Sthe manual is retained for the entire service life of the machine;
Sthe user reads the manual carefully before carrying out any operations on the machine;
Sthe machine is used exclusively for the purpose for which it is intended; incorrect use of the machine shall release the
manufacturer from any liability.
This manual has been prepared to enable the end ---user to carry out only those operations that can be done with the panels
closed. Any operations that require the opening of doors or equipment panels must be carried out only by qualified personnel.
Each machine is equipped with an electric isolating device which allows the operator to work in conditions of safety. This
device must always be used to eliminate risks during maintenance (electric shocks, scalds, automatic restarting, moving
parts and remote control).
The panel key supplied with the unit must be kept by the person responsible for maintenance.
For identification of the unit (model and serial no.) in case of the necessity for assistance or spare parts, read the identification
labels affixed to the outside and inside of the unit.
IMPORTANT: This manual may be subject to modification; for complete and up ---to --- date information the user should always consult the manual supplied with the machine.
This handbook is aimed at enabling both the installer and the operator to carry out the correct installation, operation and maintenance of the refrigerating machine, without damaging it or causing injuries to the relevant staff.
The handbook is thus an aid for the qualified staff in the arrangement of the specific equipment for the correct installation,operation and maintenance in compliance with the local regulations
in force.
The MATRIX S water chillers can be identified as follows:
BH004
Cooling C apacity “kW”
Nominal cooling capacity / 10
Compressor:
H Hermetic Scroll
Each unit is completely factory assembled; after evacuation, the
necessary quantity of refrigerant is added to the refrigerant circuit(s) and the unit is tested.
All the units are equipped with oneor two independent refrigerating circuits, each one composed of: an air --- cooled condenser,
a hermetic Scroll compressor and a braze---welded plate evaporator. The components of the liquid line are the charging valves,
filters - --dryers, solenoid valve, shut ---off valve, moisture indicator
and thermostatic expansion valve.
The hydraulic circuit is made up of hydraulic lines both in steel
and flexible EPDM rubber, connected by fittings and threaded
joints, a flow switch (optional) and, in the freecooling versions,
chilled water coils and a three ---way valve.
The hermetic scroll compressors are complete with the following
protection/safety devices: oil heater (if necessary), electronic
protection monitoring the temperature of the motor windings
and the direction of rotation (the latter may be enclosed in the
electronics of the compressor or external, depending on the
model). The ”MATRIX S” water chillers are controlled by the ”MICROFACE” microprocessor, managing all the unit operating
conditions. The user can change and/or modify the operating
parameters through the display keyboard installed on the electrical panel.
The electrical control board is equipped with all the safety and
operating devices required for reliable operation. The compressor motors are equipped with protection on all three phases and
are started by three --- pole contactors.
Version:
B Base
L Low Noise
Q Quiet
Execution:
C Chiller
S Superchiller
1.2 --- Responsibility
Liebert Hiross accepts no present or future responsibility for
damage to persons, things or to the machine itself due to operators’ negligence, failing to comply with the installation, operation
and maintenance instructions of this handbook, failed application of the safety norms in force for the system and the qualified
staff charged with the operation and maintenance.
1 . 3 ---I n s p e c t i o n
All units are fully assembled and wired in the manufacturing
plant. Before shipment they are charged with the necessary
quantities of refrigerant and oil and then tested at the operating
conditions normally required by the customer. The machine’s
hydraulic circuit is equipped with drain plugs and open vent
valves; the free -- -cooling coils are supplied dry to avoid possible
problems due to frostin the storage period. Immediately inspect
the machine carefully on delivery to check for damage during
transportation or missing components; possible claims must be
made immediately to the carrier and the factory or its representative.
1 . 4 ---G e n e r a l d e s c r i p t i o n
MATRIX S units with air---cooled condensers have been designed and manufactured for producing chilled water.
They are also available in versions with a built ---in freecooling
module, in versions with heat recovery for simultaneous heating
of thermal circuit water, with a pump assembly installed on the
machine and/or inertial buffer tank inside the machine; the chilling units can be equipped with several options indicated in the
price list.
The ”MATRIX S” product line has been designed utilising the
state---of---the---art techniques available nowadays in the industry, and includes all the components necessary for automatic
and efficient operation.
2 ---Preliminary Operations
2.1 --- Operating limits
The units can operate within the indicated operating ranges (see
Tab. 5). These limits apply to new machines, subject to correct
installation and maintenance.
