Installation, Operation and Maintenance Manual - 50/60Hz
Precision Cooling
For Business-Critical Continuity™
Figure iProduct model nomenclature
Example: DCDF165-Y
DD165-Y
D = Disconnect Switch
(optional on Fan Speed
Control, Chiller &
Standard Lee-Temp
Condensers; standard
on Quiet-Line and VFD
Control condensers
T = TVSS & Disconnect
Switch; available only
on the VFD Control
condensers
NOT ALL POSSIBLE COMBINATIONS OF MODELS,
CONTROLS AND VOLTAGES ARE AVAILABLE.
C
Condenser
F
F = Fan Speed Control
L = Main Control / Lee-Temp
C = No Control / Chiller
Lee-Temp
T = Ambient Fan Cycle/
Lee-Temp
V = Variable Frequency
Drive (VFD) Control
(available only for dual
refrigerant circuit
condensers
S = Single Refrigerant Circuit
D = Dual Refrigerant Circuit
*
Reserved
Model Size
* Single-phase voltage is only voltage available as standard
on Fan Speed Control 1-fan condensers
* Three-phase voltage is only voltage available as standard
on condensers with VFD Control, Lee-temp receivers, and
Fan Speed Control (2-8 fan models only).
* VFD Control Condensers are not available in 575-3-60.
P = 208/230V-1ph-60Hz
Z = 460V-1ph-60Hz
V = 575V-1ph-60Hz
W = 200/230V-1ph-50Hz
Y = 208/230V-3ph-60Hz
A = 460V-3ph-60Hz
B = 575V-3ph-60Hz
N = 200/230V-3ph-50Hz
M = 380/415V-3ph-50Hz
The Liebert condenser is low-profile direct-drive propeller fan-type air cooled unit suitable for mounting outdoors. It provides for the heat rejection of either one or two separate refrigeration circuits,
matching heat rejection capacity varying with the outdoor ambient temperatures with each corresponding compressors heat rejection requirements. Constructed with an aluminum cabinet and a copper-tube aluminum fin coil, the unit is quiet and corrosion resistant. The condenser is quickly and
easily installed, because all internal wiring is completed at the factory with only electrical connections to be made at the job site. All electrical connections and controls are enclosed in an integral
weatherproof section of the condenser.
Figure 1Liebert two-fan condenser
Introduction
1.2Head Pressure Control Types
1.2.1Fan Speed
Fan speed control utilizes a wave-chopper control to vary the air volume over the condenser coil,
based on refrigerant head pressure. The fan motor next to the electrical panel (two fans on 6-fan and
8-fan models) is a single-phase, permanent split capacitor motor with motor speed adjusted in
response to refrigerant pressure. The balance of fans on multi-fan units cycle on ambient thermostats.
The control system provides refrigerant head pressure control for outdoor ambients as low as
-20°F (-28.9 °C).
1.2.2Variable Frequency Drive
VFD Condenser control system utilizes a variable frequency drive, inverter duty fan motor operating
from 0% to 100% motor RPM based on head pressure, sensed by refrigerant pressure transducers.
VFD, ambient-temperature thermostat(s), motor overload protection and electrical control circuit are
factory-wired in the integral control panel. VFD controls the fan adjacent to the connection end of the
condenser and remains energized with active compressor operation. The balance of fans on multi-fan
units cycle on ambient thermostats. This system provides refrigerant head pressure control for outdoor ambients as low as -20°F (-28.9°C).
1
1.2.3Liebert Lee-Temp™ Refrigerant Control
The Liebert Lee-Temp head pressure control system is designed to maintain proper operating head
pressures in outdoor temperatures down to -30°F (-34.4°C). The condensers utilize head pressure control valves, extra refrigerant and insulated refrigerant receivers with heater pads. It works by flooding the condenser coil with liquid refrigerant to a level that balances the system condensing
requirements with the condenser coil surface available to reject the system heat. During the summer,
the system requires the entire condenser coil surface for heat rejection and most of the refrigerant is
stored in a receiver. In the winter, the same amount of heat can be rejected by only a fraction of the
coil surface. As head pressure begins to fall, the control valve restricts the flow of liquid refrigerant
exiting from the condenser. This extra liquid refrigerant reduces the effective condenser surface area
available for heat transfer. The head pressure control valve also bypasses hot gas into the receiver to
warm the liquid and maintain liquid pressure for proper operation of the expansion valve. Condenser
fan controls are either fan cycling on ambient temperature or constant on. Lee-Temp control is
required for Quiet-Line Condensers.
