LG LZ-H100GXN4 Instructions for quick setup

P/NO : MFL69268905
www.lg.com
Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
For more information, Refer to the CD or LG Web site (www.lg.com).
Krijgsman 1, 1186 DM Amstelveen, The Netherlands
[Manufacturer] LG Electronics Inc. Changwon 2nd factory 84, Wanam-ro, Seongsan-gu, Changwon-si,
Gyeongsangnam-do, KOREA
VENTILATOR
Original instruction
QUICK MANUAL
AIR CONDITIONER
ENGLISH
PORTUGUÊS
MALTI
ITALIANO
MAGYAR
SLOVENČINA
ESPAÑOL
БЪЛГАРСKN
SLOVENŠČINA
FRANÇAIS
SRPSKI
LATVIEŠU VALODA
DEUTSCH
HRVATSKI
LIETUVIŲ KALBA
ΕΛΛΗΝΙΚΆ
SVENSKA
GAEILGE
ČEŠTINA
NORSK
МАКЕДОНСКИ
NEDERLANDS
SUOMI
SHQIP
POLSKI
DANSK
ÍSLENSKA
LIMBA ROMÂNĂ
EESTI KEEL
BOSANSKI
2
ENGLISH
IMPORTANT SAFETY INSTRUC­TIONS
READ ALL INSTRUCTIONS BEFORE USING THE AP­PLIANCE.
Always comply with the following precautions to avoid dangerous situ­ations and ensure peak performance of your product
WARNING
This symbol indicates the possibility of death or serious injury.
CAUTION
This symbol indicates the possibility of injury or damage.
WARNING
Installation
• Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
- There is risk of fire or electric shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or an Author­ized Service Center.
- Do not disassemble or repair the product.
There is risk of fire or electric shock.
• Always ground the product.
- There is risk of fire or electric shock.
• Install the panel and the cover of control box securely.
- There is risk of fire or electric shock.
• Always install a dedicated circuit and breaker.
- Improper wiring or installation may cause
fire or electric shock
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Do not modify or extend the power cable.
- There is risk of fire or electric shock.
• Do not install, remove, or re-install the unit by yourself (customer).
- There is risk of fire, electric shock, explo-
sion, or injury.
• Be cautious when unpacking and installing the product.
- Sharp edges could cause injury.
• For installation, always contact the dealer or an Authorized Service Center.
- There is risk of fire, electric shock, explo-
sion, or injury.
• Do not install the product on a defective in­stallation stand.
- It may cause injury, accident, or damage to
the product.
• Do not let the product run for a long time when the humidity is very high and a door or a window is left open.
- Moisture may condense and wet or dam-
age furniture.
• For re-installation of the installed product, al­ways contact the dealer or an Authorized Service Center.
- There is risk of fire, electric shock, explo­sion or injury.
• Do not open the maintenance cover of the main body during operation.
- Otherwise, it may cause electrical shock.
• Use the outdoor air suction hole with the net installed to ensure that birds could not come in.
- Remove estrange things like the bird’s
nest. Otherwise, it may cause scarcity of indoor oxygen.
• Install the air intake where polluted air can not be directly sucked in.
- It may cause various accidents, including
suffocation, due to the suction of harmful gasses(CO, etc.)
• Do not install this product in a refrigerated warehouse, heated swimming pool or other location where the temperature and humid­ity are significantly different.
- There is risk of electrical shock, malfunc-
tioning.
• Install this product in an environment where the temperature ranges from -10 °C to +45 °C and the relative humidity is less than 80 %. It condensation is expected to form, heat up the fresh outside air using a duct heater etc.
• Install this product in and environments where the outside air intake meets the fol­lowing conditions: temperature range is be­tween -15 °C and +40 °C and the relative humidity is 80 % or less.
• Use the designated electrical wires for the terminal board connections, and connect the wires securely so that they will not become disconnected. (Failure to ensure proper con­nections may cause fire.)
