The SiteGate-232 is part of the Liebert SiteScan gateway family and provides communications between
a workstation and a control module network (CMnet) consisting of fewer than 50 modules. The
SiteGate-232 provides two EIA-232 Console Ports for connecting a workstation and/or a modem. The
console ports are switch selectable for baud rates up to 38.4k bps.
Communication between the SiteGate-232 and the CMnet is provided through a EIA-485 port. The
SiteGate-232 does not have a Direct Network (DN) connection.
NOTE: You must use FB Link v2.7 or later in order to transfer to any module containing Exec 6.0 or
later.
The CMnet is a peer-to-peer network which allows the various control modules to communicate with
each other. An IBM-compatible computer can communicate on the CMnet through the SiteGate-232
when direct-connected (DC) or modem-connected (MC), or it can communicate on the CMnet through
any other module with a Direct-Network (DN) connection. The SiteGate-232 does not have a DirectNetwork (DN) connection.
The CMnet communicates using the EIA-485 standard. A "token passing" scheme is used so that each
module has the token in turn. When a module has the token, it broadcasts whatever information is
appropriate from its FBs, while all other modules on the CMnet listen. Any module may receive
information from any other module, but it may broadcast only when it has the token.
When a module is finished with the token, it passes it to the next module (or back to the gateway, if
using grabless token passing) by broadcasting a token-pass message using the next module's address.
The receiving module must acknowledge this message to complete the pass. The SiteGate-232 listens
for an address which is equal to the total number of modules on the CMnet plus one (also referred to as
the Maxnet value). When the last module on the CMnet attempts to pass the token by broadcasting
the Maxnet value, the SiteGate-232 acknowledges the token and starts the cycle over.
Signal integrity on the CMnet is affected by the wire gauge and the total amount of wire in the
segment. A segment is defined as the network of modules between main nodes. Main nodes can be
represented by a gateway module, or a repeater (part no. REPOPT). A repeater can be used to end one
segment and begin another, all on the same CMnet.
It is recommended that only a dedicated, 22AWG to 18AWG twisted pair copper wire be used for
CMnet (EIA-485) wiring. Wire sizes smaller than 22 gauge or wires that are not twisted may cause
intermittent communication problems.
NOTE: For further explanation of communications wiring, see the Technical Handbook.
System Architecture
The Liebert Architecture is designed to support both large and small systems. Small systems (those
using less than 50 control modules) require only a single SiteGate-232 which serves the entire Control
Module Network, or CMnet (see Figure 2). The SiteGate-232 communicates with the workstation via a
EIA-232 serial communication port. A second EIA-232 port can be used for communication with
another operator workstation or a portable field computer via modem or direct EIA-232 connection.
The SiteGate-232 communicates with the CMnet through a EIA-485 port. This CMnet is a peer-to-peer
local area network which uses a "token-passing" protocol to allow all control modules to communicate
with one another with equal authority. Each control module is capable of stand-alone DDC (Direct
Digital Control), thus increasing system reliability and performance.
Mounting
Mount the SiteGate-232 in an enclosure using the four holes provided on the module's cover plate (see
Figure 3). Recommended screw size is 8. Make sure that nothing comes in contact with the back of
the printed circuit board, and leave approximately 2 inches on each side for wiring.
The SiteGate-232 is designed to be mounted inside the building envelope. All warranties are void if
mounted outside.
CAUTION: The SiteGate-232 modules are Class 2 devices (less than 30 VAC). Take appropriate
isolation measures when mounting a SiteGate-232 module in a control panel where Class 1 devices or
wiring are present.
NOTE: Whenever possible, terminate and verify power and communication to all modules before
terminating any inputs and outputs.
1. Terminate AC power at the wiring source (usually a circuit breaker or other AC source).
2. Apply power to the transformer.
3. Turn the SiteGate-232's power switch OFF (see Figure 1 for location) to prevent the module from
being powered up until proper voltage is verified.
4. If you are using an internally grounded transformer, terminate the Earth Ground wire to the Gnd
screw terminal as indicated in Figure 4.
CAUTION: Be sure to follow proper polarity on power connections. Note INCORRECT power wiring
in Figure 5.
If the transformer is not internally grounded, terminate the two power wires as indicated in
Figure 6.
5. Verify that 24 VAC is present at the power input terminals and turn the SiteGate-232's power
switch on.
6. Once the power wiring procedure has been completed, the "Run" LED should turn on and begin
blinking. If this does not occur, turn the power switch off and check for wiring errors.
The SiteGate-232 module's address is factory-set as control module #1 and cannot be changed.
NOTE: The CMnet Baud Rate jumper (see Figure 1 for location) is only used to configure the CMnet for
156k bps. If the CMnet Baud Rate jumper is set to 156k, the CMnet Baud DIP switch is ignored.
The CMnet communication speed and baud rates for the SiteGate-232's console ports are configured
using an 8-position DIP switch. The following is a list of each switch position and its function.
DIP Switch
NumberFunction
1This switch selects the CMnet communication baud rate. When this switch is in the left
position, the SiteGate-232's CMnet baud rate is set at 9600 bps. When the switch is in the
right position, the CMnet baud rate is set at 38.4k bps.
NOTE: All modules on the CMnet must use the same baud rate.
2This switch selects Console 1's communication baud rate. When this switch is in the left
position, the Console 1 baud rate is set at 9600 bps. When the switch is in the right
position, the Console 1 baud rate is set at 38.4k bps.
3This switch selects Console 2's communication baud rate. When this switch is in the left
position, the Console 2 baud rate is set at 9600 bps. When the switch is in the right
position, the Console 2 baud rate is set at 38.4k bps.
4-8Not used.
Example:
As shown in Figure 7, switch 1 is in the 38.4k position, switch 2 is in the 9600 position, and switch 3
is in the 38.4k position. As a result, the SiteGate-232 is configured as follows: