Liebert 308 415, 510 616 830 User Manual

Page 1
Liebert® Air Cooled, Direct Drive Condensers
Installation, Operation and Maintenance Manual - 50/60Hz
Precision Cooling For Business-Critical Continuity™
Page 2
Figure i Product model nomenclature
Example: DCDF165-Y
D = Disconnect Switch
(optional on Fan Speed Control, Chiller & Standard Lee-Temp Condensers; standard on Quiet-Line and VFD Control condensers
T = TVSS & Disconnect
Switch; available only on the VFD Control condensers
NOT ALL POSSIBLE COMBINATIONS OF MODELS, CONTROLS AND VOLTAGES ARE AVAILABLE.
C
Condenser
F
F = Fan Speed Control L = Main Control / Lee-Temp C = No Control / Chiller
Lee-Temp
T = Ambient Fan Cycle/
Lee-Temp
V = Variable Frequency
Drive (VFD) Control (available only for dual refrigerant circuit condensers
S = Single Refrigerant Circuit D = Dual Refrigerant Circuit
*
Reserved
Model Size
* Single-phase voltage is only voltage available as standard
on Fan Speed Control 1-fan condensers
* Three-phase voltage is only voltage available as standard
on condensers with VFD Control, Lee-temp receivers, and Fan Speed Control (2-8 fan models only).
* VFD Control Condensers are not available in 575-3-60.
P = 208/230V-1ph-60Hz Z = 460V-1ph-60Hz V = 575V-1ph-60Hz W = 200/230V-1ph-50Hz Y = 208/230V-3ph-60Hz A = 460V-3ph-60Hz B = 575V-3ph-60Hz N = 200/230V-3ph-50Hz M = 380/415V-3ph-50Hz
Page 3
TABLE OF CONTENTS
1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1 Product Description and Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Head Pressure Control Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2.1 Fan Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2.2 Variable Frequency Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2.3 Liebert Lee-Temp
1.3 Sound Level Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3.1 Standard Condenser. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3.2 Quiet-Line Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.4 Transient Voltage Surge Suppression Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.5 Typical System Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.0 SITE PREPARATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.1 Site Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Refrigerant Planning Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.0 INSPECTION AND INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
3.1 Equipment Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1.1 Packing Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2 Handling Unit on the Skid. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.3 Unpacking the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.4 Preparing a 1-, 2-, 3- or 4-Fan Condenser for Moving and Installation . . . . . . . . . . . . . . . . 15
3.4.1 Removing the Skid and Attaching Slings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.5 Preparing a 6-Fan or 8-Fan Condenser for Moving and Installation . . . . . . . . . . . . . . . . . . 16
3.5.1 Removing the Skid and Attaching Slings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.5.2 Mounting the Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.6 Electrical Supply Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.6.1 Line Voltage Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.6.2 Low Voltage Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.6.3 Low Voltage Monitoring Wiring—TCDV Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.7 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.7.1 VFD Control Condensers (TCDV) only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.7.2 Wye-Connected Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.7.3 Delta-Connected Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.8 Electrical Field Connection Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.9 Refrigeration Piping Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.9.1 Piping Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.9.2 Field Piping Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.10 System Dehydration/Leak Test and Charging Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Refrigerant Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
4.0 CHECKLIST FOR COMPLETED INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
4.1 Moving and Placing Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.2 Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.3 Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
i
Page 4
4.4 Other . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.0 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
5.1 Startup Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.2 Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6.0 SYSTEM MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
6.1 General Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
6.2 Special Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6.2.1 Condenser Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6.2.2 Maintenance Inspection Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
FIGURES
Figure i Product model nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Inside Front Cover
Figure 1 Liebert two-fan condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Figure 2 Typical system configuration—indoor unit and outdoor condenser and field piping . . . . . . . . . . . 3
Figure 3 Condenser planning dimensional data—One-fan and two-fan units. . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 4 Condenser planning dimensional data—Three-fan and four-fan units . . . . . . . . . . . . . . . . . . . . . . 6
Figure 5 Condenser planning dimensional data—Six- and eight-fan units . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 6 Typical condenser footprint—dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 7 Piping connection locations for 1-, 2-, 3- and 4-fan VFD Control and Fan Speed Condensers . . . 8
Figure 8 Piping connections for 1-, 2-, 3- and 4-fan Lee-Temp and Quiet-Line Condensers . . . . . . . . . . . . . 9
Figure 9 Piping connections for 6- and 8-fan Fan Speed Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 10 Piping connections for 6- and 8-fan Lee-Temp and Quiet-Line Condensers . . . . . . . . . . . . . . . . . 10
Figure 11 Equipment recommended for handling a Liebert condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 12 Removing shipping crate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 13 Attaching legs and sling to a 1-, 2-, 3- or 4-fan condenser for moving . . . . . . . . . . . . . . . . . . . . . . 15
Figure 14 Attaching legs to a 6-fan or 8-fan unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 15 Attaching sling to a 6-fan or 8-fan unit for moving. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 16 Wye-connected power diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 17 Delta-connected power diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 18 Disconnecting EMC filter for operation with Delta-connected power . . . . . . . . . . . . . . . . . . . . . . 22
Figure 19 Electrical field connections for Fan Speed Control Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 20 Electrical field connections for VFD control condensers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 21 Electrical field connections for Liebert Lee-Temp control condensers. . . . . . . . . . . . . . . . . . . . . . 25
Figure 22 VFD and Fan Speed Control condenser piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 23 Lee-Temp head pressure control condenser piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 24 General arrangement—Air cooled models with Lee-Temp control . . . . . . . . . . . . . . . . . . . . . . . . 29
TABLES
Table 1 Condenser shipping weights, dimensions and volume, approximate . . . . . . . . . . . . . . . . . . . . . . . 4
Table 2 Condenser physical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Table 3 R-22 and R-407C refrigerant required, approximate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Table 4 Interconnecting piping refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Table 5 60Hz condenser data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 6 60Hz condenser data, Quiet-Line (Lee-Temp controlled/fan-cycling) . . . . . . . . . . . . . . . . . . . . . . 19
Table 7 50Hz condenser full load amp values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 8 Lee-Temp receiver electrical data, 50Hz and 60Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 9 Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
ii
Page 5

1.0 INTRODUCTION

1.1 Product Description and Features

The Liebert condenser is low-profile direct-drive propeller fan-type air cooled unit suitable for mount­ing outdoors. It provides for the heat rejection of either one or two separate refrigeration circuits, matching heat rejection capacity varying with the outdoor ambient temperatures with each corre­sponding compressors heat rejection requirements. Constructed with an aluminum cabinet and a cop­per-tube aluminum fin coil, the unit is quiet and corrosion resistant. The condenser is quickly and easily installed, because all internal wiring is completed at the factory with only electrical connec­tions to be made at the job site. All electrical connections and controls are enclosed in an integral weatherproof section of the condenser.

Figure 1 Liebert two-fan condenser

Introduction

1.2 Head Pressure Control Types

1.2.1 Fan Speed

Fan speed control utilizes a wave-chopper control to vary the air volume over the condenser coil, based on refrigerant head pressure. The fan motor next to the electrical panel (two fans on 6-fan and 8-fan models) is a single-phase, permanent split capacitor motor with motor speed adjusted in response to refrigerant pressure. The balance of fans on multi-fan units cycle on ambient thermostats. The control system provides refrigerant head pressure control for outdoor ambients as low as
-20°F (-28.9 °C).

1.2.2 Variable Frequency Drive

VFD Condenser control system utilizes a variable frequency drive, inverter duty fan motor operating from 0% to 100% motor RPM based on head pressure, sensed by refrigerant pressure transducers. VFD, ambient-temperature thermostat(s), motor overload protection and electrical control circuit are factory-wired in the integral control panel. VFD controls the fan adjacent to the connection end of the condenser and remains energized with active compressor operation. The balance of fans on multi-fan units cycle on ambient thermostats. This system provides refrigerant head pressure control for out­door ambients as low as -20°F (-28.9°C).
1
Page 6

1.2.3 Liebert Lee-Temp™ Refrigerant Control

The Liebert Lee-Temp head pressure control system is designed to maintain proper operating head pressures in outdoor temperatures down to -30°F (-34.4°C). The condensers utilize head pressure con­trol valves, extra refrigerant and insulated refrigerant receivers with heater pads. It works by flood­ing the condenser coil with liquid refrigerant to a level that balances the system condensing requirements with the condenser coil surface available to reject the system heat. During the summer, the system requires the entire condenser coil surface for heat rejection and most of the refrigerant is stored in a receiver. In the winter, the same amount of heat can be rejected by only a fraction of the coil surface. As head pressure begins to fall, the control valve restricts the flow of liquid refrigerant exiting from the condenser. This extra liquid refrigerant reduces the effective condenser surface area available for heat transfer. The head pressure control valve also bypasses hot gas into the receiver to warm the liquid and maintain liquid pressure for proper operation of the expansion valve. Condenser fan controls are either fan cycling on ambient temperature or constant on. Lee-Temp control is required for Quiet-Line Condensers.

