Liebert 600TTM User Manual

POWER PROTECTION
Series 600T™ UPS
Multi-Module Three Phase 500 kVA to 750 kVA, 60 Hz
Installation
Manual
The following WARNING applies to all battery cabinets supplied with UPS systems:
WARNING
HAZARD
Battery cabinets contain non-spillable batteries. Keep units upright. Do not stack. Do not tilt.
Failure to heed this warning could result in smoke, fire or electric hazard. Call 1-800-LIEBERT prior to moving battery cabinets.
Table of Contents
1.0 SAFETY PRECAUTIONS ............................................................. 3
2.0 I
2.1 TypesofSystemControlCabinets ............................................ 6
3.0 U
4.0 I
4.1 ExternalInspections ....................................................... 8
4.2 InternalInspections........................................................ 8
5.0 E
6.0 B
6.1 BatterySafetyPrecautions................................................. 10
6.2 MatchingBatteryCabinets................................................. 13
6.3 Non-StandardBatteries.................................................... 13
7.0 C
7.1 PreferredGroundingConfiguration,Wye-ConnectedService...................... 15
7.2 GroundingConfiguration,DeltaSource....................................... 16
7.3 PreferredGroundingConfigurationwithPower-TieSwitchgear................... 17
7.4 GroundingConfigurations,BatterySystems................................... 18
NSTALLATION CONSIDERATIONS ..................................................... 4
NLOADING AND HANDLING ........................................................ 7
NSPECTIONS
QUIPMENT LOCATIO N............................................................. 9
ATTERY INSTALLATION
ONFIGURING YOUR NEUTRAL AND GROUND CONNECTIONS
8.0 W
8.1 PowerWiring............................................................ 20
8.2 ControlWiring........................................................... 21
8.3 BatteryWiring........................................................... 22
9.0 W
10.0 W
Table1PowerWiringTerminals-FactorySupplied................................... 27
Table2TorqueSpecifications ..................................................... 27
Table 3 Table 310-16 ............................................................ 28
11.0 I
12.0 A
Table 4 Series 600T Multi-Module Systems, 500-750 k V A - 480 Volt Input. . ............... 81
Table 5 Series 600T Multi-Module Systems, 500-750 k V A - 600 Volt Input . ............... 82
13.0 A
Table6One-HoleLugs .......................................................... 83
IRING CONSIDERATIONS
IRING CONNECTIONS ............................................................ 25
IRING INSPECTION
NSTALLATION DRAWINGS ......................................................... 29
PPENDIX A-SITE PLANNING DATA
PPENDIX B-FIELD SUPPLIED LUGS
i
List of Figures
Figure1 UPSMulti-ModuleUnitBlockDiagram........................................... 5
Figure2 SystemControlCabinets....................................................... 6
Figure3 PreferredGroundingConfiguration,480or600VACInputandOutput................15
Figure4 GroundingConfigurationwithUngroundedDeltaSourceInput...................... 16
Figure5 PreferredGroundingConfiguration,Power-TieSystems ............................ 17
Figure6 BatteryCabinetGroundingConfiguration........................................ 18
Figure7 TypicalMulti-ModuleConfigurations............................................ 23
Figure8 OutlineDrawing,500kVAMulti-ModuleUPS,6-PulseRectifier...................... 29
Figure9 OutlineDrawing,500kVAMulti-ModuleUPS,12-PulseRectifier..................... 30
Figure10 OutlineDrawing,625-750kVAMulti-ModuleUPS,6-PulseRectifier.................. 31
Figure11 OutlineDrawing,625-750kVAMulti-ModuleUPS,12-PulseRectifier................. 32
Figure12 OutlineDrawing,SystemControlCabinet(SCCT),200-1200Amps ................... 33
Figure 13 Outline Drawing, System Control C abinet (SCCT), 1600-2500 Amps . . . ............... 34
Figure14 OutlineDrawing,SystemControlCabinet(SCCT),3000Amps....................... 35
Figure15 OutlineDrawing,SystemControlCabinet(SCCT)4000Amps ....................... 36
Figure16 BatteryPowerPack,SizeA.................................................... 37
Figure17 BatteryPowerPack,SizeB.................................................... 38
Figure18 BatteryPowerPack,Three-PackSystem......................................... 39
Figure19 BaseMountingPatterns,500kVAModule,12-PulseRectifier........................ 40
Figure 20 Base Mounting Patterns, 625-750 kVA Module, 6-Pulse. ............................ 41
Figure 21 Base Mounting Patterns, 625-750 kVA Module, 12-Pulse Rectifier .................... 42
Figure 22 Base Mounting Patterns, System Control Cabinets (SCCT) 20 0-1200 Amps............. 43
Figure 23 Base Mounting Patterns, System Control Cabinet (SCCT), 1600-2500 A mps . . . ......... 44
Figure24 BaseMountingPatterns(SCCT),3000Amps...................................... 45
Figure25 BaseMountingPatterns(SCCT),4000Amps...................................... 46
