Liebert 600T User Manual

POWER PROTECTION
Series 600T™ UPS
Single Module Three Phase 500 kVA to 750 kVA, 60 Hz
Installation
Manual
Table of Contents
2.0 I
3.0 U
4.0 I
4.1 External Inspections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.2 Internal Inspections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5.0 E
6.0 B
6.1 Battery Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
6.2 Battery Cabinets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.3 Non-Standa r d B a t te r ie s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7.0 C
7.1 Preferred G r ou n d i n g Co n fi gu r a tion, Wye-Con n e cted Service . . . . . . . . . . . . . . . . . . 13
7.2 Alternative G ro u n d in g Configurati o n , W y e -C o n n e ct e d Se rvice . . . . . . . . . . . . . . . . 14
7.3 Grounding Configuration, Delta Source or Impedance-Grounded Wye . . . . . . . . . . 15
7.4 Preferred G r ou n d i n g Co n fi gu r a tion with Power-Tie™ Swit ch ge a r. . . . . . . . . . . . . . 16
7.5 Preferred Grounding Configuration, Battery Systems. . . . . . . . . . . . . . . . . . . . . . . . 17
NSTALLATION CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
NLOADING AND HANDLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
NSPECTIONS
QUIPMENT LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
ATTERY INSTALLATION
ONFIGURING YOUR GROUND AND NEUTRAL CONNECTIONS
8.0 W
IRING CONSIDERATIONS
8.1 Power and Cont r ol W ir i n g . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.2 Battery Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
9.0 W
10.0 W
IRING CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
IRING INSPECTION
Table 1 Power Wiring Terminals - Factory Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Table 2 Torque Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Table 3 Table 310-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
11.0 INSTALLATION DRAWINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
12.0 A
PPENDIX A - SITE PLANNING DATA
Table 4 Site Planning Data, 480 Volt Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Table 5 Site Planning Data, 600 Volt Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Table 6 Circuit Breaker Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
13.0 APPENDIX B - FIELD SUPPLIED LUGS
Table 7 One-Hole Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
List of Figures
Figure 1 Preferred Grounding Configuration, 480 or 600 VAC input and output. . . . . . . . . . . . . . . . . 13
Figure 2 Alternative Grounding Configuration, 480 or 600 VAC input and output . . . . . . . . . . . . . . . 14
Figure 3 Preferred Grounding Configuration with Delta Source Input . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 4 Preferred Grounding Configuration, Power-Tie™ Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 5 Preferred Battery Cabinet Grounding Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 6 Typical Power Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 7 Outline Drawing, 500 kVA Single Module UPS, 6-Pulse Rectifier . . . . . . . . . . . . . . . . . . . . . 26
Figure 8 Outline Drawing, 500 kVA Single Module UPS, 12-Pulse Rectifier . . . . . . . . . . . . . . . . . . . . 27
Figure 9 Outline Drawing, 625-750 kVA Single Module UPS, 6-Pulse Rectifier . . . . . . . . . . . . . . . . . 28
Figure 10 Outline Drawing, 625-750 kVA Single Module UPS, 12-Pulse Rectifier . . . . . . . . . . . . . . . . 29
Figure 11 Battery Cabinet, Size A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Figure 12 Battery Cabinet, Size B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 13 Parallel Battery Power Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 14 Base Mounting Patterns, 500 kVA SMS, 12-Pulse Rectifier . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Figure 15 Base Mounting Patterns, 625-750 kVA SMS, 6-Pulse Rectifier . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 16 Base Mounting Patterns, 625-750 kVA SMS, 12-Pulse Rectifier . . . . . . . . . . . . . . . . . . . . . . 35
Figure 17 Shipping Split Detail, 500 kVA SMS, 12-Pulse Rectifier. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 18 Shipping Split Detail, 625-750 kVA SMS, 6-Pulse Rectifier . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 19 Shipping Split Detail, 625-750 kVA SMS, 12-Pulse Rectifier . . . . . . . . . . . . . . . . . . . . . . . . . 38
