Liebert 308 415, 510 616 830 User Manual

Liebert® Air Cooled, Direct Drive Condensers
Installation, Operation and Maintenance Manual - 50/60Hz
Precision Cooling For Business-Critical Continuity™
Figure i Product model nomenclature
Example: DCDF165-Y
D = Disconnect Switch
(optional on Fan Speed Control, Chiller & Standard Lee-Temp Condensers; standard on Quiet-Line and VFD Control condensers
T = TVSS & Disconnect
Switch; available only on the VFD Control condensers
NOT ALL POSSIBLE COMBINATIONS OF MODELS, CONTROLS AND VOLTAGES ARE AVAILABLE.
C
Condenser
F
F = Fan Speed Control L = Main Control / Lee-Temp C = No Control / Chiller
Lee-Temp
T = Ambient Fan Cycle/
Lee-Temp
V = Variable Frequency
Drive (VFD) Control (available only for dual refrigerant circuit condensers
S = Single Refrigerant Circuit D = Dual Refrigerant Circuit
*
Reserved
Model Size
* Single-phase voltage is only voltage available as standard
on Fan Speed Control 1-fan condensers
* Three-phase voltage is only voltage available as standard
on condensers with VFD Control, Lee-temp receivers, and Fan Speed Control (2-8 fan models only).
* VFD Control Condensers are not available in 575-3-60.
P = 208/230V-1ph-60Hz Z = 460V-1ph-60Hz V = 575V-1ph-60Hz W = 200/230V-1ph-50Hz Y = 208/230V-3ph-60Hz A = 460V-3ph-60Hz B = 575V-3ph-60Hz N = 200/230V-3ph-50Hz M = 380/415V-3ph-50Hz
TABLE OF CONTENTS
1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1 Product Description and Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Head Pressure Control Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2.1 Fan Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2.2 Variable Frequency Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2.3 Liebert Lee-Temp
1.3 Sound Level Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3.1 Standard Condenser. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3.2 Quiet-Line Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.4 Transient Voltage Surge Suppression Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.5 Typical System Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.0 SITE PREPARATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.1 Site Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Refrigerant Planning Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.0 INSPECTION AND INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
3.1 Equipment Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1.1 Packing Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2 Handling Unit on the Skid. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.3 Unpacking the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.4 Preparing a 1-, 2-, 3- or 4-Fan Condenser for Moving and Installation . . . . . . . . . . . . . . . . 15
3.4.1 Removing the Skid and Attaching Slings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.5 Preparing a 6-Fan or 8-Fan Condenser for Moving and Installation . . . . . . . . . . . . . . . . . . 16
3.5.1 Removing the Skid and Attaching Slings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.5.2 Mounting the Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.6 Electrical Supply Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.6.1 Line Voltage Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.6.2 Low Voltage Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.6.3 Low Voltage Monitoring Wiring—TCDV Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.7 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.7.1 VFD Control Condensers (TCDV) only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.7.2 Wye-Connected Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.7.3 Delta-Connected Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.8 Electrical Field Connection Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.9 Refrigeration Piping Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.9.1 Piping Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.9.2 Field Piping Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.10 System Dehydration/Leak Test and Charging Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Refrigerant Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
4.0 CHECKLIST FOR COMPLETED INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
4.1 Moving and Placing Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.2 Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.3 Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
i
4.4 Other . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.0 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
5.1 Startup Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.2 Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6.0 SYSTEM MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
6.1 General Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
6.2 Special Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6.2.1 Condenser Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6.2.2 Maintenance Inspection Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
FIGURES
Figure i Product model nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Inside Front Cover
Figure 1 Liebert two-fan condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Figure 2 Typical system configuration—indoor unit and outdoor condenser and field piping . . . . . . . . . . . 3
Figure 3 Condenser planning dimensional data—One-fan and two-fan units. . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 4 Condenser planning dimensional data—Three-fan and four-fan units . . . . . . . . . . . . . . . . . . . . . . 6
Figure 5 Condenser planning dimensional data—Six- and eight-fan units . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 6 Typical condenser footprint—dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 7 Piping connection locations for 1-, 2-, 3- and 4-fan VFD Control and Fan Speed Condensers . . . 8
Figure 8 Piping connections for 1-, 2-, 3- and 4-fan Lee-Temp and Quiet-Line Condensers . . . . . . . . . . . . . 9
Figure 9 Piping connections for 6- and 8-fan Fan Speed Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 10 Piping connections for 6- and 8-fan Lee-Temp and Quiet-Line Condensers . . . . . . . . . . . . . . . . . 10
Figure 11 Equipment recommended for handling a Liebert condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 12 Removing shipping crate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 13 Attaching legs and sling to a 1-, 2-, 3- or 4-fan condenser for moving . . . . . . . . . . . . . . . . . . . . . . 15
Figure 14 Attaching legs to a 6-fan or 8-fan unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 15 Attaching sling to a 6-fan or 8-fan unit for moving. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 16 Wye-connected power diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 17 Delta-connected power diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 18 Disconnecting EMC filter for operation with Delta-connected power . . . . . . . . . . . . . . . . . . . . . . 22
Figure 19 Electrical field connections for Fan Speed Control Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 20 Electrical field connections for VFD control condensers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 21 Electrical field connections for Liebert Lee-Temp control condensers. . . . . . . . . . . . . . . . . . . . . . 25
Figure 22 VFD and Fan Speed Control condenser piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 23 Lee-Temp head pressure control condenser piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 24 General arrangement—Air cooled models with Lee-Temp control . . . . . . . . . . . . . . . . . . . . . . . . 29
TABLES
Table 1 Condenser shipping weights, dimensions and volume, approximate . . . . . . . . . . . . . . . . . . . . . . . 4
Table 2 Condenser physical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Table 3 R-22 and R-407C refrigerant required, approximate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Table 4 Interconnecting piping refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Table 5 60Hz condenser data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 6 60Hz condenser data, Quiet-Line (Lee-Temp controlled/fan-cycling) . . . . . . . . . . . . . . . . . . . . . . 19
Table 7 50Hz condenser full load amp values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 8 Lee-Temp receiver electrical data, 50Hz and 60Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 9 Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
ii

