LG PQRCVSL0, PQRCVSL0QW User Manual

ENGLISH
LG
New Wide Wired Remote Controller
LG
IMPORTANT
• Please read this owner's & installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Please retain this owner's & installation manual for future reference after reading it thoroughly.
Owner's & Installation Manual
Models: PQRCVSL0 PQRCVSL0QW
P/No.: MFL62129202
ITALIANO ESPAÑOL
FRANÇAIS
DEUTSCH
кмллдав
PORTUGUÊS
Safety Precaution
Owner’s & Installation Manual 3
ENGLISH
2 New Wide Wired Remote Controller
New Wide Wired Remote Controller Owner’s & Installation Manual
TABLE OF CONTENTS
Safety Precaution .........................................................................................................................................3
Part Description............................................................................................................................................4
Installation instruction.................................................................................................................................5
Group control..............................................................................................................................................7
Installer Setting - How to enter installer setting mode................................................................................8
Installer Setting - Test Run Mode.............................................................................................................11
Installer Setting - Setting Address of Central Control...............................................................................12
Installer Setting - E.S.P. ...........................................................................................................................13
Installer Setting - Thermistor ....................................................................................................................15
Installer Setting - Ceiling Height Selection ...............................................................................................16
Installer Setting - Static Pressure Setting.................................................................................................17
Installer Setting - Remote Controller Master/Slave Setup .......................................................................18
Installer Setting - Override Master/Slave Setting .....................................................................................19
Installer Setting - Dry Contact Mode Setting ............................................................................................20
Installer Setting - Zone State....................................................................................................................21
Installer Setting - Celsius / Fahrenheit Switching.....................................................................................22
Installer Setting - Zone Type Setting........................................................................................................23
Installer Setting - Zone Number Setting ...................................................................................................24
Installer Setting - Emergency Heater Setting ..........................................................................................25
Installer Setting - Option Function Setting................................................................................................27
Owner's instruction....................................................................................................................................28
Standard Operation - Standard Cooling...................................................................................................28
Standard Operation - Power Cooling .......................................................................................................29
Standard Operation - Heating Mode ........................................................................................................29
Standard Operation - Dehumidification Mode ..........................................................................................30
Standard Operation - Fan Mode...............................................................................................................30
Standard Operation - Auto Operation Mode ............................................................................................31
Standard Operation - Temperature Setting/Room Temperature Check...................................................32
Standard Operation - Airflow Setting........................................................................................................33
Sub function - Direct Wind / Indirect Wind ..............................................................................................34
Sub function - Plasma Purification ...........................................................................................................36
Sub function - Humidifier..........................................................................................................................37
Sub function - Electric Heater...................................................................................................................38
Sub function - Energy-Saving Cooling Operation.....................................................................................39
Sub function - Robot Cleaning Manual Setup ..........................................................................................40
Function setting - Child Lock....................................................................................................................41
Function setting - Robot Cleaning Automatic Setup.................................................................................42
Function setting - Filter Sign Clear...........................................................................................................43
Function setting - Elevation Grill...............................................................................................................44
Function setting - Vane Angle Control......................................................................................................45
Function Setting - Change Temp .............................................................................................................46
Function setting - Zone Control................................................................................................................47
Function setting - Changing Current Time ..............................................................................................48
Function setting - Auto Cleaning .............................................................................................................50
Programming - Simple Reservation .........................................................................................................51
Programming - Sleep Reservation ...........................................................................................................52
Programming - ON Reservation...............................................................................................................53
Programming - OFF Reservation .............................................................................................................55
Programming - Weekly Reservation.........................................................................................................57
Programming - Holiday Reservation ..............................................................................................
..........59
Ventilation Product User Manual - Interlinked Air conditioner and Ventilation .........................................60
Ventilation Product User Manual - Interlinked operation with general ventilation ...................................61
Manual Conversion - Pressing ‘Ventilation’ button in ventilation mode will manually convert..................62
Ventilation Product User Manual - Interlinked Operation with Direct Expansion Ventilation....................63
Ventilation Product User Manual - Single Operation with Direct Expansion Ventilation ..........................64
Ventilation Product Additional Operations - Fast / Power Saving ............................................................65
Ventilation Product Function Settings ......................................................................................................66
Ventilation Product Reservations Settings ...............................................................................................67
Ventilation Product Installer Setting Functions - Entering Method ...........................................................68
Different mode drive ................................................................................................................................69
Checkups before reporting breakdown ....................................................................................................70
Be sure to request to the service center or installation specialty store when installing products.
