Liebert AccuVar ACV Installation, Operation And Maintenance Manual

INSTALLATION, O
PERATION AND
MAINTENANCE MANUAL
TRANSIENT VOLTAGE SURGE SUPPRESSION
AccuVar ACV
Liebert
Surge
®
Suppression
Systems
LIEBERT ACCUVAR® ACV SERIES
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
TABLE OF CONTENTS
UNPACKING AND INSTALLATION
Unpacking and Preliminary Inspection......................................................................................3
Storage...........................................................................................................................................3
Location Considerations..............................................................................................................3
ELECTRICAL CONNECTIONS
Voltage Ratings & Power Source Configurations....................................................................4
Overcurrent Protection .................................................................................................................4
Connection.....................................................................................................................................5
System Grounding & Bonding....................................................................................................5
OPERATION.......................................................................................................................................7
Summary Alarm Contact Option................................................................................................7
TROUBLESHOOTING / MAINTENANCE / SERVICING
Inspection and Cleaning..............................................................................................................7
Troubleshooting............................................................................................................................7
Corrective Maintenance...............................................................................................................7
Servicing ........................................................................................................................................7
LIMITED WARRANTY.......................................................................................................................9
DECLARATION OF CONFORMITY..............................................................................................11
FIGURES
Figure 1. AccuVar ACV Series Dimensions............................................................................2
Figure 2. Installation Diagram...................................................................................................8
TABLES
Table 1. Terminal Wire Size Range & Suggested Wiring Overcurrent Protection............4
Table 2. Voltage Ratings & Power Source Configurations...................................................6
Installation, Operation ACV Series and Maintenance Manual - 1 - Rev 2, 3/00
Surge
®
Suppression
Systems
INSTALLATION INSTRUCTIONS FOR THE LIEBERT
ACCUVAR® ACV SERIES SURGE PROTECTIVE DEVICE
WITH OPTIONAL FILTERING
The Liebert AccuVar® ACV Series Surge Protective Device (SPD) is a high quality, high energy surge current diversion system designed to protect sensitive equipment from damaging transient surges and electrical line noise. Proper installation is required for maximum system performance.
The installer should perform the following steps to assure a quality installation. The entire installation manual should be read before starting installation. These instructions do not replace national or local electrical codes. Check applicable electrical codes to ensure compliance. Installation of the Liebert AccuVar ACV Series Surge Protective Device should only be performed by qualified personnel.
Figure 1. AccuVar ACV Series Dimensions.
Installation, Operation ACV Series and Maintenance Manual - 2 - Rev 2, 3/00
Surge
®
UNPACKING AND INSTALLATION
Suppression
Systems
Unpacking and Preliminary Inspection
1. Inspect the shipping crate(s) for damage or
signs of mishandling before unpacking the
unit.
2. If any damage as a result of shipping is
observed, immediately file a claim with the
shipping agency and forward a copy to your
local Liebert Sales Representative.
Storage
The unit should be stored in a clean, dry environment. Storage temperature range is -55ºC (-67ºF) to +85ºC (+185ºF). Care should be taken to avoid condensation. All packing and shipping materials should be left intact until the unit is ready for final installation. If the unit has been stored for an extended period of time, the unit should be cleaned and carefully inspected before placing into service.
Location Considerations
Environment – The unit is designed for operation indoors in ambient temperatures of -40ºC (-40ºF) to +50ºC (+122ºF) with a relative humidity of 0% to 95% (non-condensing).
The cover screws and “O” rings are supplied inside of the unit in the small plastic bag that also contains the wiring ring terminals. To properly attach the cover to the enclosure the four “O” rings must be used with the four screws provided, prior to placing the screw in hole of cover. Screws should be torqued between 4 and 10 inch-pounds.
Note: To maintain the integrity of the “O” rings, protection against direct sunlight is advised.
Equipment Performance – For maximum system
performance, the unit must be located as close to the protected circuit as practical to minimize interconnecting wiring length.
For optimum transient surge protection, coordinated surge suppression should be applied at the service entrance, at all other electrical connections to the building (telephone, CATV, etc.), and at known transient surge generating loads within the building (large motors, arc welders, switched capacitors, etc.). Electrical line noise protection should also be applied close to the point of usage for sensitive electronic loads (computers, electronic appliances, solid state motor drives, etc.). For interconnected electronic loads (such as by way of data cabling), communication line protectors may also be applied to the interconnect wiring.
The unit is provided in a NEMA 12, 4, and 4X rated industrial use enclosure, which is dust, drip, and water tight and should not be installed in areas with flammable materials or explosive atmospheres.