1.3 Sound Level Options

1.3.1 Standard Condenser

All Fan Speed and VFD Condensers are standard condensers with moderate operating sound levels. Lee-Temp Condensers with standard-size coils matching Fan Speed and VFD coil sizes are standard sound level condensers.

1.3.2 Quiet-Line Condenser

Introduction
Quiet-Line condensers can help your facility meet the strictest noise codes and do so at less cost than traditional condensers with acoustical shielding. The Quiet-Line condensers utilize the same reliable construction features of the standard condensers and have oversized coils and slower speed fan motors which yield the required heat rejection needed at significantly lower sound levels. Lee-Temp control is required for Quiet-Line Condensers.

1.4 Transient Voltage Surge Suppression Option

Transient Voltage Surge Suppression (TVSS) panel is standard in the VFD Condenser models only. Surge protection is necessary because rooftop voltage supply often is not conditioned the same as the voltage supply inside the data center. The TVSS is designed to protect sensitive electronic condenser components from high voltage transients, up to 25kVA/phase.
An illuminated green LED indicates power supply is On and panel status is OK. An illuminated red LED indicates conditions require service and the TVSS may require replacement to restore surge pro­tection to the condenser.

1.5 Typical System Configurations

Figure 2 shows a single refrigeration circuit diagram, displaying the indoor air conditioning unit, the outdoor condenser (VFD, Fan Speed Control or Lee-Temp) and field supplied interconnection piping.
2
Page 7
Figure 2 Typical system configuration—indoor unit and outdoor condenser and field piping
Introduction
Inverted trap on discharge & liquid lines to ext end above base of coil by a minimum of 7-1/2” (190mm ).
Fusible Plug
Condenser Coil
(Fan Speed
and VFD )
Fan Speed and VFD
28-42kW Digital Solenoid Valve
53-70kW Digital
Solenoid Valve
Service Valve
Compressor
Chec k Valve
Service Valve
Chec k Valve
Lee-Temp R eceiv er
Condenser Coil
(Lee-Temp )
Lee-Temp
Liquid
Sensing Bulb
Evaporator C oil
Suction
External Equalizer
Pitch horizontal hot gas piping 1/2" per 10 ft. (42mm per 10m) in direction of refr igerant/oil flow.
Relief Valve
Service Valve
Liquid Return
Head Pressure
Control Valve
Hot Gas
Discharge
* Traps every 25ft (7.6m) of rise
Field-installed relief v alve (s) required for 50 Hz EU C E units rated maximum 480 PSIG (33 Bar).
* Isolation valve
Hot Gas Discharge
Expansion Valve
Solenoid
Filter DryerSight Glass
Valve
Factory Refrigerant Piping
Field Refrigerant Piping
Service/Schrader (Access) Connection No Valve Core
Liquid R eturn
Components are not supplied by
*
Liebert, but are recommended for proper circuit operation and maintenance.
Service/Schrader (Access) Connection W ith Valve Core
Note: Sc hematic representation shown . Do not use for specific connection loc ations .
Two refrigeration circuits provided . Single refrigeration circuit shown for clarity .
3
* Isolation valve
DPN000798 Rev. 2
Page 8

2.0 SITE PREPARATION

2.1 Site Considerations

The condensers should be installed in a location offering maximum security and access for mainte­nance.
Avoid ground-level sites with public access and areas that contribute to heavy snow or ice accumula­tions. Utilize Piggyback condensers whenever interior building locations must be used. To ensure ade­quate air supply, Liebert recommends that condensers be installed in an area with clean air, away from loose dirt and foreign matter that might clog the coil. In addition, condensers should not be located near steam, hot air or fume exhausts. Also, the condensers should be located no closer than 3 feet (1m) from a wall, obstruction or adjacent unit.
The condenser must not be installed in a pit.
The condenser must be installed on a level surface to ensure proper refrigerant flow.
For roof installation, mount the condenser on suitable curbs or other supports in accordance with local codes.
Lee-Temp receiver tanks should be mounted on the condenser legs for proper operation. Remote mounting of tanks must be within 10 feet of the condenser—Contact Liebert Application Engineering Department for assistance.
Site Preparation

2.2 Dimensions and Weights

Table 1 Condenser shipping weights, dimensions and volume, approximate

Number
Model
*C**083 1 330 (150)
DC**063 1 350 (159) 435 (197)
*C**165 2 490 (222)
*C**205 2 560 (254) 760 (345)
DC**119 2 490 (222) 690 (313)
DC**127 2 560 (254) 760 (345)
DC**143 2 655 (297) 855 (388)
*C**251 3 590 (268)
DC**214 3 885 (401) 1165 (528)
*C**415 4 935 (424)
DC**286 4 1185 (537) 1485 (674)
*C**616 6 1560 (708)
DC**409 6 1620 (735) 2070 (939)
*CD*830 8 1930 (875)
DC**572 8 2575 (1168) 3075 (1395)
of Fans
Weight
lb (kg)
Domestic Packaging Export Packaging
Dimensions
(LxWxH)
in. (mm)
59x30x51
(1500x760x1300)
97x30x51
(2460x760x1300)
139x30x51
(3530x760x1300)
179x30x51
(4550x760x1300)
144x36x97
(3660x910x2460)
184x36x97
(4670x910x2460)
Volume
3
ft
(m3)
52 (1.4)
86 (2.4)
123 (3.4)
158 (4.4)
291 (8.3)
372 (10.)
Weight
lb (kg)
415 (188)
690 (313)
870 (395)
1235 (560)
2010 (912)
2430 (1102)
Dimensions
(LxWxH) in. (mm)
60x31x52
(1520x790x1320)
98x31x52
(2490x790x1320)
140x31x52
(3560x790x132)0
180x31x52
(4570x790x1320)
145x37x97
(3680x940x2460)
185x37x97
(4700x940x2460)
Volume
3
ft
(m3)
56 (1.5)*C**104 1 350 (159) 435 (197)
91 (2.5)
131 (3.5)*C**308 3 760 (345) 1040 (472)
168 (4.5)*C**510 4 1230 (558) 1530 (694)
301 (8.4)
384 (10.)*CD*1010 8 2910 (1321) 3410 (1548)
4
Page 9
Figure 3 Condenser planning dimensional data—One-fan and two-fan units
Site Preparation
51-1/2"
(1308mm)
43-3/16"
(1097mm)
43-9/16"
(1106mm)
18"
(457mm)
44"
(1118mm)
Note: Overall height to the top of fan guard 43-1/8" (1095mm)
42"
ANCHOR PLAN
(1067 mm)
37-7/8"
(962mm)
91-1/2"
(2324mm)
43-3/16"
(1097mm)
ANCHOR PLAN
42"
(1067 mm)
43-9/16"
(1106mm)
37-7/8"
(962mm)
18"
(457mm)
84"
(2134mm)
Liebert recommends a clearance of 36" (915mm) on each side for proper operation and component access.
82" (2083mm)
One -Fan
Condenser
See Figure 6 for typical condenser footprint dimensions.
41-3/16"
(1046 mm)
Electric
Box
End
Legs supplied with Lee-Temp option only
Two-Fan
Condenser
41-3/16"
(1046mm)
5
Page 10
Figure 4 Condenser planning dimensional data—Three-fan and four-fan units
43-9/16"
(1106mm)
131-1/2"
(3340mm)
37-7/8"
(457mm)
124"
(3150mm)
43-3/16"
(1097mm)
Note: Overall height to the top of fan guard 43-1/8" (1095mm)
ANCHOR PLAN
42"
(1067mm )
(962mm)
18"
Eyebolts for Lifting
43-3/16"
(1097mm)
122" (3099 mm)
171-1/2"
(4356mm)
70"
(1778mm)
164"
(4166mm)
Liebert recommends a clearance of 36" (915mm) on each side for proper operation and component access.
Site Preparation
43-9/16"
(1106mm)
37-7/8"
(962mm)
18"
(457mm)
See Figure 6 for typical condenser footprint dimensions.
Electric
Box
End
Electric
Box End
Legs s upplied with Lee-Temp option only
ANCHOR PLAN
82" (2083 mm)
42"
(1067mm)
Legs s upplied wit h Lee-Temp option only
Three -Fan
Condenser
41-3/16 "
(1046mm )
80"
(2032 mm)
Four-Fan
Condenser
41-3/16"
(1046mm)
6
Page 11
Figure 5 Condenser planning dimensional data—Six- and eight-fan units
87-1/8"
131-1/2"
(3340mm)
86-3/4"
(2203mm)
Overalll height to the top of the fan guard is 43-1/8” (1095mm).
42"
(1067 mm )
122" (3099 mm)
(2213mm)
59"
(1499mm)
(3150mm)
18"
(457mm)
124"
ANCHOR PLAN
37-7/8"
(962mm)
(4356mm)
86-3/4"
(2203mm)
171-1/2"
1-1/2" (38mm) diameter hole for rigging (typ.4)
Site Preparation
87-1/8"
(2213mm)
37-7/8"
(962mm)
18"
(457mm)
70" (1778mm)
164"
(4166mm)
Liebert recommends a clearance of 36" (915mm) on each side for proper operation and component access.
Electric
Box End
Legs s upplied with Lee-Temp option only
Electric
Box End
Six-Fan
Condenser
82" (2083 mm)
42"
(1067mm)
Legs s upplied with Lee-Temp option only
84-3/ 4"
(2153mm )
See Figure 6 for typical condenser footprint dimensions.
ANCHOR PLAN
80" (2032 mm )
Eight -Fan
Condenser
84-3/4"
(2153 mm)
7
Page 12
Figure 6 Typical condenser footprint—dimensions
1”
(25.4mm)
1-3/4”
(44.5mm)
4-1/4”
(108mm)
1-3/4”
(44.5mm)
2”
(50.8mm)
Site Preparation
4-1/4”
(108mm)
2”
(50.8mm)
9/16" (14mm)
Typical Diameter

