This document provides all the necessary information to operate and maintain a Helios DC Sys-
tem 4000/48 power system.
The installation procedures for the Helios DC System 4000/48 power system are covered in instal-
lation manual SL-60034.
1.2Applicability of This Document
This document applies to Helios DC System 4000/48 power systems having any configuration of
equipment.
About This Document 1
2.0I
NTRODUCTION
2.1Description
The Helios DC System 4000/48 is a positive ground, -48 V DC nominal power system consisting of
one control and distribution cabinet and one or more rectifier cabinets. It is available in capacities
of 1500, 3000, 4000 and 6000 A. Auxiliary distribution cabinets can be added as required for additional distribution. Remote monitoring, temperature compensation and battery disconnect
options are also available. The 1500, 3000 and 4000 A versions use internal -48 V bussing and
external BR+ bussing, while the 6000 A version uses overhead bussing.
bottom fed 4000 A system, while
Figure 1Front view of a typical bottom fed 4000 A Helios DC System 4000/48 power system
Figure 2
shows a typical 6000 A system.
Figure 1
shows a typical
1200 A rectifier cabinets
Main cabinet
Aux dist. cabinet
2 Introduction
Figure 2Front view of a typical 6000 A Helios DC System 4000/48 power system
Aux dist. cabinetsMain cabinet
Cables are used for inter-cabinet connections (1500, 3000 and 6000 A systems) or connections to
the overhead busbars (6000 A system) for ease of expansion on live systems. In a 1500, 3000 or
4000 A systems, the power system battery return (BR) busbar is mounted externally from the cab-
inet to facilitate the connections of the battery return cables. In a 6000 A system, a separate BR
busbar dedicated to the battery returns for the loads is mounted externally from the overhead
busbar duct to facilitate the connections of the load battery return cables.
The Helios DC System 4000/48 provides a variety of monitoring and alarm features, such as high/
low float and high/low voltage alarm, high voltage shutdown, fuse and breaker alarm and rectifier
failure alarms.
The Helios DC System 4000/48 uses Helios Rectifiers 200I/48, Helios Rectifiers 200E/48 or Helios
Rectifiers 100/48 connected in parallel as building blocks to reach the maximum capacities. The
Helios Rectifiers 200I/48 operate from a 380 V to 415 V three phase, 50 or 60 Hz AC source. The
Helios Rectifiers 200I/48 operate from a 480 V three phase, 50 or 60 Hz AC source. The Helios
Rectifiers 100/operate from a 208 V to 240 V single phase, 50 or 60 Hz AC source.
The 1200 A rectifier cabinet accepts up to six Helios Rectifiers 200I/48 or 200E/48, while the 1000
A rectifier cabinet accepts up to 10 Helios Rectifiers 100/48.
The control and distribution cabinet and the auxiliary distribution cabinets are available with
distribution busbar risers of 2000 A or 3000 A capacity.
The cabinets are seismic qualified to zone 4 (Bellcore) when anchored to a concrete floor whose
compressive strength is at least 2.11 kg/mm
The cabinets are seismic qualified to zone 2 without the seismic kit.
2
(3000 psi) and when equipped with a seismic kit.
1200 A rectifier cabinets
The cabinets are equipped with a ventilated, lockable door, a ventilated top cover and two rear
ventilated panels.
In many applications, such as with DMS, a consistent single-point ground (SPG) topology must be
maintained for all associated equipment. The Helios DC System 4000/48 complies with this
requirements for single-point grounding (the isolation kit is required).
2.2Applications
The Helios DC System 4000/48 is designed to operate with DMS systems or any other telecommu-
nication systems whose input is nominal -48 V DC and whose current requirements do not exceed
6000 A capacity.
Introduction 3
2.3Control and Distribution Cabinets - Typical Configurations
Figure 3
DC System 4000/48 (bottom cabled cabinets are illustrated - top cabled versions are available).
Figure 3Typical configurations for Helios DC System 4000/48 control, distribution and rectifier
shows the front and side views of typical rectifier and distribution cabinets for a Helios
cabinets
Control and Distribution cabinet 1200A Rectifier cabinet
4 Introduction
Cabinets are available in a variety of configurations as listed in the following tables. Note that for
a 6000 A system, the cabling is always at the top.
Table 1Rectifier cabinets
Rectifier
Cabinet Capacity
1200 AHelios Rectifier 200I6Top
1200 AHelios Rectifier 200I6Bottom
1000 AHelios Rectifier 100/4810Top or bottom
1200 AHelios Rectifier 200E6Top
1200 AHelios Rectifier 200E6Bottom
1200 AHelios Rectifier 200E6Top
1200 AHelios Rectifier 200E6Bottom
Cabled top or bottomTypeQty
Table 2Control and distribution cabinets
Nominal cabinet capacityShunt capacityRiser busbar capacityCabled top or bottom
1500 A2500 A2000 ATop
3000 A4000 A3000 ATop
4000 A5000 A3000 ATop
1500 A2500 A2000 ABottom
3000 A4000 A3000 ABottom
4000 A5000 A3000 ABottom
For a 6000 A system, the charge busbars and the shunt are mounted externally from the control and distribution cabinet.