Figure26 ShippingSplitDetail,500kVAMulti-ModuleUPS,12-PulseRectifier................. 47
Figure 27 Shipping Split De tail, 625-750 kVA Multi-Module UPS, 6-Pulse Rectifie r .............. 48
Figure 28 Shipping Split Detail, 625-750 kVA Multi-Module UPS, 12-Pulse Rectifier ............. 49
Figure29 TerminalDetails,500kVAModule,6-PulseRectifier............................... 50
Figure30 TerminalDetails,500kVAModule,12-PulseRectifier.............................. 51
Figure31 TerminalDetails,625&750kVAModules,6-Pulseand12-Pulse..................... 52
Figure32 TerminalDetails,750kVAwithInputBusBars................................... 53
Figure33 ControlWiring,ExternalInterconnections,StandardUPSModule ................... 54
Figure34 ControlConnectionLocation,500kVAModules ................................... 55
Figure35 ControlConnectionLocationDiagram,625&750kVAModules...................... 56
Figure36 ControlConnectionLocationDiagram,SCCC&SCCI.............................. 57
Figure37 ControlConnectionLocationDiagram,SCCT..................................... 58
Figure38 ControlWireList,ExternalInterconnections,StandardUPSModule ................. 59
Figure39 ControlWireList,ExternalInterconnections,SystemControlCabinet,Part1of3....... 60
Figure40 ControlWireList,ExternalInterconnections,StandardSCC,Part2of3 .............. 61
Figure41 ControlWireList,ExternalInterconnections,StandardSCC,Part3of3............... 62
Figure42 ControlWireList,ExternalInterconnections,AlarmStatusContacts ................. 63
Figure43 OptionWiring,MaintenanceBypassInterlock .................................... 64
Figure44 OptionWiring,RemoteStatusPanelInterface.................................... 65
Figure45 OptionWiring,InternalModem................................................ 66
Figure 46 Option Wiring, Customer Alarm Interface, SCC with Momentary-Duty Static Switch . . . . 67
Figure 47 Option Wiring, Customer Alarm Interface, SCC with Continuous-Duty Static Switch. . . . . 68
iii
Figure48 OptionWiring,BatteryTemperatureSensor......................................69
Figure49 OptionWiring,SNMPInterface ................................................70
Figure50 ExternalInterconnections,Module1/SCC,CableGroups21and22 ...................71
Figure51 ExternalInterconnections,Module2/SCC,CableGroups21and22 ...................72
Figure52 WiringConfigurations,UPSVideoDisplayTerminal ...............................73
Figure 53 Module Battery Disconnect, 600-1200 Amps, withou t Input Isolation Transformer . ......74
Figure 54 Module Battery Disconnect, 30 0-1200 Amps, with Input Isolation Transformer ..........75
Figure55 RemoteStatusPanel,SurfaceMount............................................76
Figure 56 Circuit Breaker Schedule , Multi-Module UPS, 300-750 k VA .........................77
Figure57 CircuitBreakerSchedule,Merlin-GerinBreakers,SCCT,200-4000Amps..............78
Figure 58 Circuit B reaker Schedule, General Electric Breakers, SCCT, 200-4000 Amps ...........79
iv
IMPORTANT SAFETY INSTRUCTIONS
Save These Instructions.
This manualcontains important instructions that shouldbe followedduring installation of your Series 600T UPS and batteries.
WARNING
!
EXERCISE EXTREME CARE WHEN HANDLING UPS CABINETS TO AVOID EQUIPMENT DAMAGE OR INJURY TO PERSONNEL. THE UPS MODULE WEIGHT RANGES UP TO 12,000 POUNDS (5,455 KG), INCLUDING INPUT TRANSFORMER. THE BATTERY CABINETS WE IGH BETWEEN 3000 POUNDS (1364 KG) AND 4900 POUNDS (2227 KG).
LOCATE CENTER OF GRAVITY SYMBOLS BEFORE HANDLING EACH CABINET. TEST LIFT AND BALANCE THE CABINETS BEFORE TRANSPORTING. MAINTAIN MINIMUM TILT FROM VERTICAL AT ALL TIMES.
SLOTS AT THE BASE OF THE MODULES AND BATTERY CABINETS ARE INTENDED FOR FORKLIFT USE. BASE S LO TS WILL SUPPORT THE UNIT ONLY IF THE FORKS ARE COMPLETELY BENEATH THE UNIT.
SYSTEM CONTROL CABINETS (SCC’S) HAVE HOLES INTENDED FOR RIGGING BARSOR CHAINS. PREVENT CHAINS OR CABLES FROM CONTACTING CABINET BY USING SPREADER BAR AND ADEQUATE PADDING.
FOLLOW ALL BATTERY SAFETY PRECAUTIONS WHE N INSTALLING, CHARGING, OR SERVICING BATTERIES. IN ADDITION TO THE HAZARD OF ELECTRIC SHOCK, GAS PRODUCED BY BATTERIES CAN BE EXPLOSIVE AND SULFURIC ACID CAN CAUSE SEVERE BURNS.
IN CASE OF FIRE I NVOLVING ELECTRICAL EQUIPMENT, ONLY CARBON DIOXIDE FIRE EXTINGUISHERS, OR THOSE APPROVED FOR USE IN ELECTRICAL FIRE FIGHTING, SHOULD BE USED.
EXTREME CAUTION IS REQUIRED WHEN PERFORMING MAINTENANCE.
BE CONSTANTLY AWAR E THAT THE UPS SYSTEM CONTAINS HIGH DC AS WELL AS AC VOLTAGES.
CHECK FOR VOLTAGE WITH BOTH AC AND DC VOLTMETERS PRIOR TO MAKING CONTACT.
1
WARNING
!
LOCATE CENTER OF GRAVITY SYMBOLS AND DETERMINE UNIT WEIGHT BEFORE HANDLING CABINET.
If you require assistance fo r any reason, call the toll-free Liebert Global Services number; 1-800­543-2378. For LGS to assist you e xpediently, please have the following information available:
Part Numbers: Serial Numbers: kVA Rating: Date Purchased: Date Installed: Location: Input Voltage: Output Voltage: Battery Reserve Time:
______________________________________________________________ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________
2

