To prevent injury to the user or other people and property damage, the following instructions must be followed.
n Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the follow-
ing indications.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
n Meanings of symbols used in this manual are as shown below.
Be sure not to do.
Be sure to follow the instruction.
Dangerous Voltage
Be sure to disconnect the power cable plug from the plug socket before disassembling the equipment for a repair.Internal components and circuit boards are at
main potential when the equipment is connected to the power cables. This voltage is extremely dangerous and may cause death or severe injury if come in contact with it.
Do not touch the discharging refrigerant gas during the repair work.
The discharging refrigerant gas.The refrigerant gas can cause frostbite.
Release the refrigerant gas completely at a well-ventilated place first.
Otherwise, when the pipe is disconnected, refrigerant gas or refrigerating
machine oil discharges and it Can cause injury.
When the refrigerant gas leaks during work, execute ventilation. If the refrigerant
gas touches to a fire, poisonous gas generates. A case of leakage of the refrigerant and the closed room full with gas is dangerous because a shortage of oxygen
occurs. Be sure to execute ventilation.
When removing the front panel or cabinet, execute short-circuit and discharge
between high voltage capacitor terminals. If discharge is not executed, an electric
shock is caused by high voltage resulted in a death or injury.
Do not turn the air-conditioner ON or OFF by plugging or unplugging the power
plug. There is risk of fire or electrical shock.
Do not turn on the breaker under condition that front panel and cabinet are
removed.
Be sure to earth the air conditioner with an earthing conductor connected to the
earthing terminal.
Conduct repair works after checking that the refrigerating cycle section has
cooled down sufficiently. Otherwise, working on the unit, the hot refrigerating
cycle section can cause burns.
Do not tilt the unit when removing panels. Otherwise, the water inside the unit
can spill and wet floor.
Do not use the welder in a well-ventilated place. Using the welder in an enclosed
room can cause oxygen deficiency.
Be sure to turn off power switch before connect or disconnect connector, or parts
damage may be occurred.
Do not use a defective or underrated circuit breaker. Use the correctly rated
breaker and fuse. Otherwise there is a risk of fire or electric shock.
Install the panel and the cover of control box securely. Otherwise there is risk of
fire or electric shock due to dust, water etc.
Indoor/outdoor wiring connections must be secured tightly and the cable should
be routed properly so that there is no force pulling the cable from the connection
terminals. Improper or loose connections can cause heat generation or fire.
Do not touch, operate, or repaire the product with wet hands. Hoding the plug by
hand when taking out. Otherwise there is risk of electric shock or fire.
Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air
purge. Do not compress air or Oxygen and Do not use Flammable gases.
Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
Check to see if the parts are mounted correctly and wires are connected.
Improper installation and connections can cause an electric shock or an injury.
Check the installation platform or frame has corroded. Corroded installation platform or frame can cause the unit to fall, resulting in injury.
Be sure to check the earth wire is correctly connected.
After the work has finished, be sure to do an insulation tset to check the resistance is 2[Mohm] or more between the charge section and the non-charge metal
section (Earth position). If the resistance value is low, a disaster such as a leak or
electric shock is caused at userʼs side.
Check the drainage of the indoor unit after the repair. If drainage is faulty the
water to enter the room and wet floor.
Check to see if the power cable plug is not dirty or loose. If the plug is dust or
loose it can cause an electrical shock or fire.
Do not use a joined power cable or extension cable, or share the same power
outlet with other electrical appliances. otherwise, it can cause an electrical shock,
excessive heat generation or fire.
Do not insert hands or other objects through the air inlet or outlet while the product is operating. There are sharp and moving parts that could cause personal
injury.