SAmbient air minimum temperature: --- 25ûC for Superchiller,
+15ûC for Chiller without fan speed control (Operation allowed only in summer mode), --- 10ûC for Chiller with continuous fan speed control (Either Triac or EC fan);
SMaximum outdoor air temperature is in relation to each mod-
el, as indicated in Tab. 5. In any case outdoor temperatures
aver 45ûC are not admitted; such limits are determined by
electrical and electronic components fitted on units;
SMaximum water flow allowed: depending on the pressure
drop corresponding to the required thermal difference (usually not lower than 3.5ûC --- 4 ûC);
SMinimum allowed water flow: compatible with a sufficient
evaporation temperature, to avoid the intervention of the
safety devices (to be evaluated for a thermal difference not
higher than 8ûC);
STemperature range of the water exiting the evaporator: 4ûC
--- 1 5 ûC;
SMaximum temperature of the water entering the unit: 20ûC;
higher temperatures are allowed only at the system start--up and not during normal operation;
SMaximum glycol concentration: 50% (35% with the optional
pump assembly installed on the machine);
SMinimum allowed glycol concentration: depending on the
minimum temperature of the ambient air expected at the
installation site (see Tab. a);
SMaximum pressure of the hydraulic circuit: 5 bar;
SVoltage range for the electric supply: 400 V
Avoid positioning in areas with strong dominant winds that may
impair the operation and effect the indicated limits.
2.2 --- Sound pressure levels
The Tab. 6 shows the noise data for the units in standard configuration (without pumps), operating continuously and measured
according to the ISO 3744 norm, in free field conditions.
The highest noise levels are detected on the condenser coil side.
+
/
10%; max.
---
1
Note:
Avoid positioning in areas with possible reverberation of the
sound waves, which can adversely effect the noise levels.
2 . 3 ---T r a n s p o r t
SHandle the unit by lifting it with a crane from above;
SThe lifting holes are positioned in the frame’s base (when lift-
ing, use spreader bars to protect the sides, see Fig. 2 and
Fig. 3).
Note:
Place the lifting tubes in the holes in the base indicated by ”LIFT
HERE”. Lock the ends of the tubes with the locking pins and
splits pins as shown in Fig. 2. As an alternative, shackles/hooks
(optional) fastened at the base ends can be used as a lifting system: in this case the lifting point must be on the vertical line
passing through the machine’s centre of gravity (as indicated in
Fig. 3) to prevent any load imbalance.
The capacity of the lifting gear must be adequate to lift the load
in question. Check the weight of the units, the capacity of the lifting gear and ropes and the condition and suitability of the aforementioned equipment.
2.4 --- Foundations
SThe unit must be placed on a level surface which will support
its weight.
SIf necessary, position the unit on suitable anti --- vibration sup-
ports that can be supplied as an option (in rubber or spring --type). Refer to the manual ”Installation of the spring anti --vibration supports” for their correct positioning.
SWhen positioned, level the unit.
Note:
For weight distribution see Fig. 4 and Fig. 5.
Note:
The weights and their distribution refer to standard units without
options; if the pump assembly, or other options are installed on
the machine, add the weights of the installed accessories to
those of the standard units (see Tab. 8).
2.5 --- Service area
SIn order to allow free air flow and maintenance of the unit, a
minimum area must be left free of obstructions around the
unit (see Fig. 1).
SThe hot air expelled by the fans must be allowed to rise unim-
peded by obstacles for a minimum height of 2.5 m.
SAvoid recirculation of hot air between the suction and dis-
charge, otherwise the unit performance may be impaired or
the standard operation can be interrupted.
3 ---Installation
3.1 --- Hydraulic connections
3.1.1 -- Hydraulic circuit construction (Fig. a)
The piping must be connected to the chiller. Construct a chilled
water circuit as described below, see Fig. a:
1) Place shut ---off valves within the circuit to allow servicing;
2) Install a pump system suitable for the flow rate required at
a pressure head equal to the sum of all the pressure drops
(see project data).
Matrix S chillers can be equipped, upon request, with
pumps having performance as indicated in Tab. 8;
3) Install manometers at the chiller inlet/outlet;
4) Install thermometers at the chiller inlet/outlet;
5) Connect the pipes to the chiller by flexible joints to avoid
transmitting vibrations and to balance the thermal expansion; proceed in the same way even if the pump set is outside the chiller;
6) It is useful to include a water pressure switch to give an early
warning of low water pressure;
7) Place a mesh filter at the inlets of the pump and water chiller
(Can be supplied as an optional accessory --- Not fitted);
8) Install, at the highest points in the circuit, apparatus which
allows the bleeding of air and possibly the filling of glycol;
9) Place a drain valve at the lowest point in the circuit and immediately at the outlet of the water chiller;
10) Install a water filling set including the following:
a) filling water meter;
b) manometer;
c) non-- -return valve;
d) air separator;
e) removable supply tube, which must be disconnected
after each charge/top---up;
11) For maximum protection ensure that all tubing exposed to
low outdoor temperatures is fitted with anti ---freeze heaters
and insulated using closed cell synthetic rubber (elastomer);
12) The circuit must include an expansion vessel (with safety
valve) of suitable capacity;
13) Connect the lines avoiding stresses on the machine inner
parts.