1.0 INTRODUCTION

1.1 Product Description and Features

The Liebert condenser is low-profile direct-drive propeller fan-type air cooled unit suitable for mount­ing outdoors. It provides for the heat rejection of either one or two separate refrigeration circuits, matching heat rejection capacity varying with the outdoor ambient temperatures with each corre­sponding compressors heat rejection requirements. Constructed with an aluminum cabinet and a cop­per-tube aluminum fin coil, the unit is quiet and corrosion resistant. The condenser is quickly and easily installed, because all internal wiring is completed at the factory with only electrical connec­tions to be made at the job site. All electrical connections and controls are enclosed in an integral weatherproof section of the condenser.

Figure 1 Liebert two-fan condenser

Introduction

1.2 Head Pressure Control Types

1.2.1 Fan Speed

Fan speed control utilizes a wave-chopper control to vary the air volume over the condenser coil, based on refrigerant head pressure. The fan motor next to the electrical panel (two fans on 6-fan and 8-fan models) is a single-phase, permanent split capacitor motor with motor speed adjusted in response to refrigerant pressure. The balance of fans on multi-fan units cycle on ambient thermostats. The control system provides refrigerant head pressure control for outdoor ambients as low as
-20°F (-28.9 °C).

1.2.2 Variable Frequency Drive

VFD Condenser control system utilizes a variable frequency drive, inverter duty fan motor operating from 0% to 100% motor RPM based on head pressure, sensed by refrigerant pressure transducers. VFD, ambient-temperature thermostat(s), motor overload protection and electrical control circuit are factory-wired in the integral control panel. VFD controls the fan adjacent to the connection end of the condenser and remains energized with active compressor operation. The balance of fans on multi-fan units cycle on ambient thermostats. This system provides refrigerant head pressure control for out­door ambients as low as -20°F (-28.9°C).
1

1.2.3 Liebert Lee-Temp™ Refrigerant Control

The Liebert Lee-Temp head pressure control system is designed to maintain proper operating head pressures in outdoor temperatures down to -30°F (-34.4°C). The condensers utilize head pressure con­trol valves, extra refrigerant and insulated refrigerant receivers with heater pads. It works by flood­ing the condenser coil with liquid refrigerant to a level that balances the system condensing requirements with the condenser coil surface available to reject the system heat. During the summer, the system requires the entire condenser coil surface for heat rejection and most of the refrigerant is stored in a receiver. In the winter, the same amount of heat can be rejected by only a fraction of the coil surface. As head pressure begins to fall, the control valve restricts the flow of liquid refrigerant exiting from the condenser. This extra liquid refrigerant reduces the effective condenser surface area available for heat transfer. The head pressure control valve also bypasses hot gas into the receiver to warm the liquid and maintain liquid pressure for proper operation of the expansion valve. Condenser fan controls are either fan cycling on ambient temperature or constant on. Lee-Temp control is required for Quiet-Line Condensers.

