LG LZ-H100GXN4 INSTALLATION INSTRUCTIONS

www.lg.com
Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
[
Representative] LG Electronics Inc. EU Representative : LG Electronics European
Shared Service Center B.V. Krijgsman 1, 1186 DM Amstelveen, The Netherlands
[Manufacturer] LG Electronics Inc. Changwon 2nd factory 84, Wanam-ro,
Seongsan-gu, Changwon-si, Gyeongsangnam-do, KOREA
INSTALLATION MANUAL
AIR CONDITIONER
P/NO : MFL69268904
For more information, Refer to the CD or LG Web site (www.lg.com).
VENTILATOR Original instruction
ENGLISH ITALIANO ESPAÑOL
FRANÇAIS DEUTSCH
ΕΛΛΗΝΙΚΆ
ČEŠTINA
NEDERLANDS
POLSKI
LIMBA ROMÂNĂ
2 Ventilator
Ventilator Installation Manual
TABLE OF CONTENTS
Safety Precaution.................3
Introduction ..........................8
Feature Dimension
Diagram...............................8
Standard drawing of installa-
tion ........................................9
Installation ..........................11
Selection of the best
location ..............................11
Ceiling dimension and hang-
ing bolt location .................12
Indoor Unit Installation.......13
Drain Piping and Water Sup-
ply Work..............................15
Check the drainage ...........16
Install the water supply
piping.................................16
Insulate all piping that
passes indoors ..................17
Duct Connection ................18
Connecting Pipes...............19
Preparation of Piping.........19
Connecting the pipings to the indoor unit and drain hose to
drain pipe...........................20
Insulation, Others ..............20
Wiring Connection .............21
Electrical Wiring
..................21
Method to Connect Wiring
...23
Wiring for the Humidity Regu-
lator (Locally Procured) .....25
Wiring Example .................26
Installer Setting and Test Run
...............................27
Installer setting - How to enter installer setting mode
.........27
Installer Setting – Function
explanation ........................29
Run the humidifier .............31
In case of finding a problem at a test run
..............................32
Airborne Noise Emission
.....32
Limiting concentration ..........32
• Screws
• Nuts
• Ceiling Fixing Bolt(M10~12)
• Washer
• Aluminium Tape
• Screws
• Screw Driver
• Spanner
• Cutter
• Cutter
• Screw Driver
Installation
Requirements
Required Parts Required Tools
Safety Precautions
Installation Manual 3
ENGLISH
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
CAUTION
This symbol indicates the possibility of injury or damage.
Installation
Do not use a defec­tive or underrated cir­cuit breaker. Use this appliance on a dedi­cated circuit.
• There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
• Do not disassemble or repair the product. There is risk of fire or electric shock.
Always ground the product.
• There is risk of fire or electric shock.
Install the panel and the cover of control box securely.
• There is risk of fire or electric shock.
Always install a dedi­cated circuit and breaker.
• Improper wiring or installation may cause fire or electric shock
Use the correctly rated breaker or fuse.
• There is risk of fire or electric shock.
WARNING
Do not modify or extend the power cable.
• There is risk of fire or electric shock.
Do not install, remove, or re-install the unit by yourself (customer).
• There is risk of fire, electric shock, explo­sion, or injury.
Be cautious when unpacking and installing the prod­uct.
• Sharp edges could cause injury.
Safety Precautions
4 Ventilator
For installation, always contact the dealer or an Authorized Service Center.
• There is risk of fire, electric shock, explo­sion, or injury.
Do not install the product on a defec­tive installation stand.
• It may cause injury, accident, or damage to the product.
Do not let the product run for a long time when the humidity is very high and a door or a window is left open.
• Moisture may condense and wet or damage fur­niture.
Install the air intake where polluted air can not be directly sucked in.
• It may cause various accidents, including suf­focation, due to the suc­tion of harmful gasses(CO, etc.)
Do not install this product in a refriger­ated warehouse, heated swimming pool or other location where the tempera­ture and humidity are significantly differ­ent.
• There is risk of electrical shock, malfunctioning.
Install this product in an environment where the tempera­ture ranges from –15°C to +45°C and the relative humidity is less than 80%. It condensation is expected to form, heat up the fresh out­side air using a duct heater etc.
For re-installation of the installed product, always contact the dealer or an Autho­rized Service Center.
• There is risk of fire, electric shock, explosion or injury.