Table 3Auxiliary distribution cabinets
Nominal cabinet capacityTop busbar capacityRiser busbar capacityCabled top or bottom
2000 A3000 A2000 ATop
2000 A3000 A2000 ABottom
3000 A4000 A3000 ATop
3000 A4000 A3000 ABottom
Introduction 5
3.0S
PECIFICATIONS
3.1Framework
The Helios DC System 4000/48 uses cabinet type frameworks. The same cabinet design is used for
the main control and distribution cabinet, the auxiliary distribution cabinets and the rectifier cabinets. The cabinet is always equipped with a front door and door frame (lockable, equipped with
ground straps, and easily removable for installation or maintenance access), a ventilated top
cover made of non-flammable plastic, and two ventilated rear cover panels (equipped with ground
strap and easily removable for installation and maintenance access). Bussing and equipment
(controller, rectifiers, distribution panels, etc.) are added as required, depending on the use of the
cabinet. Seismic bracing is also available as options.
When using the Cable Trough, overhead cabling cannot enter from the front or rear of the system.
It must be confined to the system foot print and enter at the ends of the lineup.
The cabinets may be either top or bottom cabled as determined by the location of the bussing.
3.1.1Mechanical Specifications of a Cabinet
The mechanical specifications of an empty cabinet are listed in
Table 4Mechanical specifications of the cabinet (empty)
Framework typeHeightDepthWidthWeight
Cabinet2134 mm
Refer to
Figure 3
(84.0 in.)
for typical views of cabinets.
600 mm
(23.6 in.)
3.1.2Electrical Specifications of the Cabinets
The electrical specifications of equipped cabinets are as follows:
• The main control and distribution cabinet for a 1500 A system has a 2000 A busbar riser and
a common equipment panel e/w one 1500 A CHG and DISCH busbar and a 2500 A system
shunt.
• The main control and distribution cabinet for a 3000A system has a 3000 A busbar riser and a
common equipment panel e/w two 1500 A CHG and DISCH busbars and a 4000 A system
shunt.
• The main control and distribution cabinet for a 4000A system has a 3000 A busbar riser and a
common equipment panel e/w three 1500 A CHG and DISCH busbars and a 5000 A system
shunt.
• A 6000 A system has a 3000 A busbar riser in the main control and distribution cabinet (the
CHG and DISCH busbar and the shunt are external).
• The auxiliary distribution cabinet is available with a 2000 or 3000 A busbar riser.
• A 1200 A rectifier cabinet has 1500 A busbar risers for the DC output of the rectifiers.
600 mm
(23.6 in.)
Table 4.
114 kg
(251 lb)
6 Specifications
3.2Conventional Controller
3.2.1Mechanical Specifications of the Conventional Controller
The mechanical specifications of the Conventional Controller are listed in
Table 5Mechanical specifications of the Conventional Controller
FigureHeightDepthWidthWeight
Figure 4
152 mm
(6.0 in.)
76 mm
(3.0 in.)
584 mm
(23 in.)
Figure 4Front view of the Conventional Controller
3.2.2Electrical Specifications of the Conventional Controller
The operating voltage is -48 V DC. Refer to the
listed in
6.0 - Reference Documents
for a detailed list of specifications, operating parameters
and features of the Conventional Controller.
4.0 - Operation
Table 5.
4.5 kg
(10 lb)
and the appropriate user manual
Specifications 7
3.3Distribution Panels
3.3.1Fuse Panels
Mechanical specifications of the fuse panels
The mechanical specifications of the fuse panels are listed in
Table 6
below.
Table 6Mechanical specifications of the fuse panels
Panel descriptionFigureHeightWidthWeight
(20) QFF 0-5 A
60 A max
(16) QFF 0-5 A &
(12) ABS 5-30 A
300 A max
(16) QFF 0-5 A &
(6) TPN 5-30 A
250 A max
(8) TPN 5-30 A
250 A max
(4) RS100P 70-100 A
300 A max
(4) CRS200P 150-200 A
600 A max
(4) CRS200P 150-200 A
(w/load shunts)
600 A max
(4) TPL 225-600 A
1600 A max
(18) TPS 1-70 A
600 A max
An alarm circuit pack with an alarm indication LED is standard on all panels
Note 1:
(4) CRS200P 150-200 A (w/load shunts) is equipped with four shunts.
Note 2:
Figure 5
Figure 6
Figure 7
Figure 8
Figure 9
Figure 10
Figure 10
Figure 11
Figure 12
76.2 mm
(3.0 in.)
76.2 mm
(3.0 in.)
152.4 mm
(6.0 in.)
152.4 mm
(6.0 in.)
152.4 mm
(6.0 in.)
228.6 mm
(9.0 in.)
228.6 mm
(9.0 in.)
304.8 mm
(12.0 in.)
178 mm
(7.0 in.)
584 mm
(23.0 in.)
584 mm
(23.0 in.)
584 mm
(23.0 in.)
584 mm
(23.0 in.)
584 mm
(23.0 in.)