Figure 7 Piping connection locations for 1-, 2-, 3- and 4-fan VFD Control and Fan Speed Condensers

Entering Hot Gas Line
Leaving Liquid Line
Traps to extend above coil base by a minimum of 7-1/2" (190mm)
Inverted Traps (field-supplied)
Metal
Fasten liquid and hot gas lines to leg using flat surface clamps with isolators (field-supplied). Support field piping separately
See Detail A-A
clamp
Isolator
Detail A-A
to avoid coil damage and loss of charge.
DPN000665 Rev. 02
8
Page 13

Figure 8 Piping connections for 1-, 2-, 3- and 4-fan Lee-Temp and Quiet-Line Condensers

Site Preparation
Hot Gas Line
Liquid
to extend 8" (203mm) above coil base
Line
Fasten liquid and hot gas lines to leg using flat surface clamps with isolators (field-provided). Support field piping separately to avoid coil damage and loss
Inverted Traps (field-supplied)
of charge.
See Detail A-A
Metal clamp
Isolator
Detail A-A

Figure 9 Piping connections for 6- and 8-fan Fan Speed Condensers

Access Valve (Hot Gas) on Condensers (Typ. 2)
Entering Hot Gas Line
Leaving Liquid Line
Position elbow to direct relief valve downward
DPN001067 Rev. 0
Inlet Connection Upper Headers (Typ.)
Fasten liquid and hot gas lines to leg using flat surface clamps with isolators (field-supplied).
Entering Hot Gas Line
Condenser Connections, Typical
Leaving Liquid Line
Inverted traps (field-supplied) to extend above base of coil by a minimum of 7-1/2" (190mm).
Metal
Clamp See Detail
Isolator
A-A
Detail A-A
DPN000668 Rev. 01
9
Page 14

Figure 10 Piping connections for 6- and 8-fan Lee-Temp and Quiet-Line Condensers

A
ccess Valve (Hot Gas) on
Condensers (Typ. 2)
Site Preparation
Inlet Connection Upper Headers (Typ.)
Condenser Connections, Typical
Liquid Line
Hot Gas Line
Inverted traps (field-supplied) to extend above base of coil by a minimum of 7-1/2" (190mm).
Entering Hot Gas Line
Leaving Liquid Line
Fasten liquid and hot gas lines to leg using flat surface clamps with isolators (field-supplied).
See Detail A-A
Metal Clamp
Position elbow to direct relief valve downward
Note: Two circuits supplied; single circuit shown for clarity.
Isolator
Detail A-A
DPN000670 Rev. 01
10
Page 15

Table 2 Condenser physical data

Connection Size, OD, In.
Net Weight
lb (kg) Hot Gas Liquid
Model #
Number
of Fans
Number
of Circuits
Standard Models
CS*083 1 1 7/8 5/8 295 (134)
CD*104 1 2 7/8 1/2 315 (143)
CS*104 1 1 1-1/8 5/8 315 (143)
CD*165 2 2 7/8 5/8 425 (193)
CS*165 2 1 1-1/8 7/8 425 (193)
CD*205 2 2 1-1/8 7/8 495 (225)
CS*205 2 1 1-1/8 7/8 495 (225)
CD*251 3 2 1-1/8 7/8 500 (227)
CS*251 3 1 1-3/8 1-1/8 500 (227)
CD* 308 3 2 1-3/8 1-1/8 670 (304)
CS*308 3 1 1-5/8 1-1/8 670 (304)
CD* 415 4 2 1-3/8 1-1/8 840 (381)
CS*415 4 1 1-5/8 1-1/8 840 (381)
CD*510 4 2 1-5/8 1-1/8 1188 (539)
CD*616 6 2 1-5/8 1-1/8 1380 (626)
CS*616
1
6 1 (2)1-5/8 (2)1-1/8 1380 (626)
CD*830 8 2 1-5/8 1-1/8 1750 (794)
CD*1010 8 2 2-1/8 1-5/8 2640 (1197)
Quiet-Line Models
DCS*063 1 1 1-1/8 5/8 315 (143)
DCD*063 1 2 7/8 1/2 315 (143)
DCS*119 2 1 1-1/8 7/8 425 (193)
DCD*119 2 1 1-1/8 7/8 425 (193)
DCS*127 2 1 1-1/8 7/8 495 (225)
DCD*127 2 2 1-1/8 7/8 495 (225)
DCS*143 2 1 1-1/8 7/8 515 (234)
DCD*143 2 2 1-1/8 7/8 515 (234)
DCS*214 3 1 1-5/8 1-1/8 840 (381)
DCD*214 3 2 1-1/8 7/8 840 (381)
DCS*286 4 1 2-1/8 1-1/8 1105 (501)
DCD*286 4 2 1-1/8 7/8 1105 (501)
DCD*409 6 2 1-5/8 1-1/8 1380 (626)
DCD*572 8 2 2-1/8 1-1/8 2430 (1102)
1. Interconnection piping (field-supplied and installed) required. Configure piping for parallel refrigerant flow between condenser sections.
Site Preparation
11
Page 16

2.3 Refrigerant Planning Values

Planning for the refrigerant requirements of the completed system is the addition of the charges from Indoor Unit, Condenser (including Lee-Temp receiver, if used) and the interconnecting piping. Tables 3 and 4 provide the approximate charge required for the condensers and the interconnecting piping. Consult indoor unit manuals for indoor unit charge requirements.
These values can be used for obtaining adequate refrigerant for the system, but should not be used for final charging. Consult indoor unit manual for charging procedures.