Do not block the inlet or outlet of air flow. It may cause product failure
Drain pumpO
E.S.P. controlO
Electric heaterX
High ceiling operationX
Auto Elevation GrilleX
Reliability
Hot startO
Self diagnosisO
Soft dry operationO
Convenience
Auto changeoverO
Auto cleaningX
Auto operation(artificial intelligence)X
Auto RestartO
Child lockO
Forced operationX
Group controlO
Sleep modeO
Timer(on/off)O
Timer(weekly)O
Two thermistor controlO
• By the horizontal airflow direction control key input, the left/right louver automatically operates with the auto swing or it
is fixed to the desired direction.
2.2 Auto swing (up & down)
• By the auto swing key input, the upper/lower vane automatically operates with the auto swing or it is fixed to the
desired direction.
2.3 Chaos swing (up/down)
• By the Chaos swing key input, the upper/lower vane automatically operates with the chaos swing or it is fixed to the
desired direction.
NOTE: Some Models are different by swing width and swing pattern.
2.4 Air flow step
• Indoor fan motor control have 6 steps.
• Air volume is controlled "SH", "H", "Med", Low" by remote controller.
• "LL" step is selected automatically in Hot start operation.
2.5 Chaos wind (auto wind)
• When "Auto" step selected and then operated, the high, medium, or low speed of the airflow mode is operated for
2~15 sec. randomly by the Chaos Simulation
2.6 Jet Cool Mode Operation
• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input.
When it is input while in the other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min. at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C.
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then operated
in order that the air outflow could reach further.
2.7 Swirl wind Swing
• It is the function for comfort cooling/heating operation.
• The diagonal two louvers are opened the more larger
than the other louvers. After one minute, it is opposite.
The PLASMA Air Purifying System not only removes microscopic contaminants and dust, but also removes house
mites, pollen, and pet fur to help prevent allergic diseases like asthma. This filter that can be used over and over again
by simply washing with water.
This is the function that decides the strength of the wind for each wind level and because this function is to make the
installation easier.
• If you set ESP incorrectly, the air conditioner may malfunction.
• This setting must be carried out by a certificated-technician.
• Precaution shall be taken not to alter the E.S.P value corresponded to each air flow section.
• E.S.P value can be varied according to the products.
• In the case of going to the next air flow rate stage by pressing the fan-speed button during the setup of the
E.S.P value, the E.S.P value of previous air flow rate will be maintained by remembering the E.S.P value
prior to the shift.
TEMP
FAN
SPEED
OPER
MODE
OPER
MODE
OPER
MODE
When pressing the button and
1
button simultaneously for more than 3
seconds, the system will be entered into the
installer setting mode.
- After entering into the installer setting
mode, select the E.S.P code value by
pressing the button.
* E.S.P code value : 03
Select the desired air flow rate with
2
3
4
5
FAN
SPEED
the button. Whenever pressing
FAN
the button, [SLo→Lo→Med→Hi→Po] will
SPEED
be indicated.
Select the desired air flow rate value with
the temperature up(s), down(t) button.
* E.S.P value range : 0~255
-
E.S.P value will be indicated at the upper
right section of the display window.
When pressing the button, currently
established E.S.P value will be set up.
When pressing the button and button
simultaneously for more than 3 seconds after the
setting has been completed, the setting mode will
be released.
- If there isn’t any button input for more than
25 seconds, the installer setting mode will
also be released.
1. To get the desired Airflow & E.S.P. combination from the table set the matching value from the table. Value other than that in
table will not give the combinations of airflow & E.S.P. which are mentioned in the table.
2. Table data is based at 230V. According to the fluctuation of voltage, air flow rate varies.
• When heating is started, the indoor fan is stopped or very slow to prevent the cold air carry out
• When the temp. of heat exchanger reach 30°C(model by model), indoor fan is started.
5.2 Self-diagnosis Function
• The air conditioner installed can self-diagnosed its error status and then transmits the result to the central control.
Therefore, a rapid countermeasure against failure of the air conditioner allows easy management and increases the
usage life of air conditioner.
• Refer to trouble shooting guide.