• When passing metal ducts through wooden buildings clad with metal laths, wire laths or metal, these ducts must be installed in such a way that they will not make electrical con­tact with the metal laths, wire laths or metal sheets. (Power leakage can cause ignition)
Operation
• When the product is soaked (flooded or sub­merged), contact an Authorized Service Cen­ter.
- There is risk of fire or eletric shock.
• Don't touch a dedicated circuit or breaker with wet hands.
- There is risk of electric shock.
• Do not store or use flammable gas or com­bustibles near the product.
- There is risk of fire or failure of product.
• When flammable gas leaks, turn off the gas and open a window for ventilation before turn the product on.
- Do not use the telephone or turn switches
on or off. There is risk of explosion or fire.
!
!
!
3
ENGLISH
• Be cautious that water could not enter the product.
- There is risk of fire, electric shock, or prod-
uct damage.
• Turn the breaker off when cleaning or main­taining the product.
- There is risk of electric shock.
• The outside ducts must be tilted at a gradi­ent (1/30 or more) down toward the outdoor area from the ventilator unit, and properly in­sulated. (The entry of rain water may cause power leaks, fire or damage to household property.)
• Glove should be worn when doing the instal­lation work. (There is risk of injury.)
CAUTION
Installation
• Don't connect the ground wire to the win­dow frame or water cock.
- There is risk of electric shock.
• Do not install the product at a smoky and oily place like kitchen or factory.
- Otherwise, oil may adhere to the filter or
heating exchanger and cause trouble.
• Install the product in an insulated space from outdoor air.
- In case of installing the product outside of
the insulated layer, dewing occurs inside of the main body in winter. And it causes electrical shock or falling of condensed water.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• Use two or more people to lift and transport the product.
- Avoid personal injury.
• Do not install the product where it will be exposed to sea wind (salt spray) directly.
- It may cause corrosion on the product. Cor-
rosion, particularly on the condenser and evaporator fins, could cause product mal­function or inefficient operation.
Operation
• Use a soft cloth to clean. Do not use harsh detergents, wax or thinner, etc.
- Otherwise, color or surface of the oroduct
mav deteriorate.
• Clean the filter and the heat exchanger regu­larly and use the gloves for cleaning.
- Adhering to a mass of dust may cause the
deterioration of air volume.
• Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer ventilator, not a precision refrigeration system.
- There is risk of damage or loss of property.
• Do not block the inlet or outlet of air flow.
- It may cause product failure.
• Do not step on or put anyting on the prod­uct.
- There is risk of personal injury and failure
of product.
According to IEC 660335-1 This appliance is not intended for use by
persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
According to EN 660335-1 This appliance can be used by children aged
from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understnd the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision
The A-weighted sound pressure emitted by this product is below 70 dB.
** The noise level can vary depending on the site.
The figures quoted are emission level and are not necessarily safe working levels.
Whilst there is a correlation between the emission and exposure levels, this cannot be used reliably to determine whether or not further precautions are required.
Factor that influence the actual level of exposure of the workforce include the characteristics of the work room and the other sources of noise, i.e. the number of equipment and other adjacent processes and the length of time for which an operator exposed to the noise. Also, the permissible exposure level can vary from country to country.
This information, however, will enable the user of the equipment to make a better evaluation of the hazard and risk.
!
Airborne Noise Emission
4
OWNER’S MANUAL
ENGLISH
1 OPERATION INDICATION
screen
2 SET TEMPERATURE button 3 FAN SPEED button 4 ON/OFF button 5 OPRATION MODE
SELECTION button
6 WIRELESS REMOTE(*)
CONTROLLER RECEIVER
- Some products don't receive the wireless signals.
7 AIR FLOW button(*) 8 SUB FUNCTION button 9 FUNCTION SETTING button 10 VENTILATION button 11 RESERVATION 12 UP,DOWN,LEFT,RIGHT
button
13 ROOM TEMPERATURE
button(*)
14 SETTING/CANCEL button 15 EXIT button
h Some functions may not be operated and displayed depending on
the product type. Refer to remote controller in order to know detail functions.
h (*) : Functions for air conditioner.