Table 3 R-22 and R-407C refrigerant required, approximate

Approximate R-22 Refrigerant Needed Approximate R-407C Refrigerant Needed
Single Circuit
lb (kg)
Standard
Condenser
Models
83 5 (2.3) 27 (12.3) 3 (1.4) 15 (6.8) 5 (2.3) 26 (11.8) 3 (1.4) 15 (6.8)
104 8 (3.6) 39 (17.7) 7 (3.2) 21 (9.5) 8 (3.6) 37 (16.8) 7 (3.2) 20 (9.0)
165 15 (6.8) 53 (24.0) 5 (2.3) 27 (12.3) 15 (6.8) 50 (22.7) 5 (2.3) 26 (11.8)
205 20 (9.1) 76 (34.5) 7 (3.2) 38 (17.2) 19 (8.6) 72 (32.7) 7 (3.2) 36 (16.3)
251 19 (8.6) 75 (34.0) 10 (4.6) 38 (17.2) 18 (8.2) 71 (32.23) 10 (4.6) 36 (16.3)
308 29 (13.2) 113 (51.3) 11 (5.0) 58 (26.3) 28 (12.7) 107 (48.5) 11 (5.0) 55 (24.9)
415 54 (24.5) 182 (82.6) 15 (6.8) 75 (34.0) 51 (23.1) 173 (78.4) 15 (6.8) 71 (32.2)
510 72 (32.7) N/A 30 (13.6) 149 (67.6) 68 (30.8) N/A 29 (13.2) 142 (64.4)
616 N/A 267 (121.3) 27 (12.3) 113 (51.3) N/A 254 (115.2) 26 (11.8) 108 (49.0)
830 N/A N/A 30 (13.6) 149 (67.6) N/A N/A 29 (13.2) 142 (64.4)
1010 N/A N/A 60 (27.2) 154 (69.9) N/A N/A 57 (25.9) 147 (66.7)
Quiet-Line Condenser Models
63 N/A 39 (17.7) N/A 21 (9.5) N/A 37 (16.8) N/A 20 (9.1)
119 N/A 50 (22.7) N/A 27 (12.3) N/A 48 (21.8) N/A 26 (11.8)
127 N/A 76 (34.5) N/A 38 (17.2) N/A 72 (32.6) N/A 36 (16.3)
143 N/A 126 (57.2) N/A 64 (29.0) N/A 120 (54.5) N/A 61 (27.7)
214 N/A 161 (73.0) N/A 81 (36.7) N/A 153 (69.4) N/A 77 (34.9)
286 N/A 196 (88.9) N/A 125 (56.7) N/A 186 (84.4) N/A 119 (54.0)
409 N/A N/A N/A 129 (58.5) N/A N/A N/A 125 (55.8)
572 N/A N/A N/A 196 (88.9) N/A N/A N/A 186 (84.4)
FSC or
VFD
Lee-Temp
(includes
receiver)
Dual Circuit
lb/circuit (kg/circuit)
Lee-Temp
FSC or
VFD
(includes
receiver)
Single Circuit
lb (kg)
FSC or
VFD
Lee-Temp
(includes
receiver)
Site Preparation
Dual Circuit
lb/circuit (kg/circuit)
Lee-Temp
FSC or
VFD
(includes
receiver)

Table 4 Interconnecting piping refrigerant charge

Line Size,
O.D., in.
3/8 3.8 (1.7) 3.7 (1.7)
1/2 7.3 (3.3) 6.9 (3.1)
5/8 11.7 (5.3) 2.1 (1.0) 11.0 (5.0 2.2 (1.0)
3/4 16.6 (7.5) 3.0 (1.4) 15.7 (7.1) 3.1 (1.3)
7/8 24.4 (11.1) 4.4 (2.0) 23.0 (10.4) 4.5 (1.9)
1-1/8 41.4 (18.9) 7.8 (3.5) 39.3 (17.8) 7.8 (3.5)
1-3/8 63.3 (28.7) 11.8 (5.4) 59.8 (27.1 11.8 (5.4)
1-5/8 16.7 (7.6) 16.7 (7.6)
R-22, lb/100 ft. (kg/30m) R-407C, lb/100 ft. (kg/30m)
Liquid Line Hot Gas Line Liquid Line Hot Gas Line
12
Page 17

3.0 INSPECTION AND INSTALLATION

3.1 Equipment Inspection

Before unpacking the condenser, verify that the labeled equipment matches the bill of lading. Care­fully inspect all items for damage, either visible or concealed. Report any damage immediately to the carrier and your local Liebert representative. File a damage claim with the carrier and send a copy to your local Liebert representative.

3.1.1 Packing Material

All material used to package this unit is recyclable. Please save it for future use or dispose of the material appropriately.

SAFETY INFORMATION

WARNING
!
Risk of top-heavy unit falling over. Can cause equipment damage, injury or death.
Read all of the following instructions before attempting to move, lift, remove packaging from or preparing unit for installation.
WARNING
!
Risk of sharp edges, splinters and exposed fasteners. Can cause personal injury.
Inspection and Installation
R
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes, glasses and protective clothing should attempt to move, lift, remove packaging from or prepare unit for installation.
NOTICE
Risk of overhead interference. Can cause unit and/or structure damage. Refer to the installation plans prior to moving the unit to verify clearances.
NOTICE
Risk of damage from forklift. Improper handling with the forklift. Can cause exterior and/or underside damage.
Keep tines of the forklift level and at a height suitable to fit below the skid.
NOTICE
Risk of unit damage if improperly stored. Keep the unit upright, indoors and protected from dampness, freezing temperatures and contact damage.

Figure 11 Equipment recommended for handling a Liebert condenser

13
Page 18

3.2 Handling Unit on the Skid

Transport the unit using a fork lift or a crane with sling and spreader bars.
• If using a fork lift, make sure the forks (if adjustable) are spread to the widest allowable distance to still fit under the skid.
• Ensure the fork length is suitable for the unit length.
• When moving the packaged unit, do not lift the unit any higher than 6" (152mm) off the ground. Exercise great care if the unit must be lifted higher than 6" (152mm). Personnel not involved in moving the unit must be at least 20' (6m) from the lift point of the unit.

3.3 Unpacking the Unit

Remove outer packaging when ready to install the unit. Be sure to locate, and set aside, the bag of mounting hardware that is to be used for mounting the support legs on the unit.

Figure 12 Removing shipping crate

Inspection and Installation
Three-fan unit shown for illustration. Methods for other sizes of condensers are the same.
14
Page 19
Inspection and Installation

3.4 Preparing a 1-, 2-, 3- or 4-Fan Condenser for Moving and Installation

3.4.1 Removing the Skid and Attaching Slings

1. Install the legs, provided by Liebert, on the condenser with the mounting bolts, also provided by Liebert. Liebert recommends using a 5/8" socket and ratchet.
2. Place slings or equivalent items through holes in the legs on 1, 2- and 3-fan condensers (see Step 2 and Step 3 in Figure 13). Use eyebolts for attaching a sling or similar equipment to 4-fan units.
3. Using spreader bars and a crane, or similar lifting equipment, lift the condenser off the skid to allow safely turning the condenser upright.
4. Lift the condenser and move it to the installation location.
Figure 13 Attaching legs and sling to a 1-, 2-, 3- or 4-fan condenser for moving
Step 1
Step 2
Three-fan unit shown for illustration. Method for 1-fan and 2--fan condensers is the same. Attach sling to 4-fan condensers with eyebolts.
Step 3
15
Page 20
Inspection and Installation

3.5 Preparing a 6-Fan or 8-Fan Condenser for Moving and Installation

3.5.1 Removing the Skid and Attaching Slings

The following procedure is one recommended process for removing a Liebert condenser from its ship­ping skid. Other methods may be used, provided that the methods are safe for personnel, the con­denser and equipment.
1. Place a sling through to rigging attachment points as shown in Step 1 in Figure 14.
2. Raise the condenser high enough that the skid can be safely removed.
3. Place protective material under the unit to protect it from scrapes and gouges. Lower the condenser onto the material.
4. Lower the condenser to an angle and distance that will allow attaching the legs to one side of the condenser. The number of legs varies according to the condenser model.
5. Install the legs, provided by Liebert, on the condenser with the mounting bolts, also provided by Liebert. Liebert recommends using a 5/8" socket and ratchet.
6. Turn the condenser so that the legs just installed support one side of the unit as shown in Step 3 in Figure 14.
7. Remove the sling and it attach it to the opposite side of the condenser as shown in Step 4 in Figure 15.
8. Raise the condenser to an angle to safely install legs on the opposite side of the condenser.
9. Lower the condenser so all legs support it.
10. Place slings on both sides of the condenser to lift and move it to the installation location.
Figure 14 Attaching legs to a 6-fan or 8-fan unit
Step 3
Step 1
Step 2
Protective Material Under the Condenser
Six-fan unit shown for illustration. Method for eight-fan condenser is the same.
16
Page 21
Figure 15 Attaching sling to a 6-fan or 8-fan unit for moving
Step 4
Step 5
Inspection and Installation

