Liberty Pumps AE21L=3, AE24L=3, AE21H=3, AE21L=4, AE21H=4 Installation Manual

...
Page 1
Single Phase Duplex
ELECTRICAL SHOCK HAZARD
Disconnect power before installing or servicing this product. A qualified service person must install and service this product according to applicable electrical and plumbing codes.
EXPLOSION OR FIRE HAZARD
Do not use this product with flamable liquids Do not install in hazardous locations as defined by National Electrical Code, ANSI/NFPA 70.
Failure to follow these precautions could result in serious injury or death. Replace product immediately if switch cable becomes damaged
or severed. Keep these instructions with warranty after installation. This product must be installed in accordance with National Electric
Code, ANSI/NFPA 70 so as to prevent moisture from entering or accumulating within boxes, conduit bodies, fittings, float housing, or cable.
AE21L=3, AE21H=3, AE21L=4, AE21H=4
AE24L=3, AE24H=3, AE24L=4, and AE24H=4
Manufactured by SJE-Rhombus
Installation Instructions and Operation/Troubleshooting Manual
7000 Apple Tree Avenue
Bergen, New York 14416
Phone: 1-800-543-2550
Email: liberty@libertypumps.com
www.libertypumps.com
This control panel must be installed and serviced by a licensed electrician in accordance
with the National Electric Code NFPA-70, state and local electrical codes.
to rain, splashing water or hose-directed water. NEMA 4X enclosures are for indoor or outdoor use, primarily to provide a degree of protection against corrosion, windblown dust and rain, splashing water and hose-directed water. Cable connectors must be liquid-tight in NEMA 4X enclosures.
®
Warranty void if panel is modifi ed.
Call factory with servicing questions:

7249000B

1-800-543-2550
Page 2
Installation Instructions
Most single phase duplex panels are designed to operate as three or four fl oat systems. The three fl oat system is standard performing the common pump stop, lead pump start, and lag pump start/high level alarm functions. The four fl oat system utilizes separate fl oats for lag pump start and high level alarm.
NOTE: Options ordered may affect the number of fl oats and their functions. Please reference the schematic provided with the control panel for proper installation.
Installation of Floats
CAUTION: If control switch cables are not wired and mounted in the correct location, the pump system will not function properly .
WARNING: Turn off all power before installing fl oats in pump chamber. Failure to do so could result in serious or fatal electrical shock.
1. Use oat label kit to identify and label cables on both oat and stripped ends (stop, lead, lag, alarm, etc.). See schematic for oat options.
2. Determine your normal operating level, as illustrated in
Figures 1-2.
FIGURE 1: Three oat duplex
FIGURE 2: Four oat duplex
FIGURE 3: Internally weighted oat
3. Mount oat switches at appropriate levels as illustrated in Figures 3-5. Be sure that oats have free range of motion
without touching each other, or other equipment in the basin.
If using the mounting clamp; follow steps 4-6.
4. Place the cord into the clamp as shown in Figure 5.
5. Locate the clamp at the desired activation level and secure the clamp to the discharge pipe as shown in Figure 5.
NOTE: Do not install cord under hose clamp.
6. Tighten the hose clamp using a screwdriver . Over tightening
may result in damage to the plastic clamp. Make sure the oat cable is not allowed to touch the excess hose clamp band during operation.
NOTE: All hose clamp components are made of 18-8
stainless steel material. See your SJE-Rhombus® supplier for replacements.
FIGURE 4: Float with cable weight
FIGURE 5: Mounting clamp detail
7249000B
- 2 -
Page 3
Installation Instructions
Mounting the control panel
1. Determine mounting location for panel. If distance exceeds the length of either the fl oat switch cables or the pump power cables, splicing will be required. For outdoor or wet installation, we recommend the use of a SJE­Rhombus® liquid-tight junction box with liquid­tight connectors to make required connections.