OPERATING INSTRUCTIONS (ACCESSORY)
Name and Function of Remote Controller
Model: PREMTB100
Available accessories
Remote controller (PQRCVSL0/PQRCVSL0QW/PREMTB100) CO
2
sensor (AHCS100H0)
Operation display win­dow
Operation and Settings status display
Back button
When you move to the previous stage from
the menu’s setting stage Up/down/left/right but­ton
When you change the menu’s setting value
OK button
When you save the menu’s setting value
On/Off button
When you turn ON/OFF the air conditioner
1
10
9
8
7
11
12
13
14
15
Models : PQRCVSL0
PQRCVSL0QW
Please attach the inform label inside of the door. Please choose proper language depend on your country.
2
3
4
5
6
Operation display window
Back button
Up/Down/Left/Right Button
OK Button
On/Off Button
INSTALLATION MANUAL
5
ENGLISH
POSITION OF CONSOLE BOLT
- A place where the unit will be leveled and that can support the weight of the unit.
- A place where the unit can withstand its vibration.
- A place where service can be easily performed.
Case 2
- Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc.
- Avoid places where inflammable gas is generated, flows in, is stored or vented.
- Avoid places where sulfurous acid gas or corrosive gas is generated.
- Avoid places near high frequency generators.
Ceiling dimension and hanging bolt location
Install the unit above the ceiling correctly.
POSITION OF SUSPENSION BOLT Apply a Flexible duct between the unit and duct to absorb unnecessary
vibration.
Case 1
Install the unit leaning to a drainage hole side as a figure for easy water drainage.
Installation of Unit
Washer
Indoor Unit Installation
- Select and mark the position for fixing bolts.
- Drill the hole for set anchor on the face of ceiling.
- Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling.
- Mount the suspension bolts to the set anchor firmly.
- Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.
1 Set anchor
Plate washer
Spring washer
Nut
Suspension bolts
Old building New building
2
3
4
5
CAUTION
Tighten the nut and bolt to prevent unit falling.
!
- Attach the hanger bracket to the suspension bolt. Be sure to fix it securely by using nuts and washers (locally procured) from the upper and lower sides of the hanger bracket.
- Install the unit after checking the indoor (SA/RA) and outdoor (EA/OA) in accordance with the figure duct direction label.
- Adjust the height of the unit. (Tighten the double nuts securely.)
- Check the unit is horizontally level.
- Tighten the upper nut.
CAUTION
• Install declination of the ventilation unit with DX coil is very important for the drain
• Minimum thickness of the insulation for the connecting pipe shall be 10 mm.
!
CAUTION
Use a level instrument to make sure that the unit is level and that the tilt (down slope) to the drain piping connection is within 1 degree. (Refer to above figures.) If there is no slope in the direction toward the drain piping, it may cause water leak­age.
!
Exhaust Air(EA)
Outdoor Air(OA)
Hanger bracket
1006 599
600
600
Return Air(RA)
Supply Air(SA)
1204
1140
Inspection hatches
600
600
Nut Wash e
Wash er
Double nut
1 de gree or less 1 de gree or less
Drain hole
Horizontal line
Drain hole Duct connecting Flange
6
INSTALLATION MANUAL
ENGLISH
Method to Connect Wiring
- Pass the power supply wiring and the ground wiring through the wiring through-hole into the electrical parts box and secure with the included clamping material after connecting the wires to terminal blocks.
Connect the wires to the terminals on the control board individually according to the outdoor unitconnection.
- Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.
WARNING
Make sure that the screws of the terminal are free from looseness.
!
CAUTION
The Power cord connected to the unit should be selected according to the follow­ing specifications.
!
WIRING CONNECTION
Electrical Wiring
Perform the electrical wiring work according to the electrical wiring connection.
- All wiring must comply with local requirements.
- Select a power source that is capable of supplying the current required by the ventilator.
- Use a recognized ELCB(Electric Leakage Circuit Breaker) between the power source and the unit. A disconnection device to adequately disconnect all supply lines must be fitted.