• It will cause fire or electric shock or explosion or injury.
Request to the service center or installation specialty store when reinstalling the installed product.
• It will cause fire or electric shock or explosion or injury.
Do not disassemble, fix, and modify products randomly.
• It will cause fire or electric shock.
Do not place flammable stuffs close to the product.
• It will cause fire.
Do not allow water to run into the product.
• It will cause electric shock or breakdown.
Do not give the shock to the product.
• It will cause breakdown when giving the shock to the product.
Installation
Safety Precaution
• The installation requires expert skills, and it should be installed by the service center or other shops specialized in the installation and recognized by our company.
• For all the problems arising after installation by someone who has no relevant qualifications, our company will not provide free service.
• The following safety cautions are provided to prevent unexpected dangers or losses.
: If the user does not follow the mandatory items, it may result in serious injury or death.
: If the user does not follow the mandatory items, it may cause personal injury or property
damage.
: Warning and Caution are to call the user’s attention to the possible danger. Read and follow
them carefully in order to prevent a safety accident.
: Warning and Caution are indicated in this guide and the product itself to help protect the users
from danger.
WARNING
In-use
Request to the service center or installation specialty store when the product becomes wet.
• It will cause fire or electric shock.
Do not give the shock using sharp and pointed objects.
• It will cause breakdown by damaging parts.
In-use
CAUTION
Do not clean using the powerful detergent like solvent but use soft cloths.
• It will cause fire or product deformation.
Do not press the screen using powerful pressure or select two buttons.
• It will cause product breakdown or malfunction.
Do not touch or pull the lead wire with wet hands.
• It will cause product breakdown or electric shock.
WARNING
CAUTION
Owner’s & Installation Manual 5
ENGLISH
4 New Wide Wired Remote Controller
Installation instruction
2
2
1
3
3
1. Please fix tightly using provided screw after placing remote controller setup board on the place where you like to setup.
- Please set it up not to bend because poor setup could take place if setup board bends.
Please set up remote controller board fit to the reclamation box if there is a reclamation box.
- Install the product so as not to make a gap with the wall side and to prevent shaking after the installation.
2. Can set up Wired remote controller cable into three directions.
- Setup direction: the surface of wall reclamation, upper, right
- If setting up remote controller cable into upper and right side, please set up after removing remote controller
cable guide groove.
Remove guide groove with long nose.
Reclamation to the surface of the wall
Upper part guide groove
Right part guide groove
Installation instruction
Part Description
Part Description
Name and Function of Remote Controller
OPERATION INDICATION SCREEN
SET TEMPERATURE BUTTON FAN SPEED BUTTON ON/OFF BUTTON OPRATION MODE SELECTION
BUTTON WIRELESS REMOTE
CONTROLLER RECEIVER
• Some products don't receive the wireless signals.
AIR FLOW BUTTON SUBFUNCTION BUTTON FUNCTION SETTING BUTTON VENTILATION BUTTON RESERVATION UP,DOWN,LEFT,RIGHT BUTTON
• To check the indoor temperature, press button.
ROOM TEMPERATURE BUTTON SETTING/CANCEL BUTTON EXIT BUTTON
1
2
3
4
5
6
7
8
9 10
11
12
13
14 15
Connection Cable
(1EA, 10m)
Screw (4 EA)
Owner's / Installation
manual
Inform label
(8EA-8Languages)
Accessory
Some functions may not be operated and displayed depending on the product type.
<Wire guide grooves>
1
10
9 8
7
11 12 13
14 15
Please attach the inform label inside of the door. Please choose proper language depend on your country.
2 3
4
5
6
Owner’s & Installation Manual 7
ENGLISH
Installation instruction
6 New Wide Wired Remote Controller
Installation instruction
GND
GND
12V
Signal wire
Signal wire
GND
12V
B Y R B Y R
MASTER SLAVE
Signal wire
GND
12V
Signal wire
Group control
1. When installing more than 2 units of air conditioner to one wired remote controller, please connect as the right figure.
