LG LVN181HV4 Installation instructions

INSTALLATION MANUAL
AIR CONDITIONER
ENGLISH FRANÇAIS
ESPAÑOL
Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
Vertical Air Handling Unit
www.lghvac.com
MFL67206513
Rev.04_091620
Copyright © 2016 - 2020 LG Electronics Inc. All Rights Reserved.
www.lg.com
IMPORTANT!
Please read this instruction sheet completely before installing the product.
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
!
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others. Installation of all field wiring and components MUST conform with local building codes or, in the absence of local codes, with the National Electrical Code 70 and the National Building Construction and Safety Code or Canadian Electrical code and National Building Code of Canada.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
CAUTION
Safety Precautions
NOTE TO INSTALLING DEALER: The Owners Instructions and Warranty are to be given to the owner
:
Improper installation, adjustment, alteration, service or maintenance can void the warranty. The weight of the condensing unit requires caution and proper handling procedures when lifting or moving to avoid personal injury. Use care to avoid contact with sharp or pointed edges.
• Always wear safety eye wear and work gloves when installing equipment.
• Never assume electrical power is disconnected. Check with meter and equipment.
• Keep hands out of fan areas when power is connected to equipment.
• R-410A causes frostbite burns.
• R-410A is toxic when burned.
or prominently displayed near the indoor Furnace/Air Handler Unit.
!
SPECIAL WARNINGS
When wiring:
Electrical shock can cause severe personal injury or death. Only a qualified, experienced electrician should attempt to wire this system.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
The choice of materials and installations must comply with the applicable local/national or international standards.
When transporting:
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your finger.
When installing...
... in a wall: Make sure the wall is strong enough to hold the unit's weight.
... in a room: Properly insulate any tubing run inside a room to prevent "sweating" that can cause
... in moist or uneven locations:
... in an area with high winds: Securely anchor the outdoor unit down with bolts and a metal
... in a snowy area(for Heat Pump Model): Install the outdoor unit on a raised platform that is
When connecting refrigerant tubing
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Check carefully for leaks before starting the test run.
When servicing
• Turn the power OFF at the main power box(mains) before opening the unit to check or repair
electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have
been left inside the unit being serviced.
It may be necessary to construct a strong wood or metal frame to provide added support.
dripping and water damage to wall and floors.
level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
frame. Provide a suitable air baffle.
higher than drifting snow. Provide snow vents.
Use a raised concrete pad or concrete blocks provide a solid,
2 Vertical Air Handling Unit
TABLE OF CONTENTS
TABLE OF CONTENTS
4 SAFETY INSTRUCTIONS
6 FEATURES
7 Duct Connection Dimensions
8 INSTALLATION
8 Selection of the best location
9 Upflow Installation
10 Downflow Installation
12 Horizontal-Right Installation
13 Duct work
14 Horizontal-left Installation
15 Combination indoor units (Multi Zone)
16 Flaring work
17 Connection of piping - Indoor, Outdoor, BD Unit
18 Plumbing materials and storage methods
19 Insulation
20 Condensate Drain
22 Wiring Connection
24 REMOTE CONTROLLER INSTALLATION
26 Wired remote controller installation
ENGLISH
27 3RD PARTY THERMOSTAT
28 INTERNAL ELECTRIC HEATER(ACCESSORY)
29 DIP SWITCH SETTING OF INDOOR UNIT PCB
30 PRODUCT DATA
30 Minimum airflow by heater capacity
Installation Manual 3
Safety Instructions
Safety Instructions
The following safety guidelines are intended to prevent unforeseen risks or damage from unsafe or incorrect operation of the appliance. The guidelines are separated into ‘WARNING’ and ‘CAUTION’ as described below.
This symbol is displayed to indicate matters and operations that can cause risk.
!
Read the part with this symbol carefully and follow the instructions in order to avoid risk.
!
WARNING
This indicates that the failure to follow the instructions can cause serious injury or death.
!
CAUTION
This indicates that the failure to follow the instructions can cause the minor injury or damage to the product.