1.3Sound Level Options
1.3.1Standard Condenser
All Fan Speed and VFD Condensers are standard condensers with moderate operating sound levels.
Lee-Temp Condensers with standard-size coils matching Fan Speed and VFD coil sizes are standard
sound level condensers.
1.3.2Quiet-Line Condenser
Introduction
Quiet-Line condensers can help your facility meet the strictest noise codes and do so at less cost than
traditional condensers with acoustical shielding. The Quiet-Line condensers utilize the same reliable
construction features of the standard condensers and have oversized coils and slower speed fan
motors which yield the required heat rejection needed at significantly lower sound levels. Lee-Temp
control is required for Quiet-Line Condensers.
1.4Transient Voltage Surge Suppression Option
Transient Voltage Surge Suppression (TVSS) panel is standard in the VFD Condenser models only.
Surge protection is necessary because rooftop voltage supply often is not conditioned the same as the
voltage supply inside the data center. The TVSS is designed to protect sensitive electronic condenser
components from high voltage transients, up to 25kVA/phase.
An illuminated green LED indicates power supply is On and panel status is OK. An illuminated red
LED indicates conditions require service and the TVSS may require replacement to restore surge protection to the condenser.
1.5Typical System Configurations
Figure 2 shows a single refrigeration circuit diagram, displaying the indoor air conditioning unit, the
outdoor condenser (VFD, Fan Speed Control or Lee-Temp) and field supplied interconnection piping.
2
Figure 2Typical system configuration—indoor unit and outdoor condenser and field piping
Introduction
Inverted trap on discharge & liquid
lines to ext end above base of coil
by a minimum of 7-1/2” (190mm ).
Fusible
Plug
Condenser Coil
(Fan Speed
and VFD )
Fan Speed and VFD
28-42kW Digital Solenoid Valve
53-70kW Digital
Solenoid Valve
Service
Valve
Compressor
Chec k
Valve
Service
Valve
Chec k
Valve
Lee-Temp R eceiv er
Condenser Coil
(Lee-Temp )
Lee-Temp
Liquid
Sensing
Bulb
Evaporator C oil
Suction
External
Equalizer
Pitch horizontal hot gas piping
1/2" per 10 ft. (42mm per 10m)
in direction of refr igerant/oil flow.
Relief
Valve
Service
Valve
Liquid Return
Head Pressure
Control Valve
Hot Gas
Discharge
* Traps every
25ft (7.6m)
of rise
Field-installed relief v alve (s) required
for 50 Hz EU C E units rated maximum
480 PSIG (33 Bar).
* Isolation
valve
Hot Gas Discharge
Expansion
Valve
Solenoid
Filter DryerSight Glass
Valve
Factory Refrigerant Piping
Field Refrigerant Piping
Service/Schrader (Access) Connection No Valve Core
Liquid R eturn
Components are not supplied by
*
Liebert, but are recommended
for proper circuit operation and
maintenance.
Service/Schrader (Access) Connection W ith Valve Core
Note: Sc hematic representation shown . Do not use for specific connection loc ations .
Two refrigeration circuits provided . Single refrigeration circuit shown for clarity .
3
* Isolation
valve
DPN000798
Rev. 2
2.0SITE PREPARATION
2.1Site Considerations
The condensers should be installed in a location offering maximum security and access for maintenance.
Avoid ground-level sites with public access and areas that contribute to heavy snow or ice accumulations. Utilize Piggyback condensers whenever interior building locations must be used. To ensure adequate air supply, Liebert recommends that condensers be installed in an area with clean air, away
from loose dirt and foreign matter that might clog the coil. In addition, condensers should not be
located near steam, hot air or fume exhausts. Also, the condensers should be located no closer than
3 feet (1m) from a wall, obstruction or adjacent unit.
The condenser must not be installed in a pit.
The condenser must be installed on a level surface to ensure proper refrigerant flow.
For roof installation, mount the condenser on suitable curbs or other supports in accordance with
local codes.
