Liebert 700-3000 VA User Manual

Page 1
R
UPStation GXT™
700-3000 VA
230V
USER MANUAL
English / Deutsch / Français /
Italiano / Español
Page 2
IMPORTANT SAFETY INSTRUCTIONS
WARNING: Do not attempt to service this product yourself except to replace
the battery. Opening or removing the cover may expose you to dangerous voltages, even when the AC cord is disconnected from the electrical outlet.
Refer all servicing to qualified service personnel.
1. SAVE THESE INSTRUCTIONS. THIS MANUAL CONTAINS IMPORTANT SAFETY INSTRUCTIONS. Read all safety and operating instructions before operating the Uninterruptible Power System (UPS). Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions.
2. This product is designed for Commercial/Industrial use only. It is not intended for use with life support and other designated “critical” devices. Maximum load must not exceed that shown on the UPS rating label. If uncertain, consult your dealer. See Limited Warranty.
3. WHEN REPLACING THE BATTERIES, USE THE APPROPRIATE LIEBERT-APPROVED REPLACEMENT BATTERY KIT. PROPER DISPOSAL OF BATTERIES IS REQUIRED. REFER TO YOUR LOCAL LAWS AND REGULATIONS FOR DISPOSAL REQUIREMENTS.
4. Always turn off the UPS and unplug it before starting the battery replacement procedure. To replace batteries, refer to the battery replacement procedure. If you feel unqualified to replace the batteries, do not open the battery door. Refer all servicing to qualified service personnel.
5. CAUTION: Do not open or mutilate the batteries. Released electrolyte is harmful to skin and eyes and may be toxic.
6. The mains supply socket or means of isolation must be within 2 meters of the equipment and accessible to the operator. The UPS is designed for data processing equipment.
7. The UPS comes with two output power leads with molded connectors - do not modify these leads. Consult dealer if connector does not match the load socket. UPS must be grounded at all times while in use. Turn UPS off before unplugging it, or the safety earth will be removed.
8. The UPStation GXT™ models 700 VA, 1000 VA, 1500 VA, and 2000 VA are not supplied with an input power lead for connection to the mains supply socket. Use the input mains supply power lead from your data processing equipment to connect the UPS to the mains supply. For the 3000 VA model, use the supplied 16 ampere rated input mains supply lead. For UK supply systems, consult a qualified electrician to connect the lead supplied for the 3000 VA model to the mains supply.
CAUTION: The UPS and the connected load combined total earth leakage
current must not exceed 3.5 milliamperes. If the connected load earth leakage current is likely to exceed 2.0 milliamperes or you are unsure, then convert the input lead attachment to either a fixed wiring installation or an industrial plug/socket (e.g. CEE 17 connector). This task should be carried out by a competent electrical engineer who is conversant with local electrical codes/regulations.
Page 3
9. The UPS output supply sockets may be electrically live whenever the input power lead is plugged into the mains supply socket. Turning the UPS off does not electrically isolate the internal parts. To isolate the UPS, turn the UPS off then isolate it from the mains supply.
10. When installing the UPS or making input and output connections, comply with relevant safety standards (e.g. IEC950, VDE0805, EN50091-1).
11. This equipment complies with the requirements of the EMC Directive 89/336/EEC and the published technical standards. Continued compliance requires installation in accordance with these instructions and the use of manufacturer approved accessories with output cables not exceeding 10 metres (30 ft.) in length. Use a shielded cable for the external communications interface.
12. Operate UPS only from a properly earthed, 50 Hz or 60 Hz, 208-240 VAC mains supply. Models are available for 100-127 VAC supply voltages.
13. Route power supply cords so they are not walked on or pinched.
14. Never block or insert any object into the ventilation holes or other openings. Maintain a minimum clearance of 100 mm (4 inches) in front and rear of the UPS for proper air flow and cooling.
15. Operate the UPS in an indoor environment only with an ambient temperature range of 0° C to +40° C (32° F to +104° F). Install it in a clean environment, free from moisture, flammable liquids, gasses, or corrosive substances.
16. Storing magnetic media on top of the UPS may result in data loss or corruption.
17. Turn the UPS off and unplug the UPS before cleaning. Use only a soft cloth, never liquid or aerosol cleaners.
18. This equipment can be operated by individuals without previous training.
Page 4
INTRODUCTION AND SYSTEM DESCRIPTION
Congratulations on your choice of the UPStation GXT™ Uninterruptible Power System (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment.
Upon generation, AC power is clean and stable. However, during transmission and distribution it may be subject to voltage sags, spikes, or complete power failure which may interrupt computer operations, cause data loss, or even damage equipment. The UPStation GXT™ protects equipment from these disturbances.
The UPStation GXT™ comes in nominal power ratings of 700, 1000, 1500, 2000, or 3000 VA. Complete specifications appear near the end of this section.
The UPStation GXT™ is a compact, “on-line” UPS. An “on-line” UPS continuously conditions and regulates its output voltage, whether the mains power is present or not. It supplies connected equipment with clean sinewave power. Sensitive electronic equipment operates best from sinewave power.
For ease of use, the UPStation GXT™ contains a light emitting diode (LED) display to indicate either “load percentage” or “battery capacity” depending upon the mode of operation. It also provides self-diagnostics, a combination On/Alarm Silence/Manual Battery Test button, a combination Off/Bypass button, and two levels of alarms when the unit is operating on battery.
The UPStation GXT™ has an interface port for communications between the UPS and a LAN server or other computer system. This port provides detailed operating information including voltages, currents, and alarm status to the host system when used in conjunction with the SiteNet® 2 software. SiteNet® 2 software can also remotely control UPS operation.
GLOSSARY OF SYMBOLS USED ON PRODUCT
Indicates AC Input Indicates AC Output Indicates Caution: Note the accompanying instruction
indicates the position of a fuse Indicates the position of a fuse Requests the user to consult the manual for additional
information Indicates that the unit contains a valve regulated lead acid
battery
Page 5