Figure 20 Bussing Details, 500 kVA SMS, 6-Pulse Rectifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Figure 21 Bussing Details, 500 kVA SMS, 12-Pulse Rectifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Figure 22 Bussing Details, 625-750 SMS, 12-Pulse Rectifier. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 23 Bussing Details, 750 kVA/675 kW Standard and 750 kVA/600 kW Optional Input Busbars 42
Figure 24 Control Wiring, External Interconnect Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Figure 25 Control Connection Location Diagram, 500 kVA SMS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Figure 26 Control Connection Location Diagram, 625-750 kVA SMS . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Figure 27 Control Wire List, External Interconnections, 500-750 kVA SMS . . . . . . . . . . . . . . . . . . . . . 46
Figure 28 Control Wiring, Alarm Status Contacts Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Figure 29 Control Wiring, Maintenance Bypass Interlock Option. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Figure 30 Control Wiring, Remote Status Panel Interface Option. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Figure 31 Control Wiring, Remote Terminal IFM (RS-232 Communications) Option . . . . . . . . . . . . . . 50
Figure 32 Control Wiring, SiteScan Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Figure 33 Control Wiring, Customer Alarm Interface Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Figure 34 Control Wiring, Battery Temperature Sensor Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Figure 35 Control Wiring, SNMP Interface Option. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Figure 36 Control Wiring, Internal Modem Option. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Figure 37 Control Wiring, Maintenance Bypass Cabinet Option. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Figure 38 Wiring Configurations, UPS Video Display Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Figure 39 Outline Drawing, Module Battery Disconnect, 500 kVA SMS with 6-Pulse Rectifier . . . . . . 58
Figure 40 Outline Drawing, Module Battery Disconnect, 500-750 kVA SMS with 12-Pulse Rectifier . 59
Figure 41 Remote Status Panel, Surface Mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Figure 42 Circuit Breaker Schedule, 300-750 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
IMPORTANT SAFETY INSTRUCTIONS
Save These Instructions.
This manual contains important instructions that should be followed during installation of your Series 600T UPS and batteries.
WARNING
!
EXERCISE EXTREME CARE WHEN HANDLING UPS CABINETS TO AVOID EQUIPMENT DAMAGE OR INJURY TO PERSONNEL. THE UPS MODULE WEIGHT RANGES FROM 4200 POUNDS (1909 KG) TO 9170 POUNDS (4170 KG), INCLUDING TRANSFORMER CABINET. THE BATTERY CABINETS WEIGH BETWEEN 3000 POUNDS (1364 KG) AND 4900 POUNDS (2227 KG).
LOCATE CENTER OF GRAVITY SYMBOLS BEFORE HANDLING EACH CABINET. TEST LIFT AND BALANCE THE CABINETS BEFORE TRANSPORTING. MAINTAIN MINIMUM TILT FROM VERTICAL AT ALL TIMES.
SLOTS AT THE BASE OF THE MODULES AND BATTERY CABINETS ARE INTENDED FOR FORKLIFT USE. BASE SLOTS WILL SUPPORT THE UNIT ONLY IF THE FORKS ARE COMPLETELY BENEATH THE UNIT.
FOLLOW ALL BATTERY SAFETY PRECAUTIONS WHEN INSTALLING, CHARGING, OR SE RVICING BATTERIES. IN ADDITION TO THE HAZARD OF ELECTRIC SHOCK, GAS PRODUCED BY BATTERIES CAN BE EXPLOSIVE AND SULFURIC ACID CAN CAUSE SEVERE BURNS.
IN CASE OF FIRE INVOLVING ELECTRICAL EQUIPMENT, ONLY CARBON DIOXIDE FIRE EXTINGUISHERS, OR THOSE APPROVED FOR USE IN ELECTRICAL FIRE FIGHTING, SHOULD BE USED.
EXTREME CAUTION IS REQUIRED WHEN PERFORMING MAINTENANCE.
BE CONSTANTLY AWARE THAT THE UPS SYSTEM CONTAINS HIGH DC AS WELL AS AC VOLTAGES.
CHECK FOR VOLTAGE WITH BOTH AC AND DC VOLTMETERS PRIOR TO MAKING CONTACT.
1
WARNING
!
LOCATE CENTER OF GRAVITY SYMBOLS AND DETERMINE UNIT WEIGHT BEFORE HANDLING CABINET.
If you require assistance for any reason, call the toll-free Liebert Global Services number; 1-800­543-2378. For LGS to assist you expediently, please have the following information available:
Part Number: Serial Number: kVA Rating: Date Purchased: Date Installed: Location: Input Voltage: Output Voltage: Battery Reserve Time:
______________________________________________________________ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________ ______________________________________________________________
2