3.5.2 Mounting the Condenser

The condenser must be installed so that it is level within 1/2" (13mm) to ensure proper refrigerant flow. For roof installation, mount the condenser on suitable curbs or other supports; follow all local and national codes. Secure the legs to the mounting surface using a field-supplied 1/2" (13mm) diame­ter bolt in each of the two 5/8" (16mm) holes in each leg. See Figures 3, 4 and 5 for anchor dimen- sions.
Six-fan unit shown for illustration. Method for 8-fan condenser is the same.
17
Page 22

3.6 Electrical Supply Preparation

Line voltage electrical service is required for all models. Refer to equipment nameplate regarding wire size and circuit protection requirements. Electrical service must conform to national and local electrical codes. Refer to Figures 19, 20 and 21 for electrical service entrances into unit. Refer to electrical schematic when making connections.
Each unit is shipped from the factory with all internal unit wiring completed.
WARNING
!
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electrical power supplies before working within the electrical enclosure.
The line side of the disconnect remains energized when the disconnect is Off.
Use a voltmeter to verify that the electrical power is Off before performing any electrical and/or mechanical service and/or maintenance operations.
WARNING
!
Risk of high speed moving parts. Can cause injury or death.
The fan(s) blades can start to rotate unexpectedly when the power is On. Disconnect all local and remote electrical power supplies before working within the fan compartment.
Inspection and Installation
Use a voltmeter to verify that the electrical power is Off before performing any electrical and/or mechanical service and/or maintenance operations.
Each unit is shipped from the factory with all internal unit wiring completed. Refer to the electrical schematic supplied with the condenser when making line voltage supply, low voltage indoor unit interlock and any low voltage alarm connections. All wiring must be done in accordance with all appli­cable local, state and national electrical codes.

3.6.1 Line Voltage Wiring

WARNING
!
Risk electrical fire and short circuit. Can cause property damage, injury or death.
Select and install the electrical supply wire and overcurrent protection device(s) according to the specifications on the unit nameplate(s), per the instructions in this manual and according to the applicable national, state and local code requirements. Use copper conductors only. Make sure all electrical connections are tight. Unit-specific wiring diagrams are provided on each unit.
Condenser-rated voltage should be verified with available power supply before installation. Refer to the unit’s electrical schematic and serial tag for specific electrical requirements.
Line voltage electrical service is required for all condensers at the location of the condenser. The power supply does not necessarily have to be the same voltage supply as required by the indoor unit connected to the condenser. See the unit’s serial tag for specific condenser electrical requirements. A unit disconnect is standard on VFD and Quiet-Line Condensers and is optional on Fan Speed Control and standard Lee-Temp condensers. However, a site disconnect may be required per local code to iso­late the unit for maintenance. Route the supply power to the site disconnect switch and then to the unit. Route the conduit through the hole provided in the cabinet. Connect earth ground to lug pro­vided near terminal board.
NOTE
Lee-Temp and Quiet-Line Condensers require a separate line voltage electrical supply for the heated receivers. See Table 8 for power requirements.
18
Page 23
Inspection and Installation
Table 5 60Hz condenser data
Model # 83, 104 165, 205 251, 308 415, 510 616 830, 1010
# of Fans 1 2 3 4 6 8
Input
Voltage ph FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
Fan Speed Controlled
208/230
460 2.5 3.1 15
575 1.9 2.4 15
208/230
460 4.2 4.8 15 5.9 6.5 15 7.6 8.2 15 11.8 12.4 15 15.2 15.8 20
575 3.3 3.8 15 4.7 5.2 15 6.1 6.6 15 9.4 9.9 15 12.2 12.7 15
VFD Controlled
208/230
460 1.8 2.3 15 3.5 4.0 15 5.2 5.7 15 6.9 7.4 15 N/A N/A N/A N/A N/A N/A
Lee-Temp Controlled/Fan-Cycling
208/230
460 1.7 2.1 15 3.4 3.8 15 5.1 5.5 15 6.8 7.2 15 10.2 10.6 15 13.6 14.0 15
575 1.4 1.8 15 2.8 3.2 15 4.2 4.6 15 5.6 6.0 15 8.4 8.8 15 11.2 11.6 15
FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device
4.86.015————— ——— ——— ————
1
8.3 9.5 15 11.8 13.0 15 15.3 16.5 20 23.6 24.8 25 30.6 31.8 35
3
3.7 4.6 15 7.2 8.1 15 10.7 11.6 15 14.2 15.1 20 N/A N/A N/A N/A N/A N/A
3
3.5 4.4 15 7.0 7.9 15 10.5 11.4 15 14.0 14.9 15 21.0 21.9 25 28.0 28.9 30
3
Table 6 60Hz condenser data, Quiet-Line (Lee-Temp controlled/fan-cycling)
Model # ph 63 119, 127, 143 214 286 409 572
# of Fans 1 2 3 4 6 8
Input
Voltage ph FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
208/230
460 0.9 1.1 15 1.8 2.0 15 2.7 2.9 15 3.6 3.8 15 5.4 5.6 15 7.2 7.4 15
575 0.7 0.9 15 1.4 1.6 15 2.1 2.3 15 2.8 3.0 15 4.2 4.4 15 5.6 5.8 15
FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device
1.8 2.3 15 3.6 4.1 15 5.4 5.9 15 7.2 7.7 15 10.8 11.3 15 14.4 14.9 15
3
Table 7 50Hz condenser full load amp values
Condenser
Control Type
Model## of
Fans
83, 104 1 4.0 - 3.7 1.8 3.5 1.7 63 1.8 0.9
165, 205 2 3.7 7.2 3.5 7.0 3.4
251, 308 3 5.4 10.7 5.2 10.5 5.1 214 5.4 2.7
415, 510 4 7.1 14.2 6.9 14.0 6.8 286 7.2 3.6
616 6 10.8 21.0 10.2 409 10.8 5.4
830, 1010 8 14.2 28.0 13.6 572 14.4 7.2
Fan Speed Controlled
Input
Voltage - Phase
200/230-1 380/415-3 200/230-3 380/415-3 200/230-3 380/415-3 200/230-3 380/415-3
VFD
Controlled
Input
Voltage - Phase
Lee Temp
Controlled/Fan-Cycling
Input
Voltage - Phase
Quiet-Line (Lee Temp
Controlled/Fan-Cycling)
Input
Model
#
119, 127,
143
Voltage - Phase
3.6 1.8
19
Page 24
Table 8 Lee-Temp receiver electrical data, 50Hz and 60Hz
Rated Voltage - Single Phase 120 200/208/230
Watts/Receiver 150 300 450 150 300 450
Full Load Amps 1.4 2.8 4.2 0.7 1.4 2.1
Wire Size Amps 1.8 3.5 5.3 0.9 1.8 2.7
Maximum Overcurrent Protection Device, Amps
15 15 15 15 15 15

3.6.2 Low Voltage Control Wiring

NOTICE
Risk of control malfunction. Can cause improper unit operation. Make sure that all low voltage electrical wiring has been performed per the schematic diagram provided and that all low voltage wiring connections are tight.
A control interlock between the condenser and the indoor cooling units is required. Field-supplied cop­per wire (Class 1 for TCDV models and Class 2 for all other condenser models) is required for connec­tion between like-numbered terminals 70 & 71 on both units. Wiring must be sized so that the voltage drop in the circuit does not exceed 1 volt. See Figures 19, 20 and 21 and indoor unit manual for loca­tion of terminals on condensers and indoor units.
3.6.3 Low Voltage Monitoring Wiring—TCDV Only
Inspection and Installation
Condensers with monitoring terminals may be wired with Class 1 copper wire to the indoor cooling unit or other monitoring panel. Wiring must be sized so that the voltage drop in the circuit does not exceed 1 volt. Dry contacts close when a monitored event occurs. Consult condenser electrical sche­matic, supplied with the unit, for details.
Contact closure on VFD Drive monitoring terminals indicates a permanent VFD fault. A factory-pro­grammed VFD must be used as the replacement.
Contact closure on TVSS monitoring terminals may indicate unit trouble ranging from electrical sup­ply issues to TVSS replacement required. A properly trained and qualified electrician is required.

