LG Ceiling Duct-Type Fan Coil Unit
INSTALLATION MANUAL
L G
IMPORTANT
• Please read this installation manual carefully and thoroughly before installing and operating the unit.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
LOW STATIC PRESSURE FCU MODELS
2 Fan Coil Unit
Fan Coil Unit Installation Manual
TABLE OF CONTENTS
FOR YOUR RECORDS
Write the model and serial numbers here:
Model #
Serial #
You can find them on a label on the side of each unit.
Dealer's Name
Date Purchased
Staple your receipt to this page in the event you need it
to prove date of purchase or for warranty issues.
READ THIS MANUAL
Inside you will find many helpful hints on how to use and maintain your air conditioner properly. Just a little preventive care on your part can save you a great deal of time and money over the life of your air conditioner.
You'll find many answers to common problems in the chart of troubleshooting tips. If you review our chart of
Troubleshooting Tips first, you may not need to call for service at all.
PRECAUTION
• Contact the installer for installation of this unit.
• The unit is not intended for use by young children or invalids without supervision.
• Young children should be supervised to ensure that they do not play with the unit.
• When the power cord is to be replaced, replacement work shall be performed by authorized personnel only using only genuine replacement parts.
• Installation work must be performed in accordance with the National Electric Code by qualified and authorized personnel only.
Safety Precautions.................3
Care and maintenance...........8
Before you call for service ..10
Installation ............................11
Installation Manual 3
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage.
Be sure not to do.
Be sure to follow the instruction.
WARNING
Installation
Do not use a defective or underrated circuit breaker. Usethisapplianceona dedicated circuit.
• There is risk of fire or electric
shock.
For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
• Do not disassemble or repair the product. There is risk of fire or electric shock.
Always ground the product.
• There is risk of fire or electric shock.
Always install a dedicated circuit and breaker.
• Improper wiring or installation may cause fire or electric shock
Use the correctly rated breaker or fuse.
• There is risk of fire or electric shock.
Do not modify or extend the power cable.
• There is risk of fire or electric shock.
WARNING
CAUTION
4 Fan Coil Unit
Do not store or use flammable gas or combustibles near the product.
• There is risk of fire or failure of product.
Do not use the product in a tightly closed space for a long time.
• Oxygen deficiency could occur.
When flammable gas leaks, turn off the gas and open a window for ventilation before turn the product on.
• Do not use the telephone or turn switches on or off. There is risk of explosion or fire
Safety Precautions
Operation
Do not install, remove, or re-install the unit by yourself (customer).
• There is risk of fire, electric shock, explosion, or injury.
Be cautious when unpacking and installing the product.
• Sharp edges could cause injury. Be especially careful of the case edges and the fins on the evaporator.
For installation, always contact the dealer or an Authorized Service Center.
• There is risk of fire, electric shock, explosion, or injury.
Do not plug or unplug the power supply plug during operation.
• There is risk of fire or electric shock.
Do not touch(operate) the product with wet hands.
• There is risk of fire or electrical shock.
Do not place a heater or other appliances near the power cable.
• There is risk of fire and electric shock.
Do not let the unit run for a long timewhenthehumidityisveryhigh and a door or a window is left open
.
• Moisture may condense and wet or damage furniture.
Take care to ensure that power cable could not be pulled out or damaged during operation.
• There is risk of fire or electric shock.
Do not place anything on the power cable.
• There is risk of fire or electric shock.
Gasolin
Installation Manual 5
Safety Precautions
If strange sounds, or small or smoke comes from product. Turn the breaker off or disconnect the power supply cable.
• There is risk of electric shock or fire.
Stop operation and close the window in storm or cyclone. If possible, remove the product from the window before the cyclone arrives.
• There is risk of property damage, failure of product, or electric shock.
When the product is soaked (flooded or submerged), contact an Authorized Service Center.
•Thereisriskoffireorelectric shock.
Be cautious that water could not enter the product.
• There is risk of fire, electric shock, or product damage.
Ventilate the product from time to time when operating it together with a stove, etc.
• There is risk of fire or electric shock.
Turn the main power off when cleaning or maintaining the product.
•Thereisriskofelectricshock.
When the product is not be used for a long time, disconnect the power supply plug or turn off the breaker.
• There is risk of product damage or failure, or unintended operation.
Safety Precautions
6 Fan Coil Unit
Installation
CAUTION
Operation
Use two or more people to lift and transport th
e product.
• Avoid personal injury.
Do not install the product where it will be expose
d to sea wind (salt spray) directly.
• It may cause corrosion on the product. Corrosion, particularl
y on the condenser and evaporator fins,
coul
d cause product malfunction or inefficient
operation.
Do not expose the skin directl
y to cool air for long periods of time. (Don'
t sit in the draft.)
• This could harm to your health.
Do not use the product for specia
l purposes, such as preserving foods, works of art
, etc. It is a consumer air
conditioner
, not a precision
refrigeratio
n system.
