MID CORE 2
Remove hardware, install wires
from Core 3 then reuse hardware
Torque 180 in-lb (20.0 Nm)
SECTION B-B
Page 63
Figure 37 Shipping split, 1000-1200kVA Liebert EXL UPS, SMS and 1+N multi-module unit, Page 2
F
F
CORE TO CORE BUSBARS
(2) SIDE BY SIDE FOR BATT NEG (-)
(2) SIDE BY SIDE FOR BATT POS (+)
3
4
2
3
3
2
3
4
Route harness from input in duct to
Core 1 (connectors - J400, J11, J12)
bypass (connectors - J100, J200, J300)
Core 1, 2 & 3 prechg (See Section F-F)
Connect to input harness
(Connectors P400, P11)
Connect to input harness
(Connectors P12)
Route harness from bypass
in duct to input
(Connectors P100, P200, P300)
Rear
Wiring Duct
Front
Wiring Duct
Connected together in rear duct.
Route harness from bypass in
duct to input (Connector - P20)
Core 1
Core 2
Core 1
Core 2
Core 3
Core 3
Input (Connector HVAB
P20) See Sheet 3
Route harness from input in duct to
Core 1 (Connectors -P1, P2, P3, P66)
Core 2 (Connectors - P1, P2, P3)
Core 3 (Connectors - P1, P2, P3)
Bypass (Connectors - P99A, P1)
Rear Wire Duct
From Input
Core 1 Prechr Ph A
(Brown Wire)
Core 3 Prechr Ph A
(Brown Wire)
Core 2 Prechr Ph A
(Brown Wire)
Core 1 Prechr Ph B
(Orange Wire)
Core 2 Prechr Ph B
(Orange Wire)
Core 3 Prechr Ph B
(Orange Wire)
Batt Neg (-) & Batt Pos(+) Flex
from Input Cabinet
Installed in Factory
Installed in Factory
Installed in Factory
x 6
4
x 6
2
x 6
x 8
x 6
x 8
x 8
2x 6
3x 8
Core 1
Core 2
Core 3
AC Input Flex from Input Cabinet
Core-to-Core Busbars
1 per Phase
Core-to-Core Busbars
1 per Phase
AC Output Flex
from Bypass Cabinet
Cabinet-to-Cabinet Power Connections
Typical Flex to Core Busbar Hardware
M8 Large Flat Washer (1) {PN: 09-43E00Z-00}
M8 Belleville Washer (2) {PN: 09-39D00Z-A7}
M8 X 50 Bolt (1) {PN: 09-02EL0Z-16}
Torque 180 in-lb (20 Nm)
Typical Single Core to Core Busbar Hardware
M8 Large Flat Washer (1) {PN: 09-43E00Z-00}
M8 Belleville Washer (2) {PN: 09-39D00Z-A7}
M8 X 35 Bolt (1) {PN: 09-02EL0Z-13}
Torque 180 in-lb (20 Nm)
Typical Double Core to Core Busbar Hardware
M8 Large Flat Washer (1) {PN: 09-43E00Z-00}
M8 Belleville Washer (2) {PN: 09-39D00Z-A7}
M8 X 40 Bolt (1) {PN: 09-02EL0Z-14}
Torque 180 in-lb (20 Nm)
BATT Pos (+)
BATT Neg (-)
BATT Neg (-)
BATT Neg (-)
BATT Pos (+)
AC Ph-A
AC Ph-B
AC Ph-C
AC Ph-A
AC Ph-B
AC Ph-C
AC Ph-C
AC Ph-B
AC Ph-A
SECTION F-F
J100
J200
J300
J11
J400
J12
Bypass
Bypass
Bypass
Core 1
Core 1
Core 3
P100
P200
P300
P11
P400
P12
Rear
Rear
Rear
Rear
Rear
Rear
Input
Input
Input
Input
Input
Input
Cabinet
Start
Cabinet
Finish
Connector
Label
Connector
Label Duct
Core Prechg Ph A
Core Prechg Ph B
Core Prechg Ph A
Core Prechg Ph B
Core 1 Prechg Ph A
Core 1 Prechg Ph B
Core 3 Prechg Ph A
Core 3 Prechg Ph B
Core 2 Prechg Ph A
Core 2 Prechg Ph B
Rear
Rear
Rear
Rear
Input
Input
Input
Input
Cabinet
Start
Cabinet Finish
Connector Label
Connector Label
Duct
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 57
Page 64
Figure 38 Shipping split, 1000-1200kVA Liebert EXL UPS, SMS and 1+N multi-module unit, Page 3
P1
P20
P1
P2
P3
P66
P1
P2
P3
P99
P1
P3
P66
P99
P2
P1006
P1005
DETAIL E
DETAIL D
Connectors
P1, P2, P3
Connectors
P1, P2, P3
Connectors
P1, P2, P3
Connectors
FIB1 P66
FIB1 P99
Core 1 Core 2 Core 3
FIB2 P66, FIB 2 P99, P1005 & P10 06
Optional CB2 Motor OP Wir es TB1-1 & TB1-2
Connectors
Core 1 Connector Board
Core 2 Connector Board
Core 2 Connector Board
Core 1 FIB 1
(Fan Interface Board)
Core 3 FIB 2
(Fan Interface Board)
Connect to TB1 from bypass cabinet
Only if CB2 is equipped with motor operator
(Wire will be in bypass wire duct)
TB1-1
TB1-2
Connectors
Incoming: P1, CB2 P99A
Outgoin g: FIB2 P99, P1005 & P1006
Optional CB2 Mtr Op Wir es TB1-1 & TB1-2
Bypass Connector Board
Tem per at ure
Interface Board
CB2 Interface Board