MAJOR COMPONENTS

Dynamic
Bypass
Inverter
OUTPUT
INPUT
TVSS
and
EMI/RFI
Filters
Battery
Charger
Rectifier/PFC
DC to DC
Converter
Battery
TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI FILTERS
These UPS components provide surge protection, and filter both electromagnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the mains line and keep the sensitive equipment protected.
RECTIFIER/POWER FACTOR CORRECTION (PFC) CIRCUIT
In normal operation, the rectifier/power factor correction (PFC) circuit converts mains AC power to regulated DC power for use by the inverter, while ensuring that the waveshape of the input current used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives: the mains power is used as efficiently as possible by the UPS, and the amount of distortion reflected on the mains is reduced. This results in cleaner power being available to other devices in the building not being protected by the UPStation GXT™.
INVERTER
In normal operation, the inverter utilizes the DC output of the power factor correction circuit and “inverts” it into precise, regulated sinewave AC power. Upon a mains power failure, the inverter receives its required energy from the battery through the DC-DC converter. In both modes of the operation, the UPS inverter is on-line and continuously generating clean, precise, regulated AC output power.
BATTERY CHARGER
The battery charger utilizes energy from the mains power and precisely regulates it to continuously “float” charge the battery system. The battery system charges whenever the UPStation GXT™ is plugged in.
Page 6
DC TO DC CONVERTER
The DC-DC converter utilizes energy from the battery system and raises the DC voltage to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, thus increasing reliability.
BATTERY
The UPStation GXT™ employs valve regulated, nonspillable, lead acid batteries. At typical room temperatures and with the UPS float charging, the battery system will last many years. Optional external battery cabinets are available to provide extended run times for the rack-tower (RT) models. For battery run times, refer to the Typical Battery Discharge Curves.
DYNAMIC BYPASS
The UPStation GXT™ provides an alternate path for mains power to the connected load, in the unlikely event of a UPS malfunction. Should the UPS have an overload, over temperature, or UPS failure condition, the UPS automatically transfers the connected load to bypass. Bypass operation is indicated by an alarm and an illuminated Bypass LED (other LED’s may be illuminated to indicate the diagnosed problem). To manually transfer the connected load from the inverter to bypass power, press the Off button once. NOTE: The bypass power path does NOT protect the connected equipment from disturbances on the mains supply.
GENERAL INSTALLATION
MINI-TOWER/TOWER UPS INSTALLATIONS
1. Unpack the UPS carefully noting the packing method. Retain the box and
packing material for possible future shipment.
2. CAUTION: The UPS is heavy (see specifications). Take proper precautions when lifting or moving it.
3. Visually inspect the UPS for freight damage. Report damage to the carrier and your dealer.
4. Locate the UPS indoors in a controlled environment, where it cannot be accidentally disconnected. Locate it in an area with unrestricted airflow, away from water, flammable liquids, gases, or corrosives. Maintain a minimum of 100 mm (4 inches) clearance around the UPS. Maintain an ambient temperature range of 0° to 40° C (32° to 104° F).
NOTE: UPS operation in
temperatures above 25° C (77° F) reduces battery life. Ensuring load equipment is turned off, plug all loads into the UPS output sockets.
5. For 700-2000 VA models, unplug
power input cable (A) from load equipment input socket (D) and plug it into UPS input socket (C).
Page 7
Re-plug the power input cable (A) into mains supply socket. Proceed
with step 9.For 3000 VA models, a CEE 19 input cable is supplied. Proceed with the next step.
6. Connect the molded connector of the mains AC input supply cable into the UPS.
7. Fit the supplied retainer bracket around the input supply cable and secure the bracket to the rear of the UPS using the two supplied screws.
8. The free end of the input supply cable should be connected to the electrical supply distribution system in accordance with local rules and conditions.
NOTE: The UPS On/Alarm Silence/Manual Battery Test button does not
electrically isolate the internal parts. To isolate the UPS, provide an isolator that is accessible to the operator and located within two meters of the UPS.
The wires in the mains lead are colored with the following code: Green and Yellow = Earth, Blue = Neutral, Brown = Live As the color of the wires in the mains lead may not correspond with the
colored marking identifying the terminals in the plug, proceed as follows: The green and yellow wire must be connected to the terminal in the plug that is marked with the letter “E” or by the earth symbol, or colored green and yellow. The blue wire must be connected to the terminal that is marked with the letter “N” or colored black. The brown wire must be connected to the terminal that is marked with the letter “L” or colored red.
9. Connect the supplied CEE 22 output cable (B) between the load equipment input socket (D) and one of the UPS AC output sockets (E). Connect all load equipment to the UPS in this way.
10. Turn on the UPS by pressing the On button for at least one half second; then turn on the connected load equipment. The UPS is ready for normal operation.
Retainer
Retainer
Bracket
Bracket
Screws
Support Base
Page 8
RACK-MOUNT CONVERSION DIAGRAMS
RACK-MOUNT UPS CONVERSION AND INSTALLATION
1. Unpack the UPS carefully noting the packing method. Retain the box and
packing material for possible future shipment.
2. CAUTION: The UPS is heavy (see specifications). Take proper precautions when lifting or moving it.
3. Visually inspect the UPS for freight damage. Report damage to the carrier and your dealer.
4. Remove the two screws located at the rear of the top cover with a Phillips (cross head) screwdriver. Push the top cover towards back of UPS and lift off. Remove and retain the two flange screws located at the front of UPS.
5. Gently lay unit on its right side and remove the six rubber feet with the screwdriver. Remove and retain screws from the two front feet.
NOTE: The rubber feet are not used for rack-mount installations.
6. Locate securing flanges in the top of packing material and fasten to the UPS using the flange screws from steps 4 and 5.
7. Remove display template to change the orientation of the display. You may also rotate the “Liebert UPStation GXT™” plate located at left of display area.
8. NOTE: UPS unit MUST be supported by a shelf, brackets or slide rails on each side. The securing flanges WILL NOT support the weight of the UPS.
9. For slide rail installations, securing hardware is provided with the UPS and is located in the packing material (slide rails sold separately). Fasten the slides into position with the screws per the instructions included with the slide rails.
10. The UPS automatically starts up in the bypass mode once the UPS is plugged into the mains socket. The UPS is now ready to be placed into the equipment rack.
Page 9
11. Ensure the load equipment is turned off, and plug all loads into the UPS output sockets.
12. For 700-2000 VA models, unplug power input cable from load equipment input socket and plug it into UPS input socket. Re-plug the power input cable into mains supply socket. Proceed with step 16. For 3000 VA models, a CEE 19 input cable is supplied. Proceed with the next step.
13. Connect the molded connector of the mains AC input supply cable into the UPS.
14. Fit the supplied retainer bracket around the input supply cable and secure the bracket to the rear of the UPS using the two supplied screws.
15. The free end of the input supply cable should be connected to the electrical supply distribution system in accordance with local rules and conditions. Note: The UPS On/Alarm Silence/Manual Battery Test button does not electrically isolate the internal parts. To isolate the UPS, provide an isolator that is accessible to the operator and located within two meters of the UPS.
The wires in the mains lead are colored with the following code: Green and Yellow = Earth, Blue = Neutral, Brown = Live
As the color of the wires in the mains lead may not correspond with the colored marking identifying the terminals in the plug, proceed as follows: The green and yellow wire must be connected to the terminal in the plug that is marked with the letter “E” or by the earth symbol, or colored green and yellow. The blue wire must be connected to the terminal that is marked with the letter “N” or colored black. The brown wire must be connected to the terminal that is marked with the letter “L” or colored red.
16. Connect the supplied CEE 22 output cable between the load equipment input socket and one of the UPS AC output sockets. Connect all load equipment to UPS in this way.
17. Turn on the UPS by pressing the On button; then turn on the connected load equipment. The UPS is ready for normal operation.
Retainer Bracket
Screws
Page 10
10
OPTIONAL BATTERY CABINET(S) INSTALLATION
Up to two optional battery cabinets may be connected to the UPS to provide additional run time. Battery cabinets are designed to be placed on either side or beneath the UPS.
1. Unpack the UPS battery cabinet(s) carefully noting the packing method. Retain the box and packing material for possible future shipment.
2. CAUTION: The battery cabinet(s) are heavy (see specifications). Take proper precautions when lifting or moving them.
3. Visually inspect the UPS for freight damage. Report damage to the carrier and your dealer.
4. Follow the same installation instructions used earlier for the UPS (tower or rack-mount).
5. Attach external battery cabinets as shown, using the enclosed metal securing plate to prevent tip-over.
6. Connect the supplied cable to the battery cabinet then to the UPS.
7. Turn on the breaker on the rear of the battery cabinet.
Battery Cabinet Installation Diagram
SECURING PLATE
BREAKER
Page 11
11
FERRITE BEAD INSTALLATION Serial Communications
Attach the smaller enclosed ferrite bead clamp to the communication cable as shown in the drawing using the following directions:
Open the ferrite bead.
Place the communication cable inside
the ferrite bead grove.
Position the ferrite beads as close as possible to the end of the cable that connects to the DB9 connector of the UPS.
Close the ferrite bead so that the ferrite bead’s case snaps closed with the cable routed inside the ferrite bead’s case.
SNMP Installation
Attach the larger enclosed ferrite bead clamp to the network cable as shown in the drawing using the following directions:
Open the ferrite bead.
Place the network cable inside the
ferrite bead grove.
Wrap the cable once around the bead.
Position the ferrite cable as close as possible to the end of the cable that connects to the UPS.
Close the ferrite bead so that the ferrite bead’s case snaps closed with the cable routed inside the ferrite bead’s case.
Page 12
12
On/Alarm Silence/
Manual Battery Test
Button
Load/Battery Level
Mini-Tower
Rack Tower
Rack Tower
Rack Tower
6
2
4
6
6
2
2
4
4
3
5
7
3
5
3
3
1- Output Receptacles
2- DB-9 Interface Port
Communications Port
5- Circuit Protector or fuse
5
Off/ Bypass Button
3- AC Inlet 4- Intellislot TM
UPSTATION GXT™
Fault Indicator Bypass Indicator
UPS On Indicator Battery Indicator
AC Input Indicator
Indicators
6- Output Voltage Selector Switches 7- Battery Cable Connector
6 4
2
7
5
3
700/1000 VA
1
1000/1500 VA
7
1
2000 VA
3000 VA
Page 13
13