1.0 SAFETY PRECAUTIONS

Read this manual thoroughly, paying special attention to the sections that apply to you, before working with the UPS. Retain this manual for use by installing personnel.
Under typical operation and with all UPS doors closed, only normal safety precautions are neces­sary. The area around the UPS system should be kept free from puddles of water, excess mois­ture, or debris.
Special safety precautions are required for procedures involving handling, installation, and main­tenance of the UPS system or the battery. Observe all safety precautions in this manual before handling or installing the UPS system. Observe all precautions in the Operation and Mainte- nance Manual, before as well as during perfo rmance of a ll main tena nce procedu res. Obse rve a ll battery safety precautions before working on or near the battery.
This equipment contains several circuits that are energized with high volta ge. Only test equipment designated for troubleshooting should be used. This is particularly true for oscillo­scopes. Always check with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when the power is turned Off, dangerously high potentials may exist at the capacitor banks and at the batteries.
ONLY qualified service personnel should perform maintenance on the UPS system.
When performing maintenance with any part of the equipment under power, service personnel and test equipment should be standing on rubber mats. The service personnel should wear insu­lating shoes for isolation from direct contact with the floor (earth ground).
Unless all power is removed from the equipment, one person should never work alone. A second person should be standing by to assist and summon help in case an accident should occur.
Three types of messages are use d th roughout t he manual to st res s import an t text . Careful ly rea d the text below each Warning, Caution, and Note and use professional skills and prudent care when performing the actions described by that text.
A Warning signals the presence of a possible serious, life-threatening condition. For example:
WARNING
!
LETHAL VOLTAGES MAY BE PRESENT WITHIN TH IS UNIT EVEN WHEN IT IS APPARENTLY NOT OPERATING. OBSERVE ALL CAUTIONS AND WARNINGS IN THIS MANUAL. FAILURE TO DO SO COULD RESULT IN SERIOUS INJURY OR DEATH. DO NOT WORK ON OR OPERATE THIS EQUIPMENT UNLESS YOU ARE FULLY QUALIFIED TO DO SO!! NEVER WORK ALONE.
A Caution indicates a condition that could seriously damage equipment and possibly injure per­sonnel. For example:
CAUTION
!
Extreme care is necessary when removing shoring braces. Do not strike the cabinet with hammers or other tools.
A Note emphasizes important text. If the note is not followed, equipment could be damaged or may not operate properly. For example:
NOTE
If the UPS system has a blown fuse, the cause shoul d be determined before you replace the fuse. Contact Liebert Global Services.
Safety Precautions 3