Do not open the maintenance cover of the main body during operation.
• Otherwise, it may cause electrical shock.
Use the outdoor air suction hole with the net installed to ensure that birds could not come in.
• Remove estrange things like the bird’s nest. Oth­erwise, it may cause scarcity of indoor oxy­gen.
Safety Precautions
Installation Manual 5
ENGLISH
Install this product in and environments where the outside air intake meets the fol­lowing conditions: temperature range is between –15°C and +40°C and the rela­tive humidity is 80% or less.
Use the designated electrical wires for the terminal board connections, and connect the wires securely so that they will not become dis­connected. (Failure to ensure proper con­nections may cause fire.)
When passing metal ducts through wood­en buildings clad with metal laths, wire laths or metal, these ducts must be installed in such a way that they will not make electrical con­tact with the metal laths, wire laths or metal sheets. (Power leakage can cause ignition)
Avoid fire equipment
• There is risk of fire.
When the product is soaked (flooded or submerged), contact an Authorized Service Center.
• There is risk of fire or eletric shock.
Don't touch a dedicat­ed circuit or breaker with wet hands.
• There is risk of electric shock.
Operation
When the product is not be used for a long time, disconnect the power supply plug or turn off the breaker.
• There is risk of product damage or failure, or unintended operation.
Do not store or use flammable gas or combustibles near the product.
• There is risk of fire or failure of product.
When flammable gas leaks, turn off the gas and open a window for ventilation before turn the product on.
• Do not use the tele­phone or turn switches on or off. There is risk of explosion or fire
Safety Precautions
6 Ventilator
CAUTION
Don't connect the ground wire to the win­dow frame or water cock.
• There is risk of electric shock.
Do not install the prod­uct at a smoky and oily place like kitchen or factory.
• Otherwise. oil may adhere to the filter or heating exchanger and cause trouble.
Install the product in an insulated space from outdoor air.
• In case of installing the product outside of the insulated layer, dewing occurs inside of the main body in winter.And it causes electrical shock or falling of con­densed water.
Installation
Glove should be worn when doing the installation work. (There is risk of injury.)
Be cautious that water could not enter the product.
• There is risk of fire, electric shock, or prod­uct damage.
Turn the breaker off when cleaning or maintaining the prod­uct.
• There is risk of electric shock.
The outside ducts must be tilted at a gradient (1/30 or more) down toward the outdoor area from the ventilator unit, and properly insulated. (The entry of rain water may cause power leaks, fire or damage to household property.)
Safety Precautions
Installation Manual 7
ENGLISH
Keep level even when installing the prod­uct.
• To avoid vibration or water leakage.
Use two or more peo­ple to lift and trans­port the product.
• Avoid personal injury.
Do not install the product where it will be exposed to sea wind (salt spray) directly.
• It may cause corrosion on the product. Corro­sion, particularly on the condenser and evapora­tor fins, could cause product malfunction or inefficient operation.
Use a soft cloth to clean. Do not use harsh detergents, wax or thinner, etc.
• Otherwise, color or sur­face of the oroduct mav deteriorate.
Clean the filter and the heat exchanger regu­larly and use the gloves for cleaning.
• Adhering to a mass of dust may cause the deterioration of air vol­ume.
Do not use the prod­uct for special purpos­es, such as preserving foods, works of art, etc. It is a consumer ventilator, not a preci­sion refrigeration sys­tem.
• There is risk of damage or loss of property.
Operation
Do not block the inlet or outlet of air flow.
• It may cause product failure.
Do not step on or put anyting on the product.
• There is risk of personal injury and failure of product.
Do not install the ventilation unit alone for controlling room temperature.
• If this is needed, install with another Indoor unit (air conditioner).