You must use conduit sealant to prevent moisture or gases from entering the panel.
2. Mount control panel with mounting anges
furnished with control panel.
8. Run conduit to junction box. Drill proper size holes for the type of conduit used. Attach liquid­tight connectors to junction box.
9. Identify and label each wire before pulling through conduit into control panel and junction box. Pull pump power cables and control switch cables through connectors into junction box. Make wire splice connections at junction box.
10. Firmly tighten and seal all fi ttings on junction box. Insure all cable connectors are liquid-tight and sealed.
3. Determine conduit entrance locations on control panel. Check local codes and schematic for the number of power circuits required.
NOTE: Be sure the incoming power, voltage,
amperage, and phase meet the requirements of the pump motors being installed. If in doubt, see the pump identifi cation plate for electrical requirements.
4. Drill proper size holes for type of connectors being used.
NOTE: If using conduit, be sure that it is of
adequate size to pull the pump and switch cables through. You must use conduit
sealant to prevent moisture or gases from entering the panel.
5. Attach cable connectors and/or conduit
connectors to control panel.
11. If a junction box is not required, connect pump and fl oat wires to proper position on terminals. See schematic inside control panel for terminal layouts.
12. Connect control/alarm and pump power conductors to proper position on terminals. See schematic inside control panel for terminal connections.
NOTE: It is the recommendation of the factory to
use separate pump and control/alarm power sources.
VERIFY CORRECT OPERATION OF CONTROL
P ANEL AFTER INST ALLATION
IS COMPLETE.
FOR INSTALLATION REQUIRING A SPLICE,
FOLLOW STEPS 6-10;
FOR INSTALLATION WITHOUT A SPLICE,
GO TO STEP 11.
6. Determine location for mounting junction box according to local code requirements. Do not mount the junction box inside the sump or basin.
7. Mount junction box to proper support.
7249000B
- 3 -
Page 4
Operations
Single phase duplex panels are designed to oper­ate with three or four fl oats for pump sequencing. The standard fl oat functions are common pump stop, lead pump start, lag pump start/alarm (three
oats), or separate lag and alarm fl oats (four oats).
Three Float Operation: As the liquid level rises to the stop fl oat and tips it to the ON (closed) position, the panel will remain inactive. As the liquid level tips the lead fl oat, the lead pump will start. If the liquid level tips the lag/alarm fl oat, the lag pump will start and the audio/visual alarm will activate. Both pumps and the alarm will remain active until the liquid level drops and the lag fl oat is in the OFF (open) position. At this time the alarm will silence. Both pumps will remain on until the liquid level drops to normal and all three fl oats are in the OFF (open) position. When both pumps have stopped running, the alternator will switch the lead pump and lag pump operating functions in the next sequence. Four Float Operation: The alarm will activate and remain on only if the alarm fl oat is tipped to the ON (closed) position.
Control and Alarm Lights
Lights will illuminate when control/alarm power is supplied.
Float Status Lights
Lights will illuminate when the respective fl oat is in the closed position.
Circuit Breaker (optional)
The pump circuit has a thermal-magnetic circuit breaker which provides pump disconnect and branch circuit protection.
Dry Auxiliary Contacts (standard feature)
Normally open - Contacts are open under nor­mal conditions and closed when alarm condition is present. Normally closed - Contacts are closed under normal conditions and open when alarm condition is present. Both types automatically reset once alarm condition is cleared.
Alarm System (Horn and Indicator ­standard)
When an alarm condition occurs, a red light and a horn will be activated. If the test/normal/silence switch is moved to the silence position, the horn will be silenced. When the alarm condition is cleared, the alarm system is reset. The alarm system can be tested by moving the test/normal/ silence switch to the test position.
HOA Switch
A hand-off-automatic switch is provided for each pump. In the hand mode, the pump will turn on unless other safety features are employed. In the automatic mode, the pump will turn on from commands by the fl oat switch(es).