2.0 INSTALLATION CONSIDERATIONS

Install your Series 600T UPS in accordance with the submittal drawing package and the follow­ing procedures.
A Liebert authori zed representative must perform the initial system check-out and start-up to ensure proper system operation. Equipment warranties will be voided unless system start-up is performed by a Liebert a uthoriz ed represent ative. C ontac t your loca l Liebert sales rep rese ntative or Liebert Global Services at 1-800-543-2378 to arrange for system start-up.
CAUTION
!
Read this manual thoroughly before attempting to wire or operate the unit. Improper installation is the most significant cause of UPS start-up problems.
Do not install this equipment near gas or electric heaters. It is preferable to install the UPS in a restricted location to prevent access by unauthorized personnel.
1. Proper planning will speed unloading, location, and connection of the UPS. Refer to
Figure 7 through Figure 33 and Appendix A - Site Planning Data.
2. Refer to information later in this manual regarding the optional Battery Cabinet(s), Maintenance Bypass Cabinet, and Transformer Cabinet. Observe all battery safety
precautions when working on or near the battery.
3. Use the shortest output distribution cable runs possible, consistent with logical equipment arrangements and with allowances for future additions if planned.
4. Recommended ambient operating temperature is 25°C (77°F). Relative humidity must be less than 95%, non-condensing. Note that room ventilation is necessary, but air conditioning may not be required. Maximum ambient operating temperature is 40°C (104°F) without derating. The batteries should not exceed 25°C (77°F). At elevations above 4,000 feet (1219 meters) derating may be required (consult your Liebert sales representative).
5. Even though your Liebert UPS unit is 92.5 to 94% efficient, the heat output is substantial. For more specific information, see Appendix A - Site Planning Data. Be sure environmental conditioning systems can accommodate this BTU load, even during utility outages.
6. The routing (inside the facility) to the installation site, as well as the floor at the final equipment location, must be capable of supporting the cabinet weight and the weight of any moving equipment. The modules weigh between 5,000 and 10,000 pounds. The battery cabinets weigh between 3100 and 5100 pounds. Refer to Appendix A - Site Planning Data.
7. Plan the routing to ensure that the unit can move through all aisleways, doorways, and around corners without risking damage. If the modules and batteries must be moved by elevator, check the size of the door openings and the weight-carrying capacity of the elevator.
WARNING
!
LOCATE CENTER OF GRAVITY SYMBOLS AND DETERMINE UNIT WEIGHT BEFORE HANDLING CABINET.
4 Installation Considerations

3.0 UNLOADING AND HANDLING

The UPS module is shipped in one cabinet to allow easy handling at the site. Because the weight distribution in the cabinet is uneven, use extreme care during handling and transport. Your installation may also include Battery Cabinet(s), a Maintenance Bypass Cabinet, and an optional transformer cabinet.
WARNING
!
EXERCISE EXTREME CARE WHEN HANDLING UPS CABINETS TO AVOID EQUIPMENT DAMAGE OR INJURY TO PERSONNEL. THE UPS MODULE WEIGHT RANGES FROM 2770 POUNDS TO 7500 POUNDS, NOT INCLUDING THE OPTIONAL TRANSFORMER CABINET. BATTERY CABINETS WEIGH BETWEEN 3100 AND 5100 POUNDS.
LOCATE CENTER OF GRAVITY SYMBOLS BEFORE HANDLING CABINET. TEST LIFT AND BALANCE THE CABINET BEFORE TRANSPORTING. MAINTAIN MINIMUM TILT FROM VERTICAL AT ALL TIMES. SLOTS AT THE BASE OF THE UNIT ARE INTENDED FOR FORKLIFT USE. BASE SLOTS WILL SUPPORT THE UNIT ONLY IF THE FORKS ARE COMPLETELY BENEATH THE UNIT.
To reduce the possibility of shipping damage, cabinets are shored with 2x4 bracing, secured with screw-type nails. This shoring must be carefully removed prior to unloading.
CAUTION
!
Extreme care is necessary when removing shoring braces. Do not strike cabinet with hammers or other tools.
Unloading and Handling 5

4.0 INSPECTIONS

4.1 External Inspections

1. While the UPS system is still on the truck, inspect the equipment and shipping container(s) for any signs of damage or mishandling. Do not attempt to install the system if damage is apparent. If any damage is noted, file a damage claim with the shipping agency within 24 hours and contact Liebert Global Services at 1-800-543-2378 to inform them of the damage claim and the condition of the equip ment.
2. Locate the bag containing the keys for the front access door. The bag is attached to the cabinet.
3. Compare the conten ts of t he shi pmen t wit h t he b il l of l a ding. Repo rt an y missi ng it ems to the carrier and to Liebert Global Services immediately.
4. Check the nameplate on the cabinet to verify that the model number corresponds with the one specified. Record the model number and serial number in the front of this installation manual. A record of this information is necessary should servicing become required.