Introduction
8 Ventilator
Introduction
Feature Dimension Diagram
Model : LZ-H050GXN4, LZ-H080GXN4, LZ-H100GXN4
LZ-H050GXH4, LZ-H080GXH4, LZ-H100GXH4
Model
1667 1140 365 599 1006 1204 185 242 252 74 510 488 449 70 67 278 29 55 83 1239 105
ABCD EFGHJ KLMNPQRSTU Vkg
LZ-H050GXN4/LZ-H050GXH4
LZ-H080GXN4/LZ-H080GXH4
LZ-H100GXN4/LZ-H100GXH4
Figure Duct Pitch
Pipe Connec-
tion
Drain Hose Connection
Water Supply Pip-
ing Connection
Wei-
ght
Width
Pitch of Suspension
Fixture
Duct Connection
Flange
Unit : mm
Application tools (CMH)
Standard drawing of installation
Installation Manual 9
ENGLISH
Standard drawing of installation
LZ-H050GXN4 / LZ-H080GXN4 / LZ-H100GXN4
EA
(Exaust air outlet)
OA
(Fresh air outlet)
Duct normal diameter
ØC(user-supplied)
EA
(Exaust air outlet)
(Fresh air outlet)
OA
Ceiling suspension
bolts position
More than 600
150~250
C
Refrigerant piping (Gas pipe) (Φ12.7 Flare connection)
Duct slope: More than 1/30(toward the wall) Obtaining of right distance (preventing penetration of rain water)
A
B
Inspection
hatch
Inspection part
450( 600)
Inspection
hatch
600
600600
150~200
Maintenance space
Total heat Exchanger
()
Air Filter
Ceiling Fixing Bolt
(user-supplied)
Refrigerant piping
(Liquid pipe)
(Φ 6.35 Flare con
nection)
C
Drain pipe (Inner diameter : 25.4)
Sloping downwards at a Gradient of the 1/100
RA
(Return air)
Air return grille (user-supplied)
Air return grille
Air supply grille (user-supplied)
Y duct connecting
(user-supplied)
SA
(Supply air)SA(Supply air)
Air supply grille
LZ-H050GXN4 LZ-H080GXN4 LZ-H100GXN4
[Unit : mm]
CBAModel
25012041006
Standard drawing of installation
10 Ventilator
LZ-H050GXH4 / LZ-H080GXH4 / LZ-H100GXH4
CBAModel
LZ-H050GXH4 LZ-H080GXH4 LZ-H100GXH4
[Unit : mm]
Duct slope: More than 1/30(toward the wall) Obtaining of right distance (preventing penetration of rain water)
Ceiling Fixing Bolt
(user-supplied)
Air supply grille
Air return grille
Inspection hatch
Duct normal diameter
ØC(user-supplied)
EA
(Exaust air outlet)
OA
(Fresh air outlet)
RA
(Return air)
SA
(Supply air)
SA
(Supply air)
C
C
Water supply shut-off valve (user-supplied)
Drain valve
(user-supplied)
Strainer
(user-supplied)
Refrigerant piping (Liquid pipe)
(Ø 6.35 Flare connection)
Sloping downwards at a
Drain pipe (Inner diameter : 25.4)
Feed water pipe (Φ6.35 Flare connection)
Gradient of the 1/100
Cistern Tank
Refrigerant piping (Gas pipe) (Ø12.7 Flare connection)
25012041006
EA
(Exaust air outlet)
OA
(Fresh air outlet)
Ceiling suspension
bolts position
Maintenance space
Total heat Exchanger
Air Filter
Air supply grille (user-supplied)
Air return grille (user-supplied)
Y duct connecting
(user-supplied)
()
Inspection
hatch
Inspection
hatch
150~250
More than 600
150~200
600600
600
B
A
Installation
Installation Manual 11
ENGLISH
Installation
Selection of the best location
Read completely, then follow step by step.
Install the ventilator in the location that satisfies the following conditions.
• The place shall easily bear a load exceeding four times the indoor unit’s weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.(Suitable dimension “*C” is necessary to get a slope to drain as figure.)
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical noise.
• The place where air circulation in the room will be good .
• There should not be any heat source or steam near the unit.
In case that the unit is installed near the sea, the installation parts may be corroded by salt, The installation parts (and the unit) should be taken appropriate anti-corro­sion measures.
CAUTION
Front view
(unit : mm)
Unit (mm)
800 or more
Maintenance
Electric parts box
space
Side view
minimum
hight
C
20 or more
Installation
12 Ventilator
Installation of Unit
Install the unit above the ceiling correctly.
• Apply a Flexible duct between the unit and duct to absorb unnecessary vibration.
• Install the unit leaning to a drainage hole side as a figure for easy water drainage.
• A place where the unit will be leveled and that can support the weight of the unit.
• A place where the unit can withstand its vibration.
• A place where service can be easily performed.
• Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder
is in suspension in factories, etc.
• Avoid places where inflammable gas is generated, flows in, is stored or vented.
• Avoid places where sulfurous acid gas or corrosive gas is generated.