Lee-Temp receiver tanks should be mounted on the condenser legs for proper operation. Remote
mounting of tanks must be within 10 feet of the condenser—Contact Liebert Application Engineering
Department for assistance.
Site Preparation
2.2Dimensions and Weights
Table 1Condenser shipping weights, dimensions and volume, approximate
Number
Model
*C**0831330 (150)
DC**0631350 (159)435 (197)
*C**1652490 (222)
*C**2052560 (254)760 (345)
DC**1192490 (222)690 (313)
DC**1272560 (254)760 (345)
DC**1432655 (297)855 (388)
*C**2513590 (268)
DC**2143885 (401)1165 (528)
*C**4154935 (424)
DC**28641185 (537)1485 (674)
*C**61661560 (708)
DC**40961620 (735)2070 (939)
*CD*83081930 (875)
DC**57282575 (1168)3075 (1395)
of Fans
Weight
lb (kg)
Domestic PackagingExport Packaging
Dimensions
(LxWxH)
in. (mm)
59x30x51
(1500x760x1300)
97x30x51
(2460x760x1300)
139x30x51
(3530x760x1300)
179x30x51
(4550x760x1300)
144x36x97
(3660x910x2460)
184x36x97
(4670x910x2460)
Volume
3
ft
(m3)
52 (1.4)
86 (2.4)
123 (3.4)
158 (4.4)
291 (8.3)
372 (10.)
Weight
lb (kg)
415 (188)
690 (313)
870 (395)
1235 (560)
2010 (912)
2430 (1102)
Dimensions
(LxWxH)
in. (mm)
60x31x52
(1520x790x1320)
98x31x52
(2490x790x1320)
140x31x52
(3560x790x132)0
180x31x52
(4570x790x1320)
145x37x97
(3680x940x2460)
185x37x97
(4700x940x2460)
Volume
3
ft
(m3)
56 (1.5)*C**1041350 (159)435 (197)
91 (2.5)
131 (3.5)*C**3083760 (345)1040 (472)
168 (4.5)*C**51041230 (558)1530 (694)
301 (8.4)
384 (10.)*CD*101082910 (1321)3410 (1548)
4
Figure 3Condenser planning dimensional data—One-fan and two-fan units
Site Preparation
51-1/2"
(1308mm)
43-3/16"
(1097mm)
43-9/16"
(1106mm)
18"
(457mm)
44"
(1118mm)
Note:
Overall height to the top of fan guard
43-1/8" (1095mm)
42"
ANCHOR PLAN
(1067 mm)
37-7/8"
(962mm)
91-1/2"
(2324mm)
43-3/16"
(1097mm)
ANCHOR PLAN
42"
(1067 mm)
43-9/16"
(1106mm)
37-7/8"
(962mm)
18"
(457mm)
84"
(2134mm)
Liebert recommends a clearance
of 36" (915mm) on each side for
proper operation and component
access.
82" (2083mm)
One -Fan
Condenser
See Figure 6 for typical condenser
footprint dimensions.
41-3/16"
(1046 mm)
Electric
Box
End
Legs supplied with
Lee-Temp option only
Two-Fan
Condenser
41-3/16"
(1046mm)
5
Figure 4Condenser planning dimensional data—Three-fan and four-fan units
43-9/16"
(1106mm)
131-1/2"
(3340mm)
37-7/8"
(457mm)
124"
(3150mm)
43-3/16"
(1097mm)
Note:
Overall height to the top of fan guard
43-1/8" (1095mm)
ANCHOR PLAN
42"
(1067mm )
(962mm)
18"
Eyebolts
for Lifting
43-3/16"
(1097mm)
122" (3099 mm)
171-1/2"
(4356mm)
70"
(1778mm)
164"
(4166mm)
Liebert recommends a clearance
of 36" (915mm) on each side for
proper operation and component
access.
Site Preparation
43-9/16"
(1106mm)
37-7/8"
(962mm)
18"
(457mm)
See Figure 6 for typical
condenser footprint
dimensions.
Electric
Box
End
Electric
Box
End
Legs s upplied with
Lee-Temp option only
ANCHOR PLAN
82" (2083 mm)
42"
(1067mm)
Legs s upplied wit h
Lee-Temp option only
Three -Fan
Condenser
41-3/16 "
(1046mm )
80"
(2032 mm)
Four-Fan
Condenser
41-3/16"
(1046mm)
6
Figure 5Condenser planning dimensional data—Six- and eight-fan units
87-1/8"
131-1/2"
(3340mm)
86-3/4"
(2203mm)
Overalll height to the top
of the fan guard is 43-1/8” (1095mm).
