LG PRLK396A0 INSTALLATION INSTRUCTIONS

MFL70524403
Rev.01_121720
INSTALLATION MANUAL
AHU EEV KIT Original instruction
AIR CONDITIONER
Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
Copyright © 2019 - 2021 LG Electronics Inc. All Rights Reserved.
ENGLISH
MAGYAR
ITALIANO
БЪЛГАРСKИ
ESPAÑOL FRANÇAIS
SRPSKI
HRVATSKI
SLOVENČINA
DEUTSCH
SLOVENŠČINA
ΕΛΛΗΝΙΚΆ
ČEŠTINA
NEDERLANDS
POLSKI
PORTUGUÊS
IMPORTANT SAFETY INSTRUCTIONS
2
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product.
• This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
• Children should be supervised to ensure that they do not play with the appliance.
• If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
WARNING
!
It can result in serious injury or death when the directions are ignored.
CAUTION
!
It can result in minor injury or product damage when the directions are ignored.
WARNING
!
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• Installation MUST conform with local building codes or, in the absence of local codes.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
IMPORTANT SAFETY INSTRUCTIONS
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
Installation
• Don’t use a power cord, a plug or a loose socket which is damaged.
- Otherwise, it may cause a fire or electrical shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
- Do not disassemble or repair the product. There is risk of fire
or electric shock.
• Always ground the product.
- There is risk of fire or electric shock.
• Install the panel and the cover of control box securely.
- There is risk of fire or electric shock.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Do not modify or extend the power cable.
- There is risk of fire or electric shock.
• Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
- Moisture may condense and wet or damage furniture.
• Be cautious when unpacking and installing the product.
- Sharp edges could cause injury. Be especially careful of the
case edges and the fins on the condenser and evaporator.
• You need to use a safely insulated power supply which follows IEC61558-2-6 and NEC Class2.
- If you do not follow, It may cause fire, electric shock,
explosion or injury.
• Securely attach the electrical part cover to EEV Controller Module.
- If the electric part cover of EEV Controller Module is not
attached securely, it could result in a fire or electric shock due to dust, water, etc.
3
ENGLISH
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
4
• Do not keep or use flammable gases or combustibles near the equipment.
- Otherwise, it may cause a fire or the failure of product.
• Do not install, remove or reinstall the unit by yourself.
- Otherwise, it may cause a fire, electrical shock, explosion or
injury.
• Do not disassemble or repair the product randomly.
- It will cause a fire or electrical shock.
• Do not install the product in a place where there is the concern of falling down.
- Otherwise, it may result in personal injury.
• Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to the product.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it,
causing property damage, product failure, and personal injury.
• There is a risk of fire and explosion.
- Inert gas (nitrogen) should be used when you check
plumbing leaks, cleaning or repairs of pipes etc. If you are using combustible gases including oxygen, product may have the risk of fires and explosions.
Operation
• Do not store or use flammable gas or combustibles near the product.
- There is risk of fire or failure of product.
• Do not share the outlet with other appliances.
- It will cause an electric shock or a fire due to heat
generation.
• Do not use the damaged power cord.
- Otherwise, it may cause a fire or electrical shock.
• Do not modify or extend the power cord randomly.
- Otherwise, it may cause a fire or electrical shock.
IMPORTANT SAFETY INSTRUCTIONS
• Take care so that the power cord may not be pulled during operation.
- Otherwise, it may cause a fire or electrical shock.
• Unplug the unit if strange sounds, smell, or smoke comes from it.
- Otherwise, it may cause electrical shock or a fire.
• Keep flames away.
- Otherwise, may occur a fire.
• Take the power plug out if necessary, holding the head of the plug and do not touch it with wet hands.
- Otherwise, it may cause a fire or electrical shock.
• Do not use the power cord near the heating tools.
- Otherwise, it may cause a fire and electrical shock.
• Do not allow water to run into electrical parts.
- Otherwise, it may cause the failure of machine or electrical
shock.
• Hold the plug by the head when taking it out.
- It may cause electric shock and damage.
• Be cautious that water could not enter the product.
- Otherwise, it may cause a fire electrical shock or product
damage.