• Avoid places near high frequency generators.
CASE 1
CASE 2
Ceiling dimension and hanging bolt location
POSITION OF SUSPENSION BOLT
POSITION OF CONSOLE BOLT
1006 599
Return Air(RA)
Exhaust Air(EA)
Supply Air(SA)
1204
1140
Outdoor Air(OA)
Inspection hatches
600
600
600
600
Nut Washer
Double nut
Hanger bracket
Installation
Installation Manual 13
ENGLISH
Select and mark the position for fixing bolts.
Drill the hole for set anchor on the face of ceiling.
• Insert the set anchor and washer onto the suspension bolts for locking the suspen­sion bolts on the ceiling.
• Mount the suspension bolts to the set anchor firmly.
• Secure the installation plates onto the sus­pension bolts (adjust level roughly) using nuts, washers and spring washers.
Indoor Unit Installation
Tighten the nut and bolt to prevent unit falling.
CAUTION
Old building New building
1 Set anchor 2 Plate washer 3 Spring washer
4 Nut
5 Suspension bolts
Installation
14 Ventilator
• Attach the hanger bracket to the suspension bolt. Be sure to fix it securely by using nuts and washers (locally procured) from the upper and lower sides of the hanger bracket.
• Install the unit after checking the indoor (SA/RA) and outdoor (EA/OA) in accordance with the figure duct direction label.
• Adjust the height of the unit. (Tighten the double nuts securely.)
• Check the unit is horizontally level.
• Tighten the upper nut.
• Install declination of the ventilation unit with DX coil is very important for the drain
• Minimum thickness of the insulation for the connecting pipe shall be 10mm.
CAUTION
Use a level instrument to make sure that the unit is level and that the tilt (down slope) to the drain pip­ing connection is within 1 degree. (Refer to above figures.) One thing to watch out for in particular is if it is installed so that the slope is not in the Direction of the drain piping, as this might cause leaking.)
CAUTION
1 degree or less 1 degree or less
Drain hole
Horizontal line
Drain hole Duct connecting Flange
Drain Piping and Water Supply Work
Installation Manual 15
ENGLISH
100 mm
or more
Central drain piping
(Install with a downward slope of at least 1/100)
• Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air pock-
ets from forming.
• If converging multiple drain pipes, install according to the procedure shown below. (Install a drain
trap for each indoor unit.)
CAUTION
Drain Piping and Water Supply Work
• Always lay the drain with downward inclination (1/100 to 1/50). Prevent any upward flow or reverse flow in any part.
• 10mm or thicker formed thermal insulator shall always be provided for the drain pipe.
CORRECT
• Install the P-Trap (or U-Trap) to prevent a water leakage caused by the blocking of intake air filter.
Unit
Make sure to be closed.
• Upward routing not allowed
INCORRECT
Applied U-Trap Dimension
70 mm
A B ≥ 2C C
2 x SP
SP = External Pressure
(mmAq)
Ex) External Pressure
= 10 mmAq A ≥ 70 mm B ≥ 40 mm C ≥ 20 mm
Thermal insulator
(Local supply)
Drainage pipe (Local supply)
Drainage hole
C
A
B
U-Trap
Drain Piping and Water Supply Work
16 Ventilator
Test the drainage by pouring 1000cc of water into the drain pan through the inspection hole by remov­ing the maintenance cover (8 screws) or through the outlet duct joint of supply air to room (SA).
• Make sure that heat insulation work is executed on the Indoor drain piping and Drain outlet to pre­vent any possibility water leakage due to dew condensation.
Check the drainage
• Connect the water supply with strainer, other pipes and valves (locally procured) to the indoor unit as shown in the figure at below.
Install the water supply piping
When installing the water supply piping, wash the pipes with tap water so that all dirt is removed from them or install a drain valve somewhere along the piping and drain the pipes thoroughly until the water flowing through them is clear. Make sure no cutting oils or detergents get into the pipes.
CAUTION
Maintenance cover
Drain piping
(Locally procured)
Drain outlet
Duct connecting flange (SA)
Flexible hose
Feed Water
Water supply piping with strainer
Water supply shut-off valve
Water supply pipe
(Locally procured)
(Locally procured)
(Locally procured)
(Locally procured)
(Locally procured)
Cap
Drain valve
Drain outlet
Duct connecting flange (SA)
Drain Piping and Water Supply Work
Installation Manual 17
ENGLISH
• After checking that the drain piping connections do no leakage, insulate them using the insulation. (Tighten with a clamp material)
• Wrap the drain piping with insulation to prevent condensation from forming.