Outdoor Use – To assure water tightness for outdoor use, “O” rings must be used with screws to secure cover!
Installation, Operation ACV Series and Maintenance Manual - 3 - Rev 2, 3/00
Mounting – The unit is to be wall mounted. Refer to Figure 1 for mounting dimensions.
Surge
®
WARNING
!!
ELECTRICAL CONNECTIONS
Suppression
Systems
All electrical connections should be installed by a qualified (licensed) electrician only. All wiring must comply with the National Electrical Code (NEC) and applicable local codes.
VERIFY THAT ALL POWER
CIRCUITS ARE DE-ENERGIZED AND
LOCKED OUT BEFORE MAKING
ELECTRICAL CONNECTIONS.
Terminals are provided inside the Liebert AccuVar SPD units for the line (phase), neutral (if used), and transient ground connections.
Voltage Ratings & Power Source Configurations
Before making connections to the unit, verify that the unit model number and nameplate voltage rating are appropriate for connection to the intended power source. See Figure 2 for voltage rating applications with typical power source configurations and assure that system voltages do not exceed the maximum continuous operating voltage (MCOV) on the unit’s data label.
Surge Voltage Ratings – To obtain the suppression voltage ratings (SVRs), as obtained by Underwriters Laboratories, Incorporated, in accordance with the Standard for Safety, Surge
protective devices, (SPD), Standard 1449, Second
Edition, dated August 15, 1996, marked on this
product, #10 AWG wire must be utilized to connect the AccuVar® to your facilities’ power grid. Connections made with other that #10 AWG conductors may result in different suppression voltage ratings.
Circuit Ampacity Limitations – Representative samples of this device have been investigated by Underwriters Laboratories, Incorporated to withstand, without exposing live circuits or components on power sources, with voltage of two times (2x) the device ratings, and fault currents of up to 300,000 AIC, as described in the Standard
for Safety, Surge protective devices, (SPD), Standard 1449, Second Edition, dated August 15,
1996.
Overcurrent Protection
The SPD unit conducts practically no current under normal operation and only conducts during very short duration transient conditions. The Liebert AccuVar ACV Series SPD units contain UL approved 300 kAIC internal system fusing to protect against device failure. This overcurrent protection, while not currently required by SPD safety agencies or installation codes (NEC Article
280), has proven to be prudent engineering practice.
External overcurrent protection is not specifically required, nor is it desired since it impedes the performance of the transient surge suppressor. If overcurrent protection of the conductors to the transient surge suppressor is desired, the suggested fuse sizes based on the unit’s transient surge current capabilities and suggested wire sizes are shown in Table 1.
Table 1. Terminal Wire Size Range and Suggested Wiring Overcurrent Protection (All Models).
SUGGESTED
WIRE SIZE
(AWG)
10* 6-32 screw ring or spade terminal required. 30A 12 (Spare terminal screws enclosed) 20A
Installation, Operation ACV Series and Maintenance Manual - 4 - Rev 2, 3/00
SPECIAL NOTES
* Must be used for UL1449 performance.
SUGGESTED
FUSE / CIRCUIT BREAKER
AMPACITY (IF USED)
Surge
®
Suppression
Systems
Connection
With the AccuVar’s parallel connection, the length of wiring to the transient voltage surge suppression (SPD) unit must be minimized for best performance. Wire lengths longer than 10 feet must be avoided. Wiring connections may be made directly into circuit breakers.
To reduce the wiring impedance to surge currents, the phase, neutral (if required), and ground conductors are recommended to be twisted together and routed in the same raceway (conduit). Avoid any sharp bends in the conductors.
Wire Sizing - With parallel connection, the size of the wiring to the SPD unit is independent of the protected circuit’s ampacity. Suggested wire sizes based on the unit’s transient surge current capabilities are shown in Table 1.
System Grounding & Bonding
The performance and safety of any SPD system is dependent on proper grounding. Grounding is required primarily for safety. Correct implementation also enhances equipment performance. Incorrect grounding can reduce or impede the SPD’s operation.
All electrical circuits to or from the SPD must include an equipment grounding conductor as required by the NEC and local codes.
An insulated grounding conductor is recommended for the SPD. The grounding conductor should be the same wire size as the associated power conductors and should be connected in close proximity to the SPD.
Grounding Electrode – Contrary to popular belief, transient surge suppressors do not discharge all surges to ground (earth). Transient surge suppressors divert the surge current back to its source to complete the electrical circuit.