Factor y-Instal led
Jumper (555648G1)
CB2 P99A
For Units
Without CB2
TIB P99
TEMPERATURE INTERFACE BOARD
Located in Bypass Cabinet
See Detail E for Exact Loc ation
CB2 INTERFACE BOARD
Located in Bypass Cabinet
See Detail E for Exact Loc ation
BYPASS CONNECTOR BOARD
Located in Bypass Cabinet
See Detail E for Exact Loc ation
Bypass Connector
Board - P1
HV AT TENUATOR BUR D E N BOA R D
Located in Input Cabinet
See Sheet 1 for Exact Locatio n
CB2 P99A
For Units With
CB2 Installed
HVAB P20
Bypass
Input
Input
Bypass
Duct
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
HV Attenuator Burden Board
Bypass Connector Board
CB2 Interface Board
Temperature Interface Board
Detail D
Detail D
Detail D
Detail D
Detail D
Detail D
Detail D
Detail D
Detail D
Detail D
Detail D
Detail D
Detail D
Detail D
Detail D
Detail D
(P20) HVAB
(P1) Bypass Connector BD
(P99A) CB2 I/F BD
(P99A) TIB BD
(P66) FIB 1
(P1) Core Connector Bd
(P2) Core Connector Bd
(P3) Core Connector Bd
(P1) Core Connector Bd
(P2) Core Connector Bd
(P3) Core Connector Bd
(P1) Core Connector Bd
(P2) Core Connector Bd
(P3) Core Connector Bd
(P66) FIB 2
(P99) FIB 2
(P1005) FIB 2
(P1006) FIB 2
(TB11)
(TB12)
CT7-CT9
P50
View OptionDuct
Connector Label
(Connect This End)
Cabinet
Finish
Connector Label
(Factory-Connected)Cabinet Start
CB2
No CB2
CB2 Mtr Op Only
CB2 Mtr Op Only
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Core 1
Bypass
Bypass
Bypass
Bypass
Bypass
Input P66A
P99
P11
P12P1P21
P22P2P31
P32P3FIB 1 (P99)
BFB I/F BD (P66)
Fan 13
Fan 14
F701
F691
Bypass
Core 1
Core 1
Core 1
Core 1
Core 2
Core 2
Core 2
Core 3
Core 3
Core 3
Core 3
Core 3
Core 3
Core 3
Core 3
Core 3
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 58
Page 65
Figure 39 Kickplate installation—625-800kVA units
Panel Rear Bottom
LEFT HAND REAR
Panel Rear Bottom
RIGHT HAND FRONT
Panel Rear Bottom
Panel Side Bottom
Panel Front Bottom
M10 Flat Washer ZP, Typical
Screw Cap HH M101.5x25mm ZP
M10 Lock Washer, Split ZP, Typical
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 59
Panel Front Bottom
Panel Front Bottom
Hexagonal Cap Black M10 (17mm) Typical
Panel Side Bottom
553029P1 Pg. 1, Rev. 2
Page 66
Figure 40 Kickplate installation—1000-1200kVA, single module units
RIGHT HAND FRONT
Panel Front Bottom
Panel Rear Bottom
Panel Front Bottom
Panel Rear Bottom
M10 Flat Washer ZP, Typical
Panel Front Bottom
Panel Front Bottom
LEFT HAND REAR
Panel Rear Bottom
Panel Rear Bottom
Panel Front Bottom
Panel Rear Bottom
Panel Side Bottom
Panel Side Bottom
Screw Cap HH M101.5x25mm ZP
M10 Lock Washer, Split ZP, Typical
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 60
Hexagonal Cap Black M10 (17mm) Typical
555130P1 Pg. 1, Rev. 0
Page 67
Figure 41 Kickplate installation—1000-1200kVA, 1+N multi-module units
RIGHT HAND FRONT
Panel Front Bottom
Panel Rear Bottom
Panel Front Bottom
Panel Rear Bottom
Panel Front Bottom
Panel Front Bottom
LEFT HAND REAR
Panel Rear Bottom
M10 Flat Washer ZP, Typical
Panel Rear Bottom
Panel Front Bottom
Panel Rear Bottom
Panel Rear Bottom
Panel Side Bottom
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 61
Screw Cap HH M101.5x25mm ZP
M10 Lock Washer, Split ZP, Typical
Hexagonal Cap Black M10 (17mm) Typical
555130P1 Pg. 2, Rev. 0
Page 68
NOTES
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 62
Page 69
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 63
Page 70
Vertiv™| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 64
Page 71
TECHNICAL SUPPORT / SERVICE
Web Site
www.vertivco.com
Monitoring
liebert.monitoring@vertivco.com
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
LOCATIONS
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
Fax: +63 2 730 9572
Page 72
SL-26085_REV3_02-17
Loading...