• Do not step on the indoor/outdoor unit and do not put anything on it.
- It may cause an injury through dropping of the unit or falling
down.
• Do not place a heavy object on the power cord.
- Otherwise, it may cause a fire or electrical shock.
• When the product is submerged into water, always contact the service center.
- Otherwise, it may cause a fire or electrical shock.
5
ENGLISH
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
6
CAUTION
!
Installation
• Always check for gas (refrigerant) leakage after installation or repair of product.
- Low refrigerant levels may cause failure of product.
• Install the drain hose to ensure that water is drained away properly.
- A bad connection may cause water leakage.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
- It may cause a problem for your neighbors.
• Do not install the product where it will be exposed to sea wind (salt spray) directly.
- It may cause corrosion on the product. Corrosion, particularly
on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
• Thickness of copper pipes used are as shown “Flaring work” Table.
- Never use copper pipes thinner than that in the table even
when it is available on the market
• Do not use copper pipes having a collapsed.
- Otherwise, the expansion valve or capillary tube may
become blocked with contaminants.
• For R410A model, use piping, flare nut and tools which is specified for R410A refrigerant.
- Using of (R22) piping, flare nut and tools may cause
abnormally high pressure in the refrigerant cycle (piping), and possibly result in explosion and injury.
• It is desirable that the amount of residual oil less than 40 mg/10m.
TABLE OF CONTENTS
TABLE OF CONTENTS
2 IMPORTANT SAFETY INSTRUCTIONS
8 INSTALLATION COMPOSITION
9 TECHNICAL SPECIFICATION
9 Specification Sheet 9 Combination of AHU Communication Kit and ODU system with EEV Kit. 9 Compatibility of EEV Kits and IDUs.
11 EEV Kit INSTALLATION
11 Product Installation 16 Welding
17 ELECTRICAL CONNECTION
20 EEV CONTROLLER MODULE SPECIFICATION
20 Dimension 20 Installation
7
ENGLISH
21 EEV CONTROLLER INSTALLATION
21 Electric wiring work (EEV Controller)
22 THERMISTORS INSTALLATION
22 Pipe thermistors Installation
INSTALLATION COMPOSITION
8
ENGLISH
INSTALLATION COMPOSITION
This EEV Kit is a product that connects an AHU with an outdoor unit with the following composition.
Ώ
Α
Β
΍
Γ
Ύ
Control Signal (field supply) Thermistor Signal Pipe Refrigerant flow (cooling) Refrigerant flow (heating)
Installation components
No. Name Notes
1
AHU Local supply
Model Connectable outdoor unit capacity
PRLK048A0 2 ~ 10 HP
2
EEV Kit
PRLK096A0 12 ~ 20 HP
PRLK396A0 22 ~ 40 HP
PRLK594A0 42 ~ 60 HP
3
AHU Communication Kit -
4
5
6
7
Outdoor unit MULTI V
Remote controller LG wired remote controller(Optional)
Pipe in(Liquid) thermistor Sensor: Ø 5, Length: 5m, Cable color: Black
Pipe out(Gas) thermistor Sensor: Ø 7, Length: 5m, Cable color: Red
ΐ
TECHNICAL SPECIFICATION
TECHNICAL SPECIFICATION
Specification Sheet
Model PRLK048A0 PRLK096A0 PRLK396A0 PRLK594A0
Width mm 217 217 349.5 409.5
Dimensions
Net. Weight kg 3.1 3.1 4.3 5.5
Casing
Composition
Rated Voltage V DC12 ±1.2 Connectable Outdoor Unit Capacity HP 2 ~ 10 12 ~ 20 22 ~ 40 42 ~ 60 Liquid Pipe Size mm 12.7 12.7 19.05 19.05 Operation Pressure MPa 0 ~ 4.5
Color Warm Gray Material Galvanized steel plate
Pipe Sensor
Installation Manual EA 1 1 1 1 EEV Controller (PAEEVA020) EA - - - 1
Combination of AHU Communication Kit and ODU system with EEV Kit.