3.7 Electrical Connections

Electrical service is required for all models. Electrical service shall conform to national and local elec­trical codes. Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to electrical schematic when making connections. Refer to Figures 19, 20 and 21 for electrical service entrances into unit.
A manual electrical disconnect switch should be installed in accordance with local codes. Consult local codes for external disconnect requirements.
WARNING
!
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working in the unit. Unit contains lethal voltage in some circuits. Use voltmeter to make sure power is turned Off before making any electrical connections.
NOTICE
Installation and service of this equipment should be done only by properly trained and qualified personnel who have been specially trained in the installation of air conditioning equipment.
NOTICE
Use copper wiring only. Make sure that all conections are tight.
20
Page 25

3.7.1 VFD Control Condensers (TCDV) only

The installer/startup technician must determine the type of 3-phase supply power being used for the VFD Control Condenser: Wye-connected power or Delta- connected power.
Wye-connected power has two different voltages that can be measured: Phase-to-Phase voltage (this is equal to the nominal input voltage) and Phase-to-Neutral voltage (typically used for small single phase loads (120 VAC or 277 VAC). See Figure 16.
Delta-connected power only has one voltage level that can be measured: Phase-to-Phase. See Figure 17.

3.7.2 Wye-Connected Power Supply

No control changes are required if the Liebert VFD Control Condenser will be operated with Wye-con­nected power.
Figure 16 Wye-connected power diagram
Inspection and Installation
Phase A
Winding
A
Winding
C

3.7.3 Delta-Connected Power Supply

Figure 17 Delta-connected power diagram
Winding
C-A
Winding
B
Winding B-C
Phase B
Neutral
Phase C
Phase A
Winding
A-B
Phase B
21
Phase C
Page 26
Disconnect EMC Filter for Delta-Connected Power
Installer/startup technician needs to disconnect the EMC filter on the VFD to ensure proper operation if the Liebert VFD Control Condenser will be operated with Delta-connected power.
1. Disconnect the power supply before working on the unit.
2. Open the electrical panel cover and locate the VFD (Refer to Figure 20).
3. Using Figure 18, locate the small black plastic tab immediately to the right of the wiring connection block of the VFD control
4. Pull the tab to fully extend it, disconnecting the EMC filter from the circuit.
Figure 18 Disconnecting EMC filter for operation with Delta-connected power
A
Internal
EMC filter
Tab fully inserted: EMC filter fitted
B
Internal
EMC filter
Inspection and Installation
Tab fully extended: EMC filter disconnected
22
Page 27

3.8 Electrical Field Connection Descriptions

Figure 19 Electrical field connections for Fan Speed Control Condensers

Electric service connection terminals when factory
Electric service connection and fuse block.
Factory wired to 24V Class 2 control circuit.
Control interlock (70, 71) Field-supplied Class 2 wiring to interlock condenser 24V controls to Liebert room unit; 7/8 in. (22.2mm) diameter hole provided in bottom of electric box.
disconnect is NOT supplied.
Inspection and Installation
Electric service connection terminals when factory disconnect is supplied.
Factory installed disconnect switch (optional).
Factory-wired to components on electric panel.
Earth ground bar (optional on 50Hz only). Connection terminals with factory ground from each high voltage component for field-supplied earth grounding wire.
Earth ground connection (60Hz). Connection terminals for field supplied earth grounding wire when factory disconnect is NOT supplied.
NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.
Earth ground connection (60Hz). Connection terminal for field­supplied earth grounding wire when factory disconnect is supplied.
Electric service entrance. A 7/8 in. (22.2mm) diameter hole in a 1 1/8 in (28.6mm) knockout provided in bottom of electric box.
Electric service, not by Liebert. Single-phase for condenser models CSF, CDF with single fan motor. Three-phase for all other condenser models.
DPN000666 Rev. 0
23
Page 28

Figure 20 Electrical field connections for VFD control condensers

A
Factory-wired to 24V control circuit.
Control interlock (70, 71) Field-supplied Class 1 wiring to interlock condenser 24V controls to Liebert room unit; 7/8 in. (22.2mm) diameter hole provided in bottom of electric box.
larm Connections Field-supplied 24V Class 1 wiring to remote alarm circuits Variable Frequency Drive (VFD) alarm contact connections (13, 14) Transient Voltage Surge Suppressor (TVSS) alarm contact connections (11, 12).
Factory-wired to components on electric panel.
Earth ground bar (optional on 50Hz only). Connection terminals with factory ground from each high voltage component for field-supplied earth grounding wire.
NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.
Earth ground connection (60Hz). Connection terminal for field-supplied earth grounding wire when factory disconnect is supplied.
Inspection and Installation
Factory-installed fuse block on 60Hz units. Circuit breaker supplied in lieu of fuse block on 50Hz units.
Electric service connection terminals with factory­supplied disconnect.
Factory-installed disconnect switch.
Electric service entrance. A 7/8" (22.2mm) diameter hole in a 1-1/8 in (28.6mm) knockout provided in bottom of electric box.
Electric service, not by Liebert
DPN001051 Rev. 0
24
Page 29

Figure 21 Electrical field connections for Liebert Lee-Temp control condensers

Lee-Temp receiver tank (1 per circuit). NOTE: Standard heater pads are 150 watts each. (Optional 300 watt heater pads are available.) Standard heater pad voltage is 230V. (120V heater pad voltage is optional.)
Electrical connection box with cover.
Electrical service connection. Pigtails in electric handy box are factory wired to Lee­Temp heater pads for field connection of separate continuous electric source,
Electric service connection and fuse block.
Factory wired to 24V Class 2 control circuit.
Control interlock (70, 71) Field-supplied Class 2 wiring to interlock condenser 24V controls to Liebert room unit; 7/8 in. (22.2mm) diameter hole provided in bottom of electric box.
70
71
Factory-wired to components on electric panel.
Earth ground bar (optional on 50Hz only). Connection terminals with factory ground from each high-voltage component for field-supplied earth grounding wire.
Earth ground connection (60Hz). Connection terminal for field-supplied earth grounding wire when factory disconnect is NOT supplied.
NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.
Earth ground connection (60Hz). Connection terminal for field-supplied earth grounding wire when factory disconnect is supplied.
wiring not by Liebert.
Electric service connection terminals when factory disconnect is NOT supplied.
Electric service connection terminals when factory disconnect is supplied.
Factory-installed disconnect switch (optional).
Electric service entrance. A 7/8 in (22.2mm) diameter hole in a 1 1/8 in (28.6mm) knockout provided in bottom of electric box.
Electric service. Three-phase for all models. Wiring not by Liebert.
Inspection and Installation
DPN000683 Rev. 0
25
Page 30

3.9 Refrigeration Piping Connections

WARNING
!
Risk of explosive discharge from high-pressure refrigerant. Can cause equipment damage, injury or death. Relieve pressure before working with piping.
WARNING
!
Risk of refrigerant system rupture or explosion from overpressurization. Can cause equipment damage, injury or death.
If a pressure relief device is not provided with the condenser unit, the system installer must provide and install a discharge pressure relief valve rated for a maximum of 500 psig (34bar) in the high side refrigerant circuit. Do not install a shutoff valve between the compressor and the field installed relief valve.
One or more additional pressure relief valves are required downstream of any and all field installed isolation valves as shown in Figures 2 and 24. Do not isolate any refrigerant circuits from overpressurization protection.
NOTE
POE (polyol ester) oil, required with R407C and used with some R22 systems, is much more hygroscopic than mineral oils. This means that POE oil absorbs water at a much faster rate when exposed to air than previously used mineral oils. Because water is the enemy of a reliable refrigeration system, extreme care must be used when opening systems during installation or service. If water is absorbed into the POE oil, it will not be easily removed and will not be removed through the normal evacuation process. If the oil is too wet, it may require an oil change. POE oils also have a property that makes them act as a solvent in a refrigeration system. Maintaining system cleanliness is extremely important because the oil will tend to bring any foreign matter back to the compressor.
Inspection and Installation