Note:
If the water chiller is complete with an expansion vessel (supplied as an option), check if the capacity is enough, and install
a second vessel in the circuit, if required (see par. 8.4).
Follow the indications in Fig. c for the correct sizing.
Note:
The whole circuit must contain a water volume suitable for the
capacity of the installed chiller. Check if the inertial capacity given by the sum of the hydraulic volume inside the machine (including the volume of the optional interna tank, if fitted) and the
system volume is sufficient, or possibly install a tank in the circuit.
Follow the indications in Fig. b for the correct sizing.
Note:
The hydraulic circuit must ensure a constant water supply to the
evaporator in every operating condition. Otherwise, the compressors may be damaged by repeated returns of liquid refrigerant on their suction.
Note:
The water flow switch is a compulsory safety component that
must be installed and correctly wired to the Matrix S chillers,
otherwise the guarantee will be invalidated.
It is installed, as standard, on units with the optional on --- board
pump set, and is available as a option for units without pumps
on board: in the latter case the flow switch, if not installed on the
machine, can be installed on the hydraulic circuit by the installer,
butitiscompulsorythatitiswiredtotheelectricpanelterminal
board, as indicated on the wiring diagram.
3.1.2 -- Addition of water and ethylene glycol
Very important:
Add water and ethylene glycol to the circuit with a % depending
on the minimum temperature of the outside air expected at the
installation site. Do not exceed the nominal operating pressure
of the circuit’s components.
Notes:
STo avoid stratification run the circulation pump for at least 30
minutes after adding any glycol.
SAfter adding water to the hydraulic circuit always discon-
nect the water supply coming from the sanitary supply;
this avoids the danger of glycol entering the sanitary water
system.
SAfter any topping --- up of the water check the concentration
and add glycol if necessary.
3.1.3 -- Water--glycol mixture
Water---glycol mixtures are used as the thermal carrier fluid in
very cold climates or with temperatures below zero degrees centigrade. Determine the ethylene glycol % which must be added
to the water, with the assistance of Tab. a.
2
Tab.a--Ethyleneglycoltobeaddedtowater(%in
weight of total mixture)
Ethylene glycol
(% in weight)
Freezing tempera-
(*)
ture, ûC
Mixture density at
(*)
,kg/l
20ûC
(*) Values are for Shell antifreeze 402. For different brands, check
manufacturer’s data.
For the chiller internal water volume refer to Tab. 1. If the optional
buffer tank is installed on the machine, add the tank hydraulic
volume.
ALWAYS CHARGE THE HYDRAULIC CIRCUIT WITH THE REQUIRED GLYCOL % NECESSARY FOR THE MINIMUM AMBIENT TEMPERATURE AT THE INSTALLATION SITE. FAILING
TO COMPLY WITH THIS INSTRUCTION SHALL INVALIDATE
THE UNIT WARRANTY.
3.2 --- Connection of the safety valve dis-
charge
Safety valves are installed on the high pressure side of the refrigeration circuit(s): the discharge of these valves must be conveyed outside through a suitable pipe, having a diameter of at
least that of the valve outlet, without burdening the valve body.
Convey the discharge to areas where the jet cannot harm
people and the surrounding environment.
Fig. a --Ideal chilled water circuit
disconnect af-
ter charge
10e
10d10c10b10a
12
Fig. b --Inertia tank sizing
The total optimum hydraulic volume of the system where the Matrix S chiller is installed can be calculated by the
following formula:
43 x Rt
V =
where:
---V=minimum required total water volume expressed in litres
---Rt=refrigeration capacity expressed in kW
---Xd=differential band set on the control and expressed in degrees centigrade
Xd
flow
9
Vpt
Ta n k
11327436
5
TT
CHILLER
559
USER
11
11
4
8
Please note that the sum of the hydraulic volume of the Matrix S chiller (Vm) plus the volume of the hydraulic circuit
connected to it (Vpc) must be greater than, or equal to the minimum required total water volume (V). If this condition is not satisfied, it is necessary to install an inertia tank (Vpt, as indicated in the Fig. a) with a volume at least
equal to the following value: Vpt=V ---Vm---Vpc
3
Fig. c --Sizing of the expansion vessel
The total volume of the expansion vessel is calculated with the following formula:
C x e
V =
1 --
Pi
Pf
where:
---C=quantity of water inside the system expressed in litres
---e=water expansion coefficient, with water at 10ûC as a reference
---Pi=absolute pressure of initial charging, equivalent to the vessel pre--- charge pressure (typical value
2.5 bara)
---Pf=absolute final tolerated pressure, lower than the operating pressure of the safety valve calibration
pressure (typical value 4.0 bara).