1.0 SAFETY PRECAUTIONS

Read this m a nual thoroughly, paying special attention to the sections that apply to you, before working with the UPS. Retain this manual for use by installing personnel.
Under typical operation and with all UPS doors closed,only normal safety precautions are neces­sary. The area around the UPS system should bekept free from puddles of water, excess mois­ture, or debris.
Special safety precautions are required for procedures involving handling, installation, and main­tenance of the UPS system or the battery. Observe all safety precautions in this manual before handling or installing the UPS system. Observe all precautions in the Operation and Mainte- nance Manual, before as well as during performance of all maintenance procedures. Observe all battery safety precautions before working on or near t he battery.
This equipment contains several circuits that are energized with high voltage. Only test equipment designated for troubleshooting should be used. This is particularly true for oscillo­scopes. Always check with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when thepower i s turned Off, dangerously high potentials may exist at the capacitor banks and at the batteries.
ONLY qualified service personnel should perform maintenance on the UPS system.
When performing maintenance with any part of the equipment under power, service personnel and test equipment should be standing on rubber mats. The service personnel should wear insu­lating shoes for isolation fr om direct contact with the floor (earth g round).
Unless all power is removed from the equipment, one person should never work alone. Asecond person should be standing by to assist and summon help in case an accident should occur.
Four types of mess ages are used throughout the manual to stress important text. Carefully read the text below each Danger, Warning, Caution, and Note and use professional skills and prudent care when performing the actions described by that text.
A Danger signals immediate hazards resulting in severe personal injury or death. For example:
DANGER
!
A DANGER SIGNALS IMMEDIATE HAZARDS WHICH WILL RESULT IN SEVERE PERSONAL INJURY OR DEATH.
A Warning signals the presence of a possible serious, life-threatening condition. For ex ample:
WARNING
!
LETHAL VOLTAGES MAY BE PRESENT WITHIN THIS UNIT EVEN WHEN IT IS APPARENTLY NOT OPERATING. OBSERVE ALL CAUTIONS AND WARNINGS IN THIS MANUAL. FAILURE TO DO SO COULD RESULT IN SERIOUS INJURY OR DEATH. DO NOT WORK ON OR OPERATE THIS EQUIPMENT UNLESS YOU ARE FULLY QUALIFIED TO DO SO!! NEVER WORK ALONE.
A Cautionindicates a condition that could seriously damage equipment and possibly injure per- sonnel. For example:
CAUTION
!
Extreme care is n ecessary when removing shoring braces. Do not strike the cabinet with hammers or other tools.
A Note emphasizes important tex t. If the note is not followed, equipment could be damaged or may not operate properly. For example:
NOTE
If the UPS system has a blown fuse, the cause should be determined before you replace the fuse. Contact Liebert Global Services.
Safety Precautions 3

2.0 INSTALLATION CONSIDERATIONS

Install your S er ies 600T UPS in accordance with the submittal drawing package and the follow­ing procedures.
A Liebert authorized representative must perform the initial system check-out and start-up to ensure proper system operation. Equipment warranties willbe voided unless system start-up is performedby a Liebert authorized representative. Contact your local Liebert sales r epresentative or Liebert Global Services at 1-800-543-2378 to arrange for system start-up.
CAUTION
!
Read this ma nual thoroughly before attempting to wire or operate the unit. Improper installation is the most significant cause of UPS start-up problems.
Do not install this equipment near gas or electric heaters. It is preferable to install the UPS in a restricted location to prevent access by unauthorized personnel.
1. Proper planning will speed unloading, location, and connection of the UPS. Refer to
Figure 8 through Figure 58 and Appendix A - Site Planning Data.
2. Refer t o information later in this manual regarding the optio nal Battery Cabinets and Transformer Cabinets. Observe all battery safety precautions when working on or
near the battery.
3. Use the shortest output distribution cable runs possible, consistent with logical equipment arrangements and with allowances for future additions i f planned.
4. Recommended ambient operating temperature is 25°C (77°F). Relative humidity must be less than 95%, non-condensing. Note that room ventilation is nece ssary, but air conditioning may not be required. Maximum ambient o perating temperature is 40°C (104°F) without d erating. The batteries should not exceed 25°C (77°F). At elevations above 4,000 feet (1219 meters) derating may be required (consult your Liebert s ales representative).
5. Even though your Liebert UPS unit is at least 93% efficient, the heat output is substantial. For more specific information, see Appendix A - Site Planning Data. Be sure environmental conditioning systems can accommodate this BTU load, even during utility outages.
6. The routing (inside th e facility) to the installation site, as well as the f l oor at the final equipment location, must be capable of supporting the cabinet weight and the weight of any moving equipment. The modules weigh up to 12,000 po unds. The batt er y cabinets weigh between 3000 and 4900 pounds. The System Control Cabinets weigh between 1000 and 2550 pounds. Refer to Appendix A - Site Planning Data.
7. Plan the routing to ensure that the unit can move through all aisleways, doorways, and around corners without risking dama ge. If the modules and batteries mu st be moved by elevator, check the size of the door openings and the weight-carrying capacity of the elevator.
WARNING
!
LOCATE CENTER OF GRAVITY SYMBOLS AND DETERMINE UNIT WEIGHT BEFORE HANDLING CABINET.
4 Installation Considerations
Figure 1 UPS Multi-Module Unit Block Diagram
Installation Considerations 5
Figure 2 System Control Cabinets
SCCT Dimensions
Amp WxD Weight
Ratings (Inches) (lbs.)
200-1200 37x37 1000
1600 62x48 1525
2000-2500 62x48 2850
3000 62x48 3100 4000 138x60 5850