5.3 Soft dry operation
• When the dehumidification operation input by the remote control is received, the intake air temperature is detected and
the setting temp is automatically set according to the intake air temperature.
• While compressor off, the indoor fan repeats low airflow speed and stop.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification operation and 4-min compressor off repeat.
Compressor ON Temp. ‘ Setting Temp+0.5°C
Compressor OFF Temp. ‘ Setting Temp-0.5°C
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
5. Reliability
Intake air Temp.Setting Temp.
26°C ≤ intake air temp.25°C
24°C ≤ intake air temp.< 26°Cintake air temp. -1°C
22°C ≤ intake air temp. < 24°Cintake air temp. -0.5°C
18°C ≤ intake air temp. < 22°Cintake air temp.
• Operating frequency of compressor depends on the load condition, like the difference between the room temp. and
the set temp., frequency restrictions.
• If the compressor operates at some frequency, the operating frequency of compressor cannot be changed within 30
seconds. ( not emergency conditions)
• Compressor turned off when
- intake air temperature is in between ±0.5°C of the setting temp. limit for three minutes continuously.
- intake air temperature reaches below 1.0°C of the temperature of setting temp..
• Compressors three minutes time delay.
- After compressor off, the compressor can restart minimum 3 minutes later.
6. Convenience Functions & Controls
6.1.2 Heating Mode
• Operating frequency of compressor depend on the load condition, The difference between the room temp. and set
temp., frequency restrictions.
• If compressor operates at some frequency, the operating frequency of compressor cannot be changed within 30 seconds.
• Condition of compressor turned off
- When intake air temperature reaches +4°C above the setting temperature.
• Condition of compressor turned on
- When intake air temperature reaches +2°C above the setting temperature.
* Condition of indoor fan turned off
- While in compressor on : indoor pipe temp. < 20°C
- While in compressor off : indoor pipe temp. < 30°C
• While in defrost control, between the indoor and outdoor fans are turned off.
• Compressor 2minutes delay
- After compressor off, the compressor can restart minimum 2 minutes later.
CST/Duct/CVT type indoor unit matched with
Universal Outdoor unit
CST/ Duct/CVT type indoor unit
matched with Single Outdoor unit/Multi
Outdoor unit/Multi V Outdoor unit
Thermo ON : +2 °C above setting temp.
Thermo OFF : +4 °C above setting temp.
Thermo ON : Setting temp.
Thermo OFF : +3 °C above setting temp.
NOTE: Some Models are different by temperature of thermo ON/OFF.
• Whenever there is electricity failure to the unit, and after resumption of the power, unit will start in the same mode prior
to the power failure. Memorized condition are on / off condition, operating mode (cooling/ heating), set temperature and
fan speed. The unit will memorize the above conditions and start with same memorized condition.
6.2 Auto cleaning operation
• Function used to perform Self Cleaning to prevent the Unit from Fungus and bad odor.
• Used after the Cooling Operation before turning the unit off, clean the Evaporator and keep it dry for the next operation.
• The function is easy to operate as it is accessed through the Remote controller.
Unit
Operation
ON
OFF
Comp.
Indoor
Fan
ON
OFF
ON
OFF
Setting step
OFFL Low
Setting step
(Cooling Only)
6.3 Auto changeover operation
• The air conditioner changes the operation mode automatically to keep indoor temperature.
• When room temperature vary over ±2°C with respect to setting temperature, air conditioner keeps the room temperature in ±2°C with respect to setting temperature by auto change mode.
It is the function to use preventing children or others from careless using.
It is the function to use preventing children or others from careless using.
During the operation, when pressing the
TEMP
FAN
SPEED
OPER
MODE
1
button and button for approx. 3 seconds,
the ‘Child Lock’ Function can be used.
-
At the time of initial setting of the ‘Child Lock’,
the ‘CL’ Will be indicated approx. 3 seconds
at the temperature Display section before
resuming to the previous mode.