Insulate all piping that passes indoors
When installing the water supply piping, wash the pipes with tap water so that all dirt is removed from them or install a drain valve somewhere along the piping and drain the pipes thoroughly until the water flowing through them is clear. Make sure no cutting oils or detergents get into the pipes.
CAUTION
Tie wrap
(Locally procured)
Insulation (for drain piping)
18 Ventilator
Duct Connection
Duct Connection
• The change of air discharge grill’s location should be examined when the cold draft from air dis­charge grill is feared. The fan is driving while defrost operation, and the cold air is often blowing.
• After securely connect the duct with the duct connection flange, wrap it with a commercial aluminium tape so that air cannot be leaked.
• Adjust the duct from the ceiling so that no force is applied to the main body of the ventilation system.
• Always use two ducts at the outdoor with the heat insulating material for prevention of dewing.
Aluminum tape (Locally procured)
Aluminum tape (Locally procured)
Insulation material (Locally procured)
Slope :
Over 1/30
Outdoor duct
Make sure there is no slack in the duct.
Duct connecting flange
Duct to OA
Main Body
Heat Insulating Material
Aluminium
Duct Connection Flange
Rapid Bending Excessive Bending
Too Close Bending
to Outlet
Rapid Reduction of
Duct Diameter
• Check that there are no foreign materials
(paper, vinyl, etc) or cutoff powders in the duct before connecting the duct.
Take care so that shock may not be applied to the damper plate within the main body when performing the duct connection work.
It is recommended to perform adiabatic treat­ment even to the duct pipe at the indoor side where ambient temperature is expected when the main body of the ventilation system for cool­ing in summer.
Take care so that work may not be performed as in the left figure. Otherwise, it may cause reduction of air volume or abnormal noise.
CAUTION
Outdoor duct slop
: More than 1/30(toward the wall) Obtaining of right distance (preventing penetration of rain water)
Installation Manual 19
ENGLISH
Connecting Pipes
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the follow­ing procedure.
Cut the pipes and the cable.
• Use the accessory piping kit or the pipes pur­chased locally.
• Measure the distance between the indoor and the outdoor unit.
• Cut the pipes a little longer than measured dis­tance.
Cut the cable 1.5m longer than the pipe length.
Burrs removal
• Completely remove all burrs from the cut cross section of pipe/tube.
Put the end of the copper tube/pipe to downward direction as you remove burrs in order to avoid to let burrs drop in the tubing.
Putting nut on
• Remove flare nuts attached to indoor and out­door units, than put them on pipe/tube having completed burr removal. (Not possible to put them on after flaring work)
Flaring work
Carry out flaring work using dedicated flaring tool for R-410A as shown below.
Firmly hold copper tube in a bar(or die) as indicat­ed dimension in the table above.
Check
• Compare the flared work with figure below.
• If flare is noted to be defective, cut off the flared section and do flaring work again.
Outside diameter "A"
mm inch mm Ø6.35 1/4 1.1~1.3 Ø9.52 3/8 1.5~1.7 Ø12.7 1/2 1.6~1.8
Ø15.88 5/8 1.6~1.8 Ø19.05 3/4 1.9~2.1
Connecting Pipes
Preparation of Piping
Copper
tube
Point down
Copper tube
Slanted Uneven Rough
90°
Pipe
Flare nut
Reamer
Bar
Copper pipe
Smooth all round
Even length
all round
Handle
Bar
"A"
Clamp handle
Inside is shining without scratches
= Improper flaring =
Inclined
Surface
damaged
Yoke
Red arrow mark
Cracked Uneven
thickness
Cone
20 Ventilator
Connecting Pipes
Connecting the pipings to the indoor unit and drain hose to drain pipe
Insulation, Others
• Align the center of the pipings and sufficiently tighten the flare nut by hand.
• Tighten the flare nut with a wrench.
• When extending the drain hose at the indoor
unit, install the drain pipe.
• Insulate the joint and tubes completely
mm inch kg.m Ø6.35 1/4 1.8~2.5 Ø9.52 3/8 3.4~4.2 Ø12.7 1/2 5.5~6.6
Ø15.88 5/8 6.6~8.2 Ø19.05 3/4 9.9~12.1
Outside diameter Torque
All thermal insulation must comply with local require­ment.