Pump Run Lights
The run light will be ON in either the hand or the automatic mode when the pump is called to run.
NOTE: Some options ordered may not be included in this manual. Certain options will require alterna­tive circuitry not including fl oat status and control/ alarm indicators.
For information regarding the operations
of options not listed here or servicing
questions, please call a Liberty Pumps
customer service technician at
1-800-543-2550
Warranty void if panel is modifi ed.
Control and Alarm Fusing
The control circuit and alarm circuit are fused separately.
7249000B
- 4 -
Page 5
Troubleshooting
Control/Alarm Circuit Board Power
If the green power status indicators are not illuminated:
1. Check to see if the fuses on the circuit board are blown.
2. Check to see if the incoming control/alarm power is present at TB1-1 and TB1-2.
the alarm light. If the light does not activate, replace with bulb of same type.
Float Controls
Check the floats during their entire range of operation. Clean, adjust, or replace damaged fl oats.
Checking the float resistance - The float resistance can be measured to determine if the oat is operating correctly or is defective. Use the following procedure to measure the fl oat resistance.
Warning: Disconnect all incoming power to panel. Failure to do so could result in serious or fatal electrical shock.
1. Isolate the oat by disconnecting one or both of
the fl oat leads from the fl oat terminals.
If voltage is present and fuse is not blown, please call factory for assistance.
Circuit Breaker (optional)
Check each pole of the circuit breaker for proper resistance reading using the following procedure:
Warning: Disconnect all incoming power to control panel. Failure to do so could result in serious or fatal electrical shock.
1. Isolate the circuit breaker by disconnecting
either the line side or load side wires.
2. Place the ohmmeter leads across the corresponding line and load terminals of each pole.
3. With the ohmmeter on the R X 1 scale and the breaker in the OFF position, the reading should be infinity (very high resistance). With the breaker in the ON position, the reading should be nearly zero ohms (very low resistance). If the readings are not as stated, replace the circuit breaker with one of the same ratings.
2. Place one ohmmeter lead on one of the fl oat wires, and the other ohmmeter lead on the other oat wire.
3. Place the ohmmeter dial to read ohms and place on the R X 1 scale. With the fl oat in the “off” position, the scale should read infi nity (high resistance). Replace the fl oat if you do not get this reading. With the fl oat in the ON position, the scale should read nearly zero (very low resistance). Replace the fl oat if you do not get this reading.
NOTE: Readings may vary depending on the length of wire and accuracy of the measuring device.
Fuses
Check the continuity of each fuse. With power OFF, pull the fuses out of the fuse blocks. With the ohmmeter on the R X 1 scale, measure resistance. A reading of infi nity indicates a blown fuse and must be replaced. Replace fuse with same type, voltage and amp rating.
Alarm Horn
Moving the test/normal/silence switch to the test position or activating the alarm fl oat should turn on the alarm horn. If the horn does not sound, replace horn with same type.
Alarm Light
Moving the test/normal/silence switch to the test position or activating the alarm fl oat should turn on
7249000B
Magnetic Contactor Coil
Warning: Disconnect all incoming power to panel. Failure to do so could result in serious or fatal electrical shock. Check the coil by
disconnecting one of the coil leads. Measure the coil resistance by setting the ohmmeter on the R X 1 scale. A defective coil will read zero or infi nity, indicating a short or opened coil respectively. Replace defective contactor with same type.
- 5 -
Page 6
Liberty Pumps Three-Year Limited Warranty
*
NOTE: Liberty Pumps, Inc. assumes no responsibility for damage or injury due to disassembly in the eld. Disassembly, other than at Liberty Pumps or its authorized service centers, automatically voids warranty.
Liberty Pumps, Inc. warrants that pumps of its manufacture are free from all factory defects in material and workmanship for a period of 3 years from the date of purchase. The date of purchase shall be determined by a dated sales receipt noting the model and serial number of the pump. The dated sales receipt must accompany the returned pump if the date of return is more than 3 years from the “CODE” (date of manufacture) number noted on the pump nameplate.