4.2 Internal Inspections

1. Verify that all items have been received.
2. If spare parts were ordered, verify arrival.
3. Open doors and remove cabinet panels to check for shipping damage to internal components.
4. Check for loose connections or unsecured components in the cabinet(s).
5. Check for installation of circuit breaker line safety shields. There should be no exposed circuit breaker terminals when the cabinet doors are opened.
6. Check for any unsafe condition that may be a potential safety hazard.
7. UPS modules are shipped with internally mounted shipping brackets. The shipping brackets (painted orange) must be removed from the rear (remove rear panels).
6 Inspections

5.0 EQUIPMENT LOCATION

1. Handle cabinet(s) in accordance with WARNINGS in 16.0 - Unloading and Handling. Use
a suitable material handling device to move cabinet to its final location. Exercise extreme care because of the uneven weight distribution. Carefully lower the cabinet to the floor.
2. Verify that the UPS system is installed in a clean, cool and dry location.
3. Installation and serviceability will be easier if adequate access is provided on all sides of the
equipment, but only front access is required. a. Verify that there is adequate clearance to open cabinet doors. See drawings and local
codes (4 feet is recommended).
b. Verify that there is adequate area in front of circuit breakers to perform mai ntenance.
Check installation drawings for location of breakers. Check with local codes.
c. Verify that there is adequate clearance above all cabinets to allow exhaust air to flow
without restriction (2 feet minimum, unobstructed).
Equipment Location 7

6.0 BATTERY INSTALLATION

6.1 Battery Safety Precautions

Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
When replacing batteries, use the same number and type of batteries.
CAUTION
!
Lead-acid batteries contain hazardous materials. Batteries must be handled, transported, and recycled or discarded in accordance with federal, state, and local regulations. Because lead is a toxic substance, lead-acid batteries should be recycled rather than discarded.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. Do not dispose of battery or batteries in a fire. The battery may explode.
A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries:
1. Remove watches, rings, or other metal objects.
2. Use tools with insulated handles.
3. Wear rubber gloves and boots.
4. Do not lay tools or metal parts on top of batteries.
5. Disconnect charging source prior to connecting or disconnecting battery terminals.
6. Determine if battery is inadvertently grounded. If inadvertently grounded, remove source of ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance.
Lead-acid batteries can present a risk of fire because they generate hydrogen gas. The following procedures should be followed:
1. DO NOT SMOKE when near batteries.
2. DO NOT cause flame or spark in battery area.
3. Discharge static electricity from body before touching batteries by first touching a grounded metal surface.
8 Battery Installation
Battery Safety Precautions in French Per CSA Requirements Instructions Importantes Concernant La Sécurité Conserver Ces Instructions
ADVERTISSEMENT
!
DES PIECES SOUS ALIMENTATION SERONT LAISSEES SANS PROTECTION DURANT CES PROCEDURES D’ENTRETIEN. UN PERSONNEL QUALIFIE EST REQUIS POUR EFFEC TUER CES TRAVAUX.
LES FUSIBLES A C.C. DE LA BATTERIE D’ACCUMULATEURS OPERENT EN TOUT TEMPS A LA TENS ION NOMINALE. LA PRESENCE D’UN FUSIBLE A C.C. BRULE INDIQUE UN PROBLEME SERIEUX. LE REMPLACEMENT DE CE FUSIBLE, SANS AVOIR DETERMINE LES RA ISONS DE LA DEFECTUOSITE, PEUT ENTRAINER DES BLESSURES OU DES DOMMAGES SERIEUX A L’EQUIPEMENT. POUR ASSISTANCE, APPELER LE DEPARTEMENT DE SERVICE A LA CLIENTELE DE LIEBERT.
DANGER
!
Les accumulateurs plomb-acide contiennent de la matière comportant un certain risque. Les accumulateurs doivent être manipulés, transportés et recyclés ou éliminés en accord avec les lois fédérales, pro vin ciales et locales. Parce que le plomb est une substance toxique, les accumulateurs plomb-acide devraient être recyclés plutôt qu’éliminés.
Il ne faut pas brûlé le ou les accumulateurs. L’accumulateur pourrait alors explosé.
Il ne faut pas ouvrir ou endommager le ou les accumulateurs. L’électrolyte qui pourrait s’en échapper est dommageable pour la peau et les yeux.
Un accumulateur représente un risque de choc électrique et de haut courant de court-circuit. Lorsque des accumulateurs sont manipulés, les mesures préventives suivantes dev r aient être observées:
1. Retirer toutes montre, bagues ou autres objets métalliques.
2. Utiliser des outils avec manchon isolé.
3. Porter des gants et des bottes de caoutchouc.
4. Ne pas déposer les outils ou les pièces métalliques sur le
dessus des accumulateurs.
5. Interrompre la source de charge avant de raccorder ou de
débrancher les bornes de la batterie d’accumulateurs.
6. Déterminer si l’accumulateur est mis à la terre par erreur. Si
oui, défaire cette mise à la terre. Tout contact avec un accumulateur mis à la terre peut se traduire en un choc électrique. La possibilitié de tels chocs sera réduit e si de telles mises à la terre sont débranchées pour la durée de l’installation ou de l’entretien.
Battery Installation 9
Les accumulateurs plomb-acide présentent un risque d’incendie parce qu’ils génèrent des gaz à l’hydrogène. Les procédures suivantes devront être respectées.
1. NE PAS FUMER lorsque près des accumulateurs.
2. NE PAS produire d e flammes ou d’étincelles près des accumulateurs.
3. Décharger toute électricité statique présente sur votre corps avant de toucher un accumulateur en touchant d’abord une surface métallique mise à la terre.
DANGER
!
L’électrolyte est un acide sulfurique dilué qui est dangereux au contact de la peau et des yeux. Ce produit est corrosif et aussi conducteur electrique. Les procédures suivantes devront être observées:
1. Porter toujours des vêtements protecteurs ainsi que des lunettes de protection pour les yeux.
2. Si l’électrolyte entre en contact avec la peau, nettoyer immédiatement en rinçant avec de l’eau.
3. Si l’électrolyte entre en contact avec les yeux, arroser immédiatement et généreusement avec de l’eau. Demander pour de l’aide médicale.
4. Lorsque l’électrolyte est renversée, la surface affectée devrait être nettoyée en utilisant un agent neutralisant adéquat. Une pratique courante est d’utiliser un mélange d’approximativement une livre (500 grammes) de bicarbonate de soude dans approximativement un gallon (4 litres) d’eau. Le mélange de bicarbonate de soude devra être ajouté jusqu’à ce qu’il n’y ait plus apparence de réaction (mousse). Le liquide résiduel devra être nettoyé à l’eau et la surface concernée devra être asséchée.
10 Battery Installation

