D = DisconnectD= Disconnect
96E- = 8-ton Evaporator, 60 Hz
95E- = 8-ton Evaporator, 50 Hz95A = 8-ton Air-Cooled Centrifugal, 50 Hz
8TCD = 8-ton Chilled-Water w/ 2-way valve98W = 8-ton Water/Glycol-Cooled, 60 Hz
8TCT = 8-ton Chilled-Water w/ 3-way valve97W = 8-ton Water/Glycol, 50 Hz
A = 460V-3ph-60 Hz
B = 575V-3ph-60 Hz2 = 2-way Water/Glycol reg valve, 150 psi
C = 208V-3ph-60 Hz3 = 3-way, Water/Glycol reg valve, 150 psi
D =230V-3ph-60 HzD = 2-way, Water/Glycol reg valve, 350 psi
M = 380/415V-3ph-50 HzT = 3-way, Water/Glycol reg valve, 350 psi
0 = No Humidifier
H = HumidifierB = 575V-3ph-60 Hz
0 = No ReheatY = 208/230V-3ph-60 Hz
E= Electric ReheatM = 380/415-3ph-50 Hz
S = SCR Reheat
L = Low Fan Speed Drive, 2 hpH = Hot Gas Bypass
H = High Fan Speed Drive, 3 hp00 = Revision Level
0 = None
A = Filter Clog
B = Smoke Detector
C = FirestatPFProp Fan Condensing Unit
D = Filter Clog & Smoke DetectorHH = Hot Gas Bypass
E = Filter Clog & Firestat
F = Smoke Detector & Firestat095A = 8-ton Air-Cooled, 50 Hz
G = Filter Clog, Smoke Detector, & Firestat
D
96A
L
A
H
096A
-
A
LL = 95
00 = Revision Level
Indoor Condensing Units
MCD96ALA00 (example)
0 = No Disconnect
96A = 8-ton Air-Cooled Centrifugal, 60 Hz
L = Lee-temp Head Pressure Control (Air-Cooled)
A = 460V-3ph-60 Hz
0 = No Hot Gas Bypass
Prop Fan Condensing Units
PFC096A-AL0 (example)
096A = 8-ton Air-Cooled, 60 Hz
- = Standard Coil
C = Coated Coil
A = 460V-3ph-60 Hz
B = 575V-3ph-60 Hz
Y = 208/230V-3ph-60 Hz
M = 380/415V-3ph-50 Hz
°F Ambient, Lee-temp
Table iiiHeat rejection matchup – 60 Hz
Condensing Unit
Nominal
Capacity
8 TonsMMD96EMCD96APFC096AMCD98W
8 TonsMMD8TCChilled Water Unit
Cooling
Unit
Indoor Air-Cooled
Centrifugal Fan
Outdoor Air-Cooled
Propeller Fan
Water/Glycol
Table ivHeat rejection matchup – 50 Hz
Condensing Unit
Nominal
Capacity
8 Tons
Cooling
Unit
MMD95EMCD95APFC095AMCD97W
MMD8TCChilled Water Unit
Indoor Air-Cooled
Centrifugal Fan
Outdoor Air-Cooled
Propeller Fan
v
Indoor Remote
Water/Glycol Cooled
Indoor
vi
1.0PRODUCT FEATURES
1.1Standard Product Features
The Mini-Mate2 is a temperature/humidity control system designed to be installed above a ceiling
grid system. The unit is available as a split system evaporator to be matched with an Indoor Centrifugal Fan Condensing Unit, Outdoor Prop Fan Condensing Unit, or Indoor Water/Glycol Condensing
Unit. A self-contained Chilled Water Fan Coil is also available.
1.1.1Controls
The Mini-Mate2 system includes a wall-mounted display panel with a liquid crystal display (LCD)
screen and a 7 membrane keypad. The control is menu-driven for ease of use. Figure 24, Section 3,
depicts the complete menu tree for the control. All control setpoints and alarm setpoints are programmable.
1.1.2Evaporator System Components
DX Evaporator Section
The evaporator section includes the evaporator coil, thermostatic expansion valves, filter dryers, and
blower. The evaporator coil is constructed of copper tubes and aluminum fins and is designed for the
high sensible heat ratio required for electronic equipment. Room air circulation is accomplished by a
double inlet, belt driven centrifugal blower that has been dynamically balanced. The blower has selfaligning bearings. Both the blower and motor have permanently lubricated ball bearings.
Product Features
Chilled-Water Model
The Chilled-Water model is self-contained and is designed for use with an existing chilled-water loop.