• If it is not event communication
indoor unit, set the unit as slave.
• Check for event communication
through the product manual.
2. When installing more than 2 wired remote controllers to one air conditioner, please connect as the right picture.
• When installing more than 2 units of wired
remote controller to one air conditioner, set one wired remote controller as master and the others all as slaves, as shown in the right picture.
• You cannot control the group as shown in
the right for some products.
Refer to the product manual for more detail.
When controlling multiple indoor units with event communication function with one remote controller, you must change the master/slave setting from the indoor unit.
- Indoor units, the master/slave configuration of the product after completion of indoor unit power
‘OFF’ and then ‘ON’ the power after 1 minutes elapsed sign up.
- For ceiling type cassette and duct product group, change the switch setting of the indoor PCB.
- For wall-mount type and stand type product, change the master/slave setting with the wireless
remote controller. (Refer to wireless remote controller manual for detail)
When installing 2 remote controllers to one indoor unit with event communication function, set
the master/slave of the remote controller. (Refer to remote controller master/slave selection) When controlling the group, some functions excluding basic operation setting, fan level Min/Mid/Max, remote controller lock setting and time setting may be limited.
<When simultaneously connecting
2 sets of wired remote controller>
• When controlling in groups, set the master/slaver of the remote controller. Refer to Installer setting section on how to set master/slave for more detail.
#3 switch OFF: Master
(Factory default setting)
#3 switch ON: Slave
Wall Side
Wall Side
Wall Side
Wall Side
<Connecting order>
<Separating order>
3. Please fix remote controller upper part into the setup board attached to the surface of the wall, as the picture below, and then, connect with setup board by pressing lower part.
- Please connect not to make a gap at the remote controller
and setup board’s upper and lower, right and left part.
- Before assembly with the installation board, arrange the
Cable not to interfere with circuit parts.
When separating remote controller from setup board, as the picture below, after inserting into the lower separating hole using screw driver and then, spinning clockwise, remote controller is separated.
- There are two separating holes. Please individually
separate one at a time.
- Please be careful not to damage the inside
components when separating.
4. Please connect indoor unit and remote controller using connection cable.
5. Please use extension cable if the distance between wired remote controller and indoor unit is more than 10m.
Please check if connector is normally connected.
Connecting cable
Indoor Unit side
When installing the wired remote controller, do not bury it in the wall. (It can cause damage in the temperature sensor.) Do not install the cable to be 50m or above. (It can cause communication error.)
• When installing the extension cable, check the connecting direction of the connector of the remote controller side and the product side for correct installation.
• If you install the extension cable in the opposite direction, the connector will not be connected.
• Specification of extension cable: 2547 1007 22# 2 core 3 shield 5 or above.
CAUTION
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Installations must comply with the applicable local/national or international standards.
• Apply totally enclosed noncombustible conduit (metal raceway) in case of local electric & building code require plenum cable usage.
CAUTION
12V Red
Signal Yellow
GND Black
1ON2345678 1ON2345678
Owner’s & Installation Manual 9
ENGLISH
8 New Wide Wired Remote Controller
Installation instruction
<Installer Setting Code Table>
1) General air-conditioner product
Some contents may not be displayed depending on the product function
Installation instruction
Installer setting mode is to set the detail function of the remote controller. If the installer setting mode is not set correctly, it can cause problems to the product, user injury or property damage. This must be set by an certificated installer, and any installation or change that is carried out by a non-certificated person should be responsible for the results. In this case, free service cannot be provided.
CAUTION
Installer Setting -How to enter installer setting mode
Function Code Value
If pressing button long for 3 seconds, it enters into remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode. Please press more than 3 seconds for sure.
1
When you enter the setting mode initially, Function code is displayed on the bottom of the LCD screen.