CONTROLS AND INDICATORS

On/Alarm Silence/Manual Battery Test Button
This button controls output power to connected load(s) and has three functions: On, Alarm Silence, and Manual Battery Test. Pressing this button will start up the UPS in order to provide conditioned and protected power into the mains socket. To silence alarms, press this button for at least one half second while alarm conditions are present. After the alarm is silenced, the UPStation GXT™ will reactivate the alarm system to alert of additional problems. NOTE: The low battery and bypass reminder alarms cannot be silenced. To initiate a manual battery test, press this button for at least one half second while operating from mains power and no alarm conditions are present. If the bottom two LEDs do not illuminate during a Battery Test, allow the UPS to recharge the batteries for 24 hours. After 24 hours, retest the batteries. If the batteries have been retested and the bottom two LEDs still do not illuminate, contact your dealer or Liebert Technical Support (LTS) for a battery replacement kit.
Off/Bypass Button
This button controls output power to connected load(s) and has dual functions: Off and Bypass. CAUTION: Pressing this button once will cause the load to be transferred to bypass power. Pressing this button a second time within 4 seconds will result in loss of power to the output sockets and connected loads. Perform all necessary shutdown procedures on connected loads before pressing this button twice.
Load/Battery Level Indicators (4 Green, 1 Amber)
The Load/Battery Level indicators have dual functions. During normal mode operation LED indicators display the approximate electrical load placed upon the UPS; and during battery mode operation LED indicators display approximate battery capacity. Refer to the Typical Battery Discharge Curves to determine the approximate amount of back up time with respect to your connected load percentage. The UPStation GXT™ is equipped with automatic and remote battery test features. The automatic test occurs every 14 days if mains has not been interrupted (14 day timer resets if unit goes to battery). Should the battery fail this test, the fault indicator along with the A and C diagnostic LEDs will illuminate and an alarm will sound (refer to Troubleshooting Guide). The remote test feature functions with either SiteNet® 2 or SiteNet® SNMP Manager software and can remotely initiate the battery test.
Fault Indicator (Red)
The Fault indicator is illuminated if the UPS has detected a problem. Also, one or more of the load/battery level indicators may be illuminated (refer to Troubleshooting Guide).
Bypass Indicator (Amber)
The Bypass indicator is illuminated when the UPS is operating from bypass power. An alarm will sound indicating the UPS detected a problem, or the manual bypass function has been activated.
Page 14
14
UPS On Indicator (Green)
Fault
BYPASS
BATTERY
76-100%
The UPS On indicator is illuminated when the UPS inverter is operating and supplying power to your connected loads. Battery Indicator (Amber)The Battery indicator is illuminated when the UPS is operating from the battery system.
AC Input Indicator (Green)
The AC Input indicator is illuminated when mains power is available and within the input specification.
Output Voltage Selector Switches
The Output Voltage Selector Switches, located on the rear of the UPS, are designed to allow selecting or changing the desired output voltage to match the mains. The settings to choose from are 208, 220, 230, and 240 VAC output. The factory default setting is 230 VAC. NOTE: Never change the switch settings while UPS is on and powering connected loads. Switch positions for voltages: 208 VAC 220 VAC 230 VAC 240 VAC NOTE: Setting output voltage to 208 VAC will cause UPS unit to be derated to 90% of the VA and Watt rating listed in specification section.