2.1 Types of System Control Cabinets

1. SCCT is a stand-alone cabinet containing system control logic for up to six UPS modules, static bypass switch, manually operated disconnects for the static bypass switch, and two motor-operatedsystem breakers. The SCCT ispainted the same coloras the Liebert UPS, but does not match the shee t metal style of the UPS.
2. SCCI has the systemcontrol logic, circuit breakers andstatic bypass sw itch integrated into a switchboard cabinet manufactured by others.
3. SCCC is an integrated configuration like the SCCI with the sta tic bypass switch rated for continuousduty.
6 Installation Considerations

3.0 UNLOADING AND HANDLING

The UPS module is shipped in one cabinet to allow easy handling at the site. Because the weight distribution in the cabinet is uneven, use extreme care during handling andtransport. Your installation may also include Battery Cabinets and a System Control Cabinet.
WARNING
!
EXERCISE EXTREME CARE WHEN HANDLING UPS CABINETS TO AVOID EQUIPMENT DAMAGE OR INJURY TO PERSONNEL. THE UPS MODULE WEIGHS UP TO 12,000 POUNDS. BATTERY CABINETS WEIGH BETWEEN 3100 AND 4900 POUNDS.
LOCATE CENTER OF GRAVITY SYMBOLS BEFORE HANDLING CABINET. TEST LIFT AND BALANCE THE CABINET BEFORE TRANSPORTING. MAINTAIN MINIMUM TILT FROM VERTICAL AT ALL TIMES.
SLOTS AT THE BASE OF THE MODULES AND BATTERY CABINETS ARE INTENDED FOR FORKLIFT USE. BASE S LO TS WILL SUPPORT THE UNIT ONLY IF THE FORKS ARE COMPLETELY BENEATH THE UNIT.
SYSTEM CONTROL CABINETS (SCC’S) HAVE HOLES INTENDED FOR RIGGING BARSOR CHAINS. PREVENT CHAINS OR CABLES FROM CONTACTING CABINET BY USING SPREADER BAR AND ADEQUATE PADDING.
To reduce the possibility of shipping damage, cabinets are shored with 2x4 bracing, secured with screw-type nails. This shoring must be carefully removed prior to unloading.
CAUTION
!
Extreme care is n ecessary when removing shoring braces. Do not strike cabinet with hammers or other tools.
Unloading and Handling 7

4.0 INSPECTIONS

4.1 External Inspections

1. While the UPS system is still on the truck, inspect the equipment and shipping container(s) for any signs of damage or mishandling. Do not attempt to install the system if damage is apparent. If any damage is noted, file a damage claim with the shipping agency within 24 hours and contact Liebert Global Services at 1-800-543-2378 to inform them of the d amage claim and the condition of the equipment.
2. Locate the bag containing the keys for the front access door. The bag is attached to the cabinet.
3. Compare thecontents of the shipment withthe bill of lading.Report any missing items tothe carrier and to Liebert Global Services immediately.
4. Check the nameplate on the cabinets to verify that the model numbers correspond with the one specified. Recordthe model numbers and serial numbers in the front of this installation manual. A record of thisinformation is necessary should servicing become required.

4.2 Internal Inspections

1. Ve rify that all items have been received .
2. If spare parts were ordered, verify arrival.
3. Open doors and remove cabinet panels to check for shipping damage to internal components.
4. Check for loose connections or unsecured components in the cabinet(s).
5. Check for installation of circuit breaker line safety shields. There should be no exposed circuit breaker terminals w hen the cabinet doors are opened.
6. Check f o r any unsafe conditio n that may be a potential safety hazard.
7. UPS modules are shipped with internally mounted ship ping brackets. The ship ping brackets (painted orange) must be removedfrom the rear (remove r ear panels).
8 Inspections

5.0 EQUIPMENT LOCA TION

1. Handle cabinet(s) in accordance with the Section 1.0 Safety Precautions and 3.0
Unloading & Handling. Use a suitable material hand ling d evice to move cabinet to its final
location. Exercise extreme care because of the uneven weight distribution. Carefully lower the cabinet to the floor.
2. Verify that the UPS system is installed in a clean, cool and dry location.
3. Installation and serviceability will be easier if adequate access is provided on all sides of the
equipment, but only front access is required. a. Verify that there is adequate clearance to open cabinet do ors. See drawings and local
codes (4 feet is recommended).
b. Verify that there is adequate area i n front of circuit breakers to perform maintenance.
Check installation drawings for location of breakers.Check w ith local codes.
c. Verify that there is adequate clearance above all cabinets to allow exhaust air to flo w
without restriction (2 feet minimum, unobstructed).
Equipment Location 9