It contains a chilled-water coil and a proportional modulating valve to control the flow of chilled
water.
1.1.3Condensing Unit Components
The condensing unit is connected to the evaporator unit by four refrigerant lines and low voltage control wires. The condensing unit requires a power source and a power disconnect switch. A single point
power kit is available for close coupled (attached) units.
Air-Cooled Condensing Unit (Indoor Centrifugal)
The Air-Cooled Condensing units (MC models) include: 3-ton and 5-ton scroll compressors with motor,
belt-driven centrifugal blower, crankcase heaters, high pressure switches, condenser coils, and LeeTemp head pressure control with receivers.
Air-Cooled Condensing Unit (Outdoor Prop Fan)
Outdoor Air-Cooled Condensing Units (PFC models) include: 3-ton and 5-ton scroll compressors with
crankcase heaters, high-pressure switch, condenser coils, direct-driven propeller fan, and Lee-Temp
head pressure control with receivers.
Water/Glycol Condensing Unit (Indoor)
The Water/Glycol-Cooled Condensing units include: 3-ton and 5-ton scroll compressors with crankcase heaters, high pressure switches, coaxial condensers, and regulating valves. Drycooler and pumps
are selected separately for glycol systems.
1
1.2Optional Equipment
1.2.1Canister Humidifier
The optional, factory-installed steam generating humidifier adds pure water vapor to the room air to
control humidity. Room humidity setpoints are established by the user. The humidifier components
include: a steam canister (replaceable), control board, inlet strainer, fill and drain valves.
1.2.2Electric Reheat
The 304/304 stainless steel electric reheat is energized when required to heat room air or to control
room temperature during dehumidification. A safety switch prevents the reheat from exceeding temperature limits.
1.2.3SCR Electric Reheat
The 304/304 stainless steel reheat is pulsed rapidly to provide precise temperature control, while cooling is locked on. A safety switch prevents the reheat from exceeding temperature limits.
1.2.4Hot Gas Bypass (Condensing Units)
This optional system bypasses compressor discharge around the condenser directly to suction to provide capacity control and reduce compressor cycling. System includes liquid injection valve to maintain proper suction superheat. Hot gas bypass is provided on both circuits.
1.2.5Free-Cooling Coil (GLYCOOL)
Product Features
When ambient temperatures are low enough, cold fluid is piped to a secondary coil or a separate
source of chilled-water may be piped to this coil.
1.2.6Smoke Detector
If smoke is detected in the return air, the unit display sounds an audible signal and the unit shuts
down.
1.2.7Firestat
When the return air temperature limit of approximately 125°F (51.7°C) is exceeded, the unit shuts
down.
1.2.8Filter Clog
If high pressure differential is detected across the return air filter, an adjustable pressure differential
switch sounds an audible signal.
2
1.3Ancillary (Ship Loose Accessories)
1.3.1Single Point Power Kit
A Single Point Power Kit allows the connection of a system (Evaporator and indoor condensing unit)
to a single power source when the units are close coupled. The kit includes a junction box with power
distribution, sub-fusing, and evaporator and condenser wiring.
1.3.2Refrigerant Line Sweat Adapter Kits
This kit includes the compatible fittings required (four suction and four liquid line connections) when
using field supplied interconnecting refrigerant piping.
1.3.3Return Air Filter Box with Duct Collar Kit
A return air filter box with duct flange, 4" (102 mm) filter, and a supply air duct flange are provided
for ducting the evaporator air.
1.3.4Condensate Pump Kit
A condensate pump is required when the evaporator is installed below the level of the gravity-fed
drain line. Components include: the pump; check valve; sump; level sensor; float switch; and controls.
Refer to detailed instructions and drawings supplied with the pump.
1.3.5Remote Monitoring and Control
Liebert can provide a variety of remote monitoring and control devices to enhance your Mini-Mate2
system. These include water detection, remote monitoring of a single unit, and remote control/monitoring of multiple units.
Product Features
1.3.6Remote Sensors
Remote temperature/humidity sensors can be mounted in the controlled space or in duct work and
includes 30 feet of control cable.
3
2.0SITE PREPARATIONAND INSTALLATION
NOTE
Before installing unit, determine whether any building alterations are required to run piping,
wiring, and duct work. Carefully follow all unit dimensional drawings and refer to the
submittal engineering dimensional drawings of individual units for proper clearances.
2.1Installation Considerations
The evaporator unit is usually mounted above the suspended ceiling using field supplied threaded
rods. Refer to Figure 1 for possible configurations. The condensing unit may be:
• Indoor Air-Cooled Centrifugal Fan Condensing Unit mounted remotely or close coupled to the
evaporator in the ceiling space.