6.2 Battery Cabinets

Two sizes of optional battery cabinets are available. Refer to Figure 11 through Figure 13. The battery cabinet cells range from 90 to 150 Ampere-hours. The same model battery cabinet may be paralleled in multiple cabinet strings for additional capacity. Battery capacity (in minutes) at your installation will depend on cabinet model, number of cabinets, and amount of critical load on the UPS.
1. Handling. The Battery Cabinet weighs between 3100 and 5100 pounds. Forklift slots are provided for easy handling.
2. Cabinet Inspection. Remove all panels and visually inspect the batteries, bus connections, and cabinet for any damage. Exercise caution; voltage is present within the Battery Cabinet even before installation. If there are signs of dama ge, do not procee d. Call Lieber t Global Services at 1-800-542-2378.
3. Battery Storage. The batteries used in the Battery Cabinet have an excellent charge retaining characteristic. The batteries can be stored for up to six months without any appreciable deterioration. Self-discharge rate of the batteries is approximately 3% per month when the batteries are stored in temperatures of 15°C to 25°C (59°F to 77°F). If the Battery Cabinet must be stored for longer than six months, contact Liebert Global Services for recommended action.
4. Installation. The Battery Cabinet(s) can be located conveniently next to the UPS module. The front-access-only-design eliminates side and rear service clearance requirements.
Environment. Locate the Battery Cabinet in a clean, dry environment. Recommended temperature range for optimum performance and lifetime is 20°C (68°F) to 25°C (77°F).
Service Clearance. Allow front access to the Battery Cabinet at all times for mainte- nance and servicing. Electrical codes require that the Battery Cabinet be installed with no less than 3 feet (1 met er) of clea ranc e a t the fro nt of t he cabi net wh en op erating . Side a nd rear panels do not require service clearance.
Side Panels. Remove protective side panels to connect battery cabinets together. Panels are retained at the bottom with three screws.
Shield Plate. The shield plate in each Battery Cabinet should be on the side toward the UPS system. Move the shield if required by your Battery Cabinet location.
Cables. Cables may be run between the cabinets through cutouts in the top of the cabi- nets, eliminating the need for external conduit runs. Route cables before moving cab- inets into final position for bolting toget her. Remove top panels fo r access. N o top o r bottom entry cables are required, except for remotely located cabinets which require con­duits. Refer to Figure 11 through Figure 13.
NOTE
The 300-450 kVA UPS module is approximately 2 inches deeper than the Battery Cabinet and is not designed to bolt directly to it.