OPERATION

NORMAL MODE OPERATION
During normal operation, mains power provides energy to the UPS. The filters, the power factor conditioning circuit and the inverter process this power to provide computer grade power to connected loads. The UPS maintains the batteries in a fully charged state. The four green LEDs indicate an approximate level of load in 25% increments. If the UPS becomes loaded beyond full rating, the fifth (amber) LED indicator will illuminate and sound an alarm. The display template indicates the percentage of load on the UPS output. Figure 1 displays approximately 51-75% loading.
Figure 1- Normal Mode Operation at 51-75% loading
!
100%
51-75%
26-50%
0-25%
INPUT
UPS
ON
AC
Page 15
15
BATTERY MODE OPERATION
Fault
BYPASS
BATTERY
100-81%
Battery mode occurs in event of an extreme input voltage condition or complete mains failure. The battery system supplies power through the DC-DC converter to the inverter to generate power for the connected load. During battery mode an alarm sounds every 10 seconds. This will change to 2 beeps every 5 seconds when battery runs low (approximately 2 minutes remaining). The AC Input LED will extinguish, and the Battery LED will illuminate to warn that a mains problem has occurred. Each load/battery level indicator represents a 20% capacity level. As capacity decreases, fewer indicators remain illuminated. Refer to the Troubleshooting Guide. For battery run times, refer to the Typical Battery Discharge Curves. To increase this time, turn off non-essential pieces of equipment (such as idle computers and monitors) or add the optional external battery cabinet.
NOTE: External battery cabinets can only be added to rack-tower (RT) models. CAUTION: Turning off the UPS while in battery mode will result in loss of output
power. Figure 2 displays approximately 61-80% battery capacity remaining.

BATTERY RECHARGE MODE

Once mains power is restored, the UPS resumes normal operation. At this time, the Battery Charger begins recharging the battery.
!
20-0%
40-21%
60-41%
UPS
ON
Figure 2 – Battery Mode Operation at 61-80% battery capacity
80-61%
AC
INPUT
Page 16
16

COMMUNICATIONS INTERFACE PORT

The UPStation GXT™ UPS contains a standard DB-9 female connector located on the rear of the UPS unit. Several signals are provided on this port and are assigned as follows:
PIN ASSIGNMENT DESCRIPTION
1 Low Battery (open collector) 2 UPS TxD (typical RS-232 levels) 3 UPS RxD (typical RS-232 levels) 4 Remote Shutdown (5-12V); battery operation 5 Common 6 Remote Shutdown (short to pin 5); all modes of operation 7 Low Battery (open emitter) 8 Mains Fail (open emitter) 9 Mains Fail (open collector)
PIN ASSIGNMENT COLLECTOR TO EMITER*
Open Collector
Open Emitter
(+)
(-)
330 Ohms
*Maximum voltage and current on pins 1,7,8,9 is 80V DC; 10.0 mA.

UPS MONITORING

The UPStation GXT™ UPS has the capability of being monitored with stand alone computers, network workstations, network servers, or UNIX hosts via the DB-9 female connector located on the rear of the UPS. This capability is used in applications requiring the UPS to provide status and power monitoring information to the computer system. For example, during a mains power failure, the information can be used by the computer’s operating system or application program to automatically save information in buffers, to close files, and shut down operations prior to battery capacity depletion. Monitoring of the UPS via a computer system is easily made with a Liebert SiteNet® 1 shutdown kit (sold separately). Consult your local Liebert representative to determine the correct software kit for your application. The kit includes special purpose cable and shutdown software.
Page 17
17

UPS INTELLIGENT COMMUNICATIONS

The UPStation GXT™ UPS has the capability to communicate intelligently with stand alone computers, network workstations, network servers, or UNIX hosts via the DB-9 female connector located at the rear of the UPS. By purchasing the optional Liebert SiteNet® 2 software package (sold separately), intelligent communications allows the following capabilities:
- Quantitative monitoring of mains and UPS power
- Quantitative monitoring of internal UPS parameters
- Periodic tests of battery quality and replacement notification
- Timed and delayed shutdown of the UPS
- Logging of power disturbances and anomalies
Consult your local Liebert sales representative for more information about SiteNet® 2 software.
UPS INTELLISLOT™ COMMUNICATIONS
The UPStation GXT™ UPS contains an Intellislot™ communications port for the optional internal Ethernet SNMP card. Optional SiteNet® SNMP Manager software is available to allow communication through several network management systems. Contact your local Liebert representative, dealer, or reseller. CAUTION: TO MAINTAIN SAFETY (SELV) BARRIERS AND FOR ELECTROMAGNETIC COMPATABILITY, SIGNAL CABLES SHOULD BE SEGREGATED AND RUN SEPARATE FROM ALL OTHER POWER CABLES, WHERE APPLICABLE.