EEV Kit
PRLK048A0 PRLK096A0 PRLK396A0 PRLK594A0 X
1) Maximum allowable capacity with HR Unit.
PAHCMR000 PAHCMS000 Heat pump Heat recovery
Depth mm 83 83 180 180 Height mm 404 404 345.5 345.5
Liquid Pipe Sensor Ø5, 5 , 5m, Black Gas Pipe Sensor Ø7, 5 , 5m, Red
AHU Communication Kit Connection by ODU system
O O O O O O O O O O O
O O
(with PAHCMS000) X
X (Max 33.7 kW1))
9
ENGLISH
Compatibility of EEV Kits and IDUs.
Case Combination
1 Multiple PRLK048A0 / PRLK096A0 O O 2 Multiple PRLK048A0 / PRLK096A0 + IDUs
3
4
5
1) Return Air is for PAHCMR000 / PAHCMC000
2) Supply Air is for PAHCMS000 / PAHCMM000 + PAHCMC000
3) IDUs includes Hydro Kit/DX ERV/FAU(OAU)
PRLK396A0 + PRLK048A0 / PRLK096A0 X X PRLK594A0 + PRLK048A0 / PRLK096A0 X X
PRLK396A0 + PRLK396A0 or PRLK594A0
PRLK594A0 + PRLK396A0 or PRLK594A0 X X
PRLK396A0 + IDUs X X PRLK594A0 + IDUs X X
(Exception : 2 x PRLK396A0)
3)
Compatibility
Return Air
1)
O X
X (O) X (O)
Supply Air
2)
ENGLISH
W
D
H
TECHNICAL SPECIFICATION
10
EEV Kit
Model
PRLK048A0 PRLK096A0
PRLK396A0 PRLK594A0
Shape
H
D
W
Quantity(EA) 1 1
Model Name
Dimension (mm)
W D H
PRLK048A0/PRLK096A0 217 83 404 -
PRLK396A0 349.5 180 345.5 -
PRLK594A0 409.5 180 345.5 EEV Controller included
Note
EEV Kit INSTALLATION
EEV Kit INSTALLATION
Product Installation
Model: PRLK048A0/PRLK096A0
1 Remove the 4 screws to separate the cover plate of the EEV Kit.
2 Drill 4 holes on correct position and fix the EEV Kit box securely with 2 screws
(M5, field supply) at the ‘A’ position and then fix the EEV Kit box with other screws(M5×2 EA) at the ‘B’ position.
11
ENGLISH
190 mm (7-1/2”)
206 mm (8-1/9”)
222 mm (8-3/4”)
B
Pipe size
Ø 12.7 mm(1/2")
AA
Hole size Ø 6 mm (1/4”)
B
6 mm (1/4”)
Ø 12 mm (1/2”)
EEV Kit INSTALLATION
12
ENGLISH
3 Prepare the inlet/outlet field piping just in front of the connection. 4 Braze the field piping. 5 Make sure that field pipes are fully insulated. Field pipe insulation must reach up to the pipe
insulation(D). Make sure that there is no gap between both ends in order to avoid condensation dripping(Finish the connection with tape eventually)
E
D
C(3 EA)
B
A
A. Inlet coming from the outdoor unit
B. Outlet to evaporator
C. Pipe fixing bracket(3 EA)
D. Pipe insulation
E. EEV Assembly
F. Field liquid pipe (Inlet / Outlet)
When brazing, wrap wet cloth
round this part.
F
F
CAUTION
!
• Make sure to cool the filters and EEV body with a wet cloth and make sure the body temperature does not exceed 120 °C during brazing.
• Make sure that the other parts such as electrical box, tie wraps and wires protected from direct brazing flames during brazing.
EEV Kit INSTALLATION
Model: PRLK396A0 / PRLK594A0
1 Remove the screws to separate the cover plate and base plate of the EEV Kit.
13
ENGLISH
1) Remove the 4 screws from the EEV Kit’s base plate. Remove the 4 screws to separate the cover plate of the EEV Kit.
2) Remove the base plate and rotate the cover of EEV Kit.
3) Remove the cover of EEV Kit.