Use the values of the water expansion coefficient indicated in the table below:
H2OT[°C]Density [kg/m3]Expansion coefficient “e”
10999.6--- --- ---
20997.90.0017
30995.60.0040
40992.20.0075
50988.10.0116
3.3 --- Electrical connections
1) Before proceeding with the electrical connections, ensure
that:
Sall electrical components are undamaged;
Sallterminalscrewsaretight;
Sthe supply voltage and frequency are in accordance with
the rating (with tolerance in accordance with IEC 8--- 6
norms, March 1990)
Sthe allowed phase to phase variability is 3% maximum
(see Fig. d). Variability in excess of 3% invalidates the
guarantee.
2) Supply cable connections (see Tab. 4):
SConnect the cable to the supply terminals.
SUse appropriately sized 3---pole cable. An earth wire
must also be connected.
SAfter having opened the passagein the framework (pre ---
punched knock ---outs) for the supply line entry, restore
the original degree of protection using suitable accessories for the wiring and junction boxes.
Fig. d --Example of calculating phase
1) The 400 V supply has
2) The average voltage is:
3) The maximum deviation from the average is:
4) Thephasetophasevariabilityis:
Note:
The power supply should never be disconnected, except when
performing maintenance.
to phase variability
the following variability:
RS = 388 V
ST = 401 V
RT = 402 V
388 + 401 + 402
3
402 --- 397 = 5 V
5
x 100 = 1.26 (acceptable)
397
RS T
= 397
Operate (open) the main switch before carrying out any maintenance work on electrical components.
Note:
It is forbidden to work on the electrical components without
using insulating platforms, and in the presence of water or fog
or mist.
Note:
The supply to the external pump assembly mustbe made before
starting the chiller and must be kept on as long as the chiller is
in use. Incorrect operation will cause the unit to lock--- out because of the internal protections (flow switch intervention).
Note:
The compressors are equipped with an electronic protectiondevice blocking their start if the phase sequence is not correct, or
stopping their operation if a thermal relay intervenes. This device
is essential for the integrity of the mechanical and electrical components of the compressors. Reset the standard functions by
isolating this device and removing the causes of the lock---out.
Note:
The chillers are equipped with their own microprocessor control
adjustment. The use of the remote ON --- OFF input (located in
the electric panel terminal board) as a system temperature control element is forbidden.
4 ---S t a r t --- U p a n d O p e r a t i o n
4.1 --- Initial check
1) Check all water connections.
2) Open the shut---off valve on the liquid line.
3) Ensure that the intake pressure is higher than 4.0 bar; if this
is not the case, prolong pre --- heating of the compressor (if
possible) and check that the refrigerant shut --- off valve is
properly sealed, see Fig. 10 and Fig. 11.
4) Open all isolating valves and/or water ball valves.
5) In case of climates with temperatures below zero degrees C,
make sure the chilled water circuit is filled with the correct
concentration of water/glycol.
6) Bleed all air out of the chilled water circuit.
7) Verify the water flow rate and its direction.
8) Ensure that the thermal load is sufficient for start---up.
Caution:
The ambient air temperature probe must be positioned in the
shade and protected against the weather.
4
4 . 2 ---F i r s t s t a r t --- u p
(or after a long stop)
Operate as follows:
1) At least 8 hours before the start ---up, power the crank-
case heaters (if any, see point 4) by setting the main isolator switch ON. Make sure the auxiliary circuit has been
powered and check the operation (a fault due to an incorrect procedure will invalidate the compressor guarantee).
2) Open the valves of the refrigeration circuit that had been
closed before the initial check.
3) Check the machinery supplying the thermal load connected
with the unit and start the system pump(s).
4) MAKE SURE THE COMPRESSOR OIL HAS BEEN HEATED
FOR AT LEAST 8 HOURS; start the unit only then. In the
units not equipped with crankcase heaters (Chillers for summer operation only, without modulating fan speed control),
the start must be carried out in the warm season only (external T > 15ûC), and thus oil pre---heating is not necessary.
5) Make sure the fans rotate in the correct direction (anticlockwise): check the electrical connections, if necessary .
6) Make sure the pumps rotate in the correct direction.
7) During the unit start--- up an inlet water temperature
higher than 20ûC is allowed. Under standard operating
conditions check that the limits indicated in paragraph
2.1 are not exceeded.
8) Check the correct operation of the control and safety devices.
9) Check the outlet temperature of the chilled water (check if
the set--- point set on the controller is reached).
10) Check the compressor oil level.
11) With the compressor at full load, check there are no
bubbles visible in the frefrigerant sight glass. If there are any,
charge the unit according to par. 5.