2
No. Function Code Value
1 Test Run 01 01:Set 2 Address Setting 02 00~FF : Address
<ESP Step> <ESP Value> <Example> 01:VeryLow 0 ~ 255 02:Low
3 E.S.P. Value 03
03:Med 04:High 05:Very High 01:Remo
4 Thermistor 04 02:Indoor
03:2TH 01:Low 02:Med
5 Ceiling Height 05
03:High 04:Very High 01:V-H 02:F-H
6 Static Pressure 06
03:V-L 04:F-L
7 Master Setting 07
00:Slave
※ If only “Plus1” series models 00 : Group setting
01:Master
01 : Single setting
8 Override Setting 08
00:Slave 01:Master
9 Dry Contact 09
00:Auto-Off 01:Auto-On
10
Release 3 Min.
10 01:Set
Delay
11 Zone State 11
01:Variable 02:Fixed
12
Celsius
12
00:Celsius
(Optimized only for U.S.A)
Fahrenheit Switching 01:Fahrenheit
13 Zone Type 13
00:Zone Controller 01:Damper Controller
14 Zone Number 14 02~04(Zone number)
Emergency Heater
15
Setting
18
16 Plasma 20 17 Electric heater 21 18 Humidifier 22
00: Not Installed
19 Elevation Grill 23
01: Installed
20 Ventilation Kit 24 21 Auxiliary Heater 25
Some categories of the menu may not be displayed according to the function of the product, or the menu name may be different.
Select mode Setup Low Ambient Heating Operation Setup FAN Speed 00 : not use 0 : not use 0 : fan off 01 : use 1 : use – compressor off(0℉/-18℃)/on(5℉/-15℃) 1 : fan on
2 : use – compressor off(5℉/-15℃)/on(10℉/-12℃) 3 : use – compressor off(10℉/-12℃)/on(15℉/-9℃)
Function Code ESP valueESP step
Owner’s & Installation Manual 11
ENGLISH
Installation instructionInstallation instruction
Installer Setting -Test Run Mode
After installing the product, you must run a Test Run mode. For details related to this operation, refer to the product manual.
10 New Wide Wired Remote Controller
2) General Ventilation product
Some contents may not be displayed depending on the product function
No. Function Code Value
1 Test Run 01 01 : Test Run Setup
2 02 00~FF : Address of Central Control
3 SA(Supply Air) ESP 03 <ESP level> <ESP value> <Example>
4 EA(Exhaust Air) ESP 04
01 : Low 0~255 02 : High 03 : Super High
5 Product Direction 05
01 : Normal 02 : Opposite
6 Quick Refresh Priority 06
01 : Supply Air First 02 : Exhaust Air First
7 Master Setting 07
00 : Slave 01 : Master
8 Override Setting 08
00 : Slave 01 : Master
9 Dry Contact 09
00 : Auto-Off 01 : Auto-On
10 Release Of 3 Minute Delay 10 01 : Set
11 Zone State 11
01 : Variable 02 : Fixed
12
Humidification for Singular1300 : Not in Use
Ventilation 01 : Use
13
Humidification for Heat Mode1400 : Automatic
Ventilation 01 : Manual
Address Setting
Function Code ESP valueESP step
If pressing button long for 3 seconds,
1
it enters into remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode. Please press more than 3 seconds for sure.
- Please cancel the right and left of wind direction for RAC product.
Function Code Set
Setup figure '01' blinks at the lower part
2
of indication window.
Press button to start.
3
During the test run, pressing the below
4
button will exit the test run.
- Select operation, temperature up/down, wind flow control, wind direction, start/stop button.
Owner’s & Installation Manual 13
ENGLISH
12 New Wide Wired Remote Controller
Installation instruction
If entering into ESP setup mode by using button, it indicates as the picture below.
2
Select ESP fan step by pressing button. (01: very low, 02: low, 03: medium, 04: high, 05: very high)
3
Move to ESP value setting by pressing button. (It is 000 when delivering from the warehouse.)
4
Press button to setup ESP value.
(It is possible to setup ESP value from 1 to 255, and 1 is the smallest and 255 is the biggest.)
5
Function code, ESP code
ESP value
If pressing button long for 3 seconds, it enters into remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode. Please press more than 3 seconds for sure.
1
Function Code ESP value
ESP step
Installer Setting -E.S.P.
• If you set ESP incorrectly, the air conditioner may malfunction.
• This setting must be carried out by a certificated-technician.
This is the function that decides the strength of the wind for each wind level and because this function is to make the installation easier.