• Outdoor Air-Cooled Propeller Fan Condensing Unit.
• Indoor Water/Glycol-Cooled Condensing Unit, mounted remotely or close coupled to the evaporator.
Table 1Application limits, evaporator and chilled-water units*
Input VoltageRange of Return Air Conditions to Unit
MinMaxDry Bulb Temp. Relative Humidity
-5%+10%
*Unit will operate at these conditions but will not control to these extremes.
65°F to 85°F
°C to 29°C)
(18
20% to 80%
Site Preparation and Installation
Table 2Application limits, indoor and outdoor air-cooled condensing units
Input
Voltage
MinMaxMinMax
Outdoor Prop Fan Condensing Unit
-5%+10%
Indoor Air-Cooled Centrifugal Condensing Unit
Table 3Application limits, indoor water/glycol-cooled condensing units
Input VoltageEntering Fluid Temperature
MinMaxMinMax
-5%+10%65°F (18.3°C) *115°F (46°C)
*Operation below 65°F (18°C) may result in reduced valve life and fluid noise.
2.1.1Room Preparation
The room should be well-insulated and must have a sealed vapor barrier. The vapor barrier in the
ceiling and walls can be a polyethylene film. Paint on concrete walls and floors should be vapor resistant.
NOTE
The single most important requirement for maintaining environmental control in the
conditioned room is the vapor barrier.
Condensing UnitsEntering Dry Bulb
Air Temperature
°F (-34°C)
-30
°F (-29°C)
-20
120
°F (49°C)
°F (46°C)
115
Outside or fresh air should be kept to a minimum when tight temperature and humidity control is
required. Outside air adds to the cooling, heating, dehumidifying and humidifying loads of the site.
Doors should be properly sealed to minimize leaks and should not contain ventilation grilles.
4
2.1.2Location Considerations
CAUTION
!
Units contain water. Water leaks can cause damage to sensitive equipment below. DO NOT
MOUNT UNITS OVER SENSITIVE EQUIPMENT. A field-supplied pan with drain must be
installed beneath cooling units and water/glycol-cooled condensing unit.
NOTE
Do not mount units in areas where normal unit operating sound may disturb the working
environment.
Locate the evaporator unit over an unobstructed floor space if possible. This will allow easy access for
routine maintenance or service. Do not attach additional devices to the exterior of the cabinet, as they
could interfere with maintenance or service.
Site Preparation and Installation
5
Figure 1System configurations—air cooled systems
Site Preparation and Installation
Evaporator
Prop Fan
Condensing Unit
Evaporator
Figure 2System Configurations—water/glycol systems
Cooling
Tower
Centrifugal Fan
Condensing Unit
Evaporator
Condensing Unit
Water/Glycol
WATER-COOLED SYSTEMS
GLYCOL-COOLED SYSTEMS
Drycooler
Evaporator
Water/Glycol
Condensing Unit
6
Figure 3System Configurations—chilled water systems
Evaporator
CHILLED-WATER SYSTEMS
Condensate Pump
Site Preparation and Installation
COUPLED COMPONENTS
(AIR-COOLED SYSTEM
Evaporator
Condensing
Unit
2.2System Weights
Table 4Unit weights
Cooling Units* lbskg
MMD96E665302
MMD95E665302
Condensing Unitslbskg
MCD96A530241
MCD95A530241
MCD98W470213
MCD97W470213
*Add 40 lbs. (20 kg.) to units with free cooling or hot water reheat coils.
2.3Equipment Inspection upon receipt
When the unit arrives, do not uncrate equipment until it is close to its final location. All required
assemblies are banded and shipped in corrugated containers. If you discover any damage when you
uncrate the unit, report it to the shipper immediately. If you later find any concealed damage, report
it to the shipper and to your Liebert supplier.
Condensate Pump
7
2.4Installing the Evaporator or Chilled-Water Units
WARNING
!
Be sure the supporting roof structure is capable of supporting the weight of the unit(s) and the
accessories during installation and service. (See 2.2 - System Weights.)
Be sure to securely anchor the top ends of the suspension rods. Make sure all nuts are tight.
The evaporator unit and indoor condensing unit are usually mounted above the ceiling and must be
securely mounted to the roof structure. The ceiling and ceiling supports of existing buildings may
require reinforcements. Be sure to follow all applicable codes. Use field-supplied 1/2"-13 tpi threaded
suspension rods and 1/2"-13 tpi hardware kit.