4.3 --- Starting and stopping
ALWAYS ENSURE THAT THE COMPRESSOR OIL HAS BEEN
PREHEATED.
FOR BRIEF STOPPAGES MAINTAIN THE SUPPLY TO THE
CRANKCASE HEATER (IF ANY).
SStart the unit setting the Microprocessor switch ON.
SStop the unit setting the Microprocessor switch OFF.
SIn case of long stops, turn the machine off using the Micro-
processor switch OFF.
In this case the compressor crankcase heaters (if any) remain powered.
SFor seasonal shutdown of the unit operate the main switch
locatedon the main electrical power supply. This will disconnect the compressor crankcase heaters.
4.4 --- Chillers serving special plants
The units are capable of cooling a water ---glycol mixture to temperatures close to 0ûC without the need for significant modifications. In the case of modification, the set values of the safety and
control components must also be changed. This can be carried
out in the factory (at the time of testing) or at the time of installation, only by qualified and authorised personnel.
4 . 5 ---F r e e c o o l i n g
The “freecooling” is a system of pre -- -cooling and/or cooling the
water/glycol mixture using ambient air when the latter is at a temperature below the return mixture temperature. If the outside
temperature is sufficiently low to dissipate the entire heat load,
the refrigeration compressors automatically switch off, and the
mixture’s temperature is controlled by the fan speed adjustment.
If the mixture temperature is too high for freecooling, the compressors will operate as long as necessary to ensure the correct
water/glycol mixture temperature.
4.6 --- Microprocessor control
Consult the ”Microface and Hiromatic” Service Manual.
5 ---R e f r i g e r a n t a n d O i l C h a r g e
All work on pipes or components of the refrigerating circuit under pressure must be exclusively carried out by qualified staff,
competent in such works.
5 . 1 ---R e f r i g e r a n t c h a r g e
WHILST REPAIRING THE REFRIGERATING CIRCUIT RECOVER ALL THE REFRIGERANT IN A CONTAINER: DO NOT
ALLOW IT TO ESCAPE. NEVER USE THE COMPRESSOR
FOR THE SYSTEM VACUUM (THIS INVALIDATES THE
WARRANTY).
SThe unit is delivered charged according to the Tab. 7.
Warning for the refrigerant charge:
SEnsure there are no refrigerant leaks.
SCheck the refrigerant type in the refrigeration circuit: a unit
originally charged by the manufacturer with R407C cannot
be charged with R22 and vice versa; possibly apply to the
Technical Support Department.
SCharge with the compressor in operation, connecting the
cylinder with the charge connector after the thermostatic expansion valve.
Flush the connection pipe between the cylinder and the
charging point; tighten the seal joint and then start charging
the unit. It is imperative that the cylinder is weighed both before and after the operation.
SFor the units with R407C the refrigerant charge must be
made exclusively with liquid refrigerant.
SCharge the unit until the bubbles in the sight glass have dis-
appeared and the working conditions of the entire refrigeration circuit have returned to normal (sub ---cooling and superheating within the limits indicated below).
SMeasure the superheating as follows:
1) Detect the temperature on the suction line, close to the
bulb of the thermostatic expansion valve, using a contact
thermometer.
2) Connect a pressure gauge (by max. a 30 --- cm pipe) with
the Schraeder connection and read the corresponding
saturated evaporating temperature.
3) The superheating is the difference between the two
readings.
4) For the units with R407C refer to the pressure gauge
scale indicated with the initials D.P. (Dew Point)
SVerify that the superheating is 5ûC --- 8 ûC.
SMeasure the sub---cooling as follows:
1) Detect the temperature on the liquid line using a contact
thermometer.
2) Connect a pressure gauge (by max. a 30 --- cm pipe) with
the Schraeder connection on the liquid line and read the
corresponding saturated condensing temperature.
3) The sub --- cooling is the difference between the two readings.
4) For the units with R407C refer to the pressure gauge
scale indicated with the initials B.P. (Bubble Point)
SVerify that at the condenser outlet, sub---cooling is 3ûC---
5ûC.
IT IS IMPORTANT TO CARRY OUT CHARGING CORRECTLY.
An excess of refrigerant causes an increase in sub ---cooling and
consequent operating difficulties in the hot season; a shortage
of charge generates an increase in superheating and possible
compressor stoppages. Whenever work is carried out on the
unit, ensure afterwards that the working conditions are correct,
checking sub---cooling and superheating.
5
5 . 2 ---O i l c h a r g e
Contact the Technical Support Department for the specifications
of the oil to be used for topping up; the oil changes according to
thetypeofusedrefrigerant.
NEVER MIX DIFFERENT OILS TOGETHER. CLEAN THE PIPING COMPLETELY BEFORE CHANGING THE TYPE OF OIL
USED.