It's the function to use for connecting central control. Please refer to central controller manual for the details
Function Code
Group No
Indoor No.
Set Group No. by pressing button.(0~F)
3
Move to Indoor No. setting option by pressing button.
4
Set Indoor No. by pressing button.
5
Press button to save.
6
Pressing button will exit settings mode. After setup, it automatically gets out of
setup mode if there is no button input for 25 seconds.
When exiting without pressing set button,
the manipulated value is not reflected.
7
If entering into address setup mode by using button, it indicates as picture below.
2
If pressing button long for 3 seconds, it enters into remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode. Please press more than 3 seconds for sure.
1
Installation instruction
Installer Setting - Setting Address of Central Control
When setting ESP value on the product without very weak wind or power wind function, it may not work.
Owner’s & Installation Manual 15
ENGLISH
14 New Wide Wired Remote Controller
Installation instruction
Installer Setting -Thermistor
The function of 2TH has different operation characteristics according to the product.
Temperature sensor selection Function
01 Remote controller Operation in remote controller temperature sensor 02 Indoor unit Operation in indoor unit temperature sensor
03 2TH
Cooling
Operation of higher temperature by comparing indoor unit's and wired remote controller’s temperature. (There are products that operate at a lower temperature.)
Heating
Operation of lower temperature by comparing indoor unit's and wired remote controller's temperature.
<Thermistor Table>
Installation instruction
Please be careful not to change the ESP value for each fan step.
It does not work to setup ESP value for very low/power step for some products.
ESP value is available for specific range belongs to the product.
This is the function to select the temperature sensor to judge the room temperature.
Select ESP fan step again by using
6
button and setup ESP value, as No. 4 and 5, that corresponds each wind flow
Press button to save.
7
Press button to exit.
8
After setup, it automatically gets out of
setup mode if there is no button input for 25 seconds.
Function code, ESP code
ESP value
When exiting without pressing set
button, the manipulated value is not reflected.
If pressing button long for 3
1
seconds, it enters into remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode. Please press more than 3 seconds for sure.
If moving to room temperature perception
2
sensor selection menu by pressing button, it indicates as picture below.
Set Thermistor value by pressing
3
button. (01: Remote Controller, 02: Indoor, 03: 2TH)
Function Code Thermistor setting
Press button to save.
4
Pressing button will exit settings mode.
5
After setup, it automatically gets out of
setup mode if there is no button input for 25 seconds.
When exiting without pressing set button,
the manipulated value is not reflected.
Owner’s & Installation Manual 17
ENGLISH
16 New Wide Wired Remote Controller
Installation instruction
Installer Setting -Static Pressure Setting
This function is applied to only duct type. Setting this in other cases will cause malfunction.
Pressure selection
Function
Zone state ESP standard value 01 V-H Variable High 02 F-H Fixed High 03 V-L Variable Low 04 F-L Fixed Low
<Static Pressure Setting Table>
Installation instruction
Installer Setting -Ceiling Height Selection
This function is to adjust FAN Airflow rate according to ceiling height (For ceiling type product)
Ceiling height setting is available only for some products.
Ceiling height of ‘Very high’ function may not exist depending on the indoor unit.
Refer to the product manual for more details.
Ceiling Height Level Description
01 Low Decrease the indoor airflow rate 1 step from standard level 02 Medium Set the indoor airflow rate as standard level 03 High Increase indoor airflow rate 1 step from standard level 04 Very high Increase indoor airflow rate 2 steps from standard level
<Ceiling Height Selection Table>
If pressing button long for 3
1
seconds, it enters into remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode. Please press more than 3 seconds for sure.
If moving to ceiling height selection menu by
2
pressing button, it indicates as picture below.
Select ceiling height value by pressing
3
button. (01:Low, 02:Medium, 03:High, 04:Very high)
Function Code Thermistor setting
Press button to save.
4
Pressing button will exit settings mode.
5
After setup, it automatically gets out of
setup mode if there is no button input for 25 seconds.
When exiting without pressing set button,
the manipulated value is not reflected.
Press button for 4 seconds
1
to enter the installer setting mode until timer segment displays “01:01”.
If pressing button repeatedly, it
2
moves to static pressure selection menu as picture below.