Recommended clearance between ceiling grids and building structural members is unit height plus 3
inches.
Install the four field-supplied rods by suspending them from suitable building structural members.
Locate the rods so that they will align with the four mounting holes in the flanges that are part of the
unit base.
Using a suitable lifting device, raise the unit up and pass the threaded rods through the four mounting holes in the flanges that are part of the unit base.
Attach the threaded rods to the unit flanges using the supplied, springs, and washers. (See Figure 4).
The coil springs provide vibration isolation.
Site Preparation and Installation
1. Use the plain nuts to hold unit in place. Adjust these nuts so that the weight of the unit is
supported by the four rods, does not rest on the ceiling grid, and is level. Ensure none of the
springs are compressed to solid height. The coil side of the unit is heavier, so these springs will be
compressed more than the other side.
NOTE
The units must be level in order to drain condensate properly.
2. Use the Nylock nuts to “jam” the plain nuts.
Figure 4Threaded rod and hardware kit installation
1" O.D. spring
1/2" flat washer
1/2" Nylock
locking nut
1/2" threaded rod
(supplied by field)
hanging bracket
base pan (ref)
1/2" hex nut
8
2.4.1Close Coupled Installations
If the evaporator and condensing units are to be mounted side-to-side (close coupled), hang each unit
before connecting them together (See Figure 5). If Single Point Power Kit is used, install the box into the
evaporator prior to suspending the units. Route power wire flex conduit into condensing unit as units are
suspended. Refer to instructions supplied with kit for details. Align bolt holes in the condensing unit and
in the evaporator. Insert rubber spacers and secure four (4) sets of hardware provided. Align the refrigerant connections and tighten them as described in 2.4.3 - Piping Connections and Coolant Require-ments. Remove “P” clamps from piping to aid fitting alignment.
Figure 5Close coupled installation
Evaporator
Site Preparation and Installation
Condensing
Unit
Isolator rubber
5/16" lock washer
5/16" capscrew
Cage
nut
NOTE: Disconnect P-clamps on lines in the evaporator
for easy close coupling.
P-clamps are for shipping purposes only.
5/16" flat washer
9
2.4.2Evaporator Air Distribution
Filter Box
The optional filter box mounts directly to the return air opening of the evaporator. The filter box is
supplied with two (2) 20% (Liebert part no. A-0320) or 30% (Liebert part no. A-0400) 25" x 20" x 4" filters.
NOTE
Do not operate the unit without filters installed in return air system.
Connections for Ducted Systems
Use flexible duct work or non-flammable cloth collars to attach duct work to the unit and to help control the transmission of vibrations to building structures. Insulation of duct work is vital to prevent
condensation during the cooling cycle. The use of a vapor barrier is required to prevent absorption of
moisture from the surrounding air into the insulation.
If the return air duct is short, or if noise is likely to be a problem, sound-absorbing insulation should
be used on the duct. Duct work should be fabricated and installed in accordance with local and
national codes.
If free-cooling or hot water coil is ordered, reduce available external static
pressure by 0.3" (8 mm). Contact Liebert Representative for other Air Volumes.
Factory setting is 0.5" (13 mm) with 2 hp motor. Field adjust to suit application.
RPM
External
Static, in.RPM
External
Static, in.
Site Preparation and Installation
NOTE
Maximum return air static pressure should not exceed 0.3" (8 mm) to provide proper drainage
of the unit.
10
2.4.3Piping Connections and Coolant Requirements
Drain Line
CAUTION
!
The drain line must not be trapped outside the unit, or water may back-up in drain pan.
Drain is internally trapped.
This line may contain boiling water. Use copper or other suitable material for the drain line.
Sagging condensate drain lines may inadvertently create an external trap.
A 3/4 in. (19.1 mm) female pipe thread (FPT) connection is provided for the evaporator coil condensate
drain. This line also drains the humidifier, if applicable. The drain line must be located so it will not
be exposed to freezing temperatures. The drain should be the full size of the drain connection.
The evaporator drain pan includes a float switch to prevent unit operation if drain becomes blocked.
Figure 6Drain installation
Site Preparation and Installation
Unit
Continuous slope
away from unit
Unit
Do not externally
trap the unit
IncorrectCorrect
Unit
These are external traps also, although
unintentional. Lines must be rigid
enough to not bow between supports.
Humidifier drain water can approach
100° Celsius.
Incorrect
11
Condensate Pump
The optional condensate pump kit is required when the evaporator is installed below the level of the
gravity-fed drain line. Refer to the installation instructions provided with the condensate pump kit.
