Liberty Pumps 2460 User Manual

IMPORTANT:
Prior to installation, record Model, Serial Number, and Code Number from pump nameplate for future reference.
MODEL ________________________
SERIAL ______________________
DATE _______________________
Installation Manual
5651000I
Features:
LSG or LSGX Series 2HP Grinder Pump  24” dia. Basin available in 60”, 72”, or 84” depths  Guide Rail System Preassembled including ball & check valves Simplex Panel with Alarm –or- Automatic Pump
with Alarm
Contents
1. General Information
2. Precautions / Pre-Installation
3. Installation Instructions
4. Maintenance & Troubleshooting
5. GR20 Assembly
2460 / 2472 / 2484 - Series Simplex Grinder Systems
7000 Apple Tree Avenue Bergen, NY 14416 Phone: (800) 543-2550 Fax: (585) 494-1839 www.libertypumps.com
©Copyright 2012 Liberty Pumps Inc. All rights reserved 1
1 General Information
Maximum fluid temperature: 140F (60C)
The LSG or LSGX Series grinder pump and the control panel are supplied with their own separate
Installation/Operation/Maintenance manuals. Ensure that you have received these manuals, and that you read and understand them prior to installing this unit. Your familiarity with the grinder pump manual and the control panel manual is critical. This installation manual gives a brief overview of the system, and deals mainly with inspection and installation of the basin, but it does not cover the specifics of the pump operation or the control panel operation. If you have any questions, call customer service at (800) 543-2550 or visit www.libertypumps.com.
2 Precautions / Pre-Installation
Risk of electric shock. Always disconnect the pump from the power source before handling or making adjustments. These pumps are not to be installed in locations classified as hazardous in accordance with the National Electric Code, ANSI/NFPA
70.
The electrical connections and wiring for a pump installation should only be made by qualified personnel. This pump is supplied with a grounding conductor or a grounding-type attachment plug. To reduce the risk of electric shock, be
certain that the grounding conductor is connected only to a properly grounded control panel or, if equipped with a grounding-type plug, that it is connected to a properly grounded, grounding-type receptacle.
Do not bypass grounding wires or remove ground prong from attachment plugs. Do not remove cord and strain relief, and do not connect conduit to pump. Do not use an extension cord. This pump requires separate, properly fused and grounded branch circuit. Make sure the power source is properly sized for the
voltage and amperage requirements of the motor, as noted on the pump nameplate.
The installation must be in accordance with the National Electric Code and all applicable local codes and ordinances. Sump and sewage pumps often handle materials which could cause illness or disease. Wear adequate protective clothing when
working on a used pump or piping.
Never enter a pump basin after it has been used. Sewage and effluent can emit several gases which are poisonous.
Pre-installation checklist:
1. Inspect system unit upon arrival to ensure that there is no shipping damage. Pay careful attention to the condition of the fiberglass basin, control floats, pump guide rail brackets, and control panel. Notify the carrier immediately if there is any damage.
2. Read all instructions and familiarize yourself with the unit’s operation prior to proceeding with the installation.
3. A qualified licensed electrician should install and test all electrical circuits.
4. Check to ensure that your power source is adequate to handle the pump amperage as noted above and on the pump nameplate. Ensure that the electrical supply circuit is equipped with fuses or breakers of the proper capacity.
5. A separate 115V branch circuit should be installed for the alarm. We do not recommend splitting the incoming pump power circuit to power the control circuit.
6. All electrical connections should be tested to ensure that a proper ground has been established