3.9.1 Piping Guidelines

Indoor units and condensers both ship with nitrogen holding charges. Do not vent the condenser until all refrigerant piping is in place, ready for connection to indoor unit and condenser.
• Use copper piping with a brazing alloy with a minimum temperature of 1350°F (732°C), such as Sil-Fos. Use a flow of dry nitrogen through the piping to prevent the formation of copper oxide scale inside the piping. Avoid soft solders such as 50/50 or 95/5.
• Isolate piping from building using vibration isolating supports.
• Refer to indoor unit user manual for appropriate piping sizes.
• Install traps on the hot gas (discharge) lines at the bottom of any rise over 5 feet high. If the rise exceeds 25 feet (7.5m), then install a trap in 20 foot (6m) increments or evenly divided.
• Pitch horizontal hot gas piping at a minimum rate of 1/2" per 10 ft. (42mm per 10m) so that grav­ity will aid in moving oil in the direction of refrigerant/oil flow.
• Consult factory if Lee-Temp condenser is located more than 15 ft (4.6m) below the evaporator or if Fan Speed/VFD Control Condenser is located more than 30 ft. (9.2m) below the evaporator.
• Consult factory if piping run exceeds 150 feet (46m) equivalent length.
• Keep piping clean and dry, especially on units with POE oil (R407C or R22 refrigerant).
• Avoid piping runs through noise-sensitive areas.
• Do not run piping directly in front of indoor unit discharge airstream.
• Refrigerant oil – do not mix oil types or viscosities. Consult indoor unit for refrigerant type and oil requirements.
NOTE
Failure to use compressor oils recommended by compressor manufacturer will void compressor warranty. Consult Liebert or compressor manufacturer for further recommendations or if you have questions about compressor oils.
Refer to ASHRAE Refrigeration Handbook for general good practices for refrigeration piping. A pressure relief valve is provided with Liebert Lee-Temp condensers. A fusible plug is
provided on Liebert Fan Speed Control and VFD condensers. The Liebert indoor cooling unit has a factory-installed high-pressure safety switch in the high side refrigerant circuit.
26
Page 31

3.9.2 Field Piping Installation

One discharge line and one liquid line must be field-installed for each circuit of the indoor unit and the outdoor condenser(s). Dual circuit condensers are available for most dual circuit indoor unit appli­cations. Refer to Figures 22, 23 and 24 below for additional field-installed piping needed at the con­denser. This piping is needed for proper system performance and for installation/interconnecting receivers and head pressure control valves for Lee-Temp systems.
NOTE
Keep the evaporator unit and condenser closed with their factory charge of dry nitrogen while all field piping is installed. Keep the field piping clean and dry during installation, and do not allow it to stand open to the atmosphere.
When all the field interconnecting piping is in place, vent the condenser’s dry nitrogen charge and connect to the field piping. Finally, vent the evaporator unit’s dry nitrogen charge and make its piping connections last.
Follow all proper brazing practices, including a dry nitrogen purge to maintain system cleanliness.
Figure 22 VFD and Fan Speed Control condenser piping
Inspection and Installation
Entering Hot Gas Line
Leaving Liquid Line
Fasten liquid and hot gas lines to leg using flat surface clamps with isolators ( field-supplied). Support field piping separately to avoid coil damage and loss of charge.
Traps to Extend Above Base of Coil by a Minimum of 7-1/2" (190mm)
Inverted Traps (Field Supplied)
Metal Clamp
See Detail A-A
Detail A-A
Isolator
DPN001065 Rev. 0
27
Page 32
Figure 23 Lee-Temp head pressure control condenser piping
Inspection and Installation
Hot Gas Line
Liquid Line
Fasten liquid and hot gas lines to leg using flat surface clamps with isolators (field-supplied). Support field piping separately to avoid coil damage and loss of charge.
Metal Clamp
Detail A-A
See Detail A-A
Isolator
Inverted Traps (field-supplied) to extend 8" (203mm) above coil base
Entering Hot Gas Line
Leaving Liquid
Line Position elbow to direct relief valve downward
DPN000669 Rev. 2
28
Page 33
Figure 24 General arrangement—Air cooled models with Lee-Temp control
Condenser Coil
Inverted Trap * on discharge line to extend 7-1/2" (190mm)
Piping Assembly **
above coil base
Rotalock Valve **
Check
Head Pressure Control with Integral Check Valve
Valve
Lee-temp
Receiver
Sight Glass
* Traps every 25 ft (7.6m) of rise on hot gas line only
Liquid Return from Condenser
Inspection and Installation
1/4" (6.4mm) Pressure Relief Valve**
Evaporator Coil
Shutoff * (Isolation) Valve
Liquid Return
Hot Gas Bypass (optional)
Hot Gas Discharge
Solenoid Valves
Sight Glass
Filter Dryer
Check Valve
Single Circuit Shown
Factory Piping
Optional Piping
Field Piping
Expansion Valve
Sensing Bulb
External Equalizers
Service Valves
Compressor***
* Components are not supplied by Liebert but are recommended for proper circuit operation and maintenance. ** Components supplied by Liebert and must be field-installed. *** Various compressor types may be available.
DPN000681 Rev. 0
29
Page 34

3.10 System Dehydration/Leak Test and Charging Procedures

Procedures for leak check and evacuation of the entire refrigeration system are contained in the installation manual of the indoor unit. Use the proper manual section corresponding to the winter control system used on the condenser (VFD/Fan Speed Control or Lee-Temp Control) and the refriger­ant to be charged into the system.
Inspection and Installation
30
Page 35

4.0 CHECKLIST FOR COMPLETED INSTALLATION

4.1 Moving and Placing Equipment

___ 1. Unpack and check received material
___ 2. Proper clearance for service access has been maintained around the equipment
___ 3. Equipment is level and mounting fasteners are tight

4.2 Electrical

___ 1. Line voltage connected and matches equipment nameplate
___ 2. Power line circuit breakers or fuses have proper ratings for equipment installed
___ 3. Control wiring connections completed between indoor cooling unit and condenser
___ 4. All internal and external high and low voltage wiring connections are tight
___ 5. TCDV condensers only—Check for Delta-Connected Power Supply and make any needed
adjustments per 3.7.1 - VFD Control Condensers (TCDV) only
___ 6. Monitoring wiring connections completed, when equipped, to indoor cooling unit or external
monitoring panel
___ 7. Confirm that unit is properly grounded to an earth ground
___ 8. Control transformer setting matches incoming power
___ 9. Electrical service conforms to national and local codes
___ 10. Check fans for proper phase rotation. Blades should rotate clockwise when viewing the unit
from the fan guard side.
Checklist for Completed Installation

4.3 Piping

___ 1. Piping is completed to corresponding indoor cooling unit refrigeration circuit.
___ 2. Piping leak-checked, evacuated and charged.
___ 3. Piping is properly sized, sloped and trapped for proper oil return.
___ 4. Piping is routed to reduce potential of rub-through or chaffing.

4.4 Other

___ 1. Fans rotate freely and in proper direction
___ 2. Adjust ambient thermostat setpoints to match setpoints on the electrical schematic supplied
___ 3. Foreign material removed from in and around all equipment installed (construction
___ 4. Installation materials and tools have been removed from in and around all equipment
___ 5. Blank start-up sheet located, ready for completion by installer or start-up technician.
with the condenser.
materials, construction debris, etc.).
(literature, shipping materials, tools, etc.).
31
Page 36

5.0 OPERATION

WARNING
!
Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric power supplies before working within. Unit contains
potentially lethal electrical voltage.
Only properly trained and qualified personnel may perform repair, maintenance and cleaning operations.
The fans may start unexpectedly. Disconnect power supply before working on unit. Line side of factory disconnect remains energized when disconnect is off. Use a voltmeter to make sure power is turned off before checking any electrical connections or functions.

5.1 Startup Checklist

Refer to 4.0 - Checklist for Completed Installation and verify that all installation items have been completed before beginning to start the condenser.