Figure 7Condensate pump installation
Drain Line
(field supplied)
Condensate Pump
AIR INLET
Site Preparation and Installation
3/8" Compression Fitting
Drain Connection
Power Supply from
Electric Service Power
Block in Fan/Coil Module.
Evaporator or
Chilled Water
Unit
10 9/16 "
(268.3mm)
Condensate
Pump
Support Bracke
6 5/8 "
(168.3mm)
t
3/4" (13mm)
Supplied on Pump Tank
Hose Barb
Notes:
1. 3/4" (13mm) Flexible Rubber Tubing Assembly (Supplied
with Pump Kit) must be installed on pump end.
2. The High Water Safety Float included with pump must be
interlocked with unit control. Wire to terminals 60 & 61 on
Evaporator terminal strip to shut down unit.
Humidifier Water Supply Line
21 1/2 "
(546mm)
FRONT OF UNIT
Condensate Drain
3/4" (13mm) FPT
Customer Connection
Flexible Rubber Tubing
DPN000239_Rev0
Units supplied with the optional humidifier package have a 1/4 in. (6.4 mm) FPT connection for water
inlet. Supply pressure range is 10 psig to 150 psig. Required flow rate is 1 gpm. A shut-off valve
should be installed in this line to isolate the humidifier for maintenance.
NOTE
DO NOT route humidifier supply line in front of filter box access panel.
12
Chilled-Water Piping—Chilled-water Systems Only
Refer to Figure 8 for recommended field installed hardware such as shut-off valves and hose bibs.
Chilled-water supply and return lines must be insulated to prevent condensation.
The minimum recommended water temperature is 42°F. Connection sizes are 1-1/4" FPT.
Figure 8General arrangement diagram - chilled-water systems
Bleed Valve
d
Chille
Water
Supply
Chilled
Water
rn
Retu
** Shutoff Valves
Female Adapters
Chilled Water
Control Valve
Site Preparation and Installation
Chilled Water Coil
** Hose Bibs
* Field piping refers to the use of hard
piping using sweat adapter kit
or precharged line set.
** Component
Liebert but are recommended for
proper circuit operation and
maintenance.
s are not supplied by
Suppl
Return
y
3 - Way Chilled Water
Control Valve
(Optional)
FIELD PIPING
FACTORY PIPING
DPN000236_Rev0
13
Site Preparation and Installation
Refrigerant (R-22) Piping
All split systems require two sets of refrigerant lines (two insulated copper suction lines and two copper liquid lines) between the evaporator and the condensing unit.
Two possible methods exist for installing the copper suction and liquid lines.
• Close coupling the units together using the quick connects.
• Using an optional Sweat Adapter Kit and hard piping between the two units.
All refrigeration piping should be installed with high temperature brazed joints. Prevailing good refrigeration practices should be employed for piping supports, leak testing, evacuation, dehydration, and
charging of the refrigeration circuits. The refrigeration piping should be isolated from the building by
the use of vibration isolating supports. To prevent tube damage when sealing openings in walls and to
reduce vibration transmission, use a soft flexible material to pack around the tubes.
When installing remote condensing units above the evaporator, the suction gas line should be trapped
at the evaporator. This trap will retain refrigerant oil in the off cycle. When the unit starts, oil in the
trap is carried up the vertical riser and returns to the compressor.
Table 6Recommended refrigerant line sizes
Equivalent
FeetCircuitLiquid Line
50 feet3-ton3/8" O.D.7/8" O.D.
100 feet3-ton1/2" O.D.7/8" O.D
150 feet3-ton5/8" O.D.1-1/8" O.D
50 feet5-ton1/2" O.D.1-1/8" O.D
100 feet5-ton5/8" O.D.1-1/8" O.D
150 feet5-ton5/8" O.D.1-3/8" O.D
Consult your Liebert representative for longer line lengths.
Suction
Line
NOTE
If field supplied refrigerant piping is installed, refrigerant (R-22) must be
added to the system.
Figure 9Refrigerant piping diagram
Evaporator
Suction Line Piping
Condensing Unit Below Evaporator
Evaporator
Pitch down 1/2" per 10 feet
NOTE: When installing remote condensing
units below the evaporator, the suction gas
line should be trapped with an inverted trap
to the height of the evaporator. This
prevents refrigerant migration to the
compressors during off cycles. Maximum
recommended vertical drop to condensing
unit is 20 feet (6.1 m).
Condensing Unit
Condensing Unit
Suction Line Piping
Condensing Unit Above Evaporator
Traps recommended every 25 feet (7.6 m) of vertical rise.
14
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.