6.0 BATTERY INSTALLATION

6.1 Battery Safety Precautions

Servicing of batteries should be performed or supervised by personnelknowledgeable of ba tteries and the required precautions. Keep unauthorizedpersonnel away from batteries.
When replacing batteries, use the same number and type of batteries.
CAUTION
!
Lead-acid batteries contain hazardous materials. Batteries must be handled, transported, and recycled or discarded in accordance with federal, state, and local regulations. Because lead is a toxic substance, lead-acid batteries should be recycled rather than discarded.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. Do not dispose of battery or batteries in a fire. The battery may explode.
A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries:
1. Remove watches, rings, or other metal objects.
2. Use tools with insulated handles.
3. Wear rubber gloves and boots.
4. Do not lay tools or metal parts on top of batteries.
5. Discon nect charging source prior to conn e cting or disconnecting battery terminals.
6. Determine if battery is inadvertently grounded. If inadvertently grounded, remove source of ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance.
Lead-acid batteries can present a risk of fire because they generate hydrogen gas. The following procedures should be followed:
1. DO NOT SMOKE when near batteries.
2. DO NOT cause flame or spark in battery area.
3. Discharge static electricity from body before touching batteries by first touching a grounded metal surface.
10 Battery Installation
Battery Safety Precautions in French Per CSA Requirements Instructions Importantes Concernant La Sécurité Conserver Ces Instructions
ADVERTISSEMENT
!
DES PIECES SOUS ALIMENTATION SERONT LAISSEES SANS PROTECTION DURANT CES PROCEDURES D’ENTRETIEN. UN PERSONNEL QUALIFIE EST REQUIS POUR EFFECTUER CES TRAVAUX.
LES FUSIBLES A C.C. D E LA BATTERIE D ’ACCUM UL ATEU RS OPERENT EN TOU T TEMPS A LA TENSION NOMINALE. LA PRESENCE D’UN FUSIBLE A C.C. BRULE INDIQUE UN PROBLEME SERIEUX. LE REMPLACEMENT DE CE FUSIBLE, SANS AVOIR DETERMINE LES RAISONS DE LA DEFECTUOSITE, PEUT ENTRAINER DES BLESSURES OU DES DOMMAGES SERIEUX A L’EQUIPEMENT. POUR ASSISTANCE, APPELER LE DEPARTEMENT DE SERVICE A LA CLIENTELE DE LIEBERT.
DANGER
!
Les accumulateurs plomb-acide contiennent de la matière comportant un certain risque. Les accumulateurs doivent être manipulés,transportésetrecyclésouéliminésenaccordavecles lois fédérales, provinciales et locales. Parce que le plomb est une substance toxique, les accumulateurs plomb-acide devraient être recyclés plutôt qu’éliminés.
Il ne faut pas brûlé le ou les accumulateurs. L’accumulateur pourrait alors explosé.
Il ne faut pas ouvrir ou endommager le ou les accumulateurs. L’électrolyte qui pourrait s’en échapper est dommageable pour la peau et les y eux.
Un accumulateur représente un risque de choc électrique et de haut courant de court-circuit. Lorsque des accumulateurs sont manipulés, les mesures préventives suivantes devraient être observées:
1. Retirer toutes montre, bagues ou autres objets métalliques.
2. Utiliser desoutils avec manchon isolé.
3. Porter des gants et des bottes de caoutchouc.
4. Ne pas déposer les outils ou les pièces métalliques sur le
dessus des accumulateurs.
5. Interr ompre la source de charge avant de raccorder ou de
débrancherlesbornesdelabatteried’accumulateurs.
6. Déterminer si l’accumulateur est mis à la terre par erreur. Si
oui, défaire cette mise à l a terre. Tout contact avec un accumulateur mis à la terre peut se traduire en un choc électrique. La possibilitié de tels chocs sera réduité si de telles mises à la terre sont débranchées pour la du rée de l’installation ou de l’entretien.
Battery Installation 11
Les accumulateurs plomb-acide présentent un risque d’incendie parce qu’ils génèrent des gaz à l’hydrogène. Les procédures suivantes devront être respectées.
1. NE PAS FUM ER lorsque près des accumulateurs.
2. NEPASproduiredeflammesoud’étincellesprèsdes accumulateurs.
3. Décharger toute électricité statique présente sur votre corps avant de toucher un accumulateur en touchant d’abord une surfacemétalliquemiseàlaterre.
DANGER
!
L’électrolyte est un acide sulfurique dilué qui est dangereux au contact de la peau et des yeux. Ce produit est corrosif et aussi conducteur electrique. Les procédures suivantes devront être observées:
1. Porter toujours des vêtements protecteurs a insi que des lunettes de protection pour les yeux.
2. Si l’électrolyte entre en contact avec la peau, nettoyer immédiatement en rincant avec de l’eau.
3. Si l’électrolyte entre en contact avec les yeux, arroser immédiatement et généreusement avec de l’eau. Demander pour de l’aide médicale.
4. Lorsque l’électrolyte est renversée, la surface affectée devrait être nettoyée en utilisant un agent neutralisant a déquat. Une pratique courante est d’utiliser un mélange d’approximativement une livre (500 grammes) de bicarbonate de soude dans approximativement un gallon (4 litres) d’eau. Le mélangedebicarbonatedesoudedevraêtreajoutéjusqu’àce qu’il n’y ait plus apparence de réaction (mousse). Le liquide résiduel devra être nettoyé à l’eau et la surface concernée devra être asséchée.
12 Battery Installation