In the case of lightning, whose potential is developed with respect to the earth, the SPD diverts the surge current to the grounding electrode (earth connection). However, for most transient surges which are developed by switching loads, the SPD diverts the surge current back to its source without involving the grounding electrode.
For proper SPD performance, the service entrance grounding electrode system must comply with the NEC by having all available electrodes (building steel, metal water pipe, driven rods, concrete encased electrodes, etc.) properly bonded together and connected to the power system grounding.
The use of a separate grounding electrode to ground the SPD defeats the effectiveness of the SPD, is a potential safety hazard, may cause equipment damage, is an NEC violation (reference NEC 250-51 and 250-54), and is not recommended.
Installation, Operation ACV Series and Maintenance Manual - 5 - Rev 2, 3/00
Surge
®
Split Single Phase, 3 W + G
Single Phase L-N, 2 W +G
Three Phase Wye, 3 W + G
VOLTAGE RATINGS & POWER SOURCE CONFIGURATIONS
Suppression
Systems
Source Configurations
Single Phase L-L, 2 W + G
Three Phase Delta, 3 W + G
Nominal
Operating Voltage
Maximum Continuous
Operating Voltage
Model Voltage
Code
100 130 L-N 100N 110 130 L-N 110N 120 150 L-N 120N 230 275 L-N 230N 277 320 L-N 277N 347 420 L-N 347N 208 130 L-L 208L 240 150 L-L 240L 400 275 L-L 400L 480 275 L-L 480L 600 420 L-L 600L
120 / 208 or 120 / 240 150 L-N 120S
277 / 480 320 L-N 277S 347 / 600 420 L-N 347S
208 250 L-L 208D 240 320 L-L 240D 380 420 L-L 380D 415 580 L-L 415D 480 580 L-L 480D
600 680 L-L 600D 120 / 240 150 L-N 240H 208 / 240 250 L-N 240H
Three Phase Delta Hi Leg, 4 W + G
Three Phase Wye, 4 W + G
No Neutral
Table 2. Voltage Ratings and Power Source Configurations.
For other voltages or source configurations, consult factory.
Installation, Operation ACV Series
and Maintenance Manual - 6 - Rev 2, 3/00
120 / 208 150 L-N 120Y 220 / 380 320 L-N 220Y 240 / 415 320 L-N 240Y 277 / 480 320 L-N 277Y 347 / 600 420 L-N 347Y
120 130 L-L 120Y
230 275 L-L 230Y
277 320 L-L 277Y
347 420 L-L 347Y
Surge
®
WARNING
!!
Suppression
Systems
OPERATION
Liebert AccuVar ACV Series SPD Systems require little or no operator intervention after installation. The units are provided with status LED, which assist in determining when the unit needs service (see Troubleshooting/Repair/ Maintenance Section).
If the unit is energized and the green LED is off (and / or the red LED is on), the AccuVar is not fully functional and will require replacement.
Summary Alarm Contact Option
Optional Form C ( 1 N.O. and 1 N.C.) relay contacts may be provided for remote indication of
TROUBLESHOOTING / MAINTENANCE / SERVICING
Inspection and Cleaning
Periodic system inspections, cleaning, and connection checks are recommended to ensure reliable system performance and continued transient protection.
(For any other problems not listed below, or if cause of the problem cannot be determined, please call Control Concepts at 800-288-6169 or 607-724-2484.)
phase loss, undervoltage (70% of line voltage, typical), power loss, and suppression failure. If the status of the contacts change (indicating a problem), one of these conditions exists.
The summary alarm contact terminals are located inside the unit. Contacts are rated for 5 amps at 125 VAC maximum.
Note: Wiring for the Form C contacts may be routed through the flexible conduit with the phase wiring. All wire must comply with the National Electrical Code (NEC) and applicable local codes.
provided to indicate when the unit needs replacement (see operation section of this manual for details). To ensure continuity of surge protection, failed units should be replaced at the earliest convenient service opportunity.
Servicing
Troubleshooting
If status failure indication occurs or Form C relay has changed states, a qualified electrician should first determine if the systems voltage and proper phasing exists.
If the AccuVar SPD remains in an alarm condition once the technician is satisfied that the electrical system and its connections are normal, the unit should be replaced.
Corrective Maintenance
The Liebert AccuVar ACV Series SPD is designed for years of trouble-free operation. However, even the most reliable equipment may fail under abnormal conditions. Diagnostic indicators are
Installation, Operation ACV Series and Maintenance Manual - 7 - Rev 2, 3/00
ONLY QUALIFIED PERSONNEL SHOULD PERFORM MAINTENANCE ON THE SYSTEM.