6.3 Non-Standard Batteries

When batteries other than a matching Battery Cabinet are used (not recommended), a remote battery disconnect switch with overcurrent protection is required per the National Electrical Code. Refer to Figure 39 and Figure 40. Contact your Liebert sales representative.
1. Install battery racks/cabinets and batteries per manufacturer’s installation and maintenance instructions.
2. Verify battery area has adequate ventilation and battery operating temperature complies with manufacturer’s specification.
If you have any questions concerning batteries, battery racks, or accessories, contact Liebert Glo­bal Services at 1-800-543-2378.
Battery Installation 11

7.0 CONFIGURING YOUR GROUND AND NEUTRAL CONNECTIONS

Improper grounding is the largest single cause of UPS installation and start-up problems. This is not an easy subject, since grounding techniques vary significantly from site to site, depending on several factors. The questions you should ask are:
• What is the configuration of the input power source? Most of the recommended schemes for UPS grounding require grounded-wye service. The UPS system requires a bypass neutral for sensing and monitoring the quality of the bypass input. If the building service is ungrounded delta or corner-grounded delta, contact your Liebert representative to ensure your system
• What is the configuration of the UPS equipment? A Power-Tie system has different needs than a standalone UPS module.
• What is the connected load? Does the critical load consist of one or more Power Distribution Units (PDUs)? Do the PDUs have isolation transformers?
The following sections discus s recommended grounding procedures for various system configura­tions.
NOTE
Some UPS modules are equipped with input isolation transformers. However, these transformers have no effect upon any system grounding considerations. These modules will be grounded exactly as shown in the following examples.
12 Configuring Your Ground and Neutral Connections
7.1 Preferred Grounding Configuration, 480 or 600 VAC Input and Output, Isolated Power Distribution Units, Wye-Connected Service
Figure 1 Preferred Grounding Configuration, 480 or 600 VAC input and output
GROUNDING ELECTRODE PER NEC 250-24
One of the most-common configura tions of the Series 6 00T UPS is the Single Module Syst em with 480 VAC input, 480 VAC output, and a connected load consisting of multiple Power Distribution Units (PDUs) with isolation transformers in the PDUs to produce 208 VAC. For Canadian cus­tomers, the UPS modules usually have 600 VAC input and output. The same principles apply if the connected load is an isolation transformer feeding various loads. Figure 1 above shows a typi­cal installation.
Notice that the UPS module main input and bypass input are connected to a grounded-wye ser­vice. In this configuration, the UPS module is not considered a separately derived source. The UPS module output neutral is solidly connected to the building service neutral, which is bonded to the grounding conductor at the service entrance equipment
The isolation transforme rs in the PDUs a re conside red a separatel y derived source . Therefo re the PDU neutral should be bonded to the PDU grounding conductor and connected to a local ground­ing electrode in compliance with NEC 250-26.
Advantages of this configuration include:
• A measure of common-mode noise attenuation, since the isolation (common-mode rejection) occurs as close to the load as practical (i.e. at the PDU).
• The UP S module can be located remotely from t he PDU without compromising co mmon-mode noise performance.
• By using UPS modules with 480 VAC input and output and creating 208 VAC at the PDU, smaller and less costly power feeders can be used and less voltage drop (as a percent of nomi­nal) occurs.
NOTE
Some UPS modules are equipped with input isolation transformers. However, these transformers have no effect upon any system grounding considerations. These modules will be grounded exactly as shown in these pages.
Configuring Your Ground and Neutral Connections 13
7.2 Alternative Grounding Configuration, 480 or 600 VAC Input and Output, Isolated Power Distribution Units, Wye-Connected Service
Figure 2 Alternative Grounding Configuration, 480 or 600 VAC input and output
This configuration is similar to that shown in Section 7.1, except that the service entrance neutral is not brought into the UPS module. In this configuration, the UPS output transformer is consid­ered a separately derived source. T he UPS modul e neutra l is bonded t o th e UPS ground , which i s connected to a local grounding electrode in accordance with NEC 250-26.
Please note that this configuration represents a price/performance trade-off. Whenever the UPS module transfers to or from bypass, two AC sources (input and bypass) are briefly connected together and circulating current must flow. In the previous configuration, the current flows through the neutral conductor. In this configuration, the current flows through the ground path, possibly tripping ground fault interruptors (GFIs) and distorting the bypass waveform reference. Proper adjustment of ground fault interrupters is necessary to avoid unwanted tripping.
This configuration is reserved for those applications which meet all the following criteria:
• The facility has Wye-connected service
• The module rectifier input and bypass input are fed from the same source
• The connected load is strictly 3-wire (such as one or more PDUs ) and does not require a neu­tral from the UPS
• Special precautions are taken to prevent tripping the ground fault interruptors. The time delay should be set to at least 30 cycles to prevent tripping when the UPS performs a transfer or retransfer operation.
CAUTION
!
Failure to properly set the ground fault interruptors could cause loss of power to the critical load.
14 Configuring Your Ground and Neutral Connections