The manufacturer’s obligation under this Warranty shall be limited to the repair or replacement of any parts found by the manufacturer to be defective, provided the part or assembly is returned freight prepaid to the manufacturer or its authorized service center, and provided that none of the following warranty­voiding characteristics are evident.
The manufacturer shall not be liable under this Warranty if the product has not been properly installed; if it has been disassembled, modifi ed, abused or tampered with; if the electrical cord has been cut, damaged or spliced; if the pump discharge has been reduced in size; if the pump has been used in water temperatures above the advertised rating, or water containing sand, lime, cement, gravel or other abrasives; if the product has been used to pump chemicals or hydrocarbons; if a non-submersible motor has been subjected to excessive moisture; or if the label bearing the serial, model and code number has been removed. Liberty Pumps, Inc. shall not be liable for any loss, damage or expenses resulting from installation or use of its products, or for consequential damages, including costs of removal, reinstallation or transportation.
There is no other express warranty . All implied warranties, including those of merchantability and fi tness for a particular purpose, are limited to three years from the date of purchase.
This Warranty contains the exclusive remedy of the purchaser, and, where permitted, liability for consequential or incidental damages under any and all warranties are excluded.
7000 Apple Tree Avenue
Bergen, New York 14416
Phone: 1-800-543-2550
Email: liberty@libertypumps.com
©SJE-Rhombus
Printed in USA
PN1025047B • Rev 06/12
7249000B
www.libertypumps.com
- 6 -
Page 7
Three Phase Duplex
ELECTRICAL SHOCK HAZARD
Disconnect power before installing or servicing this product. A qualified service person must install and service this product according to applicable electrical and plumbing codes.
EXPLOSION OR FIRE HAZARD
Do not use this product with flamable liquids Do not install in hazardous locations as defined by National Electrical Code, ANSI/NFPA 70.
Failure to follow these precautions could result in serious injury or death. Replace product immediately if switch cable becomes damaged
or severed. Keep these instructions with warranty after installation. This product must be installed in accordance with National Electric
Code, ANSI/NFPA 70 so as to prevent moisture from entering or accumulating within boxes, conduit bodies, fittings, float housing, or cable.
AE34=3-131, AE34=3-141, AE34=3-171, AE34=3-191, AE34=3-511, AE34=4-131, AE34=4-141, AE34=4-171,
AE34=4-191, AE34=5-511, AE54=3-121, and AE54=4-121
Manufactured by SJE-Rhombus
®
Installation Instructions and Operation/Troubleshooting Manual
7000 Apple Tree Avenue
Bergen, New York 14416
Phone: 1-800-543-2550
Email: liberty@libertypumps.com
www.libertypumps.com
This control panel must be installed and serviced by a licensed electrician in accordance
with the National Electric Code NFPA-70, state and local electrical codes.
Warranty void if panel is modifi ed.
Call factory with servicing questions:

7228000B

1-800-543-2550
Page 8
Installation Instructions
3.5 inch (9 cm) tether length
7"
5
5
suspended cable
4" tether length
CABLE
WEIGHT
approximate
activation level
Most three phase duplex panels are designed to operate with three or four fl oat systems. The three fl oat system is standard, perform- ing the common pump stop, lead pump start, and lag pump start/ high level alarm functions. The four fl oat system utilizes separate oats for each function.
NOTE: Options ordered may affect the number of fl oats and their functions. Please reference the schematic provided with the control panel for proper installation.
Installation of Floats
CAUTION: If control switch cables are not wired and mounted in the correct order, the pump system will not function properly.
WARNING: Turn off all power before installing fl oats in pump cham- ber. Failure to do so could result in serious or fatal electrical shock.
1. Use fl oat label kit to identify and label cables on both fl oat and stripped ends (stop, lead, lag, alarm, etc.). See schematic for oat options.