- Model of circuit breaker recommended by authorized personnel only
MCA : Min. Circuit Amps (A) ; MOP : Maximum Over current Protection kW : Fan Motor Rated Output (kW) ; FLA : Full Load Amps (A)
Ventilation unit
Power supply Fan motor
Model Hz Volts Voltage range MCA MOP kW FLA
LZ-H050GXN4 /
LZ-H050GXH4
50 220 - 240 V
Max. 264 V
Min. 198V
2.8 8 0.2x2 1.25x2
LZ-H080GXN4 /
LZ-H080GXH4
2.8 8 0.2x2 1.25x2
LZ-H100GXN4 /
LZ-H100GXH4
2.8 8 0.2x2 1.25x2
Wiring for the Humidity Regulator (Locally Procured)
LZ-H***GXH series only
- Pass into the electric parts box together with the power wire through
the power wiring through-hole.
- Remove the short-circuit wires on the accessory terminal block and connect the wiring for the humidity regulator.
- Secure with cramping material together with the power wire.
Precautions when laying power wiring Use round pressure terminals for connections to the power terminal
block.
Wiring specifications
Sheathed wire (should be complied with IEC60245 standard)
Size 0.75 - 1.25 mm
2
Legth MAX. 100 m
External contact specifications
Normally closed contact (Currenttolerance 10 mA - 0.5 A)
Wire Specification Power Cable Specification : The power cord connected to the outdoor
unit should be complied with IEC 60245 or HD 22.4 S4(Rubber insulated cord, type 60245 IEC 66 or H07RN-F)
Insulation material of supply line shall be at least those of ordinary tough rubber sheathed. (code designation 60245 IEC 53)
CAUTION
If using humidistat, install one per ventila­tion unit. Controlling more than one ventilation unit with a single humidity controller may pre­vent normal humidity operation and cause water leakage, etc.
!
Communication
Terminal Block
Input from outside (Indoor unit or MultiV outdoor unit)
Main Power
Terminal Block
Accessory
Terminal Block
Power supply wiring Ground wiring
Short-circuit wire
Remove when installing the humidistat. (locally procured)
Terminal Block Indoor
1(L)2(N)34
Ventilation unit
Power Input
SODU
BA BABA
INTERNET DRY1 DRY2 GND 12V
IDU
Outdoor unit
1 Phase(Ø)
GN/YL
20 mm
Round pressure terminal
Power wire
Main power source
Ventilation unit
ELCB
Switch box
Outdoor
INSTALLATION MANUAL
7
ENGLISH
Check the drainage
- Test the drainage by pouring 1000cc of water into the drain pan through the inspection hole by removing the maintenance cover (8 screws) or through the outlet duct joint of supply air to room (SA).
- Make sure that heat insulation work is executed on the Indoor drain piping and Drain outlet to prevent any possibility water leakage due to dew condensation.
Replacement of the Humidifier
1 Remove the maintenance cover.
- Loosen the screw (8EA) and detach the maintenance cover.
2 Prepare to replace the Humidifier.
- Uncork the Drain Cap to drain the remaining water in the feed cistern.
- Loosen the screw (3EA) and detach the lid of feed cistern.
- Loosen the screw (1EA) and Detach the clamp.
3 Pull out the Humidifier (2EA)
- Uncork the Drain Cap to drain the remaining water in the feed cistern.
- Loosen the screw (3EA) and detach the lid of feed cistern.
- Loosen the screw (1EA) and Detach the clamp.
Install the water supply piping
Connect the water supply with strainer, other pipes and valves (locally procured) to the indoor unit as shown in the figure at below.
CAUTION
When installing the water supply piping, wash the pipes with tap water so that all dirt is removed from them or install a drain valve somewhere along the piping and drain the pipes thoroughly until the water flowing through them is clear. Make sure no cutting oils or detergents get into the pipes.
!