THERMAL INSULATION
Indoor unit tubing Flare nut Pipings
Spanner (fixed)
Flare nut
Torque wrench
Indoor unit tubing
Drain pipe
Adhesive
Indoor unit drain hose
Vinyl tape(narrow)
Connection pipe
Union for liquid pipe
Refrigerant pipe and thermal insulator(Local supply)
Hose crip for thermal insulator (Local supply)
Thermal insulator for refrigerant pipe (Local supply)
Union for gas pipe
Thermal insulator for refrigerant pipe (Local supply)
Hose crip for thermal insulator(Local supply)
Make sure that there is no clearance here.
Thermal insulator for piping(Local supply)
Overlap with thermal insulator for piping.
Installation Manual 21
ENGLISH
Wire Specification
Power Cable Specification : The power cord connected to the outdoor unit should be com­plied with IEC 60245 or HD 22.4 S4(Rubber insulated cord, type 60245 IEC 66 or H07RN-F)
Precautions when laying power wiring
Use round pressure terminals for connections to the power terminal block.
• All wiring must comply with local requirements.
• Select a power source that is capable of supply­ing the current required by the ventilator.
• Use a recognized ELCB(Electric Leakage Circuit Breaker) between the power source and the unit. A disconnection device to adequately disconnect all supply lines must be fitted.
• Model of circuit breaker recommended by autho­rized personnel only
When none are available, follow the instructions below.
• Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power wiring may cause abnormal heat.)
• When connecting wiring which is the same thickness, do as shown in the figure below.
Wiring Connection
Perform the electrical wiring work according to the electrical wiring connection.
Wiring Connection
Electrical Wiring
MCA : Min. Circuit Amps (A) ; MOP : Maximum Over current Protection kW : Fan Motor Rated Output (kW) ; FLA : Full Load Amps (A)
Ventilation unit Power supply Fan motor
Hz Volts Voltage range MCA
2.8
2.8
2.8
8 8 8
0.2x2
0.2x2
0.2x2
1.25x2
1.25x2
1.25x2
MOP kW FLA
Max. 264V Min. 198V
Model LZ-H050GXN4 / LZ-H050GXH4 LZ-H080GXN4 / LZ-H080GXH4 LZ-H100GXN4 / LZ-H100GXH4
50
220-240 V
20mm
GN/YL
1 Phase(Ø)
Round pressure terminal
Power wire
Outdoor
Ventilation unit
Main power source
Switch box
ELCB
22 Ventilator
Wiring Connection
Make sure that the screws of the terminal are free from looseness.
WARNING
Connecting Cable Specification : The connecting cable, being used to connect the indoor unit and outdoor unit, should be complied with IEC 60335-1 standard (This equipment shall be provided with a cord set complying with the national regulation).
20mm
GN/YL
If the supply cable is damaged, it must be replaced by a special cable or assembly available from the manufacturer or its service agent.
Wiring Connection
Installation Manual 23
ENGLISH
Method to Connect Wiring
Make sure that the screws of the terminal are free from looseness.
WARNING
• Pass the power supply wiring and the ground wiring through the wiring through-hole into the electri­cal parts box and secure with the included clamping material after connecting the wires to terminal blocks.
Connect the wires to the terminals on the control board individually according to the outdoor unitcon­nection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.
The Power cord connected to the unit should be selected according to the following specifications .
CAUTION
Communication
Terminal Block
Input from outside (Indoor unit or MultiV outdoor unit)
Main Power
Terminal Block
Power supply wiring Ground wiring
Accessory
Terminal Block
Short-circuit wire
Remove when installing the humidistat. (locally procured)
Terminal Block Indoor
34
1(L)2(N)
Ventilation unit
Power Input
SODU
BA BABA
INTERNET DRY1 DRY2 GND 12V
IDU
Outdoor unit
24 Ventilator
Wiring Connection
Main PCB
Terminal Block
Power Supply Wiring
Remote Controller Wiring
485 PCB
Motor Driver PCB
Sub PCB
Screw
Clamp
• See “Label Circuit” on the backside of the cover of control box for electric wiring work.
• Be sure to attach the sealing material or putty (locally procured) to hole of wiring to prevent the infiltration of water as well as any insects and other small creatures from outside. Otherwise a short-circuit may occur inside the control box.