FIGURE 1: Three oat duplex
FIGURE 2: Four oat duplex
2. Determine your normal operating level, as illustrated in Figures 1 & 2.
3. Mount oat switches at appropriate levels as illustrated in Fig- ures 3-5. Be sure that oats have free range of motion without
touching each other or other equipment in the basin.
If using the mounting clamp; follow steps 4-6.
4. Place the cord into the clamp as shown in Figure 5.
5. Locate the clamp at the desired activation level and secure the clamp to the discharge pipe as shown in Figure 5.
NOTE: Do not install cord under hose clamp.
6. Tighten the hose clamp using a screwdriver. Over tightening
may result in damage to the plastic clamp. Make sure the fl oat cable is not allowed to touch the excess hose clamp band during operation.
FIGURE 3: Internally weighted oat
suspended cable
approximate
activation level
FIGURE 4: Float with cable weight
FIGURE 5: Mounting clamp detail
NOTE: All hose clamp components are made of 18-8
stainless steel material. See your SJE-Rhombus® supplier for replacements.
- 2 -
7228000B
Page 9
Installation InstructionsInstallation InstructionsInstallation InstructionsInstallation InstructionsInstallation InstructionsInstallation InstructionsInstallation InstructionsInstallation InstructionsInstallation Instructions
Mounting the Control Panel
1. Determine mounting location for panel. If dis-
tance exceeds the length of either the fl oat switch cables or the pump power cables, splicing will be required. For outdoor or wet installation, we recommend the use of an SJE-
®
Rhombus tight connectors to make required connections.
You must use conduit sealant to prevent moisture or gases from entering the panel.
2. Mount control panel with mounting devices
furnished.
3. Determine conduit entrance locations on control
panel.
NOTE: Be sure the incoming power, voltage,
amperage, and phase meet the requirements of the pump motors being installed. If in doubt, see the pump identifi cation plate for electrical requirements.
4. Drill proper size holes for type of connectors
being used.
NOTE: If using conduit, be sure that it is of ad-
equate size to pull the pump and switch cables through.
5. Attach cable connectors and/or conduit con-
nectors to control panel.
liquid-tight junction box with liquid-
8. Identify and label each wire before pulling through conduit into control panel and junction box. Make wire splice connections at junction box.
9. Firmly tighten all ttings on junction box.
10. If a junction box is not required, pull cables
through conduit into control panel.
11. Set motor protective switches:
a) set the dials to match motor full load
amps.
b) turn dial on motor protective switch to the
ON position.
NOTE: Resetting the dial with power applied
to the motor protective switch could start the motor.
12. Connect pump wires directly to the motor con-
tactors terminal positions T1, T2, and T3.
NOTE: Three-phase motors will run in either
direction. Check pump motor before installation for proper rotation. To correct rotation, change pump cable connections on any two terminals T1-T2-T3.
13. Connect “power-in” conductors to proper locations: 208/240/480 VAC on the 3 position terminal block. Install tagged factory wire to
appropriate transformer primary voltage tap.
FOR INSTALLATION WITHOUT A SPLICE,
GO TO STEP 10; FOR INSTALLATION RE-
QUIRING
A SPLICE, FOLLOW STEPS 6-9.
6. Determine location for mounting junction box according to state and local code requirements. Mount the junction box to proper support.
7. Run conduit to junction box. Drill proper size holes for the type of conduit used. Attach con­nectors to junction box.
7228000B
VERIFY CORRECT OPERATION
OF CONTROL PANEL AFTER
INSTALLATION IS COMPLETE.