1.3 Sound Level Options

1.3.1 Standard Condenser

All Fan Speed and VFD Condensers are standard condensers with moderate operating sound levels. Lee-Temp Condensers with standard-size coils matching Fan Speed and VFD coil sizes are standard sound level condensers.

1.3.2 Quiet-Line Condenser

Introduction
Quiet-Line condensers can help your facility meet the strictest noise codes and do so at less cost than traditional condensers with acoustical shielding. The Quiet-Line condensers utilize the same reliable construction features of the standard condensers and have oversized coils and slower speed fan motors which yield the required heat rejection needed at significantly lower sound levels. Lee-Temp control is required for Quiet-Line Condensers.

1.4 Transient Voltage Surge Suppression Option

Transient Voltage Surge Suppression (TVSS) panel is standard in the VFD Condenser models only. Surge protection is necessary because rooftop voltage supply often is not conditioned the same as the voltage supply inside the data center. The TVSS is designed to protect sensitive electronic condenser components from high voltage transients, up to 25kVA/phase.
An illuminated green LED indicates power supply is On and panel status is OK. An illuminated red LED indicates conditions require service and the TVSS may require replacement to restore surge pro­tection to the condenser.

1.5 Typical System Configurations

Figure 2 shows a single refrigeration circuit diagram, displaying the indoor air conditioning unit, the outdoor condenser (VFD, Fan Speed Control or Lee-Temp) and field supplied interconnection piping.
2
Figure 2 Typical system configuration—indoor unit and outdoor condenser and field piping
Introduction
Inverted trap on discharge & liquid lines to ext end above base of coil by a minimum of 7-1/2” (190mm ).
Fusible Plug
Condenser Coil
(Fan Speed
and VFD )
Fan Speed and VFD
28-42kW Digital Solenoid Valve
53-70kW Digital
Solenoid Valve
Service Valve
Compressor
Chec k Valve
Service Valve
Chec k Valve
Lee-Temp R eceiv er
Condenser Coil
(Lee-Temp )
Lee-Temp
Liquid
Sensing Bulb
Evaporator C oil
Suction
External Equalizer
Pitch horizontal hot gas piping 1/2" per 10 ft. (42mm per 10m) in direction of refr igerant/oil flow.
Relief Valve
Service Valve
Liquid Return
Head Pressure
Control Valve
Hot Gas
Discharge
* Traps every 25ft (7.6m) of rise
Field-installed relief v alve (s) required for 50 Hz EU C E units rated maximum 480 PSIG (33 Bar).
* Isolation valve
Hot Gas Discharge
Expansion Valve
Solenoid
Filter DryerSight Glass
Valve
Factory Refrigerant Piping
Field Refrigerant Piping
Service/Schrader (Access) Connection No Valve Core
Liquid R eturn
Components are not supplied by
*
Liebert, but are recommended for proper circuit operation and maintenance.
Service/Schrader (Access) Connection W ith Valve Core
Note: Sc hematic representation shown . Do not use for specific connection loc ations .
Two refrigeration circuits provided . Single refrigeration circuit shown for clarity .
3
* Isolation valve
DPN000798 Rev. 2

2.0 SITE PREPARATION

2.1 Site Considerations

The condensers should be installed in a location offering maximum security and access for mainte­nance.
Avoid ground-level sites with public access and areas that contribute to heavy snow or ice accumula­tions. Utilize Piggyback condensers whenever interior building locations must be used. To ensure ade­quate air supply, Liebert recommends that condensers be installed in an area with clean air, away from loose dirt and foreign matter that might clog the coil. In addition, condensers should not be located near steam, hot air or fume exhausts. Also, the condensers should be located no closer than 3 feet (1m) from a wall, obstruction or adjacent unit.
The condenser must not be installed in a pit.
The condenser must be installed on a level surface to ensure proper refrigerant flow.
For roof installation, mount the condenser on suitable curbs or other supports in accordance with local codes.
Lee-Temp receiver tanks should be mounted on the condenser legs for proper operation. Remote mounting of tanks must be within 10 feet of the condenser—Contact Liebert Application Engineering Department for assistance.
Site Preparation