TOP ---UPS OF UP TO 20--- 30% OF THE TOTAL AMOUNT OF
OIL CONTAINED IN THE COMPRESSOR CRANKCASE ARE
PERMITTED; FOR LARGER PERCENTAGES CONTACT THE
TECHNICAL SUPPORT DEPARTMENT.
5.2.1 -- Procedure for oil topping --up
If there has been any loss of oil then this must be topped up as
follows:
1) T ake a clean, dry, transparent container (with volume calibrations) and fill it with at least twice the amount of oil required.
2) Isolate the compressor by closing the cock on the liquid line.
3) Connect to the fittings on the compressor body (Schraeder
valves) and empty it of refrigerant until atmospheric pressure (1 bar) is reached.
4) Using a pipe, connect the oil containerto the oil service fitting
on the lower part of the compressor.
5) Open the oil service cock, lifting the container, so that the oil
flows by gravity.
6) Charge the required quantity of oil (make sure the tube always remains below the oil level in the container).
7) Stop the oil flow by closing the oil service fitting, open the
shut---off cock on the refrigerating circuit and restore the
drained refrigerant charge.
6 ---Safety Devices Settings
The water chiller has already been tested and set up by the manufacturer. The following setting values are suggested in the field.
COMPONENTSETTINGNOTES
diff.set
Operation with R407C/R22
Low pressure switch (LP)
(standard factory setting):
START: 3.6 bar
DIFF.: 0.8 bar
STOP: 2.8 bar
0.2
5
1.5
0.5
bar
bar
Operation with R407C/R22
(standard factory setting):
High pressure switch (HP)
STOP: 26 bar
START: 20 bar
DIFF.: 6 bar (fixed)
The settings for the safety valves installed on the machine are indicated below:
MODELSSETTINGSSAFETY VALVE
004 --- 204 --- 206 --- 207 --- 00828 bar
006 --- 007 --- 011 --- 014 --- 01629 bar
6.1 --- Settingthermostaticexpansion
valve
THIS OPERATION MUST BE PERFORMED BY AN EXPERIENCED REFRIGERATION TECHNICIAN.
Before beginning this adjustment be sure that the refrigerant
charge is correct, checking the the sub --- cooling (3ûC --- 5ûC, as
specified in par. 5.1).
The valve has already been factory --- set and should be reset
when the superheating is not between 5ûC --- 8 ûC, as follows:
1) Important:
Ensure that the instructions in par.5.1 have been carried out.
2) Allow the compressor to operate for 15 mins.
3) Measure the superheating as follows:
a) Connect a manometer to the Schraeder connection lo-
cated on the evaporator outlet tube, and read the manometric temperature on the scale for the refrigerant used
4) The superheating must be 5ûC --- 8 ûC; if not, set the expan-
sion valve as follows:
a) Remove the protective cover;
b) Turn the adjustment screw to return to the optimum val-
ues, tightening it in a clockwise direction to increase the
superheating, or slackening it to reduce the superheat-
ing.
c) Wait about 10 minutes;
d) Measure the superheating and repeat the operation if
necessary.
N.B:
If the superheating is too low, there is a risk of poor lubrication
and consequent breakage of the compressor as a result of pressure shock.
If the superheating is too high the output of the system is limited
and the compressor overheats.
(for the units with R407C refer to the pressure gauge
scale indicated with the initials D.P. = Dew Point).
b) Using a contact thermometer, measure the temperature
on the tube coming out of the evaporator, next to the
socket used for the manometer.
c) The superheating is the difference between the two
readings (b ---a).
reset
HP side
6
7 ---Maintenance
The Maintenance Programme below must be carried out by a
qualified technician, preferably working under a maintenance
contract.
Before any intervention on the unit or accessing the inner components (removing the outer panels), always ensure the machine is switched off. If the rear panels are removed (coil compartment) wait for the fan(s) to come to a complete stop before
accessingthe compartment; if the front panels are removed, pay
special attention when working near the compressor upper part
and the discharge line: they are very hot; possibly wait for them
to cool. Be very careful when operating close to the finned coils,
as the fins are very sharp. Do not remove the fan protection grille
before electrically isolating the whole machine. Do not insert
foreign matter through the fan protection grille. After the maintenance interventions, always close the unit with the suitable
panels, fastened by the tightening system.
Maintenance programme -- Monthly check
SCheck that the fan motor rotates freely without any abnormal noise, and ensure that the
FANS
CONDENSER AND AIR FILTER
CONTROLSCheck that the control equipment, LEDs and display are operating correctly.
ELECTRICAL CIRCUIT
REFRIGERATION CIRCUIT
CHILLED WATER CIRCUIT
bearings are not running hot.
SAlso check the current absorption.
SCheck the conditions of the filters (if they are supplied); if necessary clean them (including
the electrical panel ventilation filter).
SCheck the condenser coils and clean if necessary with compressed air or soft brushes.
SCheck the electrical supply on all phases.
SEnsure that all electrical connections are tight.
SCheck the condensing and the evaporating pressures (to be done by a refrigeration techni-
cian).
SCheck the compressor’s current absorption, the delivery temperature and possible unusual
noises.
SCheck the refrigerant charge by means of the sight glass.
SCheck that the safety devices operate correctly.
SCheck the correct operation of the thermostatic valve (superheating between 5ûC --- 8ûC).
SCheck that the oil level indicated by the compressor sight glass is higher than the min. value.
SEnsure that there are no water leaks.
SBleed any air out of the hydraulic circuit using the bleed valves.
SVerify that the water flow rate is correct.
SCheck the inlet --- outlet liquid temperature and pressure.
SCheck the correct operation of the three--- way valve (Versions with free--- cooling only).
SCheck if the system is charged with the specified glycol percentage and that no ice has
formed in the hydraulic circuit.
SCheck the evaporator cleanliness.
7.1 --- Spare parts
The use of original spare parts is recommended.
When placing an order refer to the ”Component List” enclosed
with the machine and quote the unit model no. and serial no.
7.2 --- Dismantling the unit
The machine has been designed and built to ensure continuous
operation.
The working life of some of the main components, such as the
fans and the compressors, depends on the maintenance that
they receive.
If the unit has to be dismantled, the job must be done by skilled
refrigeration technicians.
The refrigerant and the lubricating oil in the circuit must be disposedofinconformitywiththelawsinforceinyourcountry.
8 ---O p t i o n s a n d A c c e s s o r i e s
8 . 1 ---P u m p s e t
The centrifugal pump units are direct driven, with close --coupled motors and a single shaft; the induction motor has 2
poleswithIP54protectionandclassFinsulation.
The materials used for the pump main components are:
SPump body in plastic material PA 6.6 (cast iron in all high
pressure freecooling versions and on model 016 in the Chiller high head pressure version and Superchiller standard
head pressure version);
SImpeller in in plastic material PPO (stainless steel in all high
pressure freecooling versions and on model 016 in the Chiller high head pressure version and Superchiller standard
head pressure version);
SStainless steel shaft;
SGraphite impregnated ceramic mechanical seal (EPDM in
all high pressure freecooling versions and on model 016 in
the Chiller high head pressure version and Superchiller
standard head pressure version), suitable for the use of mixtures containing ethylene glycol.
The pump units have been chosen and sized to operate within
specific limits, namely:
SWater / ethylene glycol mixtures up to 65% / 35% by weight;
STemperatures of the standard pumped fluid not lower than
4°C.
The hydraulic circuitincludes,for each pump, a suctionshut---off
valve and a delivery check valve if two pumps are installed, or
suction and delivery shut---off valves if a singlepump is installed.
In the electrical panel there are automatic circuit breakers for
each pump; the microprocessor control manages the operating
rotation between the two pumps and start - --up of the stand -- -by
pump if the primary pump fails.
For the technical features of the pumps and the hydraulic schematic see Tab. 8, Fig. 12, Fig. 13, Fig. 14 and Fig. 15.
8.2 --- Water chiller with partial heat
recovery (20%)
This option enables the recovery of up to 20% of the heat normally rejected by the condensers. The system does not require any
adjustment and is made up of plate heat exchangers installed
on each circuit before the condenser. The exchangers are protected by a suitable anti --- frost heater that operates when the system is stopped. It is recommended that a safety valve be
installedin the hydraulic circuit to avoid hazards due to overpressures, if there is no water flow through the recuperator.
7
The water temperature at the recuperator inlet (in stable operating conditions) must be in the range of 25ûC---45ûC, with an out-
let differential of between 3.5ûC --- 8 ûC.
8.3 --- Waterchillerwithtotalheatrecovery
(100%)
All heat discharged by the unit to the condenser is recovered.
The system includes an additional refrigerating circuit made up
of a three--- way solenoid valve, supplying --- in case of hot water
demand --- a plate exchanger, usually by --- passed and sized so
as to discharge all condensing heat (also installed before the
finned air condenser in series with it); a check valve, a liquid receiver at the exit of the finned air condenser working as storage
for the needed additional refrigerant charge (see refrigerating
scheme). The recuperator is insulated with closed cell polyurethane and is equipped with heaters activated when the recuperator is deactivated to prevent frost in winter with the system
stopped or not perfectly drained.