After the setting of the ‘CL’, if another button
is setup, the button can not be recognized as
the ‘CL’ is indicated at the temperature
display section for approx. 3 seconds.
If the ‘CL’ function is wanted to be used
2
under the operation standby state, press the
button and Button for approx.
3 seconds under the standby mode state and
the system will be the ‘CL’ state.
FAN
SPEED
FAN
SPEED
As for the releasing method, when pressing
3
the Button and button for approx. 3
seconds, the ‘CL’ function can be released.
Press button repeatedly until
1
the is flashing.
If moving to 'setup' icon area by using button,
2
'setup' icon blinks, and child lock function is setup if
pressing button at that time.
When cancelling lock function, if moving to 'cancel' icon by pressing
3
button and then, pressing button, child lock function is
cancelled.
Press button to exit.
4
❈ After setup, it automatically gets out of setup mode if there is no
button input for 25 seconds.
❈ When exiting without pressing set button, the manipulated value is
• To operate the appliance by force in case when the remote control is lost, the forced operation selection switch is on
the main unit of the appliance, and operate the appliance in the standard conditions.
• The operating condition is set according to the outdoor temp. and intake air temperature as follows.
• The unit select the last operation mode in 3 hours.
• Operating procedures when the remote control can't be used is as follows :
- The operation will be started if the ON/OFF button is pressed.
- If you want to stop operation, re-press the button.
1. When installing more than 2 units of air conditioner to
one wired remote controller, please connect as the
right figure.
• If it is not event communication indoor unit, set the unit
as slave.
• Check for event communication through the product
manual.
2. When installing more than 2 wired remote controllers to one air
conditioner, please connect as the right picture.
• When installing more than 2 units of wired remote controller to one air
conditioner, set one wired remote controller as master and the others all
as slaves, as shown in the right picture.
• You cannot control the group as shown in the right for some products.
•
Refer to the product manual for more detail.
When controlling multiple indoor units with event communication
function with one remote controller, you must change the
master/slave setting from the indoor unit.
- Indoor units, the master/slave configuration of the product after
completion of indoor unit power ʻOFFʼ and then ʻONʼ the power
after 1 minutes elapsed sign up.
- For ceiling type cassette and duct product group, change the
switch setting of the indoor PCB.
- For wall-mount type and stand type product, change the master/slave setting with the wireless remote controller. (Refer to
wireless remote controller manual for detail)
h When installing 2 remote controllers to one indoor unit with event communication function, set the master/slave of the
remote controller. (Refer to remote controller master/slave selection)
When controlling the group, some functions excluding basic operation setting, fan level Min/Mid/Max, remote controller lock setting and time setting
may be limited.
<When simultaneously connecting
2 sets of wired remote controller>
• When controlling in groups, set the master/slaver of the remote controller. Refer to Installer setting section on how to set master/slave for more detail.
• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appliance
operation, the operation of the appliance stops.
• While the appliance is on pause, the sleep timer mode cannot be input.
• While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature increases by
1°C. After another 30 min elapse, it increases by 1°C again.
• When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to the low.
• When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to the medium.
6.9 Timer(On/Off)
6.9.1 On-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance starts to operate.
• The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
6.9.2 Off-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
• If the appliance is on pause at the time set by the timer, the pause continues.
h Indoor unit is turned on to desired temperature if it is configured using up/down button during preset of weekly operation time.
(Temperature selection range : 18℃~30℃)
- When desired temperature is not set, it is turned on automatically with desired temperature of previous operation.
Please move to 'AM/PM' setup part
10
11
of turning off by using button.
- AM/PM setup is identical with
turning on time setup.
Please move to 'hour' setup part
of turning off by using Right
button.
- It is the part to reserve the time
at which air-conditioner is
turned off.
- If 'hour' indication blinks, please
setup 'hour'.
Please setup 'hour' and 'minute'
❈
identically with the method to
setup turning on time.