42"
(1067 mm )
122" (3099 mm)
(2213mm)
59"
(1499mm)
(3150mm)
18"
(457mm)
124"
ANCHOR PLAN
37-7/8"
(962mm)
(4356mm)
86-3/4"
(2203mm)
171-1/2"
1-1/2" (38mm)
diameter
hole for rigging
(typ.4)
Site Preparation
87-1/8"
(2213mm)
37-7/8"
(962mm)
18"
(457mm)
70" (1778mm)
164"
(4166mm)
Liebert recommends a
clearance of 36" (915mm)
on each side for proper
operation and component
access.
Electric
Box
End
Legs s upplied with
Lee-Temp option only
Electric
Box
End
Six-Fan
Condenser
82" (2083 mm)
42"
(1067mm)
Legs s upplied with
Lee-Temp option only
84-3/ 4"
(2153mm )
See Figure 6 for typical
condenser footprint dimensions.
ANCHOR PLAN
80" (2032 mm )
Eight -Fan
Condenser
84-3/4"
(2153 mm)
7
Figure 6Typical condenser footprint—dimensions
1”
(25.4mm)
1-3/4”
(44.5mm)
4-1/4”
(108mm)
1-3/4”
(44.5mm)
2”
(50.8mm)
Site Preparation
4-1/4”
(108mm)
2”
(50.8mm)
9/16" (14mm)
Typical Diameter
Figure 7Piping connection locations for 1-, 2-, 3- and 4-fan VFD Control and Fan Speed Condensers
Entering
Hot Gas Line
Leaving
Liquid Line
Traps to extend above
coil base by a minimum
of 7-1/2" (190mm)
Inverted Traps
(field-supplied)
Metal
Fasten liquid and hot gas lines
to leg using flat surface clamps
with isolators (field-supplied).
Support field piping separately
See
Detail
A-A
clamp
Isolator
Detail A-A
to avoid coil damage and loss
of charge.
DPN000665
Rev. 02
8
Figure 8Piping connections for 1-, 2-, 3- and 4-fan Lee-Temp and Quiet-Line Condensers
Site Preparation
Hot Gas
Line
Liquid
to extend 8" (203mm) above
coil base
Line
Fasten liquid and hot gas lines
to leg using flat surface clamps
with isolators (field-provided).
Support field piping separately
to avoid coil damage and loss
Inverted Traps (field-supplied)
of charge.
See Detail A-A
Metal clamp
Isolator
Detail A-A
Figure 9Piping connections for 6- and 8-fan Fan Speed Condensers
Access Valve (Hot Gas) on
Condensers (Typ. 2)
Entering
Hot Gas Line
Leaving
Liquid
Line
Position elbow
to direct relief
valve downward
DPN001067
Rev. 0
Inlet Connection
Upper Headers
(Typ.)
Fasten liquid and hot gas lines
to leg using flat surface clamps
with isolators (field-supplied).
Entering
Hot Gas
Line
Condenser
Connections,
Typical
Leaving
Liquid Line
Inverted traps (field-supplied)
to extend above base of coil by
a minimum of 7-1/2" (190mm).
Metal
Clamp
See
Detail
Isolator
A-A
Detail A-A
DPN000668
Rev. 01
9
Figure 10 Piping connections for 6- and 8-fan Lee-Temp and Quiet-Line Condensers
A
ccess Valve (Hot Gas) on
Condensers (Typ. 2)
Site Preparation
Inlet Connection
Upper Headers (Typ.)
Condenser
Connections,
Typical
Liquid
Line
Hot Gas Line
Inverted traps (field-supplied)
to extend above base of coil by
a minimum of 7-1/2" (190mm).
Entering Hot
Gas Line
Leaving
Liquid Line
Fasten liquid and hot gas lines
to leg using flat surface clamps
with isolators (field-supplied).
See
Detail
A-A
Metal
Clamp
Position elbow
to direct relief
valve downward
Note: Two circuits supplied; single circuit shown for clarity.
Isolator
Detail A-A
DPN000670
Rev. 01
10