LG MS18AH INSTALLATION INSTRUCTIONS

www.lg.com
INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it thoroughly.
P/NO : 3828A20403C
ENGLISH
ITALIANO ESPAÑOL FRANÇAIS DEUTSCH
2 Room Air Conditioner
Room Air Conditioner Installation Manual
TABLE OF CONTENTS
Safety Precautions............................3
Introduction........................................5
Symbols used in this manual..........5
Features ...........................................5
Installation ..........................................6
Installation parts...............................6
Installation tools ...............................6
Installation map................................7
Selecting the best location .............8
Piping length and elevation.............9
Fixing installation plate..................10
Drilling a hole in the wall ...............10
Flaring work ...................................11
Connecting the piping ..................12
Connecting the cables ..................18
Checking the drainage..................20
Forming the piping.........................21
Air purging......................................22
Test running ...................................24
Combination indoor units................26
Max Combination Capacity.............27
Four type "A" screws & plastic
anchors
Connecting cable
Installation guide map
Pipes: Gas side
Liquid side
Insulation materials
Additional drain pipe
(Outer diameter ..............15.5mm)
Two type "B" screws
Level gauge
Screw driver
Electric drill
Hole core drill(ø70mm)
Horizontal meter
Flaring tool set
Specified torque wrenches
1.8kg.m, 4.2kg.m, 5.5kg.m,
6.6kg.m (different depending on model No.)
Spanner ........................Half union
A glass of water
Screw driver
Hexagonal wrench(4mm)
Gas-leak detector
Vacuum pump
Gauge manifold
Owner's manual
Thermometer
Remote control holder
Installation
Requirements
Required Parts Required Tools
Installation Manual 3
ENGLISH
Safety Precautions
To prevent the injury of the user or other people and property damage, the following instructions must be followed.
Be sure to read before installing the air conditioner.
Be sure to observe the cautions specified here as they include important items related to safety.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
The meanings of the symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
Safety Precautions
Do not disassemble or repair the product.
• Contact your dealer or service center.
Always earth the product.
• It will cause fire or electric shock.
Do not handle the flamable gas or explosive materials near the product.
• Otherwise, it may cause fire or failure of product.
Do not install where flamable gas could leak.
• Otherwise, it may cause esplosion or fire.
Do not install the product on an defected installation stand.
• Otherwise, It may cause injury or accident.
Be cautious when unpack and install the product.
• Sharp edges could cause injury.
For electric work, contact the dealer or service center.
• Otherwise, It will cause fire or electric shock.
Do not use damaged power cable.
• It will cause fire or electric shock.
For installation, always contact the dealer or service center.
• Otherwise, it may cause fire, electric shock, explosion or injury."
Do not install the product on an defected installation stand.
• Otherwise, It may cause injury or accident
4 Room Air Conditioner
Safety Precautions
If strange sound, smell or smoke come from product, turn the breaker off or disconnect the power supply cable.
• Otherwise, it may cause electric shock or fire.
Do not put the heater, etc. near the power cable.
• Otherwise, it may cause fire and electric shock.
Cover the electric part.
• Otherwise, it may cause fire or electric shock.
Do not turn the breaker on/off or connect/disconnect the power supply plug during operation.
• Otherwise, it may cause fire or electric shock.
Do not open the suction inlet of the product during operation.
• Otherwise, it may cause electric shock or failure.
Do not touch the metal parts of the product when removing the air filter.
• Otherwise, it may cause personal injury.
Always inspect gas leakage after installation and repair of product.
• Otherwise, it may cause failure of product.
Install the drain hose to ensure that drain can be securely done.
• Otherwise, it may cause water leakage.
Keep the level even in installing the product.
• Otherwise, it may cause vibration or water leakage.
Do not install the product where the noise or hot wind from the outdoor unit could give any casualty to the neighborhood
• Otherwise, it may cause dispute with the neighborhoods.
Do not step or put anyting on the product.
• Otherwise, it may cause personal injury and failure of product.
Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
There is the risk of death, injury, fire or explosion.
Always intstall an circuit breaker and main breaker.
• No installation may cause fire and electric shock.
Do not touch(operate) product with wet hands.
• Otherwise, it may cause fire or electric shock.
Installation Manual 5
ENGLISH
Introduction
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that may cause harm to the air conditioner.