5.2 Startup

• Locate “Liebert Condensers and Drycoolers Warranty Inspection Check Sheet” (Document # SAFM-8542-54).
• Turn the condenser disconnect ON. Indoor units should be turned on and set for cooling to allow operation of condenser.
• Check the fans for proper rotation: Clockwise when viewing the unit from the fan guard (top) side. Check that air is being drawn through the coil and discharged out the fan assembly. Some ambi­ent thermostats may need to be temporarily adjusted to lower temperature settings to observe all fans operate. Readjust thermostat settings to correspond to setpoints shown on the electrical schematic supplied with the unit.
• Complete “Liebert Condensers and Drycoolers Warranty Inspection Check Sheet” (Document # SAFM-8542-54).
Operation
NOTE
This document must be completed and forwarded to your local Liebert sales office to validate warranty.
• Contact your local Liebert sales representative or Liebert Air Product Support if you have any questions or problems during unit startup and commissioning.
• Local Liebert sales offices and Liebert air product support contacts can be found at
www.liebert.com/servicesupport_pages/ServiceSupport.aspx?x=servicesupport or by
calling 1-800-LIEBERT.
32
Page 37

6.0 SYSTEM MAINTENANCE

WARNING
!
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working in the unit. Use voltmeter to make sure power is turned Off before making any electrical connections.
Unit contains lethal voltage in some circuits.
Only properly trained and qualified personnel may perform repair, maintenance and cleaning operations.
The fans may start unexpectedly. Disconnect power supply before working on unit. Line side of factory disconnect remains energized when disconnect is off. Use a voltmeter to make sure power is turned off before checking any electrical connections or functions.

6.1 General Procedures

NOTE
When ordering replacement parts for equipment, it is necessary to specify unit model number, serial number, and voltage. Please record those numbers in the spaces below.
• Model Number ____________________________________________________
System Maintenance
• Serial Number ____________________________________________________
• Voltage/Phase/Frequency _________________________________________
Periodic attention is necessary for continued satisfactory operation of your unit. Restricted air flow through the condenser coil, reduced airflow from non-functioning fans and low refrigerant system charge levels will reduce the operating efficiency of the unit and can result in high condensing tem­peratures and loss of cooling. In winter, do not permit snow to accumulate around the sides or under­neath the condenser coil.
Monthly and semi-annual inspections and maintenance are recommended for proper system opera­tion. Use copies of 6.2.2 - Maintenance Inspection Checklist for each of these inspections.
If performance or operation problems are detected at anytime, refer to Table 9 - Troubleshooting for required action.
33
Page 38

6.2 Special Procedures

6.2.1 Condenser Cleaning

Keeping the outdoor condenser coils clean is an important factor in maintaining peak efficiency, reli­ability and long life of the equipment. It is much easier to keep up on frequent cleanings rather than wait until heavy build up has occurred which may create head pressure problems with the evaporator units.
When to Clean
Normal conditions typically dictate cleaning twice a year, spring and fall. On-site or area conditions such as cottonwood trees, construction, etc., can increase cleaning frequency. On your standard monthly preventive maintenance schedule, a visual inspection of the coil is recommended to monitor conditions.
What to Use
The best overall condenser coil cleaner to use is plain water. If the coil has been maintained and cleaned at regular intervals, water is sufficient to remove dirt and debris from the fins. Heavy build up on the exterior of the fins can be removed with a brush. Water pressure from a garden hose and sprayer usually works well. If a pressure washer is used, make sure the equipment is set to a lower pressure setting and that the nozzle is set to the fan spray, not stream. Otherwise, damage to the fins could result. If a cleaner is required, we recommend a non-acidic type cleaner be used. Acid-type cleaners can be aggressive to the coil fins as well as surrounding areas. Many sites do not allow the use of acidic cleaners for environmental reasons.
System Maintenance
How to Clean
The absolute best way to clean coils is from the inside out. This requires disconnecting the power sup­ply from the condenser before working on the unit. The fan guards and fan blades must be removed to gain access to the coil surface. The sprayer can then be worked across the coil using the water/clean­ing solution, pushing the dirt and debris out the bottom of the coil. Although this does extend the time involved, the results are well worth it. This method should be used at least once a year. Spraying the coil from the outside repeatedly can push a majority of the dirt to the inner section of the fins and con­tinue to restrict air flow. Keep in mind you may not have the luxury of shutting the unit(s) down for an extended time. A pre-scheduled shutdown with the operator may be in order. If you are using a cleaner along with the spraying process, follow recommended manufacturer instructions and be sure to rinse the coil thoroughly. Any residue left on the coil can act as a magnet to dirt.
Reinstall and secure the fan blades and fan guards after the cleaning is finished. Last, reconnect the power supply to the condenser.
34
Page 39
System Maintenance

6.2.2 Maintenance Inspection Checklist

Date:____________________________________ Prepared By:____________________________________
Model #:_________________________________ Serial Number:__________________________________
NOTE
Regular inspections are necessary to ensure that the cooling fins are clean. Should inspection reveal dirt or corrosion, appropriate cleaning should be performed.
Monthly Semiannually
Condenser
___ 1. Coil surfaces free of debris
___ 2. Fans free of debris
___ 3. Fan motors securely mounted
___ 4. Motor bearings in good
condition
___ 5. Check all refrigerant lines and
capillaries for vibration isolation. Support as necessary.
___ 6. No refrigerant leaks.
Condenser
___ 1. Complete all monthly items
___ 2. Piping in good condition
___ 3. Inspect refrigerant lines for signs of oil
leaks. Repair leaks as found.
___ 4. Check refrigerant charge level in each
receiver tank (if equipped), based on procedures in the indoor unit’s manual. Continuous system operation required.
___ 5. Wash coil as needed
___ 6. Repair bent or damaged fins.
Condenser Electrical Panel
___ 1. On TCDV models, check TVSS
protection status indicator light.
Notes
Condenser Electric Panel
___ 1. Check all electrical connections
___ 2. Check contactors for pitting
___ 3. Operational sequence/setpoints
Fan Motors
___ 1. Motor # 1 amp draw __________ amps
___ 2. Motor # 2 amp draw __________ amps
___ 3. Motor # 3 amp draw __________ amps
___ 4. Motor # 4 amp draw __________ amps
___ 5. Motor # 5 amp draw __________ amps
___ 6. Motor #6 amp draw __________ amps
___ 7. Motor # 7 amp draw __________ amps
___ 8. Motor # 8 amp draw __________ amps
Signature: _________________________________________________________________________________________
Make photocopies of this form for your records
35
Page 40
Table 9 Troubleshooting
Symptom Possible Cause Check or Remedy
No power to condenser Check voltage at input terminal block
Condenser will not start
Low indoor unit suction pressure
Low discharge pressure
High discharge pressure
VFD Condenser trips out on overvoltage (OU displayed on VFD controller)
TVSS indicator lights are extinguished or red LED is illuminated and monitoring terminals 11/12 are closed
Circuit breaker for low voltage transformer in condenser is tripped
No low voltage signal to/from indoor unit Locate open circuit and repair
Insufficient refrigerant in system Check for leaks, repair, and add refrigerant
Fan-cycling ambient thermostats setpoints too low
Faulty head pressure control valve or condenser FSC/VFD control
Dirty condenser fins Clean coil
Condenser fans not operating
High refrigerant charge Check refrigerant charge
Supply voltage is Delta configuration or is ungrounded/high impedance
No voltage or improper phasing exists at condenser
Electrical connections to TVSS are faulty
A surge exceeding the rating of the TVSS has occurred
Locate problem in condenser electrical panel and repair
Check schematic for recommended setpoints and adjust.
Replace if defective
Check for low voltage signal from indoor unit
Check fan motors and fuses
Check for correct ambient thermostat setpoints, as applicable.
Shut off AC voltage, locate the VFD, pull out the EMC tab and reconnect power
Check voltage at input terminal block
Locate connection problem and repair
Replace TVSS and inspect other components for damage and replace them if necessary
System Maintenance
36
Page 41
NOTES
System Maintenance
37
Page 42
System Maintenance
38
Page 43
Page 44
Ensuring The High Availability 0f Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility and reduced capital equipment and operating costs.
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2007 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
Technical Support / Service
Web Site
www.liebert.com
Monitoring
800-222-5877
monitoring@emersonnetworkpower.com
Outside the US: 614-841-6755
Single-Phase UPS
800-222-5877
upstech@emersonnetworkpower.com
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
powertech@emersonnetworkpower.com
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
852 2572220
Fax: 852 28029250
SL-10066_REV0_12-07
Emerson Network Power. The global leader in enabling Business-Critical Continuity.
AC Power Connectivity
DC Power
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and ser vice marks of Emerson Electric Co.
©2007 Emerson Electric Co.
Embedded Computing Embedded Power Power Switching & Controls Monitoring
Outside Plant
Precision Cooling
EmersonNetworkPower.com
Racks & Integrated Cabinets Services Surge Protection
Loading...