2.2 Dimensions and Weights

Table 1 Condenser shipping weights, dimensions and volume, approximate

Number
Model
*C**083 1 330 (150)
DC**063 1 350 (159) 435 (197)
*C**165 2 490 (222)
*C**205 2 560 (254) 760 (345)
DC**119 2 490 (222) 690 (313)
DC**127 2 560 (254) 760 (345)
DC**143 2 655 (297) 855 (388)
*C**251 3 590 (268)
DC**214 3 885 (401) 1165 (528)
*C**415 4 935 (424)
DC**286 4 1185 (537) 1485 (674)
*C**616 6 1560 (708)
DC**409 6 1620 (735) 2070 (939)
*CD*830 8 1930 (875)
DC**572 8 2575 (1168) 3075 (1395)
of Fans
Weight
lb (kg)
Domestic Packaging Export Packaging
Dimensions
(LxWxH)
in. (mm)
59x30x51
(1500x760x1300)
97x30x51
(2460x760x1300)
139x30x51
(3530x760x1300)
179x30x51
(4550x760x1300)
144x36x97
(3660x910x2460)
184x36x97
(4670x910x2460)
Volume
3
ft
(m3)
52 (1.4)
86 (2.4)
123 (3.4)
158 (4.4)
291 (8.3)
372 (10.)
Weight
lb (kg)
415 (188)
690 (313)
870 (395)
1235 (560)
2010 (912)
2430 (1102)
Dimensions
(LxWxH) in. (mm)
60x31x52
(1520x790x1320)
98x31x52
(2490x790x1320)
140x31x52
(3560x790x132)0
180x31x52
(4570x790x1320)
145x37x97
(3680x940x2460)
185x37x97
(4700x940x2460)
Volume
3
ft
(m3)
56 (1.5)*C**104 1 350 (159) 435 (197)
91 (2.5)
131 (3.5)*C**308 3 760 (345) 1040 (472)
168 (4.5)*C**510 4 1230 (558) 1530 (694)
301 (8.4)
384 (10.)*CD*1010 8 2910 (1321) 3410 (1548)
4
Figure 3 Condenser planning dimensional data—One-fan and two-fan units
Site Preparation
51-1/2"
(1308mm)
43-3/16"
(1097mm)
43-9/16"
(1106mm)
18"
(457mm)
44"
(1118mm)
Note: Overall height to the top of fan guard 43-1/8" (1095mm)
42"
ANCHOR PLAN
(1067 mm)
37-7/8"
(962mm)
91-1/2"
(2324mm)
43-3/16"
(1097mm)
ANCHOR PLAN
42"
(1067 mm)
43-9/16"
(1106mm)
37-7/8"
(962mm)
18"
(457mm)
84"
(2134mm)
Liebert recommends a clearance of 36" (915mm) on each side for proper operation and component access.
82" (2083mm)
One -Fan
Condenser
See Figure 6 for typical condenser footprint dimensions.
41-3/16"
(1046 mm)
Electric
Box
End
Legs supplied with Lee-Temp option only
Two-Fan
Condenser
41-3/16"
(1046mm)
5
Figure 4 Condenser planning dimensional data—Three-fan and four-fan units
43-9/16"
(1106mm)
131-1/2"
(3340mm)
37-7/8"
(457mm)
124"
(3150mm)
43-3/16"
(1097mm)
Note: Overall height to the top of fan guard 43-1/8" (1095mm)
ANCHOR PLAN
42"
(1067mm )
(962mm)
18"
Eyebolts for Lifting
43-3/16"
(1097mm)
122" (3099 mm)
171-1/2"
(4356mm)
70"
(1778mm)
164"
(4166mm)
Liebert recommends a clearance of 36" (915mm) on each side for proper operation and component access.
Site Preparation
43-9/16"
(1106mm)
37-7/8"
(962mm)
18"
(457mm)
See Figure 6 for typical condenser footprint dimensions.
Electric
Box
End
Electric
Box End
Legs s upplied with Lee-Temp option only
ANCHOR PLAN
82" (2083 mm)
42"
(1067mm)
Legs s upplied wit h Lee-Temp option only
Three -Fan
Condenser
41-3/16 "
(1046mm )
80"
(2032 mm)
Four-Fan
Condenser
41-3/16"
(1046mm)
6
Figure 5 Condenser planning dimensional data—Six- and eight-fan units
87-1/8"
131-1/2"
(3340mm)
86-3/4"
(2203mm)
Overalll height to the top of the fan guard is 43-1/8” (1095mm).
42"
(1067 mm )
122" (3099 mm)
(2213mm)
59"
(1499mm)
(3150mm)
18"
(457mm)
124"
ANCHOR PLAN
37-7/8"
(962mm)
(4356mm)
86-3/4"
(2203mm)
171-1/2"
1-1/2" (38mm) diameter hole for rigging (typ.4)
Site Preparation
87-1/8"
(2213mm)
37-7/8"
(962mm)
18"
(457mm)
70" (1778mm)
164"
(4166mm)
Liebert recommends a clearance of 36" (915mm) on each side for proper operation and component access.
Electric
Box End
Legs s upplied with Lee-Temp option only
Electric
Box End
Six-Fan
Condenser
82" (2083 mm)
42"
(1067mm)
Legs s upplied with Lee-Temp option only
84-3/ 4"
(2153mm )
See Figure 6 for typical condenser footprint dimensions.
ANCHOR PLAN
80" (2032 mm )
Eight -Fan
Condenser
84-3/4"
(2153 mm)
7
Figure 6 Typical condenser footprint—dimensions
1”
(25.4mm)
1-3/4”
(44.5mm)
4-1/4”
(108mm)
1-3/4”
(44.5mm)
2”
(50.8mm)
Site Preparation
4-1/4”
(108mm)
2”
(50.8mm)
9/16" (14mm)
Typical Diameter