- 3 -
Page 10
Operations
Three phase duplex panels are designed to operate with three or four fl oats for pump sequencing. The standard fl oat functions are common pump stop, lead pump start, lag pump start/alarm (three fl oats), or separate lag and alarm fl oats (four fl oats). Other oat options, such as redundant off, are available. Three Float Operation: As the liquid level passes the stop fl oat and tips it to the ON (closed) position, the panel will remain inactive. As the liquid level tips the lead fl oat, the lead pump will start. If the liquid level tips the lag/alarm fl oat, the lag pump will start and the audio/visual alarm will activate. Both pumps and the alarm will remain active until the liquid level drops and the lag fl oat is in the OFF (open) position. At this time the alarm will silence. Both pumps will remain on until the liquid level drops to normal and all three fl oats are in the OFF (open) position. When both pumps have stopped running, the alternator will switch the lead pump and lag pump operating functions in the next sequence. Four Float Operation: The alarm will activate and remain on only if the alarm fl oat is tipped to the ON (closed) position.
Alarm System (Horn and Indicator)
When an alarm condition occurs, a red light and a horn will be activated. If the test/normal/silence switch is moved to the silence position, the horn will be silenced. When the alarm condition is cleared, the alarm system is reset. The alarm system can be tested by moving the test/normal/silence switch to the test position.
Control/Alarm Switch
Allows the control/alarm power to be turned on or off.
HOA Switch
A hand-off-automatic switch is provided for each pump. In the hand mode, the pump will turn on unless other safety features are employed. In the automatic mode, the pump will turn on from commands by the fl oat switches.
wired in series with the magnetic contactor coil so that on an overload trip, the magnetic contactor will be disabled. In the event of an overload trip, the motor protective switch must be reset by fi rst turning the selector handle counterclockwise to the OFF position and then turning the handle 90 clockwise to the ON position.
o
Control/Alarm Light
The light will illuminate when the control ON/OFF switch is in the ON position.
Pump Run Lights
Each pump has a run light. The run light will be ON in either the hand or the automatic mode when the pump is called to run.
Float Status Lights
Lights will illuminate when the respective fl oat is in the closed position.
Dry Auxiliary Contacts (optional)
Normally open - Contacts are open under normal conditions and closed when alarm condition is present. Normally closed - Contacts are closed under normal conditions and open when alarm condition is present.
Both types automatically reset once alarm condition is cleared.
Seal Failure Circuit and Indicator Light (optional)
The seal fail circuit has resistance sensitivity and will sense the presence of water in the pump seal chamber. Upon installation, turn the sensitivity dial on the seal fail module to the point where the light turns on, then dial back slowly until the light turns off. If water enters the seal chamber at this point, the seal fail circuit will sense the change in resistance. After a short time delay, the indicator light will turn on. When the condition is cleared, the relay will de-energize and the indicator light will turn off. The seal fail relay has a sensitivity adjustment
so that false readings may be tuned out.
Motor Protective Switch
A motor protective switch is supplied for each pump to provide an adjustable overload, branch circuit protection and disconnect. The overload must be set in the fi eld. To set the overload, dial the amp scale to the pump’s full load amp rating (FLA). If the FLA’s are unknown, use a calibrated amp meter to measure the pump amperage draw under loaded conditions. An auxiliary contact is
7228000B
Thermal Cutout (optional)
The thermal cutout is wired in series with the magnetic contactor coil. If the pump’s thermal switch opens on high temperature, the contactor will turn off and stop the pump. When the thermal switch cools and closes, the magnetic contactor will turn on if the pump is called to run.
NOTE: Some options ordered may not be included in this manual.
- 4 -
Page 11
Troubleshooting
Alarm Horn
Pressing the alarm test/normal/silence switch to the test position or activating the alarm fl oat should turn on the alarm horn. If the horn does not sound, replace with horn of same type.
Alarm Light
Pressing the alarm test/normal/silence switch to the test position or activating the alarm fl oat should turn on the alarm light. If the light does not activate, replace with bulb of same type.
3. Place the ohmmeter dial to read ohms and place on the R X 1 scale. With the fl oat in the “off” position, the scale should read infi nity (high resistance). Replace the fl oat if you do not get this reading. With the fl oat in the ON position, the scale should read nearly zero (very low resistance). Replace the fl oat if you do not get this reading.