• There is risk of damage or los
s of property.
Do not block the inlet or outle
t of air flow.
• It may cause product failure.
After installing, the water leakage test should be perfrmed.
• A bad connection may cause water leakage.
Install the drain hose to ensure that water is drained away properly.
• A bad connection may cause water leakage.
Keep level even when installing the product.
• To avoid vibration or water leakage.
90°
Safety Precautions
Installation Manual 7
Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
There is risk of fire, electric shock, or damage to the plastic parts of the product.
Do not touch the metal parts of the product when removing the air filter. They areverysharp!
There is risk of personal injury.
Always insert the filter securely. Clean the filter every two weeks or more often if necessary.
A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
Do not insert hands or other objects through the air inlet or outlet while the product is operated.
There are sharp and moving parts that could cause personal injury.
Do not drink the water drained from the product.
It is not sanitary and could cause serious health issues.
Use a firm stool or ladder when cleaning or maintaining the product.
Be careful and avoid personal injury.
Thinner
Wax
Care and maintenance
8 Fan Coil Unit
B
e
n
z
e
n
e
S
C
O
U
R
I
N
G
C
L
B
A
R
G
E
R
S
I
N
N
E
R
Air filters
Air outlet vent
Indoor Unit
Caution: Before performing any maintenance, turn off the main power to the system.
Turn the system off before cleaning. To clean, wip
e with a soft, dry cloth. Do not use bleach or
abrasives.
Note:
Suppl
y power must be disconnected before
cleanin
g the indoor unit.
Never use any of the followings:
Water hotter than 40°C Could cause deformation and/or discoloration.
Volatile substances Could damage the surfaces of the air conditioner.
Clean the filter with a vacuum or warm, soapy water.
• If very dirty, wash with a solution of detergent in lukewarm water.
After washing with water, dry well in the shade.
Re-instal
l the air filter.
Air Filter
The air filters behind Indoor unit (th
e suction side) should be checked and cleaned
onc
e every 2 weeks or more often if necessary.
1
2
3
Care and maintenance
Air outlet vent
Air filters
Care and maintenance
Installation Manual 9
1
2
Whentheunitisnotgoingtobeusedforalongtime.
Operation Tips
Helpful information
The air filters and your electiric bill. If the air filters become clogged with dust, the cooling capacity will drop, and 6% of the electricity used to operate the air conditioner will be wasted.
When it is not going to be used for
a long time.
When the unit is to be used again.
Operate the unit on Air circulation mode for 2 to 3 hours.
This will dry out the internal parts.
CAUTION:
Turn off the circuit breaker when the air conditioner is not goingtobeusedforalongtime.
Dirt may collect and may cause a fire.
Check that the air inlet and outlet of the unit are not blocked.
Do not overcool the room.
This is not good for the health and wastes electricity.
Keep blinds or curtains
closed.
Do not let direct sunshine enter the room when the unit is in operation.
Make sure that the doors
and windows are shut tight.
Avoid opening doors and windows as much as possible to keep the cool air in the room.
Clean the air filter regularly.
Blockages in the air filter reduce the airflow and lower cooling and dehumidifying effects. Clean at least once every two weeks.
Ventilate the room
occasionally.
Since windows are kept closed, it is a good idea to open them and ventilate the room now and then.
Turn off the circuit breaker.
Before you call for service...
10 Fan Coil Unit
Check the following points before requesting repairs or service.... If the malfunction persist, please contact your
dealer.
Troubleshooting Tips! Save time and money!
The unit does not operate.
The room has a peculiar odor.
Does not cool or heat effectively.
4
4, 5, 7
Has the fuse blown or has the circuit breaker been tripped?
Check that this is not a damp smell exuded by the walls, carpet, furniture or cloth items in the room.
Is the air filter dirty? See air filter cleaning instructions.
The room may have been very hot when the unit was first turned on. Allow time for it to cool down.
Are the indoor unit's air inlet or outlet vents obstructed?
Case Explanation See page
Before you call for service...
Installation
Installation Manual 11
Installation
Selection of the best location
Install the fan coil unit in the location that satisfies the followin
g conditions.
• The place shall easily bear a load exceeding four time
s the unit’s weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.(Suitable dimension
“H” is necessary to get a slope to drain as
figure.)
• The place where the unit is not affected by an electrica
l noise.
• There should not be any heat source or steam near th
e unit
H
600600
Top view
(unit: mm)
Front view
Front
Rear
0001
300
Confirm the positional relationship between the unit an
d suspension bolts.
• Installation the ceiling opening to clean the filter or servic
e under the product.