MAINTENANCE

The UPStation GXT™ UPS requires very little maintenance. The batteries are valve regulated, nonspillable, lead acid, and should be kept charged to obtain their designed life. The UPS continuously charges the batteries when connected to the mains supply. When storing the UPS for any length of time, it is recommended to plug the UPS in for at least 24 hours every four to six months to ensure full recharge of the batteries. The UPStation GXT™ UPS is designed to allow the user to safely replace the batteries. Read the safety cautions before proceeding. Contact your dealer to obtain the appropriate replacement battery kit.
Page 18
18
BATTERY REPLACEMENT PROCEDURES
B
a
t
t
e
r
y
c
o
n
n
e
c
t
o
r
Battery door screws
CAUTION – A battery can present a risk of electrical shock and high short circuit
current. The following precautions should be observed before replacing the batteries:
- Turn off and disconnect the UPS from the mains power prior to opening the battery replacement door.
- Remove rings, watches, and other metal objects.
- Use a Phillips (cross head) screwdriver with insulated grips.
- Do not lay tools or other metal objects on top of the batteries.
- If the battery replacement kit is damaged in any way or shows signs of
leakage, contact your dealer immediately.
- Do not dispose of batteries in a fire, the batteries may explode.
- If you feel unqualified to replace the batteries, do not open the battery door.
Call Liebert Technical Support (LTS). World Wide Technical Support numbers are located at the end of this section.
MINI-TOWER BATTERY REPLACEMENT
FOR 700/1000 VA MINI-TOWER MODELS:
1. Gently lay the UPS on its right side.
2. Loosen and remove the five screws on the battery door. Remove the door by sliding it toward the rear of UPS and lifting it off. Lay the battery door aside for reassembly.
3. Gently pull battery wiring out and disconnect the battery connector.
4. Grasp the battery assembly, and pull it out of the UPS.
5. Unpack the new battery assembly taking care not to destroy the packing. Compare new and old battery assemblies to make sure they are the same quantity and voltage rating (see specifications). If so, proceed with step 6; otherwise STOP and contact your dealer or LTS.
6. Slide the new battery assembly into the cavity, noting the connector is facing outward. Connect the battery connector together.
NOTE: There will be a small spark when connecting the battery connector.
This is normal and will not harm you or the UPS.
7. Replace battery door by inserting the three metal tabs into the slots and pushing it toward the front of the UPS. Replace and tighten the five screws to lock the battery door closed.
Page 19
19
8. Carefully stand the UPS upright. Connect the UPS to the mains supply socket and turn on the UPS by pressing the on button. The UPS is ready for normal operation.
9. Dispose of batteries in accordance with your local laws and regulations.
FOR 1000 TO 3000 VA RACK/TOWER MODELS: CAUTION: The battery assembly is heavy. Take proper precautions when lifting
or moving it.
TOWER MODELS ONLY:
- Remove top cover by removing the two screws located on rear of top cover. Push the top cover towards the back of UPS and lift off. Remove the two flange screws near the front of UPS.
- Gently lay the UPS on its right side and remove the two front rubber feet. Continue with Rack/Tower Models battery replacement procedures.
RACK/TOWER MODELS:
1. Grasp the front bezel (cover) and pull forward for removal.
NOTE: The two securing flanges must be removed before front bezel
(cover) can be removed.
2. Remove the two screws from the small battery door. Remove the door by pulling it forward and lifting it off. Lay aside for reassembly.
NOTE: For 2000/3000 VA models, the small door contains a connector that
disconnects battery into a lower, safer voltage.
3. Loosen the five screws of the large battery door. Remove the door by pulling it forward and lifting it off. Lay aside for reassembly.
4. Pull battery assembly out approximately 50mm (2 in). Gently pull the battery wiring out and disconnect the battery connector.
5. Completely remove battery assembly from the UPS.
6. Unpack the new battery assembly taking care not to destroy the packing. Compare new and old battery assemblies to make sure they are the same quantity and voltage rating (see specifications). If so, proceed with the next step; otherwise STOP and contact your dealer or LTS.
7. Slide the new battery assembly into the cavity, leaving 50mm (2 in).
8. Connect the battery wire connectors together.
NOTE: On 1000/1500 VA models, there will be a small spark when
connecting the connectors. This is normal and will not harm you or the UPS.
9. Slide battery assembly completely into the UPS, reposition the large battery door and replace the screws removed in step 3.
10. Reposition small battery door and replace the screws removed in step 2 to lock top battery door closed. On 2000/3000 VA models, make sure the top door connection is made.
11. Replace front bezel (cover) on UPS. Replace the securing flanges (for Rack Tower procedures) and flange screws to secure bezel in place. For Tower procedures, replace the two front rubber feet, stand unit upright, and replace the top cover. Connect the UPS to the mains supply socket and turn on the UPS by pressing the On button. The UPS is ready for normal operation.
12. Dispose of batteries in accordance with your local laws and regulations.
Page 20
20
RACK / TOWER BATTERY REPLACEMENT
Large battery door
small battery door
Small battery door
Front bezel (cover)
w/top cover removed
Top cover screws
Rear View Aerial View
Two front rubber feet
Flange screws
Large battery door
Screw hidden by
Battery connector
Page 21
21
UPSTATION GXT BATTERY RUN TIMES
(Discharge times are at 25° C ambient)
Internal Battery (minutes)
Load% 700MT 1000MT 1000RT 1000RTE 1500RT 2000RT 3000RT
10% 52 94 94 169 78 160 101 20% 40 45 45 127 39 83 51 30% 32 33 33 94 27 47 28 40% 24 24 24 68 20 34 20 50% 18 18 18 49 15 27 15 60% 15 14 14 36 11 21 12 70% 12 12 12 28 9 18 10 80% 10 9 9 23 7 15 8 90% 8 7 7 19 6 13 7
100% 6 6 6 17 5 11 6
Internal Battery + 1 External Battery Cabinet (minutes)
Load% 700MT 1000MT 1000RT 1000RTE 1500RT 2000RT 3000RT
10% N/A N/A 479 552 408 343 273 20% N/A N/A 255 335 215 204 140 30% N/A N/A 150 210 126 133 78 40% N/A N/A 110 152 95 100 57 50% N/A N/A 85 115 75 77 44 60% N/A N/A 66 88 57 60 35 70% N/A N/A 56 72 48 50 30 80% N/A N/A 48 62 40 43 26 90% N/A N/A 41 52 35 36 22
100% N/A N/A 35 45 29 31 18
Internal Battery + 2 External Battery Cabinets (minutes)
Load% 700MT 1000MT 1000RT 1000RTE 500RT 2000RT 3000RT
10% N/A N/A 848 920 718 623 444 20% N/A N/A 425 505 365 345 236 30% N/A N/A 243 303 208 211 138 40% N/A N/A 196 238 164 156 100 50% N/A N/A 168 198 139 120 75 60% N/A N/A 133 155 112 94 59 70% N/A N/A 109 125 94 81 50 80% N/A N/A 89 103 78 70 43 90% N/A N/A 77 88 68 62 36
100% N/A N/A 66 76 58 54 31
Page 22
22
FUSE REPLACEMENT PROCEDURES
Insert flat blade
screwdriver into slot
Fuse Holder
Remove
Install
CAUTION: Before changing the input fuse, turn off the UPS, and unplug the supply lead from the AC input supply and from the UPS. Replace the fuse with the same type and rating.
and turn fuse holder to remove / install
Input Fuse
1. Remove the fuse holder by inserting a flat blade screwdriver into the slot and turning to remove as indicated in the figure above.
2. Remove the input fuse.
3. Locate the spare input fuse that is included with the UPS.
4. Insert the spare fuse into the fuse holder, and reinstall assembly into the UPS. Using the screwdriver, rotate clockwise until fuse holder locks into position.
5. Reconnect the input power lead to the UPS, and the input power lead to the input AC supply.
6. Restart the UPS. The UPS is ready for normal operation.
NOTE: For 1500 VA, 2000 VA, and 3000 VA units, reset circuit protector.
AUDIBLE ALARM CONDITIONS
CONDITION ALARM
Battery mode
(utility failure)
Low battery
Output overload (bypass) One short beep every half second
Over temperature (bypass) One second beep every four seconds
DC Bus overvoltage (bypass) One second beep every four seconds
Control power supply failure (bypass)
PFC failure (bypass) One second beep every four seconds
Inverter failure One second beep every four seconds
Battery Test failure Two second beep every minute
One short beep every ten seconds; more than two minutes of run time remaining Two short beeps every five seconds; less than two minutes of run time remaining
One second beep every four seconds
Page 23
23