NOTE: Readings may vary depending on the length of wire and accuracy of the measuring device.
Fuses
Check the continuity of the fuse. Pull the fuse out of the fuse block. With the ohmmeter on the R X 1 scale, measure resistance. A reading of infi nity indicates a blown fuse and must be replaced. Replace fuse with same type, voltage and amp rating.
Alternating Relay or Device
The alternation can be sequenced by lifting the oat switches or making jumper wires to simulate the fl oats closing. If the alternator fails during testing, replace with same type. Consult factory at 1-800-RHOMBUS (1-800-746-6287) when in doubt about testing procedures or results.
Float Controls
Check the fl oats through their entire range of operation. Clean, adjust, or replace damaged oats.
Checking the float resistance - The float resistance can be measured to determine if the oat is operating correctly or is defective. Use the following procedure to measure the float resistance:
1. Isolate the fl oat by disconnecting one or both of the fl oat leads from the fl oat terminals.
Magnetic Contactor
Contacts - Check the contacts for severely burnt or welded contacts. The contactor arm should move freely. Coil - Measure the coil by disconnecting one of the coil leads. Measure the coil resistance by setting the ohmmeter on the R X 1 scale. A defective coil will read zero or infi nity, indicating a short or opened coil respectively . If contactor is defective, replace with same type.
NOTE: Readings may vary slightly depending on the and accuracy of the measuring device.
Motor Protective Switch
T est by inserting a paper clip or other small device into the test hole and push to the left. The relay should trip.
2. Place one ohmmeter lead on one of the fl oat wires, and the other ohmmeter lead on the other fl oat wire.
7228000B
- 5 -
Page 12
Liberty Pumps Three-Year Limited Warranty
*
NOTE: Liberty Pumps, Inc. assumes no responsibility for damage or injury due to disassembly in the eld. Disassembly, other than at Liberty Pumps or its authorized service centers, automatically voids warranty.
Liberty Pumps, Inc. warrants that pumps of its manufacture are free from all factory defects in material and workmanship for a period of 3 years from the date of purchase. The date of purchase shall be determined by a dated sales receipt noting the model and serial number of the pump. The dated sales receipt must accompany the returned pump if the date of return is more than 3 years from the “CODE” (date of manufacture) number noted on the pump nameplate.
The manufacturer’s obligation under this Warranty shall be limited to the repair or replacement of any parts found by the manufacturer to be defective, provided the part or assembly is returned freight prepaid to the manufacturer or its authorized service center, and provided that none of the following warranty­voiding characteristics are evident.
The manufacturer shall not be liable under this Warranty if the product has not been properly installed; if it has been disassembled, modifi ed, abused or tampered with; if the electrical cord has been cut, damaged or spliced; if the pump discharge has been reduced in size; if the pump has been used in water temperatures above the advertised rating, or water containing sand, lime, cement, gravel or other abrasives; if the product has been used to pump chemicals or hydrocarbons; if a non-submersible motor has been subjected to excessive moisture; or if the label bearing the serial, model and code number has been removed. Liberty Pumps, Inc. shall not be liable for any loss, damage or expenses resulting from installation or use of its products, or for consequential damages, including costs of removal, reinstallation or transportation.
There is no other express warranty . All implied warranties, including those of merchantability and fi tness for a particular purpose, are limited to three years from the date of purchase.
This Warranty contains the exclusive remedy of the purchaser, and, where permitted, liability for consequential or incidental damages under any and all warranties are excluded.
7000 Apple Tree Avenue
Bergen, New York 14416
Phone: 1-800-543-2550
Email: liberty@libertypumps.com
©SJE-Rhombus
Printed in USA
PN1025048B • Rev 06/12
7228000B
www.libertypumps.com
- 6 -
Loading...