TRANSIENT VOLTAGE SURGE SUPPRESSION
AccuVar ACV
Liebert

®
Suppression
Systems
LIEBERT ACCUVAR® ACV SERIES
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
TABLE OF CONTENTS
UNPACKING AND INSTALLATION
Unpacking and Preliminary Inspection......................................................................................3
Storage...........................................................................................................................................3
Location Considerations..............................................................................................................3
ELECTRICAL CONNECTIONS
Voltage Ratings & Power Source Configurations....................................................................4
Overcurrent Protection .................................................................................................................4
Connection.....................................................................................................................................5
System Grounding & Bonding....................................................................................................5
OPERATION.......................................................................................................................................7
Summary Alarm Contact Option................................................................................................7
TROUBLESHOOTING / MAINTENANCE / SERVICING
Inspection and Cleaning..............................................................................................................7
Troubleshooting............................................................................................................................7
Corrective Maintenance...............................................................................................................7
Servicing ........................................................................................................................................7
LIMITED WARRANTY.......................................................................................................................9
DECLARATION OF CONFORMITY..............................................................................................11
FIGURES
Figure 1. AccuVar ACV Series Dimensions............................................................................2
Figure 2. Installation Diagram...................................................................................................8
TABLES
Table 1. Terminal Wire Size Range & Suggested Wiring Overcurrent Protection............4
Table 2. Voltage Ratings & Power Source Configurations...................................................6
Installation, Operation ACV Series
and Maintenance Manual - 1 - Rev 2, 3/00

®
Suppression
Systems
INSTALLATION INSTRUCTIONS FOR THE LIEBERT
ACCUVAR® ACV SERIES SURGE PROTECTIVE DEVICE
WITH OPTIONAL FILTERING
The Liebert AccuVar® ACV Series Surge
Protective Device (SPD) is a high quality, high
energy surge current diversion system designed to
protect sensitive equipment from damaging
transient surges and electrical line noise. Proper
installation is required for maximum system
performance.
The installer should perform the following steps to
assure a quality installation. The entire installation
manual should be read before starting installation.
These instructions do not replace national or local
electrical codes. Check applicable electrical codes
to ensure compliance. Installation of the Liebert
AccuVar ACV Series Surge Protective Device
should only be performed by qualified personnel.
Figure 1. AccuVar ACV Series Dimensions.
Installation, Operation ACV Series
and Maintenance Manual - 2 - Rev 2, 3/00

®
UNPACKING AND INSTALLATION
Suppression
Systems
Unpacking and Preliminary Inspection
1. Inspect the shipping crate(s) for damage or
signs of mishandling before unpacking the
unit.
2. If any damage as a result of shipping is
observed, immediately file a claim with the
shipping agency and forward a copy to your
local Liebert Sales Representative.
Storage
The unit should be stored in a clean, dry
environment. Storage temperature range is -55ºC
(-67ºF) to +85ºC (+185ºF). Care should be taken
to avoid condensation. All packing and shipping
materials should be left intact until the unit is
ready for final installation. If the unit has been
stored for an extended period of time, the unit
should be cleaned and carefully inspected before
placing into service.
Location Considerations
Environment – The unit is designed for operation
indoors in ambient temperatures of -40ºC (-40ºF)
to +50ºC (+122ºF) with a relative humidity of 0%
to 95% (non-condensing).
The cover screws and “O” rings are supplied inside
of the unit in the small plastic bag that also
contains the wiring ring terminals. To properly
attach the cover to the enclosure the four “O” rings
must be used with the four screws provided, prior
to placing the screw in hole of cover. Screws
should be torqued between 4 and 10 inch-pounds.
Note: To maintain the integrity of the “O”
rings, protection against direct sunlight is
advised.
Equipment Performance – For maximum system
performance, the unit must be located as close to
the protected circuit as practical to minimize
interconnecting wiring length.
For optimum transient surge protection,
coordinated surge suppression should be applied at
the service entrance, at all other electrical
connections to the building (telephone, CATV,
etc.), and at known transient surge generating
loads within the building (large motors, arc
welders, switched capacitors, etc.). Electrical line
noise protection should also be applied close to the
point of usage for sensitive electronic loads
(computers, electronic appliances, solid state
motor drives, etc.). For interconnected electronic
loads (such as by way of data cabling),
communication line protectors may also be applied
to the interconnect wiring.
The unit is provided in a NEMA 12, 4, and 4X
rated industrial use enclosure, which is dust, drip,
and water tight and should not be installed in areas
with flammable materials or explosive
atmospheres.
Outdoor Use – To assure water tightness for
outdoor use, “O” rings must be used with screws
to secure cover!
Installation, Operation ACV Series
and Maintenance Manual - 3 - Rev 2, 3/00
Mounting – The unit is to be wall mounted. Refer
to Figure 1 for mounting dimensions.