TROUBLESHOOTING

BATTERY
Load / Battery
Level Indicators
The information below indicates various symptoms a user may encounter in the event the UPStation GXT™ develops a problem. Use this information to determine whether external factors cause the problem and how to remedy the situation.
1. The fault indicator will illuminate indicating the UPS detected a problem.
2. An alarm will sound, alerting that the UPS requires attention.
3. One or more additional load/battery level LED indicators will be illuminated to provide a diagnostic aid to the operator, as described below:
Fault
!
BYPASS
E D C B A
All. On bypass due to output overload (beep every half second) A. On bypass due to over temperature condition (beep every 4 seconds) B. On bypass due to DC bus overvoltage (beep every 4 seconds) C. On bypass due to control power supply failure (beep every 4 seconds) D. On bypass due to PFC failure (beep every 4 seconds) E. On bypass due to inverter failure (beep every 4 seconds) A&C. UPS failed battery test (long beep every minute) C&E. UPS shutdown due to command from communication port (SNMP); no beep
The fault indicators will be illuminated indefinitely while battery charger is operational, or for a maximum of 5 minutes while battery charger is not operational. If a problem persists consult your dealer, or contact Liebert Technical Support (LTS). World Wide Technical Support numbers are located at the end of this section.
UPS
ON
AC
INPUT
Page 24
24
TROUBLESHOOTING GUIDE
PROBLEM CAUSE SOLUTION
UPS fails to start when on button is pressed
Battery indicator is illuminated
UPS has reduced battery time
Fault and Bypass indicators and all load level LEDs are illuminated
Fault and Bypass indicators and diagnostic LED A are illuminated
Fault and Bypass indicators and diagnostic LED B are illuminated Fault and Bypass indicators and diagnostic LED C are illuminated Fault and Bypass indicators and diagnostic LED D are illuminated Fault and Bypass indicators and diagnostic LED E are illuminated Fault and Bypass indicators and diagnostic LED A & C are illuminated Fault and Bypass indicators and diagnostic LED C & E are illuminated
UPS is short circuited or overloaded
Internal fuse is blown, indicating internal fault UPS not plugged in UPS is operating from battery mode,
UPS input protection has opened
Mains voltage out of UPS input range.
Batteries not fully charged Keep UPS plugged in continuously at UPS is overloaded Check load level display and reduce load Batteries may not be able to
hold a full charge due to age UPS overloaded or load equipment is faulty
UPS internal fan has a problem or UPS shutdown due to temperature condition. Load is on bypass power
UPS internal DC bus overvoltage
UPS power control fault. UPS requires service. Contact your
UPS PFC fault. UPS requires service. Contact your
UPS inverter fault. UPS requires service. Contact your
UPS failed the battery test. Replace batteries. Contact your dealer
UPS shutdown due to a command from the communications port(s)
Ensure UPS is off. Disconnect all loads and ensure nothing is lodged in output sockets. Ensure loads are not defective or shorted internally. Do not attempt to open or service the UPS. Contact your dealer or LTS.
make certain UPS is securely plugged into the wall socket UPS is operating from battery mode. Save data and close applications. Replace UPS input fuse or reset input breaker, then restart UPS. UPS is operating from battery mode. Save data and close applications. Ensure mains supply voltage is within acceptable limits for UPS.
least 24 hours to recharge batteries level
Replace batteries. Contact your dealer or LTS for replacement battery kit Check load level display and remove non-essential loads. Recalculate load VA and reduce number of loads connected to UPS. Check load equipment for faults. Ensure UPS is not overloaded, ventilation openings not blocked, or room ambient temperature not excessive. Wait 30 minutes to allow UPS to cool, then restart UPS. IF it does not restart, contact your dealer or LTS. UPS requires service. Contact your dealer or LTS.
dealer or LTS.
dealer or LTS.
dealer or LTS.
or LTS.
Your UPS has received a signal or command from the attached computer. If this was inadvertent, ensure the communication cable used is correct for your system. For assistance, contact your dealer or LTS.
Page 25
25