7.3 Grounding Configuration, 480 or 600 VAC Input and Output, Delta Source or Impedance-Grounded Wye

Figure 3 Preferred Grounding Configuration with Ungrounded Delta Source Input (top) and Corner-
Grounded Delta (bottom)
GROUNDING ELECTRODE PER NEC 250-24
GROUNDING ELECTRODE PER NEC 250-24
LOCAL GROUNDING ELECTRODE PER NEC 250-30
LOCAL GROUNDING ELECTRODE PER NEC 250-30
LOCAL GROUNDING ELECTRODE PER NEC 250-30
As previously mentioned, Series 600T UPS modules require a bypass input neutral for sensing and monitoring. With a wye-connected input source, the installer should connect the building ser­vice neutral to the module output neutral to achieve this. When the building service is delta-con­nected, however, the installer must take special steps to ensure reliable UPS functioning.
If building service is ungrounded delta (and there is no intent to operate with one corner of the delta grounded, either on purpose or accidentally), the UPS requires the Series 600T Artificial Neutral Kit for proper operation. This kit uses a resistor network to create a reference point for the bypass input. In this case, the UPS output neutral must be bonded to the UPS ground. See Figure 5 above.
If the building service is corner-grounded delta or an impedance-grounded wye, the UPS requires the Series 600T Isolated Neutral Kit. This kit uses control isolation transformers to create a refer­ence point. For this application, the UPS output neutral must not be bonded to the UPS ground.
Configuring Your Ground and Neutral Connections 15

7.4 Preferred Grounding Configuration, 480 or 600 VAC Input and Output, with Power-Tie™ Switchgear

Figure 4 Preferred Grounding Configuration, Power-Tie™ Systems
GROUNDING ELECTRODE PER NEC 250-24
GROUNDING ELECTRODE PER NEC 250-24
Single Module Systems can be used with Power-Tie switchgear to provide dual critical load bus­ses. The Power-Tie switchgear permits transferring critical loads from one critical bus to the other so that one UPS module and associated breakers can be de-energized for maintenance. Cer­tain configurations of Power-Tie equipment also permit the operator to continuously parallel the output of the UPS modules.
In tied systems, each UPS module must have its neutral solidly connected to its own building ser­vice neutral and to the Power-Tie switchgear neutral. See Figure 6 above.
NOTE
It is essential to run a neutral connection between the tie switchgear and both UPS modules as shown in the illustration above.
16 Configuring Your Ground and Neutral Connections
Loading...
+ 51 hidden pages