2 Drill holes in the correct locations and use 4 screws (M5, field supply) to fix the EEV Kit.
A
C
B
Pipe size Ø19.05 mm (3/4")
D
A
B
Hole size Ø6 mm (1/4")
Pipe size Ø19.05 mm (3/4")
6 mm (1/4”)
Ø 12 mm (1/2”)
Model
PRLK396A0
PRLK594A0
Note: PRLK396A0 has two EEV
assemblies.
length
C D
273 mm (10-3/4")
273 mm (10-3/4")
250.3 mm (9-6/7")
190.3 mm (7-1/2")
EEV Kit INSTALLATION
14
ENGLISH
3 Prepare the inlet/outlet field piping just in front of the connection. 4 Braze the field piping. 5 Make sure that field pipes are fully insulated. Field pipe insulation must reach up to the pipe
insulation(D). Make sure that there is no gap between both ends in order to avoid condensation dripping(Finish the connection with tape eventually)
E
D
C(2EA)
B
F
A. Inlet coming from the outdoor unit
B. Outlet to evaporator
C. Pipe fixing bracket(3 EA)
D. Pipe insulation
E. EEV Assembly
F. Field pipe(Inlet / Outlet)
Note: The number of EEV assemblies: PRLK396A0 has two EEV assemblies.
CAUTION
!
• Make sure to cool the filters and EEV body with a wet cloth and make sure the body temperature does not exceed 120 °C during brazing.
• Make sure that the other parts such as electrical box, tie wraps and wires protected from direct brazing flames during brazing.
PRLK594A0 has three EEV assemblies.
When brazing, wrap wet cloth
round this part.
A
F
EEV Kit INSTALLATION
Recommended installation range
CAUTION
!
- The product can be installed no more than 90° from the baseline. (Failure to do so could result in damage to or malfunction of the product.)
15
ENGLISH
Base line Base line
90°
45° 45°
Correct installation of product Incorrect installation of product
90° (Possible installation range)
Recommended
Recommended installation range
installation range
Exceeding 90º
(x) (x)
Exceeding 90º
(unable to install)
Exceeding 90º
(unable to install)
Exceeding 90º
(unable to install)
Exceeding 90º
EEV Kit INSTALLATION
16
ENGLISH
Welding
1 Check the inlet/outlet pipe before welding the EEV Kit.
Air-conditioning standard refrigerant flow
Outlet
AHU side
A
Inlet
Outdoor unit side
2 Weld the connector pipe (field supply) at the outdoor unit. 3 When connecting the outdoor unit's liquid pipe and the EEV Kit’s inlet pipe, be sure to use a
socket (field supply) that meets the necessary specifications.
4 As the size of the EEV Kit pipe and the outdoor unit's liquid pipe could vary, check the sizes
beforehand and use a socket that meets the necessary specifications.
5 When welding, make sure to follow the safety precautions at all times. 6 Be sure to insulate 'A' part after welding with insulation (15T or more).
Outdoor unit liquid pipe
Connector socket or elbow
• Be sure to pass nitrogen through when welding parts together. Failure to do so could lead
• It is essential that the part be wrapped with a wet towel before and after welding. Failure
• Use a protective panel or be especially cautious not to let welding sparks come in contact
• After welding, be sure to test for any leakage.
(field supply)
CAUTION
!
to the compressor not working properly or becoming damaged.
to do so could result in the part becoming damaged.
with the AHU panel.
Connector socket or reducer (field supply)
ELECTRICAL CONNECTION
ELECTRICAL CONNECTION
Model: PRLK048A0 / PRLK096A0
1 Open the terminal box cover(A). 2 Pass EEV cable(field supply, 6 wires) from the AHU Communication Kit through cable gland
and connect the cable wires into the terminal block (C) following instructions as describe in step
3 Route the cable out of the EEV Kit box according to figure below and fix with the support tie
wrap(D).
A
B D
E
Detail
EEV
BRRDBLORYLW
C
H
E
17
ENGLISH
A. Terminal box cover B. Cable gland C. Terminal block
4
Use a screwdriver(+) and follow indicated instructions for connecting cable wires into the
D. Support tie wrap E. Electric wiring work(filed
supply, 6 wires)
terminal block according to the circuit diagram of AHU Communication Kit.
