LG PRLK096A0 INSTALLATION INSTRUCTIONS

<![if ! IE]>

<![endif]>ENGLISH

INSTALLATION MANUAL

AIR CONDITIONER

Please read this installation manual completely before installing the product.

Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Please retain this installation manual for future reference after reading it thoroughly.

TYPE : AHU EEV Kit

Model : PRLK096A0

www.lg.com

P/NO : MFL50024803

<![if ! IE]>

<![endif]>ENGLISH

2

TIPS FOR SAVING ENERGY

 

 

TIPS FOR SAVING ENERGY

Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:

Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.

Block sunlight with blinds or curtains while you are operating the air conditioner.

Keep doors or windows closed tightly while you are operating the air conditioner.

Adjust the direction of the air flow vertically or horizontally to circulate indoor air.

Speed up the fan to cool or warm indoor air quickly, in a short period of time.

Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.

Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehumidifying functions.

For your records

Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:

Model number :

Serial number :

You can find them on a label on the side of each unit.

Dealer’s name :

Date of purchase :

SAFETY PRECAUTIONS 3

IMPORTANT SAFETY INSTRUCTIONS

READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.

Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product

! WARNING

It can result in serious injury or death when the directions are ignored

! CAUTION

It can result in minor injury or product damage when the directions are ignored

! WARNING

Installation or repairs made by unqualified persons can result in hazards to you and others.

Installation MUST conform with local building codes or, in the absence of local codes, with the Nation Electrical Code NFPA 70/ANSI C1-1003 or current edition and Canadian Electrical Code Part1 CSA C.22.1.

The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.

Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.

Installation

Don’t use a power cord, a plug or a loose socket which is damaged.

-Otherwise, it may cause a fire or electrical shock.

For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.

-Do not disassemble or repair the product. There is risk of fire or electric shock.

Always ground the product.

-There is risk of fire or electric shock.

Install the panel and the cover of control box securely.

-There is risk of fire or electric shock.

Always install a dedicated circuit and breaker.

-Improper wiring or installation may cause fire or electric shock.

Use the correctly rated breaker or fuse.

-There is risk of fire or electric shock.

Do not modify or extend the power cable.

-There is risk of fire or electric shock.

Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.

-Moisture may condense and wet or damage furniture.

Be cautious when unpacking and installing the product.

-Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator.

For installation, always contact the dealer or an Authorized Service Center.

-There is risk of fire, electric shock, explosion, or injury.

<![if ! IE]>

<![endif]>ENGLISH

4 SAFETY PRECAUTIONS

<![if ! IE]>

<![endif]>ENGLISH

• Do not install the product on a defective installation stand.

 

 

- It may cause injury, accident, or damage to the product.

 

• Be sure the installation area does not deteriorate with age.

 

- If the base collapses, the air conditioner could fall with it, causing property damage, product failure,

 

and personal injury.

 

• There is a risk of fire and explosion.

 

- Inert gas (nitrogen) should be used when you check plumbing leaks, cleaning or repairs of pipes

 

etc.

 

If you are using combustible gases including oxygen, product may have the risk of fires and explo-

 

sions.

Operation

Do not store or use flammable gas or combustibles near the product. - There is risk of fire or failure of product.

!CAUTION

Installation

Always check for gas (refrigerant) leakage after installation or repair of product.

-Low refrigerant levels may cause failure of product.

Install the drain hose to ensure that water is drained away properly.

-A bad connection may cause water leakage.

Keep level even when installing the product.

-To avoid vibration or water leakage.

Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.

-It may cause a problem for your neighbors.

Do not install the product where it will be exposed to sea wind (salt spray) directly.

-It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.

Thickness of copper pipes used are as shown “Flaring work” Table.

-Never use copper pipes thinner than that in the table even when it is available on the market

Do not use copper pipes having a collapsed.

-Otherwise, the expansion valve or capillary tube may become blocked with contaminants.

For R410A model, use piping, flare nut and tools which is specified for R410A refrigerant.

-Using of (R22) piping, flare nut and tools may cause abnormally high pressure in the refrigerant cycle (piping), and possibly result in explosion and injury.

It is desirable that the amount of residual oil less than 40 mg/10m.

TABLE OF CONTENTS

3IMPORTANT SAFETY INSTRUCTIONS

6INSTALLATION SCENE

7SUPPLIES

8PART DESCRIPTION

8EEV Kit(PRLK096A0)

9EEV KIT INSTALLATION

9Mechanical Installation

12Electrical Work

13THERMISTORS INSTAL-

LATION

13 Pipe thermistors Installation

16 TROUBLESHOOTING

TABLE OF CONTENTS

5

 

<![if ! IE]>

<![endif]>ENGLISH

LG PRLK096A0 INSTALLATION INSTRUCTIONS
<![if ! IE]>

<![endif]>ENGLISH

6 INSTALLATION SCENE

INSTALLATION SCENE

Signal

 

 

Pipe

9

 

Thermistor

 

 

 

Air flow

3

10

Refrigerant flow

 

 

 

(Cooling)

 

 

Refrigerant flow

 

 

(Heating)

 

 

7

 

6

8

 

 

 

4

 

 

 

2

1

 

 

 

5

 

Parts and components

No.

Name

Remarks

 

 

 

1

Air Handling Unit

Field supply

 

 

 

2

Outdoor Unit

Multi V

 

 

 

3

AHU Comm. Kit(PRCKA0/PRDCA0)

-

 

 

 

4

AHU EEV Kit(PRLK096A0)

-

 

 

 

5

Field piping

Field supply

 

 

 

Wiring connections

 

6

Comm kit wiring

(Power supply and communication be-

tween control kit and outdoor unit)

 

 

 

 

 

7

Pipe thermistors (EBG61287703 /

Evaporator (In/Out) control of Air Han-

EBG61287704)

dling Unit

 

 

 

 

8

Room thermistor (EBG36949303)

Return air control

 

 

 

9

Remote controller(PQRCUSA0)

Optional accessory

 

 

 

10

Dry contact PCB(PQDSBNGCM0)

Optional accessory

 

 

 