• When clamping the wires, be sure no pressure is applied to the wire connections by using the included clamping material to make appropriate clamps. Also, when wiring, make sure the lid on the control box fits snugly by arranging the wires neatly and attaching the control box cover firm­ly. When attaching the cover of control box, make sure no wires get caught in the edges. Pass wiring through the wiring through holes to prevent damage to them.
• Make sure the remote controller wiring, the wiring between the units, and other electrical wiring do not pass through the same locations outside of the unit, separating them by at least 50mm, otherwise electrical noise (external static) could cause mistaken operation or breakage.
CAUTION
Clamping of cables
Arrange 2 power cables on the control panel.
First, fasten the Plastic clamp with screw to the inner boss of control panel.
Installation Manual 25
ENGLISH
Wiring Connection
Wiring for the Humidity Regulator (Locally Procured)
<LZ-H***GXH series only>
Pass into the electric parts box together with the power wire through the power wiring through-hole. Remove the short-circuit wires on the accessory terminal block and connect the wiring for the humidity
regulator. Secure with cramping material together with the power wire.
Wiring specifications
Sheathed wire (should be complied with IEC60245 standard)
Size 0.75 - 1.25 mm
2
Length MAX. 100 m External contact specifications Normally closed contact (Current tolerance 10 mA - 0.5 A)
• If using humidistat, install one per ventilation unit. Controlling more than one ventilation unit with a single humidity controller may prevent normal humidity operation and cause water leakage, etc.
CAUTION
26 Ventilator
Wiring Example
• This unit can be used as part of the combined operation system used together with indoor units (Multi-V system air conditioners), or as an independent system for processing outside air.
<Combined operation system with Multi-V system(connected with ventilation units and stan­dard indoor units in a single refrigerant circuit)>
<Independent system (connected only with a ventilation unit in a single refrigerant circuit)>
GND
SIGNAL
Combined operated system
Communication line
LGAP Network System
12V
OK OK OK
Independent system
Communication line
LGAP Network System
OKOKOKOK
Wiring Connection
When this ventilation unit is combined with Multi V Plus 2 Series, sometimes the system does not cooling operate for self protection in low ambient temperature when the capacity of IDU, which is con­nected to ventilation unit, is less than or equal to 10% of total capacity of all IDUs. In this case, the capacity of the IDU connected to ventilation unit should be higher than 10% of total capacity of all IDUs
CAUTION
Installer Setting and Test Run
Installation Manual 27
ENGLISH
Installer Setting and Test Run
Installer setting -How to enter installer setting mode
Installer setting mode is to set the detail function of the remote controller. If the installer setting mode is not set correctly, it can cause problems to the product, user injury or property damage. This must be set by an certificated installer, and any installation or change that is carried out by a non-certificated person should be responsible for the results. In this case, free service cannot be provided.
CAUTION
Some categories of the menu may not be displayed according to the function of the prod­uct, or the menu name may be different.
• For more details, refer to the remote controller manual.
Accessory Model: PQRCVSL0/PQRCVSL0QW
If pressing button long for 3 seconds,
1
it enters into remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode. Please press more than 3 seconds for sure.
When you enter the setting mode
2
initially, Function code is displayed on the bottom of the LCD screen.
Function code Value
Installer Setting and Test Run
28 Ventilator
Accessory Model: PREMTB100
• In the menu screen, press [<,>(left/right)] button to select the setting category, and press [∧(up)]
button for 3 seconds to enter the password input screen for the installer setting.
• Input the password and press [OK] button to move to the installer setting list.
Installer setting password
Main screen → menu → setting service RMC version information SW Version Example) SW version : 1.00.1 a In the above case, the password is 1001.
Some categories of the menu may not be displayed according to the function of the prod­uct, or the menu name may be different.
• For more details, refer to the remote controller manual.
Remote controller (PQRCVSL0/PQRCVSL0QW/ PREMTB100) CO2sensor (AHCS100H0)
Available accessories
OK OK
Installer Setting and Test Run
Installation Manual 29
ENGLISH
Installer Setting – Function explanation
Test Run
When installing the product, test operation for checking the installation status
Setting Address of Central Control
When connecting central control, it sets the address of central control address of indoor unit.
Supply/Exhaust ESP setting
Set the E.S.P(RPM) value of air conditioner indoor unit.
Production Direction
Set the installation direction of ventilation indoor unit.