If finishing weekly reservation setup, please press setup/cancellation button.
12
13
Weekly reservation explanation
Reservation
number
Weekly reservation setup for the day that you set is finished.
If you setup with the method identical with above by selecting the day that
you'd like to setup, it operates weekly reservation.
If you setup both turning on reservation time and turning off reservation time
identically, it doesn't operate reservation drive.
Turning on time
Turning off time
Under bar: the indication that there is weekly reservation for
corresponding day
h The function of 2TH has different operation characteristics according to the product.
<Thermistor Table>
This is the function to select the temperature sensor to judge the room temperature.
Temperature sensor selectionFunction
01Remote controllerOperation in remote controller temperature sensor
02Indoor unitOperation in indoor unit temperature sensor
032TH
Cooling
Operation of higher temperature by comparing indoor unit's and wired remote
controllerʼs temperature.
(There are products that operate at a lower temperature.)
Heating
Operation of lower temperature by comparing indoor unit's and wired remote
controller's temperature.
When pressing the button and
1
button simultaneously for more than 3
seconds, the system will be entered into
the installer setting mode.
- After entering into the installer setting
mode, select the thermistor sensor
setting code value by pressing the
button.
* Thermistor sensor selection code
value : 04
Select the desired setting value with the
2
FAN
SPEED
TEMP
OPER
MODE
temperature up(▲), down(▼) button.
*Setting value
01: Remote
controller
Code value
02: Indoor unit
03: 2TH
OPER
MODE
OPER
MODE
Val ue
When pressing the button, currently
3
established thermistor sensor location
will be set up.
OPER
When pressing the button and
4
button simultaneously for more than 3
seconds after the setting has been
completed, the setting mode will be
released.
- If there isn’t any button input for more
than 25 seconds, the installer setting
mode will also be released.
h The function of 2TH has different operation characteristics according to the product.
<Thermistor Table>
This is the function to select the temperature sensor to judge the room temperature.
Temperature sensor selectionFunction
01Remote controllerOperation in remote controller temperature sensor
02Indoor unitOperation in indoor unit temperature sensor
032TH
Cooling
Operation of higher temperature by comparing indoor unit's and wired remote
controllerʼs temperature.
(There are products that operate at a lower temperature.)
Heating
Operation of lower temperature by comparing indoor unit's and wired remote
controller's temperature.
If pressing button long for 3 seconds, it enters into
1
remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode.
Please press more than 3 seconds for sure.
If moving to room temperature perception sensor selection menu by
2
pressing button, it indicates as picture below.
Set Thermistor value by pressing button. (01: Remote Controller,
3
02: Indoor, 03: 2TH)
Function CodeThermistor setting
Press button to save.
4
Pressing button will exit settings mode.
5
❈ After setup, it automatically gets out of setup mode if there is no button input
for 25 seconds.
❈ When exiting without pressing set button, the manipulated value is not
• This Function is for cooling operating in outdoor low temperature .
• If outdoor temperature drops below certain temperature, liquid back is prevented by reducing outdoor fan speed.
• It can prevent frosting of evaporator and keep cooling operation
7. Special Function
7.2 Space control
Vanes angle can be controlled by pair, considering its
installation environment.
• For example direct drafts can be annoying, leading to
discomfort and reduced productivity vane control
helps to eliminate this problem.
• Easily controlled by wired remote control.
• Air Flow can be controlled easily regarding any space
environment.
7.3 Auto Elevation Grille
• Auto Elevation Grille is automatically down to height
of max. 3.1 m. So it enables to install the Indoor unit
at high ceiling space. And Auto Elevation Grille
makes you cleaning the filter easily.
As for operation of Remote Controller, use it by directing the transmitter part of Remote Controller to the receiver part of front panel
directly under front panel.
• Do not drop it down or into water. Or else there is worry about
trouble failure.