SPECIFICATIONS

MODEL NUMBER GXT700MT-230 GXT1000MT-230 MODEL RATING VA/W 700 / 490 1000 / 700 DIMENSIONS: mm (in)
Unit W x D x H Shipping W x D x H
WEIGHT: kg (lbs)
Unit 13.1 (28.8) 15.8 (34.8) Shipping 15.0 (33.0) 17.7 (39.0)
INPUT AC PARAMETERS
Voltage Range (typical) 230 VAC nominal; variable based upon output load
100% - 70% Loading 160-163 VAC to 273-276 VAC
70% - 30% Loading 140-143 VAC to 273-276 VAC
30% - 0% Loading 120-122 VAC to 273-276 VAC Frequency 48.1 - 51.9 Hz or 57.6 - 62.4 Hz; auto sensing Input connector IEC320-10A IEC320-10A
OUTPUT AC PARAMETERS
Output Sockets (4) IEC320-10A (4) IEC320-10A Voltage 208/220/230/240 (switch selectable) VAC; ±3% Frequency 50 Hz or 60Hz Waveform Sinewave Main Mode Overload 200% for 8 cycles; 130% for 10 seconds with transfer to bypass
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, lead acid Qty. x Voltage x Rating 2 x 12V x7 or 7.2 AH 3 x 12V x 7 or 7.2 AH Back-up Time See Typical Battery Discharge Curves
ENVIROMENTAL
Operating Temperature 0° C to +40° C (+32° F to +104° F) Storage Temperature -15° C to +50° C (+5° F to +122 °F) Relative Humidity 0% to 95%, non-condensing Operating Elevation Up to 3000 m (10,000 ft.) at 40° C without derating Storage Elevation 15.000 m (50,000 ft.) maximum Audible Noise <45 dBA, at 1 meter
AGENCY
Safety EN50091-1, TUV/GS Listed, CE Low Voltage Directive compliant RFI/EMI EN55022, Class B; CE EMC Directive compliant Immunity
162 x 430 x 225
(6.4 x 15.6 x 8.9)
280 x 502 x 362
(11.0 x 19.75 x 14.25)
IEC 801-2, Level 4 / IEC 801-3, Level 3 / IEC 801-4,
Level 4 / IEC801-5,Level 3
162 x 430 x 225
(6.4 x 15.6 x 8.9)
280 x 502 x 362
(11.0 x 19.75 x 14.25)
Page 26
26
SPECIFICATIONS
MODEL NUMBER GXT1000RT-230 GXT1000RTE-230 MODEL RATING VA/W 1000 / 700 1000 / 700 DIMENSIONS: mm (in)
Unit W x D x H Shipping W x D x H
WEIGHT: kg (lbs)
Unit 23.6 (51.9) 31.1 (68.4) Shipping 26.8 (59.0) 34.3 (75.5)
INPUT AC PARAMETERS
Voltage Range (typical) 230 VAC nominal; variable based upon output load
100% - 70% Loading 160-163 VAC to 273-276 VAC
70% - 30% Loading 140-143 VAC to 273-276 VAC
30% - 0% Loading 120-122 VAC to 273-276 VAC Frequency 48.1 - 51.9 Hz or 57.6 - 62.4 Hz; auto sensing Input connector IEC320-10A IEC320-10A
OUTPUT AC PARAMETERS
Output Sockets (4) IEC320-10A (4) IEC320-10A Voltage 208/220/230/240 (switch selectable) VAC; ±3% Frequency 50 Hz or 60Hz Waveform Sinewave Main Mode Overload 200% for 8 cycles; 130% for 10 seconds with transfer to bypass
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, lead acid Qty. x Voltage x Rating 3 x 12V x 7 or 7.2 AH 6 x 12V x 7 AH Back-up Time See Typical Battery Discharge Curves
ENVIROMENTAL
Operating Temperature 0° C to +40° C (+32° F to +104° F) Storage Temperature -15° C to +50° C (+5° F to +122 °F) Relative Humidity 0% to 95%, non-condensing Operating Elevation Up to 3000 m (10,000 ft.) at 40° C without derating Storage Elevation 15.000 m (50,000 ft.) maximum Audible Noise <50 dBA, at 1 meter
AGENCY
Safety EN50091-1, TUV/GS Listed, CE Low Voltage Directive compliant RFI/EMI EN55022, Class B; CE EMC Directive compliant Immunity
177 x 522 x 430
(7.0 x 19.3 x 16.9)
340 x 660 x 565
(13.38 x 26.0 x 22.25)
IEC 801-2, Level 4 / IEC 801-3, Level 3 / IEC 801-4, Level 4 / IEC801-
5,Level 3
177 x 522 x 430
(7.0 x 19.3 x 16.9)
340 x 660 x 565
(13.38 x 26.0 x 22.25)
Page 27
27
SPECIFICATIONS
MODEL NUMBER GXT1500RT-230 GXT2000RT-230 GXT3000RT-230 MODEL RATING VA/W 1500 / 1050 2000 / 1400 3000 / 2100 DIMENSIONS: mm (in)
Unit W x D x H Shipping W x D x H
WEIGHT: kg (lbs)
Unit 27.7 (60.9) 36.8 (80.9) 39.0 (85.9) Shipping 30.9 (68.0) 40.0 (88.0) 42.3 (93.0)
INPUT AC PARAMETERS
Voltage Range (typical) 230 VAC nominal; variable based upon output load
100% - 90% Loading 184-187 VAC to 273-276 VAC
90% - 70% Loading 160-163 VAC to 273-276 VAC 70% - 30% Loading 140-143 VAC to 273-276 VAC
30% - 0% Loading 120-122 VAC to 273-276 VAC Frequency 48.1 - 51.9 Hz or 57.6 - 62.4 Hz; auto sensing Input connector IEC320-10A IEC320-10A IEC320-16A
OUTPUT AC PARAMETERS
Output Sockets (4) IEC320-10A (4) IEC320-10A (4) IEC320-10A; Voltage 208/220/230/240 (switch selectable) VAC; ±3%
Frequency 50 Hz or 60Hz Waveform Sinewave Main Mode Overload 200% for 8 cycles; 130% for 10 seconds with transfer to bypass
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, lead acid Qty. x Voltage x Rating 4 x 12V x 7 or 7.2 AH 8 x 12V x 6.5 or 7.0 AH 8 x 12V x 7 or 7.2 AH Back-up Time See Typical Battery Discharge Curves
ENVIROMENTAL
Operating Temperature 0° C to +40° C (+32° F to +104° F) Storage Temperature -15° C to +50° C (+5° F to +122 °F) Relative Humidity 0% to 95%, non-condensing Operating Elevation Up to 3000 m (10,000 ft.) at 40° C without derating Storage Elevation 15.000 m (50,000 ft.) maximum Audible Noise <50 dBA, at 1 meter
AGENCY
Safety EN50091-1, TUV/GS Listed, CE Low Voltage Directive compliant RFI/EMI EN55022, Class B; CE EMC Directive compliant Immunity
177 x 522 x 430
(7.0 x 19.3 x 16.9)
340 x 660 x 565
(13.38 x 26.0 x 22.25)
IEC 801-2, Level 4 / IEC 801-3, Level 3 / IEC 801-4, Level 4 / IEC801-5,Level 3
177 x 522 x 430
(7.0 x 19.3 x 16.9)
340 x 660 x 565
(13.38 x 26.0 x 22.25)
177 x 522 x 430
(7.0 x 19.3 x 16.9)
340 x 660 x 565
(13.38 x 26.0 x 22.25)
(1) IEC320-16A
Page 28
28
BATTERY CABINET SPECIFICATIONS
MODEL NUMBER GXT36VBATT GXT48VBATT GXT96VBATT Used w/ UPS Model 1000RT 1500RT DIMENSIONS: in (mm)