Model
DIMENSION
A B 03 530 04 530 06 530 08 530 10 530
12 530
14 530
945
1095 1295 1545 1745 1895
1995
Unit:mm
A(Min)
200
B(Min)
Ceiling
Service Space
A
B
14 Fan Coil Unit
Installation
CAUTION:
1. Install declination of the unit is very important for the drain of the duct type unit.
2. Minimum thickness of the insulation for the connecting pipe shall be 20mm.
• The unit must be horizontal or declined to the drain hose connected when finished installation.
• Always lay the drain with downward inclination (1/5
0 to 1/100).
Preven
t any upward flow or reverse flow in any
part.
• 5mm or thicker formed thermal insulator shall alway
s be provided for the drain pipe.
Front of view
Ceiling
CORRECT INCORRECT
CAUTION FOR GRADIENT OF UNIT AND DRAIN PIPING
CORRECT
m m 3-1
Lay the drain hose with a downward inclination so
Thermal insulator (Local supply)
Drainage pipe (Local supply)
Drainage hole Make sure to be closed.
INCORRECT
water will drain out.
Unit
m m 3-1
• Upward routing not allowed
Installation Manual 15
Installation
Insulation,others
Insulate the joint and tubes completely.
THERMAL INSULATION
All thermal insulation must comply with local requirement the thickness min 20mm.
Make sure that there is no clearance here.
Overlap with thermal insulator for piping.
Thermal insulator for water pipe (Local supply)
Thermal insulator for piping(Local supply)
Hose clip for thermal insulator(Local supply)
Union for water pipe
Water pipe and thermal
insulator(Local supply)
Thermal insulator for water pipe
(Local supply)
Hose clip for thermal insulator
(Local supply)
Air exit
Connecting Cable to the Fan Coil Unit
Connect the wires to the terminals on the control board individually according to the thermostat.
• Ensure that the color of the wires of unit and the terminal No. are the same as those of unit respectively.
Wiring Diagram
38296001
WH WH
Capacitor
WH
Capacitor
WH
Capacitor
WH
Capacitor
3
WH
Capacitor
WH
WH
Capacitor
YL
4 3 2 15
6
YL
WH
YL
WH
YL
YL
WH
YL
WH
4 3 2 1
5
6
15 2
4 3
6
50/60
MED
50/60
MED
50/60
MED
16 Fan Coil Unit
Installation
The power cord connected to the unit should be complied with the following specifications (Rubber insulation, type H05RN-F approved by HAR or SAA).
If the supply cord is damaged, it must be replaced by a special cord or assembly availible from the manufacturer of its service agent.
CAUTION
m
m
0
2
L
Y
/
N
G
NORMAL CROSS-SECTIONAL AREA 1.25mm
2
Install Power Cord
L 1 m
T/B Cover
CAUTION:
CAUTION:
Make sure that the screws of the terminal fixed tightly.
Prepare the wiring as follows:
1) Never fail to have an individual power specialized for the unit. As for the method of wiring, be guided by the circuit diagram pasted on the side panel.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal
function of a overload protection device.
Installation Manual 17
Installation
Checking the Drainage
Water Quality
Checking the Drainage
- Spray one or two glasses of water upon the evaporator.
- Ensure that water flows drain hose of unit without an
y leakage.
The standards for cooling water quality
The standards for adding water quality
Index
PH[25°C] 6.5~8.0
O O
Electric cOnductivity[25°C](µs/cm) Below 800
O O
ChlOride iOn(mgCl-/L) Below 200
O
Sulfate iOn (mgSO42-/L) Below 200
O
Acid cOnsumptiOn[PH4.8](mgCaCO3/L) Below 100
O
Calcium hardness(mgCaCO
3/L) Below 150
O
Turbidity Below 20
O O
Fe(mgFe/L) Below 1.0
O O
AmmOnium iOn(mgNH4+/L) Below 1.0
O
IOnic phases silica(mgSiO2/L) Below 50
O
SaturatiOn index 0.0~1.0
O O
Item Standards
Th
e influence of water quality
Corrosion
The formation of scale
Standard
Item
Reference
Item
Index
PH[25°C] 6.5~8.0
Electric conductivity[25°C](µs/cm) Below 200
Chloride ion(mgCl-/L) Below 50
Sulfate ion (mgSO42-/L) Below 50
Acid consumption[PH4.8](mgCaCO3/L) Below 50
Calcium hardness(mgCaCO3/L) Below 50
Turbidity Below 50
Fe(mgFe/L) Below 50
Ammonium ion(mgNH4+/L) Below 50
Ionic phases silica(mgSiO2/L) Below 50
Item Standards
Standard Item
Reference Item
Installation Manual 18
Circuit Breaker
Installation
Air
Conditioner
Main power source
Circuit Breaker Use a circuit breake or time delay fuse.
Use a recognized circuit breaker between the power source and the unit. A disconnecting device to adequately disconnect all supply lines must be fitted.
Capacity of the Circuit Breaker must lie between MCA and MOP
- MCA = 1.25 x Current of Motor
- MOP = 2.25 x Current of Motor
P/No.: MFL39192001