• Do not press hard the Remote Controller button with nail (ballpoint pen or other sharp substance). Or else there is worry
about trouble failure.
• In case when obstacle such as curtain hides the signal reception
part of receiver in between the space interval, Remote Controller
operation is infeasible.
- Depress the down button( ).
Then suction grill descends and stops automatically at a certain
distance.
- You may stop it at wanted distance point by depressing the stop button ( ) when descending.
- Depress the up button( ).
Then suction grill goes up and enters into the front panel.
1. Stop the Air Conditioner Operation
2. Descend the Suction Grill
3. Raise the Suction Grill
- Depress the stop button( ).
Make use of this when you want to stop it at your wished position.
4. Stop the Suction Grill during Rising
• Always stop the air conditioner operation for safety before operating lift grill.
• Take heed _ there is worry about dust fall etc. when suction grill descends.
• In case when the set automatic stop distance goes wrong, check the set value of operation panel and confirm if there is neither obstacle nor mankind.
• When you are not to remove obstacle, stop the operation before touching the obstacle.
Basic principle is to control the rpm of the motor by changing the working frequency of the compressor.
Three phase voltage is supplied to the motor and the time for which the voltage will supplied is controlled by IPM
(intelligent power module).
Switching speed of IPM defines the variable frequency input to the motor.
1. Normal operation
Fuzzy control : Maintain evaporating temperature (Te) to be constant on cooling mode and constant condensing temper-
ature (Tc) on heating mode by fuzzy control to ensure the stable system performance.
2. Compressor control
ActuatorCooling operationHeating operationStop state
CompressorFuzzy controlFuzzy controlStop
FanFuzzy controlFuzzy controlStop
EEV
Super heating
fuzzy control
Discharge Temp. ControlMin. Pulse
EEV operates with fuzzy control rules to keep The degree of superheat (2~3℃) or the target temperature of discharge pipe.
*Cooling mode
The degree of superheat = Tsuction – Tevaporator
Tsuction : temperature at suction pipe sensor(℃)
Tevaporator : evaporation temperature (℃)
3. EEV( Electronic Expansion Valve) control
*Heating mode
the target temperature of discharge pipe = T condenser + α
T condenser : condenser temperature (℃)
Linear control
System capacity
Cooling and heating load
Inverter linear control as cooling and heating load increasing
If abnormal voltage is supplied, the protection circuits will turn off the product in order to prevent the component
damage. The product will automatically restart after 3 minutes.
turn off the vacuum pump, and confirm that
the gauge needle does not move (approximately 5 minutes after turning off the vacuum
pump).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or
depleted, replenish as needed.
WARNING
Use a vacuum pump or lnert (nitrogen) gas when
doing leakage test or air purge. Do not compress
air or Oxygen and do not use Flammable gases.
Otherwise, it may cause fire or explosion.
nected from the vacuum pump to the valve at
the bottom of the cylinder.
– If you are using a gas cylinder, also use a
scale and reverse the cylinder so that the system can be charged with liquid.
(2) Purge the air from the charge hose.
– Open the valve at the bottom of the cylinder
and press the check valve on the charge set to
purge the air. (Be careful of the liquid refrigerant). The procedure is the same if using a gas
cylinder.
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant.
– If the system can not be charged with the spec-
ified amount of refrigerant, it can be charged
with a little at a time (approximately 150g each
time) while operating the air conditioner in the
cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then
repeat the procedure (pumping down-pin).
(4) Immediately disconnect the charge hose from
the 3-way valveʼs service port.
–
Stopping partway will allow the gas to be discharged.
–
If the system has been charged with liquid refrigerant while operating the air conditioner turn off
the air conditioner before disconnecting the hose.
(5)
Mount the valve stem nuts and the service port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
WARNING
When installing or relocation the unit, make sure
that no substance other than the specified refrigerant(R410A) enter the refrigerant circult.
- Any presence of foreign substance such as air
can cause an abnormal pressure rise and may
result in explosion or injury.