Select static pressure by pressing
3
button. (01:V-H, 02:F-H, 03:V-L, 04:F-L)
Function Code Pressure
Press button to save.
4
Pressing button will exit settings mode.
5
After setup, it automatically gets out of
setup mode if there is no button input for 25 seconds.
When exiting without pressing set button,
the manipulated value is not reflected.
Owner’s & Installation Manual 19
ENGLISH
18 New Wide Wired Remote Controller
Installation instruction
Installer Setting - Override Master/Slave Setting
Override master/slave selection function is, since Multi-V 7 series model, the function to prevent product's different mode operation. If it setup as the slave, It blocks to change opposite run mode to outdoor unit cycle (cooling/heating)
Installation instruction
Installer Setting-Remote Controller Master/Slave Setup
It is a function for settings in group control, or 2-remote controller control.
Remote controller Function
Master
Indoor unit operates based on master remote controller at group control. (Master is set when delivering from the warehouse.)
Slave
Setup all remote controllers except one master remote controller to slave at group control
When controlling in groups, basic operation settings, airflow strength weak/medium/strong,
lock setting of the remote controller, time settings, and other functions may be restricted.
Refer to the 'group control' part for details
Override master/slave selection function is possible to use only when it is connected to the
succeeding models of Multi-V 7 series.
If it is set as Override Slave, icon
is displayed on LCD Display Window. (See Figure 1)
Figure 1.
If pressing button long for 3
1
seconds, it enters into remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode. Please press more than 3 seconds for sure.
If pressing button repeatedly, it moves to
2
master/slave selection menu as picture below.
Select Master/ Slave by pressing
3
button. (00: Slave, 01: Master)
Function Code Master/Slave value
Press button to save.
4
Pressing button will exit settings mode.
5
After setup, it automatically gets out of
setup mode if there is no button input for 25 seconds.
When exiting without pressing set button,
the manipulated value is not reflected.
If pressing button long for 3
1
seconds, it enters into remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode. Please press more than 3 seconds for sure.
If pressing button repeatedly, it moves to
2
override master/slave selection menu as picture below.
Select Master/ Slave by pressing
3
button. (00: Slave, 01 : Master)
Function Code Master/Slave
Press button to save.
4
Pressing button will exit settings mode.
5
After setup, it automatically gets out of
setup mode if there is no button input for 25 seconds.
When exiting without pressing set button,
the manipulated value is not reflected.
Owner’s & Installation Manual 21
ENGLISH
20 New Wide Wired Remote Controller
Installation instruction
Installer Setting - Zone State
It is the function to setup indoor unit's wind flow to variable or fixed.
- Variable : Comp ON, setup airflow. Comp OFF, weak wind
- Fixed : Comp ON, setup airflow. Comp OFF, setup airflow
Installation instruction
Installer Setting-Dry Contact Mode Setting
Dry contact function is the function that is possible to use only when dry contact equipment is separately purchased/setup.
Please refer to dry contact manual for more details.
What is Dry Contact? Like hotel card key and body perception sensor, it is the signal of the point of contact when using air-conditioner by interlocking.
If pressing button long for 3
1
seconds, it enters into remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode. Please press more than 3 seconds for sure.
If pressing button repeatedly, it moves to
2
remote controller dry contact mode setup menu as picture below.
If pressing button long for 3
1
seconds, it enters into remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode. Please press more than 3 seconds for sure.
If moving to ceiling height selection menu by
2
pressing button, it indicates as picture below.
Select Dry contact setting by
3
pressing button. (00 : Manual, 01 : Automatic)
Function Code Dry Contact
4
5
setting value
Press button to save.
Pressing button will exit settings mode. After setup, it automatically gets out of
setup mode if there is no button input for 25 seconds.
When exiting without pressing set button,
the manipulated value is not reflected.
Select Zone State rate fixing mode by
3
pressing button. (01: Variable, 02: Fixed)
Function Code Zone State
Press button to save.
4
Pressing button will exit settings mode.
5
After setup, it automatically gets out of
When exiting without pressing set button,
fixing mode
setup mode if there is no button input for 25 seconds.
the manipulated value is not reflected.
Loading...
+ 25 hidden pages