Override Setting
Set the Override condition by setting the Mode Master/Slave of indoor unit.
<Override connecting Scene>
Mode Master Mode Slave Mode Slave Mode Slave
Outdoor unit
OK OK OK OK
Remote Controller
Remote Controller
Remote Controller
Remote Controller
30 Ventilator
Installer Setting and Test Run
Zone Stats
Set the wind strength option of indoor unit as Variable or fixed.
Selecting Celsius or Fahrenheit
Control the temperature control unit by changing it Celsius Fahrenheit.
Humidification for Singlar Ventilation
Set the power supply to humidification When operating Singular ventilation of Direct Expansion or General Ventilation unit.
- When Humidification for ventilation is set In case of connection with General Ventilation : When operation is On, you can control the humid­ification In case of connection with Direct Expansion Ventilation: When ventilation is operated only, you can control the humidification. (When operating DX Coil, impossible to control humidification)
Humidification for Heat Mode Ventilation
Set the Humidification for Heat mode of direct expansion ventilation as automatic setting or manual setting.
- Automatic setting If air conditioner operation mode is set as heat, it automatically switches on the humidification.
- Manual setting If air conditioner operation mode is set as heat, you could turn on the humidification manually. (When it is set as heat mode, even the humidification is on, you cannot turn it off manually.)
- Humidification cancellation In case of the cancellation of heating operation, the product is off.
- Power failure compensation When power failure compensation, receive the automatic/manual data from the indoor unit to set the Value.
Installation Manual 31
ENGLISH
Installer Setting and Test Run
Run the humidifier
<LZ-H***GXH series only>
Check that the water supply piping is connected securely. Open the water supply shut-off valve. (No water will be supplied at this time.) Run the ERV™ unit in heating mode. (See the operating manual included with the indoor unit for
details on how to run the unit in heating mode.) The water supply will start and the humidifier will begin operation.
After starting heating (humidifying), the sound of the water supply solenoid valve will be heard at inter­vals of several minutes (a clicking sound), so listening for that clicking sound let the unit run for 30 minutes to make sure that humidifying operation is normal.
If carpentry work is not completed when a test run is finished, tell the customer not to run the humidifi­er for the protection of indoor unit and ERV™ until it is completed.
If the humidifier is run, paint, particles generated from adhesive and other materials used for carpentry work may cause ERV™ to get dirty, causing splash or leakage of water.
CAUTION
32 Ventilator
In case of finding a problem at a test run
The Product doesn't work
The Product doesn't work through you press the 'ON' switch
Even though you change the fan speed, the operation mode doesn't change and it changes to 'Auto or Low'
Even though you push the but­ton of remote controller, any function doesn't work.
Is power not supplied?
Is the Indoor temperature less than 45°c or more than 40°C?
Is the Indoor temperature less than -10°C or more than 45°C?
Is the icon " " displaying on
remote controller?
Is the icon " " displaying on remote controller? Does the message "HL" display on remote controller when you push the button.
Supply Power
It's standby mode for protecting Total Heat Exchanger.
It's operation mode to protect Total Heat Exchanger.
It's Child Lock mode. Refer to Remote controller.
It's centralized control mode. You can't control on remote controller.
Symptom Check Item Counter-measure
In case of finding a problem at a test run
The A-weighted sound pressure emitted by this product is below 70 dB. ** The noise level can vary depending on the site.
The figures quoted are emission level and are not necessarily safe working levels. Whilst there is a correlation between the emission and exposure levels, this cannot be used reliably to determine whether or not further precautions are required. Factor that influence the actual level of exposure of the workforce include the characteristics of the work room and the other sources of noise, i.e. the number of equipment and other adjacent processes and the length of time for which an operator exposed to the noise. Also, the permissible exposure level can vary from country to country. This information, how­ever, will enable the user of the equipment to make a better evaluation of the hazard and risk.
Limiting concentration: 0.44kg/m3(R410A)
Airborne Noise Emission
Limiting concentration is the limit of Freon gas concentration where immediate measures can be taken without hurting human body when refrigerant leaks in the air. The limiting concentration shall be described in the unit of kg/m3(Freon gas weight per unit air volume) for facilitating calculation
n Calculate refrigerant concentration
Refrigerant concentration =
Limiting concentration
Total amount of replenished refrigerant in refrigerant facility (kg)
Capacity of smallest room where indoor unit is installed (m
3
)
Loading...