This is different from previous procedures.
Because you are charging with liquid refrigerant
from the gas side, absolutely do not attempt to
charge with larger amounts of liquid refrigerant
while operating the air conditioner.
1. Check temperature difference between intake and discharge air, and check for the operating current too.
CaseSymptomSupposed Caused
Temp. difference : approx. 0°C
Current : less than 80% of rated current
Temp. difference : approx. 8°C
Current : less than 80% of rated current
Temp. difference : less than 8°C
Current : over the rated current
Temp. difference : over 8°C
All amount of refrigerant leaked out.
Check refrigeration cycle.
Refrigerant leakage Clog of refrigeration cycle
Defective Compressor.
Excessive amount of refrigerant
Normal
Case 1
Case 2
Case 3
Case 4
Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is
relativery higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference
is larger.
2. Check temperature and pressure of refrigeration cycle in cooling mode.
1. The suction pressure is usually 8.5~9.5kg/cm2G(Cooling) at normal condition.(R410A)
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
NOTICE
NOTICE
Suction pressure
(Compared withCause of TroubleDescription
the normal value)
Defective compressorCurrent is low.
Defective 4-way reverse valve
* The voltage of main power supply.
* The voltage applied to the unit.
* The connecting method of Indoor/Outdoor connecting cable (each color)
* The PCB Assembly (Fuse, Noise Filter, Power Module, Bridge Diode, etc.)
• The connection of wire (Drain pump/ Float switch)
• Drain pump power input. (220V)
• Drain tube installation.
• Indoor unit installation. (Inclination)
Display
code
TitleCause of errorCheck point & Normal condition
Check Point
1. Check the wire connection. (Open / Short) ’ Repair the connection
2. Check the soldering state of connector. (Soldered poorly) ’ Repair or Change the PCB.
3. Check the volt. Of main PCB power source. (DC 12V) ’ Repair or Change the main PCB.
4. Check the installation of wired remote controller. (Noise interference) ’ Adjust the state of installation
※ To change drain pump assmbly for service, first separate c/box and disassemble drain pump assembly for
’ The Voltage is about [input voltage x 1.414]
’ if the Voltage does not come with the above Voltage,
’ Check the power input
’ Replace the PCB & Motor
2. Check the Voltage Black line to White
’ the Voltage is DC 15V
’ Check the Power input
’ Replace the motor
Check the Motor
1. Check the shaft
’ if the shaft is not turn smoothly, the Motor Power IC is defected
’ replace the motor
2. Check the motor resistance(if the shaft is turn smoothly, check the resistance)
’ Check Red line to Black line, Blue line to Black line
’ The resistance should infinite
’ replace the motor
- Overcharging of refrigerant Pipe length.
Outdoor Fan is stop
• Poor insulation of compressor
Display
code
TitleCause of errorCheck point & Normal condition
n Error Diagnosis and Countermeasure Flow Chart
n Comp checking method
Comp
Copper pipe
V
U
W
Comp
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
5. Check the CT Sensor Output signal
(LUU247HV - Check output the CT Sensor : DC 2.5±0.2V)
LUU367HV / LUU427HV - Check output pin 2.3 of the CT Sensor : DC 2.5±0.2V
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
No
Is input voltage normal ?
Yes
No
Is Inverter PCB assembly
Power connection normal?
Check L~N Voltage is 230V±15%
Check connection from terminal block to
Inverter PCB assembly CN(L), CN(N)
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
5. Inverter PCB assembly Damage (input current
sensing part)
Display
code
TitleCause of errorCheck point & Normal condition
h PFCM Moudle checking method
① Set the multi tester to diode mode.
② Check short between input signal pin which are
placed below PFC Module
③ Replace PCB assembly if it is short between pins
except No.4,5 pins.
CAUTION
PFCM module No.4,5 pins are internal short state.