Minimum cross-sectional area of conductors
Maintenance cover
Drain piping
(Locally procured)
Drain outlet
Duct connecting flange (SA)
Flexible hose
Feed Water
Water supply piping with strainer
Water supply shut-off valve
Water supply pipe
(Locally procured)
(Locally procured)
(Locally procured)
(Locally procured)
(Locally procured)
Cap
Drain valve
Drain outlet
Duct connecting flange (SA)
Screw
Maintenance cover
Screw
Screw
Clamp
Drain Cap
Lid of feed cistern
Rated current of appliance
A
Nominal cross-sectional area
mm
2
0,2
>0,2 and 3
>3 and 6
>6 and 10 >10 and 16 >16 and 25 >25 and 32 >32 and 40 >40 and 63
Tinsel cord
a
0,5
a
0,75
1,0 (0,75)
b
1,5 (1,0)
b
2,5
4 6
10
*
a
These cords may only be used if their length does not exceed 2 m between the point where the cord or cord guard enters the appliance and the entry to the plug.
b
Cords having the cross-sectional areas indicated in the parenthe­ses may be used for portable appliances if their length does not exceed 2 m.
NOTE: For supply cords supplied with multi-phase appliances, the
nominal cross-sectional area of the conductors is based on the maximum cross-sectional area of the conductors per phase at the supply cord connection to the appliance termi­nals.
Humidifier
4 Insert the new Humidifier (2EA)
Confirm that the edge of top panel of humidifier element has been hooked securely on the rail.
Assemble the water tank and drain cap, while they are not separated from each other, with a clamp.
Rail
8
INSTALLATION MANUAL
ENGLISH
WARNING
Turn the breaker off when cleaning the product.
!
CAUTION
Gloves should be worn when doing the maintenance work.
!
HUMIDIFIER MAINTENANCE
Inspection and Maintenance of the Humidifier
- Have your dealer do the following inspections in order to get the longest use.
- In order to prevent harmful bacteria from generating, ask your dealer to do maintenance on humidifying unit portion at the beginning or the end of the heating season.
Inspected Part
Content of maintenance
Problems if maintenance is not carried out
Items to be inspected
Solution
Feed water tank
Check for operation of float switch
Clean if it does not work properly due to build-up.
Insufficient humidifying. Overflowed feed water tank.
Check for dirt Clean if very dirty.
Weak fan strength. Reduced humidifying capacity.
Solenoid valve
Check for shutting and opening. Check in a similar fashion when checking the float switch operation.
Replace if it doesn’t work.
Insufficient humidifying. Overflowed feed water tank. (Increased tap water consumption.)
Replacing the Humidifier element
- The humidifier element should in general be replaced once every three years when supply water is soft water, but outside factors (water quality, operating times) may shorten its productive life.
- Contact your dealer if you have any questions.
Method to Clean and Replace Each Part
1 Cleaning of Air Filter
- Clean dirt from the air filter using a vacuum cleaner or wash with water. (if dirt is conspicuous, wash with a neutral detergent in lukewarm water)
- After washing with water, dry well in the shade. (Do not expose the air filter to direct sunlight or heat from a fire when drying it)
- If the air filter is damaged, purchase it from the service center or professional agent.
2 Cleaning of Total Heat Exchanger
Suck dusts adhered to the surface of the Total heat exchanger with a cleaner.
- Use the cleaner that attached to brush at its nozzle, and use a soft brush.
Cleaner
Air Filter
NOTE
!
This note is only applied to model that there is humidity function.
When humidifying fails, the remote con­troller does not display any error code.
(Just twinkle the icon of Humidification “ ” for 30 minutes and disappeared or dis­play warning icon on the side of Humidifi­cation icon.)
Usage under that status will lead to insuffi­cient humidification and increased tap water consumption.
The solenoid valve and float switch should be checked at the beginning of heating sea­son.
- Do not use a hard nozzle on the cleaner. (Otherwise, surface of the Total heat exchanger may be damaged.)
- Never wash the Total heat exchanger with water.
- Consider replacing after two years from the date of purchase.
- Please inquire to the Service Center about replacement costs within two years from the date of purchase.
- For service, always contact the dealer or an Authorized Service Center.
Total Heat ExchngerAir Filter
!
Loading...