584 mm
(23.0 in.)
584 mm
(23.0 in.)
584 mm
(23.0 in.)
584 mm
(23.0 in.)
3 kg
(6.6 lb)
5 kg
(11.0 lb)
7 kg
(15.4 lb)
7 kg
(15.4 lb)
8 kg
(17.8 lb)
22 kg
(48.4 lb)
24 kg
(52.9 lb)
32 kg
(70.4 lb)
35 kg
(77.0 lb)
Figure 5Front view of the 20 QFF 0-5 A fuse panels
FA
The DC output connections are wire wrap or solder.
Table 7Fuse sizes available for the (20) QFF 0-5 A fuse panels
Fuse typeCurrent (A)CPC
QFF1A1.333A0205202
QFF1B2A0205203
QFF1C3A0205204
QFF1D5A0205205
QFF1E0.18A0205206
QFF1F0.25A0205207
QFF1G0.5A0205208
QFF1H0.75A0205209
QFF3ADUMMYA0205210
8 Specifications
Figure 6Front view of the (16) QFF 0-5 A & (12) ABS 5-30 A fuse panels
FA
-48 V
The DC output connections are No. 8-32 studs equipped with two hex nuts.
Table 8Fuse sizes available for the (16) QFF 0-5 A & (12) ABS 5-30 A fuse panels
Fuse typeCurrent (A)CPC
5A0327000
8A0111415
10A0315462
4AB (ABS)
QFF1A1.333A0205202
QFF1B2A0205203
QFF1C3A0205204
QFF1D5A0205205
QFF1E0.18A0205206
QFF1F0.25A0205207
QFF1G0.5A0205208
QFF1H0.75A0205209
QFF3ADUMMYA0205210
12A0267003
15A0344157
20A0314873
25A0243206
30A0328460
Figure 7Front view of the (16) QFF 0-5 A & (6) TPN 5-30 A fuse panels
FA
ALM 1/2 A
-48 V
The DC output connections are 0.250-20 studs equipped with two hex nuts.
Table 9Fuse sizes available for the (16) QFF 0-5 A & (6) TPN 5-30 A fuse panels
Fuse typeCurrent (A)CPC
1A0380108
3A0380109
6A0380111
DC power (TPN)
10A0380112
15A0380113
20A0380147
25A0380148
30A0380149
Specifications 9
Figure 8Front view of the (8) TPN 5-30 A fuse panels
FA
ALM 1/2 A
-48 V
The DC output connections are 0.250-20 studs equipped with two hex nuts.
Table 10Fuse sizes available for the (8) TPN 5-30 A fuse panels
Fuse typeCurrent (A)CPC
35A0380150
40A0380151
DC power (TPN)
45A0380152
50A0380114
60A0380115
Figure 9Front view of the (4) RS100P 70-100 A fuse panels
-48 V
FA
ALM
(1) (2) (3) (4)
(1)
(2)(3)(4)
The DC output connections are 0.375-16 studs equipped with two hex nuts.
Table 11Fuse sizes available for the (4) RS100P 70-100 A fuse panels
Fuse typeCurrent (A)CPC
70A0722046
HRC1-K
80A0722045
90A0722044
100A0722049
10 Specifications
Figure 10 Front view of the (4) CRS200P 150-200 A / (4) CRS200P 150-200 A (w/load shunts) fuse panels
ALM
FA
(1)
(2)
(2)
(3)
(4)(1)
(3)
ALM
(4)
The DC output connections are 0.50-13 studs equipped with two hex nuts.
Table 12Fuse sizes available for the (4) CRS200P 150-200 A/(4) CRS200P 150-200 A (w/load
shunts) fuse panels
Fuse typeCurrent (A)CPC
110A0329697
125A0329696
HRC1-J
150A0722041
175A0722038
200A0614832
Figure 11 Front view of the (4) TPL 225-600 A fuse panels
-48 V
(2)
ALM
(1)
(2)
(1)
FA
The DC output connections are busbar angles that can accept 535MCM or 750MCM cables, or the
metric equivalent. The lugs must be for two 1/2” dia. bolts at 1-3/4” c-c.
Table 13Fuse sizes available for the (4) TPL 225-600 A fuse panels
Fuse typeCurrent (A)CPC
225A0380138
300A0380140
DC power (TPL)
400A0380141
500A0380142
600A0380143
(3)
(4)
(3)
ALM
(4)
Specifications 11
Figure 12 Front view of the (18) TPS 1-70 A fuse panel
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 UNIT
FA
FUSE PANEL NT6C 21XX
MAX FUSE 70A
AMPS
LOAD
600 A MAX PANEL CAPACITY
Can accept maximum 1/0 AWG cables and requires one-hole lugs for 1/4” diameter studs.
Table 14Fuse sizes available for the (18) TPS 1-70 A fuse panel
Fuse typeCurrent (A)CPC
1A0601322
3A0601323
5A0601325
6A0601326
10A0601327
DC power (TPS)
15A0601328
25A0601330
30A0601331
40A0601332
50A0601333
60A0601334
70A0601335
12 Specifications