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
High temperature in
Discharge pipe of the
inverter compressor
• Overload operation
(Outdoor fan constraint,
screened, blocked)
• Refrigerant leakage
(insufficient)
• Poor INV Comp
Discharge sensor
• LEV connector displaced
/ poor LEV assembly
• Check outdoor fan constraint/ screened/ flow
structure
• Check refrigerant leakage
• Check if the sensor is normal
• Check the status of EEV assembly
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
• Covering / clogging (outdoor unit covering during
the cooling mode / indoor unit filter clogging during heating mode)
• SVC valve clogging
• Defective outdoor unit PCB
• Defective indoor unit pipe sensor
n Error diagnosis and countermeasure flow chart
Is service valve
opened?
Yes
Are communication cable/
piping normal?
No
Open service valve
check communication/
piping correction.
Yes
Is amount of refrigerant
normal?
[refer refrigerant part]
Yes
Is strainer Ok?*
Yes
Are the value of manifold
gauge and pressure
sensor same?
(Is the low pressure value
actually low?)
Yes
Check indoor / outdoor unit LEV
Check Indoor unit PCB
Check indoor / outdoor unit
installation conditions
No
No
No
Is there pipe crack or trace
of refrigerant leakage?
Yes
Weld / reconnect the cracked
portion and recharge refrigerant
Replace the strainer
Replace the pressure sensor
No
Adjust the amount of
refrigerant (Additive charge)
* If the temperature difference between inlet and outlet of strainer
is so large that frost or ice formation can be seen or confirmed
then clogging of strainer should be checked
(Notice: it is not full ice forming of strainer, in case that there is
not at inlet portion but at outlet portion)
2. Check Input Voltage Sensor output voltage (2.5Vdc±10%)
n Error Diagnosis and Countermeasure Flow Chart
40
C/T
Sensor Error
• Initial current error
•
Malfunction of current detection circuit.
(Open / Short)
•
Check CT Sensor output voltage :
2.5Vdc ±5%
Display
code
TitleCause of errorCheck point & Normal condition
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
1. Estimate the resistance of each sensor.(Unplugged)
2. Check the value of the resistor of thermistor.
D-pipe sensor (Inverter): Normal Value of the resistor is 200kΩ at 25℃
Air sensor: Normal Value of the resistor is 10kΩ at 25℃
Cond. Mid-pipe sensor: Normal Value of the resistor is 5kΩ at 25℃
Suction pipe sensor: Normal Value of the resistor is 5kΩ at 25℃
Condenser Out-pipe sensor: Normal Value of the resistor is 5kΩ at 25℃
• Transmission circuit of outdoor PCB is abnormal.
• Transmission circuit of indoor PCB is abnormal.
Display
code
TitleCause of errorCheck point & Normal condition
Check Point
1. Check the input power AC230V. (Outdoor, Indoor unit)
2. Check the communication wires are correctly connected.
Adjust the connection of wire Confirm the wire of "Live", "Neutral"
3. Check the resistance between communication line and GND. (Normal : Over 2MΩ)
4. Check the connector for communication is correctly connected.
5. If one indoor unit is operated normally, outdoor PCB is no problem.
Check the another indoor unit.
* CH05 is displayed at indoor unit, CH53 is displayed at
outdoor unit.
6. If all indoor unit is displayed CH05 but outdoor PCB not
display
CH53 : Check the CN_COM and CN_POWER is correctly connected.
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
• Overload operation
(Outdoor fan constraint,
screened, blocked)
• Outdoor unit heat
exchanger contaminated
• EEV connector displaced
/ poor EEV assembly
• Poor Cond. Pipe sensor
assembly / burned
• Check outdoor fan constraint / screened / flow
structure
• Check if refrigerant overcharged
• Check the status of EEV assembly
• Check the status of sensor assembly / burn
CN- C/PIPE
(Violet 3Pin Connector)
Recheck power and
installation condition
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.