HAZARDOUS VOLTAGES ARE PRESENT INSIDE THE UNIT DURING NORMAL OPERATIONS.
ELECTRICAL SAFETY PRE­CAUTIONS MUST BE FOLLOWED WHEN SERVICING THIS UNIT.
TO PREVENT RISK OF ELECTRICAL SHOCK, TURN OFF AND LOCK OUT ALL POWER SOURCES TO THE UNIT BEFORE SERVICING UNIT.
Surge
®
Suppression
Systems
*
*
Figure 2. Installation Diagram.
*If neutral is provided, a reliable neutral must be pulled to the AccuVar.
Installation, Operation ACV Series and Maintenance Manual - 8 - Rev 2, 3/00
Surge
®
Suppression
Systems
LIMITED WARRANTY
This Warranty is given ONLY to purchasers who buy for commercial or industrial use in the ordinary course of each purchaser's business.
General: Control Concepts' products are in our opinion the finest available. We take pride in our products and are pleased that you have chosen them. Under certain
circumstances, we offer with our products the following Five-Year Warranty Against Defects in Material and Workmanship. Please read your Warranty carefully. This Warranty sets forth our responsibilities in the unlikely event of defect and tells you how to obtain performance under this Warranty.
FIVE YEAR LIMITED WARRANTY AGAINST DEFECTS IN MATERIAL AND WORKMANSHIP
CONTROL CONCEPTS PRODUCTS COVERED: AccuVar®.
Terms of Warranty:
As provided herein, the Control Concepts product is warranted to be free of defects in material and workmanship for a period of five (5) years from the date of delivery of the product to User. The delivery date will be determined only from the Control Concepts bill of lading. If any of the Control Concepts products fail to conform to the warranty within the warranty period, Control Concepts, at its option, will furnish new or factory remanufactured parts for repair or replacement of that part.
Warranty Extends to First Purchaser for Use, Non-transferable:
This Warranty is extended to the first person, firm, association or corporation for whom the Control Concepts product specified herein is originally installed for use in the United States (the "User"). This Warranty is not transferable or assignable without the prior written permission of Control Concepts.
Assignment of Warranties:
Control Concepts assigns to User any warranties which are made by manufacturers and suppliers of components of the Control Concepts product and which are assignable, but Control Concepts makes NO REPRESENTATIONS as to the effectiveness or extent of such warranties, assumes NO RESPONSIBILITY for any matters which may be warranted by such manufacturers or suppliers and extends no coverage under this warranty to such components.
Descriptions:
Control Concepts warrants for the period and on the terms of the Warranty set forth herein that the Control Concepts product will conform to the descriptions contained in Control Concepts' final invoices, orders and Control Concepts' product brochures. Control Concepts does not control the installation and use of any Control Concepts product. Accordingly, it is understood that the Descriptions are NOT WARRANTIES OF PERFORMANCE and NOT WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE.
Obtaining Performance Under This Warranty:
Within a reasonable time, but in no case to exceed thirty (30) days, after User's discovery of a defect, User shall contact Control Concepts and request a return authorization number. User shall ship the product, with proof of purchase, to Control Concepts freight prepaid. Control Concepts products shipped to Control Concepts without a return authorization number will be refused and returned freight collect to User at User's expense. Control Concepts products shipped by User to Control Concepts which have incurred freight damage due to User's improper packaging of the product will not be covered by this Warranty and any repairs or replacement parts, components or products needed will be invoiced in the full current price amount and returned freight collect to User.
Subject to the limitations specified herein, Control Concepts will repair or replace, at its option, without charge for Control Concepts labor or materials, subsequent to its inspection and F.O.B. Control Concepts' facility, the Control Concepts product shipped to Control Concepts with a return authorization number and warranted hereunder which does not conform to the Warranty. Replacement parts, components or products shipped to User prior to Control Concepts' receipt and inspection of the product claimed to be defective, shall be invoiced in the full current price amount and shipped freight collect F.O.B. Control Concepts' facility. Warranty coverage will be extended only after Control Concepts' receipt of the claimed defective product within thirty (30) days of shipment of any replacement parts, components or products, if applicable, Control Concepts' inspection discloses the claimed defect and the returned product shows no signs of treatment or use which would void the coverage of this Warranty.
Items Not Covered By Warranty:
THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY misuse, improper application, wrong or inadequate electrical current or connection, inadequate water or drain services, negligence, inappropriate on site operating conditions, corrosive atmosphere, repair by non-Control Concepts designated personnel, accident in transit, tampering, alterations, a change in location or operating use, exposure to the elements, Acts of God, theft or installation contrary to Control Concepts' recommendations or specifications, or in any event if the Control Concepts serial number has been altered, defaced or removed.