Unit W x D x H Shipping W x D x H
WEIGHT: lbs (kg)
Unit 61.3 (27.9) 71.6 (32.5) 71.6 (32.5) Shipping 68.4 (31) 78.7 (35.7) 78.7 (35.7)
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, lead acid
# of Strings x Qty/Str. x Batt. Voltage x Batt. Rating
Batt. Mfg./ Part # CSB GP1270F2 or Panasonic LC-R127R2CH1 Back-up Time See Typical Battery Discharge Curves Recharge Time 5 Hours to 95% capacity after full discharge into 100% load
ENVIROMENTAL
Operating Temperature +32° F to +104° F (0° C to +40° C) Storage Temperature +5° F to +122 °F (-15° C to +50° C) Relative Humidity 0% to 95%, non-condensing Operating Elevation Up to 10,000 ft. (3000 m) at 40° C without derating Storage Elevation 50,000 ft. (15.000 m) maximum
AGENCY
Safety UL 1778, c-UL Listed; TUV, CE LVD compliant RFI/EMI FCC Part 15, Subpart B, Class A; EN5022 Class B; CE ECM compliant Immunity
177 x 522 x 430
(7.0 x 19.3 x 16. 9)
13.38 x 26.0 x 22.25 (340 x 660 x 565)
2x3x12Vx7.0 or 7.2 AH 2x4x12Vx7.0 or 7.2 AH 1x8x12Vx7.0 or 7.2
IEEE 587 Category A; IEC 801-2, Level 4;
IEC801-3, Level 3 IEC801-4, Level 4 IEC801-5, Level 3
177 x 522 x 430
(7.0 x 19.3 x 16. 9)
13.38 x 26.0 x 22.25 (340 x 660 x 565)
2000RT/3000RT
177 x 522 x 430
(7.0 x 19.3 x 16. 9)
13.38 x 26.0 x 22.25 (340 x 660 x 565)
AH
Page 29
29
LIMITED WARRANTY
Liebert Corporation extends the following LIMITED WARRANTY to the purchaser and to its customer (collectively referred to as the "Purchaser"): the enclosed Uninterruptible Power System (UPS) and components are free from defects in materials and workmanship under normal use, service, and maintenance FOR A PERIOD OF TWO YEARS FROM THE DATE OF ORIGINAL PURCHASE from Liebert or the Liebert dealer or retailer. THE FOREGOING WARRANTY IS THE ONLY WARRANTY GIVEN AND NO OTHER WARANTY IS PROVIDED, EXPRESS OR IMPLIED, INCLUDING WITHOUT LIMITATION, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Certain aspects of disclaimers are not applicable to consumer products acquired by individuals and used for personal, family, or household purposes (as distinguished from industrial or other purposes). Local laws may not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. This warranty gives you specific legal rights, and you may have other rights which vary according to local law. Certain repairs or services are the responsibility of the Purchaser and the Purchaser is expected to pay for them. This warranty does not extend either to products with removed or altered serial numbers or to any losses or damages due to act of God or source external to the product, misuse, accident, abuse, neglect, negligence, unauthorized modification, alteration, or repair, use beyond rated capacity, or improper installation, maintenance, application or use, including, without limitation, use in a manner contrary to the accompanying instructions or applicable codes. WARNING: Warranty is void if the battery is allowed to discharge below the minimum battery cutoff point. To prevent such discharge DO NOT leave the unit power switch "ON" for more than two (2) days without AC power being supplied to the UPS. The battery must be recharged every four (4) to six (6) months when not in use. If the UPS fails to conform with the above warranty within the two year warranty period, Liebert will repair or replace the UPS, at Liebert's option. Repairs or replacements are warranted for the remainder of the original warranty period. Purchaser, to make a warranty claim, should call +44 (0)1793 553355 to obtain a Returned Goods Authorization number and shipping instructions. Return transportation costs to Liebert are the responsibility of the Purchaser.
This product is not recommended, and the Company will not knowingly sell this
“LIFE SUPPORT” POLICY
product, for use with life support and other designated "critical" devices. ANY SUCH USE BY A USER AUTOMATICALLY VOIDS AND DISCLAIMS ANY AND ALL WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY, IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, AND EXPRESS WARRANTIES THAT THIS PRODUCT WILL CONFORM TO ANY AFFIRMATION OR PROMISE, FOR THIS PRODUCT AND THE USER AGREES THAT IN NO EVENT SHALL THE COMPANY BE LIABLE FOR CONSEQUENTIAL OR INDIRECT DAMAGES.
Page 30
30
R
UPStation GXT™
Technical
1050 Dearborn Drive Columbus, OH 43229 614-888-0246
700-3000 VA
230 V

Technical Support

Outside the U.S.A. 614-841-6755
U.S.A. 1-800-222-5877
U.K. +44 (0) 1793 553355
France +33 1 4 87 51 52
Germany +49 89 99 19 220
Italy +39 2 98250 1
Netherlands +00 31 475 503333
E-mail upstech@liebert.com
Web site http://www.liebert.com
Worldwide FAX tech support 614-841-5471
The Company Behind The Products
With more than 500,000 installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics:
Environmental systems: close-control air conditioning from 1.5 to 60 tons.
Power conditioning and UPS with power ranges from 250 VA to more than 1000 kVA.
Integrated systems that provide both environmental and power protection in a single, flexible package.
Monitoring and control — on-site or remote — from systems of any size or location.
Service and support, through more than 100
service centers around the world, and a 24-hour
While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
©1998 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SLI-23131 (4/98) Rev. 2.0
Loading...