6.2 Matching Battery Cabinets

Two sizes ofoptional battery cabinets areavailable. Refer to Figure 16 to Figure 18. The battery cabinet cells range from 90 to 150 Ampere-hours.The same model battery cabinet may be paral­leled in multiple cabinet strings for additional capacity. Battery capacity (in minutes) at your installation will depend on cabinet model, number of cabinets, and amount of critical load on the UPS.
1. Han d ling. The Battery Cabinet weighs 3000 to 4900 pounds. Forklift slots are provided for easy handling.
2. Cabinet Inspection. Remove all panels and visually inspect the batteries, bus connections, and cabinet for any d amage. Exercise caution; v oltage is present within the Battery Cabinet even beforeinstallation.If there aresigns of damage, do notproceed. Call Liebert Global Services at 1-800-543-2378.
3. Battery Storage. The batteries used in the Battery Cabinet have an excellent ch arge retaining characteristic. The batteries can be stored for up to six months without any appreciable deterioration. Self-discharge rate of the batteries is approximately 3% permonth when the batteries are stored in temperatures of 15°C to 25°C (59°F to 77°F). If the Batt ery Cabinet is planned to be stored for longer than sixmonths, contact Liebert Customer Service for recommended action.
4. Installation. The Battery Cabinet(s) can be located conveniently next to each UPS module. The front-access-only-design eliminates side and rear service clearance requirements.
Environment. Locate the Battery Cabinet in a clean, dry environment. Recommended temperature range for optimum performance and lifetime is 20°C (68°F) to 25°C (77°F).
Service Clearance. Allow front access to the Battery Cabinet at all times for mainte­nance and servicing. Electrical codes require that the Battery Cabinet be installed with no less than 3feet (1 meter)of clearance at the front of thecabinet when operating. Side and rear panels do not require service clearance.
Side Panels. Remove protective side panels to connect cabinets together. Panels are retained at the bottom with three screws.
Shield Plate. IftheBatteryCabinetsareboltedtothesideoftheUPSmodule,theshield plate inside the Battery Cabinet should be on the side toward the UPS module for proper UPS airflow. Move the shield if required by your Battery Cabinet location.
Cables. Cables may be run between the cabinets through cutouts in the top of the cabi­net, eliminating the need for external conduit runs. Route cables before moving cabi- nets into final position for bolting together. Remove top panels for access, if required. No topor bottom entry cables are required, exceptfor remotely located cabinets which require conduits.Refer to Figure 16 through Figure 18.
Built-In Cabinets. Matching Battery Cabinets are designed as a bolt-on section to the side of the UPS module cabinet. Use bolts (3/8"-16 x 1-1/4") to connect cabinet frames at posts, two places front and two places rear. Brackets are provided to make rear connec­tions easier fr om inside the cabi net.

6.3 Non-Standard Batteries

When batteries other than a matching B attery Cabinet are used (not recommended), a remote battery disconnect switch with overcurrent protection is required per the National Electrical Code. Refer to Figure 53 and Figure 54. Contact yo ur Liebert sales representative regarding this option.
1. Install battery racks/cabinets and batteries per manufacturer’s installation and mainten a nce instructions.
2. Verify battery area has adequate ventilation and battery operating temperature complies with manufacturer’s specification.
If you have any questions concerning batteries, battery rack s, or accessories, contact Liebert Glo­bal Services at 1-800-543-2378.
Battery Installation 13

7.0 CONFIGURING YOUR NEU TRAL AND GROUND CONNECTION S

Improper grounding is the largest single cause of UPS installation and start-up problems. This is not an easy subject, since grounding techniques vary significantly from site to site, depending on several factors. The questions you should ask are:
• What is the configuration of the input power source? Most of the recommended schemes for UPS grounding require grounded-wye service. The UPS system requires a bypass neutral for sensing and monitoring the quality of the bypass input. If the building service is straight delta or corner-grounded delta, contact your Liebert representative for details of t he Artificial Neutral or Isolated Neutral kits for the System Control Cabinet.
• What a re the UPS input and output voltages? Systems with 480 VAC input and output have significantly different needs t han systems with 208/208 VAC.
• W hat is the connectedload? Does the critical load consist of one or more Power Distribution Units (PDUs)? Dothe PDUs have isolation transformers?
The following sections discuss recommended grounding procedures for various system configura­tions.
NOTE
Some UPS modules are equipped with input isolation transformers. However, these transformers have noeffect upon any system grounding considerations. These modules will be grounded e xactly as shown in the following examples.
14 Configuring Your Neutral and Ground Connections
7.1 Preferred Grounding Configuration, 480 or 600 VAC Input and Output, Isolated Power Distribution Units, Wye-Connected Service
Figure 3 Preferred Grounding Configuration, 480 or 600 VAC Input and Output
The most-common configuration of Series 600T U PS Multi-Module Systems is wit h 480 VAC input, 480 VAC output, and a connected load consi sting of multiple Power Distribution Units (PDUs) w ith isolation transformers in the PDUs to produce 208 VAC. F or Canadian customers, the UPS modules usually have 600 VAC input and output. T he same principles apply ifthe con­nected load is an isolation transformer feeding various loads. Figure 3 above shows a typical installation. The Maintenance Bypass Switchgear is shown separately for clarity, but is usually contained withinthe System Control Cabinet (SCC).
Notice that the UPS module inputandthe system bypassinput are connected to a grounded-wye service. In this configuration, the UPS module is not considered a separately derived source.
All of the UPS moduleoutput neutralsaresolidlyconnectedto the SCC neutral.TheSCC neutral is so lidly connected to the building service ne utral, which is bonded to the grounding conductor at the service entrance equipment.
The isolation transformers in the PDUs can be considered separately derived sources. Therefore the PDU neutrals should be bonded to t he PDU g rounding conductor and connected to a local grounding electrode in compliance with NEC 250-26.
NOTE
Impedance-grounded wye sources require an Isolated Neutral Kit in addition to the grounding and neutral conductors shown above.
Configuring Your Neutral and Ground Connections 15