Figure 7 Piping connection locations for 1-, 2-, 3- and 4-fan VFD Control and Fan Speed Condensers

Entering Hot Gas Line
Leaving Liquid Line
Traps to extend above coil base by a minimum of 7-1/2" (190mm)
Inverted Traps (field-supplied)
Metal
Fasten liquid and hot gas lines to leg using flat surface clamps with isolators (field-supplied). Support field piping separately
See Detail A-A
clamp
Isolator
Detail A-A
to avoid coil damage and loss of charge.
DPN000665 Rev. 02
8

Figure 8 Piping connections for 1-, 2-, 3- and 4-fan Lee-Temp and Quiet-Line Condensers

Site Preparation
Hot Gas Line
Liquid
to extend 8" (203mm) above coil base
Line
Fasten liquid and hot gas lines to leg using flat surface clamps with isolators (field-provided). Support field piping separately to avoid coil damage and loss
Inverted Traps (field-supplied)
of charge.
See Detail A-A
Metal clamp
Isolator
Detail A-A

Figure 9 Piping connections for 6- and 8-fan Fan Speed Condensers

Access Valve (Hot Gas) on Condensers (Typ. 2)
Entering Hot Gas Line
Leaving Liquid Line
Position elbow to direct relief valve downward
DPN001067 Rev. 0
Inlet Connection Upper Headers (Typ.)
Fasten liquid and hot gas lines to leg using flat surface clamps with isolators (field-supplied).
Entering Hot Gas Line
Condenser Connections, Typical
Leaving Liquid Line
Inverted traps (field-supplied) to extend above base of coil by a minimum of 7-1/2" (190mm).
Metal
Clamp See Detail
Isolator
A-A
Detail A-A
DPN000668 Rev. 01
9

Figure 10 Piping connections for 6- and 8-fan Lee-Temp and Quiet-Line Condensers

A
ccess Valve (Hot Gas) on
Condensers (Typ. 2)
Site Preparation
Inlet Connection Upper Headers (Typ.)
Condenser Connections, Typical
Liquid Line
Hot Gas Line
Inverted traps (field-supplied) to extend above base of coil by a minimum of 7-1/2" (190mm).
Entering Hot Gas Line
Leaving Liquid Line
Fasten liquid and hot gas lines to leg using flat surface clamps with isolators (field-supplied).
See Detail A-A
Metal Clamp
Position elbow to direct relief valve downward
Note: Two circuits supplied; single circuit shown for clarity.
Isolator
Detail A-A
DPN000670 Rev. 01
10
Loading...
+ 30 hidden pages