THIS WARRANTY DOES NOT COVER shipping costs, installation costs, circuit breaker resetting or maintenance or service items and further, except as provided herein, does NOT include labor costs or transportation charges arising from the replacement of the Control Concepts product or any part thereof or charges to remove same from any premises of the User.
THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY use of the Control Concepts product in combination with any electrical or electronic components, circuits, systems, assemblies, or other materials not furnished by Control Concepts. Control Concepts does NOT warrant the suitability for use or the results of the Control Concepts product in combination with the products of others.
REPAIR OR REPLACEMENT OF A DEFECTIVE PRODUCT OR PART THEREOF DOES NOT EXTEND THE ORIGINAL WARRANTY PERIOD.
Installation, Operation ACV Series and Maintenance Manual - 9 - Rev 2, 3/00
Surge
®
Suppression
Systems
Limitations:
THIS WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE.
USER'S SOLE AND EXCLUSIVE REMEDY IS REPAIR OR REPLACEMENT OF THE CONTROL CONCEPTS PRODUCT AS SET FORTH
HEREIN.
IF USER'S REMEDY IS DEEMED TO FAIL OF ITS ESSENTIAL PURPOSE BY A COURT OF COMPETENT JURISDICTION, CONTROL
CONCEPTS' RESPONSIBILITY FOR PROPERTY LOSS OR DAMAGE SHALL NOT EXCEED ONE TIMES THE NET PRODUCT PURCHASE PRICE.
IN NO EVENT SHALL CONTROL CONCEPTS ASSUME ANY LIABILITY FOR INDIRECT, SPECIAL, INCIDENTAL, OR ECONOMIC
CONSEQUENTIAL DAMAGES OF ANY KIND WHATSOEVER, INCLUDING WITHOUT LIMITATION, LOST PROFITS, BUSINESS INTERRUPTION OR LOSS OF DATA, WHETHER ANY CLAIM IS BASED UPON THEORIES OF CONTRACT, NEGLIGENCE, STRICT LIABILITY, TORT OR OTHERWISE.
Miscellaneous:
NO SALESPERSON, EMPLOYEE OR AGENT OF CONTROL CONCEPTS IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS
WARRANTY. Warranty terms may be modified, if at all, only in a writing signed by a Control Concepts' officer.
This Warranty is effective as of the date of Control Concepts receipt of payment and supersedes all previous warranties. Control Concepts reserves the right
to supplement or change the terms of this Warranty in any subsequent warranty offering to User or others.
In the event that any provision of this Warranty should be or becomes invalid and/or unenforceable during the warranty period, the remaining terms and
provisions shall continue in full force and effect.
This Warranty is given in and is intended to be construed under the laws of the State of New York.
This Warranty represents the entire agreement between Control Concepts and User with respect to the subject matter herein and supersedes all prior or
contemporaneous oral or written communications, representations, understandings or agreements relating to this subject.
Installation, Operation ACV Series and Maintenance Manual - 10 - Rev 2, 3/00
Surge
®
Suppression
Systems
DECLARATION OF CONFORMITY
All models of the AccuVar Series are in compliance with the EMC Directive 89/336/EEC, conforming to EMC standard IEC 1000-4-4 and IEC 1000-4-5.
----- Office of the Vice-President of Engineering, Binghamton, NY USA, June 1996.
Installation, Operation ACV Series and Maintenance Manual - 11 - Rev 2, 3/00
TRANSIENT VOLTAGE SURGE SUPPRESSION
A World Leader in Computer Support Systems
Environment Control Power Protection Site Monitoring / Control
Liebert Corporation designs, manufactures and markets complete systems for improve­ment of computer uptime and perfor­mance. The result is improved business operations, increased productivity and higher return on the computer investment. Liebert Systems provide dependable environ­mental control and electrical power pro­tection, combined with centralized monitoring and control. This approach represents a single-source integrated computer support network. Based on over two decades of experience and over 80,000 installations world­wide, Liebert is committed to offering the highest quality products and services for applications requiring computer support.
Control Concepts Corporation
A Subsidiary of the Liebert Corporation 328 Water Street, P.O. Box 1380 Binghamton, NY 13902 USA Tel: 607/724-2484
800/288-6169
Fax: 607-722-8713
While every precaution has been taken to ensure accuracy and completeness in this manual. Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
©1999 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice.
®Liebert and the Liebert logo are registered trademarks of Liebert Corporation.
Printed in U.S.A SL-502 (3/00)
Loading...