7.2 Grounding Configuration, 480 or 600 V AC Input and Output, Delta Source

Figure 4 Grounding Configuration with Ungrounded Delta Source Input
As previously mentioned, Series 600T UPS systems requirea bypass input n etrual for sensing and monitoring. With a wye-connected input source, the installer should always connect the building service neutral to the System Control Cabinet (SCC) output neutral to achieve this. When the building service is delta-c onnected, however, the installer must take special steps to ensure reliable UPS functioning.
If building service is ungroundeddelta (andthereisnointenttooperatewithonecornerofthe delta grounded, either on purpose or accidentally), the SCC requires the Series600T Artificial Neutral Kit for proper operation. This kit uses a resistor network to create a reference point for the bypass input. In this case, the SCC output neutral must be bonded to the SCC ground.
If the building service is corner-grounded delta or an Impedance-grounded wye, theSCC requires the Isolated Neutral Kit. This kit uses control isolation transformers to create a referen ce point. For this application, the SCC output neutral must notbe bonded to the SCC ground.
NOTE
The Artificial Neutral Kit introduces a maximum currentof 0.3 amps to ground. Take care to ensure that this does not interfere with the operation of any upstream ground-fault detection devices.
16 Configuring Your Neutral and Ground Connections

7.3 Preferred Grounding Configuration with Power-Tie Switchgear

Figure 5 Preferred Grounding Configuration, Power-Tie Systems
Multi-Module Systems can beused with Power-Tie switchgear to providedual critical load busses. The Power-Tie switchgear permits transferring critical loads from one critical bus to the other so that one UPS system and associated breakers can be de-energized for maintenance. Certain con­figurationsof Power-Tieequipmentalso permit the operator to c ontinuously parallel the output of both UPS systems.
In tied systems, each SCC must have its neutral solidly connected to the Power-Tie switchgear neutral. The UPS modules, as usual, must have their output neutrals solidly connected to their respective SCC neutrals. There shouldnot be a connection between the service entrance neutral and either the SCC or module neutrals.
NOTE
It is essential to run a neutral connection between t he tie switchgear and bothSCCsasshownintheillustrationabove.
Configuring Your Neutral and Ground Connections 17

7.4 Grounding Configurations, Battery Systems

Figure 6 Battery Cabinet Grounding Configuration
Large, open-rack battery systems are normally either locally grounded or left ungrounded, depending on local code requirements.
Battery cabinet systems, on the other hand, should be grounded to the UPS module ground bus. The figure above illustrates how a simple one-cabinet system would be grounded. For systems with multiple cabinets, the same configuration would apply. However, for simplicity the installer can connect all the battery cabinet grounds for a particular module together and run a single ground conductor to that UPS module ground.
18 Configuring Your Neutral and Ground Connections

8.0 WIRING CONSIDERATIONS

WARNING
!
ALL POWER CONNECTIONS MUST BE COMPLETED BY A LICENSED ELECTRICIAN THAT IS EXPERIENCED IN WIRING THIS TYPE OF EQUIPMENT. WIRING MU S T BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE NATIONAL AND LOCAL ELECTRICAL CODES. IMPROPER WIRING MAY CAUSE DAMAGE TO THE EQUIPMENT OR INJURY TO PERSONNEL.
VERIFY THAT ALL INCOMING HIGH AND LOW VOLTAGE POWER CIRCUITS ARE DE-ENERGIZED AND LOCKED OUT BEFORE INSTALLING CABLES OR MAKING ANY ELECTRICAL CONNECTIONS.
Refer to Appendix A - Site Planning Data a nd installation drawings (Figure 8 through Figure 58). Determine AC currents for your system (kVA, voltage, a nd options). Also refer to
equipment nameplate for the model number, rating, and voltage. Refer to Table 1 and Table 2 for wire termination data.
NOTE
Use 75°C copper wire. Selectwire s ize based on the ampacities in Table 3 of t his manual, a reprint of Table 310-16 and associated notes of the National Electrical Code (NFPA 70).
CAUTION
!
The weight of power cables must be adequately supported to avoid stress on bus bars and lugs. In addition to weight su pport, the followingrestrainingmethod is recommended to controlcable movement during external fault conditions: Wrap line cables together at 6 inches and 12 inches from the terminals with 5 wraps of 3/8 inch nylon rope or equivalent (tensile strength of 2000 po unds). Support remainder of cable with 5 wraps every 6 inches or 1 wrap every 1 inch.
Wiring Considerations 19