The operation in total recovery mode is enabled by an external
contact. The Microface control will simultaneously suit the fan
speed changing the fan speed setpoint differently from the standard operation without recovery (practically slowing the fans
down till they switch off); anyway, the operation in recovery
mode is enabled also without load at the users. Indeed, if the users do not demand heat, the water flowing to the condenser
reaches a temperature that does not enable the total condensation of the compressed gas, and the remaining portion of the
phase change can thus take place in finned coil without interrupting the recovery process through the intervention of the machine safety devices.
If the plate exchanger is supplied with too cold water, or if the system is not preset by the installation technician with a three or
two---way proportional adjustment valve for the exchanger bypass (indispensable for cold starts, see following “Recommended hydraulic circuit” ), the condensing pressure tends to
decrease too much; a prolonged condition of low condensing
temperature below the safety threshold leads the Microface microprocessor control to disable the heat recovery, protecting the
system from any possible malfunctioning.
Fig. e -- Recommended hydraulic circuit
8.5--- Waterchillerwithinertiatank
The machine can be supplied complete with a buffer tank; it performs the inertial stabilizer function, for better compressor operation, summed up in the following two points:
Sit reduces the frequency of the compressor peaks, which is
higher the lower the system thermal inertia, improving their
performance;
Sit naturally eliminates the operational problems caused by
sudden load variations (shown by variations of the chilled
water temperature).
The buffer tank is supplied insulated, with a drain valve, vent
valve and connection for immersion electric heaters; maximum
operating pressure 6 bar.
Builtincarbonsteelandcoatedwithanti---condensationinsulation. It can be installed in all MATRIX S versions inside the coil
compartment.
Mod. 004 ---006 ---007 technical data
SInternal volume:200 litres
SNet weight:110 kg
SWorking weight:310 kg
Mod. 008 ---011 ---014 --- 016 technical data
SInternal volume:400 litres
SNet weight:140 kg
SWorking weight:540 kg
Mod. 204 ---206 ---207 technical data
SInternal volume:160 litres
SNet weight:100 kg
SWorking weight:260 kg
Heat recovery
users
Heat recovery
exchanger
8.4 --- Hydraulic circuit accessories
Made up of an expansion vessel (pre --- charged at 1.5 bar, max.
operating pressure 10 bar) and a safety valve, set at 5 bar. Their
position in the hydraulic circuit is illustrated in Fig. 12, Fig. 13,
Fig. 14 and Fig. 15.
SExpansion vessel volume: 8 litres for all units.
It is recommended that the total required expansion vessel ca-
pacity is always checked, depending on the unit’s internal hydraulicvolume(withthevolumeofthebuffertank,ifinstalled),
the user circuit volume, the glycol percentage in the mixture, and
the expected maximum temperature variation of the mixture.
The water flow switch is a compulsory device protecting the unit.
It is installed, as standard, on units with the optional on --- board
pump set, and is available as a option for units without pumps
on board: in the latter case the flow switch, if not installed on the
machine, must be installed on the hydraulic circuit by the installer and wired to the electric panel terminal board, as indicated on
the wiring diagram.
8
Tab. 1 ---Internal hydraulic volume
ModelUnit volume
004800427
006900635
0071000744
2041020430
CBH
CLH
CQH
(*) Add the tank’s volume for the units with optional buffer tank
20610
20713
0082400877
0112701192
01430014110
01646016144
004800427
006900643
0071400755
2041020430
20610
20718
0082400877
01127011107
01438014134
01646016144
004800434
0061300654
0071400755
2041020437
20615
20718
0082400888
01135011131
01438014134
01646016169
(*)
[l]ModelUnit volume
SBH
SLH
SQH
20637
20747
20645
20759
20656
20759
(*)
[l]
Tab. 2 ---Partial heat recovery (20%)
Model
Heating capacity
Water flow
Water pressure drop
Water connections
Working conditions: outdoor temperature 35ûC, water inlet/outlet 12/7ûC (Chiller versions), glycol mixture 30% inlet/outlet 15/10ûC (SuperChiller versions). Heat recovery conditions: water inlet/outlet 40/45ûC.
kW
l/s
kPa
B S P --- T
004
204
10,814,818,221,629,636,444,3
0,5160,7070,8701,0321,4141,7392,117
811148111421
1”1”1”11/4”11/4”11/4”11/4”
006
206
007
207
008011014016
Tab. 3 ---Total heat recovery (100%)
Model
Heating capacity
Water flow
Water pressure drop
Water connections
Working conditions: water inlet/outlet 12/7ûC (Chiller versions). Heat recovery conditions: water inlet/outlet 40/45ûC.
kW
l/s
kPa
B S P --- T
004
204
537491105144177223
2,533,544,355,026,888,4610,65
60708060708090
2”2”2”21/2”21/2”21/2”21/2”
006
206
007
207
008011014016
9
Loading...
+ 26 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.