This symbol indicates special notes.
NOTICE
Introduction
Symbols used in this Manual
Features
Air Outlet
Air Intake
(side, rear)
Connection pipe Drain hose
Connecting wire
Control cover
Air Intake Vents
Air Outlet Vents
Base Plate
Base Plate
Connection pipe Drain hose
Connecting wire
Control cover
Air Inlet
Air Filter
Front Panel
Signal Receptor
6 Room Air Conditioner
Installation
Type "A" screw (6 EA) Type "A" screw (8 EA)
Type "B" screw Type "B" screw
Remote control holderRemote control holder
Type 1 Type 2
Installation plate Installation plate
Figure FigureName
Screw driver
Electric drill
Measuring tape, Knife
Hole core drill
Spanner
Torque wrench
Ohmmeter
Hexagonal wrench
Ammeter
Gas-leak detector
Thermometer,
Horizontal meter
Flaring tool set
Name
Installation Parts
Installation Tools
Installation
Read carefully, and then follow step by step.
Installation Manual 7
ENGLISH
Installation
Installation Map
Installation parts you should purchase.
Vertical Air deflector
Air Discarge
Forced Operation Button
Operation Indication Lamps/
Signal Receptor
Vinyl tape (Wide)
Apply after carrying out a drainage test.
To carry out the drainage test, remove the air filters and pour water into the heat exchanger.
Saddle
Gas side piping (Optional Parts) Liquid side piping (Optional Parts) Additional drain pipe
Vinyl tape (Narrow) Drain Hose
Base Plate
Connecting cable (Optional Parts)
Installation plate Sleeve Bushing-Sleeve
Putty(Gum Type Sealer)
Bend the pipe as closely on the wall as possible, but be careful that it doesn't break.
NOTICE
Air Outlet Vents
Air Inlet Vents
8 Room Air Conditioner
Installation
Indoor unit
1. Do not have any heat or steam near the unit.
2. Select a place where there are no obstacles
in front of the unit.
3. Make sure that condensation drainage can be
conveniently routed away.
4. Do not install near a doorway.
5. Ensure that the interval between a wall and
the left (or right) of the unit is more than 50cm. The unit should be installed as high as possible on the wall, allowing a minimum of 10cm from ceiling.
6. Use a stud finder to locate studs to prevent
unnecessary damage to the wall.
Outdoor unit
1. If an awning is built over the unit to prevent
direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
2. Ensure that the space around the back and
sides is more than 10cm. The front of the unit should have more than 70cm of space.
3. Do not place animals and plants in the path
of the warm air.
4. Take the weight of the air conditioner into
account and select a place where noise and vibration are minimum.
5. Select a place where the warm air and noise
from the air conditioner do not disturb neighbors.
Rooftop Installations:
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop mounting.
Select the best Location
More than 10cm
More than
5cm
More than 2.3m
More than
5cm
Install the indoor unit on the wall where the height from the floor is more than 2 meters.
more than
70cm
more than
30cm
more than
30cm
more than
20cm
more than
20cm
more than
70cm
Installation Manual 9
ENGLISH
Installation
h2
h1
h1
A
A
Branch Pipe
Main Pipe
Distributor
Distributor
B
B
h2
Multi Piping Type Distributor Type
Multi Piping Type (m)Indoor Pipe Size
Distributor Type (m)
Piping length and elevation
14k/16k 30 20 15 7.5
18k 40 25 15 7.5 24k 50 25 15 7.5 30k 70 25 15 7.5
Capacity
(Btu/h)
Total
Length
Max
Length(A/B)
Max Elevation
(h1)
In - In Elevation
(h2)
7k, 9k, 12k
3/8" 1/4"
18k, 24k 1/2" 1/4"
Capacity
(Btu/h)
Pipe Size
GAS LIQUID
40k 100 50 50 15 30 10 48k 110 50 60 15 30 10 56k 120 50 70 15 30 10
Capacity
(Btu/h)
Total Length
Max Main Pipe
Length (A/B)
Total Branch
Pipe Length
Max Branch Pipe Length
Max Elevation
(h1)
In - In Elevation
(h2)
CAUTION: Capacity is based on standard length and maximum allowance length is on the basis of reliability. Oil trap should be installed every 5~7 meters.