Field connect wires
EEV
BRRDBLORYLW
H
Detail
<Field wiring part>
123456
NOTE
1. BR : BROWN
2. RD : RED
3. BL : BLUE
4. OR : ORANGE
CAUTION
!
Field work
EEV
BRRDBLORYLW
H
5. YL : YELLOW
6. WH : WHITE
• Before connecting the wires(filed supply), make sure to compare with the wire colors between EEV Kit and AHU Communication Kit.
Make sure to connect the wires according to the circuit diagram in AHU Communication Kit.
• Use the ring type pin to connect to the terminal block.
5
Make sure that field wiring and insulation are not squeezed when closing the cover plate of EEV Kit.
6 Close the cover plate of EEV Kit.
ELECTRICAL CONNECTION
A
B
D
E
C
18
ENGLISH
Model: PRLK396A0 / PRLK594A0
1 Open the EEV Kit terminal box cover (A).
2 Check the marked color label and connect the cable using the driver (+).
• Example) Model PRLK594A0
• PRLK396A0 model has one terminal box. Electrical connection method of PRLK396A0 is the same as PRLK048A0 / PRLK096A0.
(Correct wiring)
AHU controller
AHU EEV controller
WARNING
!
• Please connect one controller with one terminal block of EEV Kit. Failure to do so may result in component damage or fire. (Refer to correct wiring.)
Detail
(Incorrect wiring)
AHU controller
WARNING
!
• Do not connect to the AHU Controller directly after wiring two terminal blocks together inside of the EEV Kit.
ELECTRICAL CONNECTION
3 Use the screwdriver (+) to connect the EEV wires to the terminal block (D) according to the
displayed instructions.
19
ENGLISH
B: Electrical connection #1
C: Electrical connection #2
AHU Controller
WH
YL
OR
BL
RD
BD
D
AHU EEV Controller
Note
NTC
BR : Brown RD : Red BL : Blue OR : Orange YL : Yellow WH : White
- - - - -: Field Wiring
WH
YL
OR
BL
RD
D
WARNING
!
• Before installation, check the color on the label and connect it to the terminal block.
• It may result in malfunction.
• Use a ring type terminal (P4) to connect to the terminal block.
91(3.58)
54(2.13) 61(2.4)
EEV CONTROLLER MODULE SPECIFICATION
20
ENGLISH
EEV CONTROLLER MODULE SPECIFICATION
This part is included in PRLK594A0 only.
Dimension
<EEV controller module>
Installation
1. Open the door using the key. (PAHCMS000)
CAUTION
!
• This model requires DC12 V ~ external power supply. (Select an insulating transformer that complies with IEC61558-2-6 and NEC Class 2.)
2. Install the DIN rail using screws in the two holes.
3. Install the EEV module on the DIN rail.
Unit: mm
EEV CONTROLLER INSTALLATION
EEV CONTROLLER INSTALLATION
This wiring is for PRLK594A0 model only.
Electric wiring work (EEV Controller)
Circuit diagram
NTC
21
ENGLISH
* Please refer to the circuit diagram of PAHCMS000 model for further details.
THERMISTORS INSTALLATION
22
ENGLISH
THERMISTORS INSTALLATION
Pipe thermistors Installation
Location of the pipe thermistors
A correct installation of the thermistors is required to ensure a good operation :
1 Pipe_In
: Install the thermistor behind the
distributor on the coldest pass the heat exchanger (contact your heat exchanger dealer).
2 Pipe_Out
: Install the thermistor at the outlet of the
heat exchanger as close as possible to the heat exchanger.
Evaluation must be done to check if the evaporator is protected against freeze-up. Execute test operation and check for freeze­up.
1
Ø6.3
Ø8.2
INSTRUCTION
• To prevent condensation from accumulating on the bottom of the pipe sensor, install the sensor by lifting it up as shown below.
Water
2
• In order to detect the temperature of the pipe well, install the sensing part so that it can be attached to the pipe well as shown below
(AHU)
45°
Most sensitive point of the thermistor