8.1 Power Wiring

1. Power wiring must be run in individual, separate conduits or cable trays. Refer to the Outline and Terminal Details drawings (Figure 8 to Figure 15 and Figure 29 to Figure 32)for locations of the various power connections within the UPS and SCC. In particular, note the location of the rectifier input power connections.
CAUTION
!
Power and control wiring must be separated!
2. Observe local, state and national electrical codes. Verify utility power and its overcurrent protection rating will accommodate the UPS input rating, including battery recharging.
3. A safety ground wire must be run from building ground to ground point in the UPS Module Cabinets, the Sy stem Control Cabinet, and thePower-Tie Cabinet(if applic able). See Sections
7.1 through 7.4. The grounding conductor shall comply with the following conditions of installation:
a. An insulated grounding conductor must be sized in accordance with th e NEC and local
codes. It must be green (with or without one or more yellow stripes) and be installed as part of the branch circuit that sup plies the unit or system.
b. The grounding conductor described above is to be grounded to earth at the service
equipment or, if supplied b y a separately derived system, at the supply transformer or motor-generator set in accordance with the instructions in Section 7 of this Manual.
c. The attachment-plug receptacles in the vicin ity of the u nit or system are all to be of a
grounding type, and the g rounding conductors serving these receptacles are to be connected to earth ground at the service equipment.
4. When possible, input to th e UPS and byp ass should be fo ur wire plus ground. When input is straight delta, the UP S artificial neutral kit should be orde red. When input is corner­grounded delta, the isolated neutral kit should b e ordered.
5. Observe clockwise phase rotation of all power wiring. Phase A leads Phase B leads Phase C. A qualified electrician should check the phase rotation.
6. Power cables must be rated for le ss than 2 volts line drop at maximum rated system current.
7. If site equipment includes a backup generator and automatic transfer switch(es), consult the manufacturers of those devices for information on sizing and interfacing to the UPS system.
8. The installing contractor can remove the access plates from the left and right side of the cable­access area in the top of the UPS in order to c ut entry holes for conduit. For units that also have bottom cable access, there is a third access p late on the right side of the module.
CAUTION
!
After cutting holes in the access plates,be certain that no foreignmatter (metal shavings, sawdust, insulation or wire fragments, etc.) remains inside the UPS. Likewise be certain to block any “extra” holes in the plates through which foreign matter could later enter the UPS.
20 Wiring Considerations

8.2 Control Wiring

Control wiring must be stranded and tinned and run in individual separate steel conduits. Con­trol wiring must be separated from power wiring. In addition, each control wiring cable group should be run in a separate conduit to minimize control signal interference.
Refer to the Control Connection Locations and Control Wire Lists, Figure 33 through Figure52. Notice that there are nine cable groups in a typical system:
• Cable group 1 carriessignalsfor the Module BatteryDisconnect.
• Cable group 2 is for the remote communications options: modem, remote terminal and remote CRT.
• Cable group 3 carriessignals for the Remote Emergency Module Off and Remote Emergency Power Off.
• Cable group 4 carries signals for the optional Remote Status Panel.
•Cablegroup5isfortheoptionalSiteScansystem.
• Cable group 6 carries signals for the reduced battery charge lim it and the reduced input cur­rent limit.
• Cable gr oup 7 carries signals to and from th e maintenance bypass switchgear.
• Cable groups 20 and 21 carry signals for general housekeeping, modules to SCC.
Other cable groups will be required for other optional equipment. If your system has any installed options, special wi re lists will be included in your Submittal Drawing Package.Contact your Lie­bert Sales Representative for assistance ifthe submittal drawingshave been lost or misplaced.
Figures AA and BB show the t ypical location of control connections inside the UPS and SCC. The position of a particular control connection may be different for your system, depending on the model and the installed options.
NOTE
The UPS control and communication wiring are considered Class 2 circuits by NEC standards. However, NEC Class 1 wiring methods are required for these circuits to ensure proper operation of the UPS.
Wiring Considerations 21

8.3 Battery Wiring

Power wiring to the Battery Cabinet connects positive, negative, and ground power cables from the Battery Cabinet to the associated UPS. Connection of the UPS to the Battery Cabinet serves to both chargeand discharg e the batteries (w he n needed). The batterydisconnect (cir cuit breaker) requires a control cable. Liebert Battery Cabinets include power and controlcables to join multi­ple cabinets together into a system. Additional (field-supplied) power or control wiring might be necessary to connect the battery cabinet system to the UPS. Refer to Figure 16 through
Figure 18.
DANGER
!
A BATTERY INTERCELL CONNECTION ON EACH TIER OF THE LIEBERT BATTERY CABINET IS DISCONNECT ED FOR SAFETY DURING SHIPMENT. DO NOT COMPLETE THESE CONNECTIONS. THE LIEBERT GLOBAL SERVICES REPRESENTATIVE WILL COMPLE TE THESE CONNECTIONS AS PART OF START-UP. AN IMPROPERLY INSTALLED UNIT CAN RESULT IN INJURY TO PERSONNEL OR DAMAGE TO EQUIPMENT.
CAUTION
!
Be sure polarity is correct when wiring the Battery Cabinetto the connected equipment (positive to positive; negative to negative). If polarity is not correct, fuse failures or equipment damage can result.
CAUTION
!
DC power cables should be installed in conduit with conductors in matched pairs (positive and negative).
NOTE
A Liebert Battery Specialist can perform a detailed inspection of the entire battery system to ensure it meets current IEEE standards. This inspection service is recommended because batteries are a very critical part of the UPS system.
22 Wiring Considerations
Loading...
+ 63 hidden pages