!
WARNING
Installation
• Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
- There is risk of fire or electric shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
- Do not disassemble or repair the product. There is risk of fire or electric shock.
• Always ground the product.
- There is risk of fire or electric shock.
• Install the panel and the cover of control box securely.
- There is risk of fire or electric shock.
• Always install a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Do not modify or extend the power cable.
- There is risk of fire or electric shock.
• Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
- Moisture may condense and wet or damage furniture.
• Be cautious when unpacking and installing the product.
- Sharp edges could cause injury. Be especially careful of the case edges and the fins on the
condenser and evaporator.
• For installation, always contact the dealer or an Authorized Service Center.
- There is risk of fire, electric shock, explosion, or injury.
• Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to the product.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it, causing property damage, product failure,
and personal injury.
4 Vertical Air Handling Unit
Safety Instructions
• Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
Operation
• Do not store or use flammable gas or combustibles near the product.
- There is risk of fire or failure of product.
!
CAUTION
Installation
• Always check for gas (refrigerant) leakage after installation or repair of product.
- Low refrigerant levels may cause failure of product.
• Install the drain hose to ensure that water is drained away properly.
- A bad connection may cause water leakage.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• Do not install product where noise or air flow from the outdoor unit could disturb neighbors.
- It may cause a problem for your neighbors.
• Use two or more people to lift and transport the product.
- Avoid personal injury.
• Do not install the product where it will be exposed to sea wind (salt spray) directly.
- It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins,
could cause product malfunction or inefficient operation.
• Safely dispose of the packing materials.
- Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.
- Tear apart and throw away plastic packaging bags so that children may not play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
ENGLISH
Installation Manual 5
Features
Features
Wiring knockouts for conduit
Wiring knockouts for conduit
Refrigerant connections
Drain connections for horizontal application
Filter access
Drain connections for upflow application
FAN SPEED
TEMP
OPER MODE
Wired Remote
Controller
(Accessory)
6 Vertical Air Handling Unit
Features
Duct Connection Dimensions
G
H
I
<Top>
Refrigerant connections
Drain connections for horizontal application
Air filter cover
D
B
<Front>
J
Drain connections for upflow application
F
ENGLISH
J
A
C
<Side-right>
ODU
Single
Zone
Multi
Zone
Capacity
(kBtu/h)
18 24 36
424855-3/16
182448-5/8
36
E
<Bottom>
Dimensions
A B C
Wiring
Knock out
I J
D E F G H
Height Width Depth Power
48-5/8 (1 236)18(457)
(1 401)25(635)
(1 236)18(457)
48-5/8 (1 236)18(457)
21-1/4
(540)
21-1/4
(540)
21-1/4
(540)
21-1/4
(540)
1-9/16
17-1/2
(40)
(445)20(530)17(432)
1-9/16
24-1/2
(40)
(623)20(530)24(610)
1-9/16
17-1/2
(40)
(445)20(530)17(432)
1-9/16
17-1/2
(40)
(445)20(530)17(432)
12-1/8
(308)
12-1/8
(308)
12-1/8
(308)
12-1/8
(308)
1-11/16
(43)
1-11/16
(43)
1-11/16
(43)
1-11/16
(43)
(Unit: inch(mm))
Refrigerant
Connections
Pipe size
Commu
Liquid Gas
nication
7/8
3/8
(9.52)
3/8
(9.52)
1/4
(6.35)
3/8
(9.52)
5/8
(15.88)
5/8
(15.88)
1/2
(12.7)
5/8
(15.88)
(22)
7/8
(22)
7/8
(22)
7/8
(22)
Installation Manual 7
Installation
Installation
Selection of the best location
• Where optimum air distribution can be ensured.
• Where nothing blocks air passage and install the duct work.
• Where condensate can be properly drained.
• Where the ceiling is strong enough to bear the indoor unit weight.
• Where the false ceiling is not noticeably on an incline.
• Where sufficient clearance for maintenance and service can be ensured.
• Where piping between indoor and outdoor units is possible within the allowable limit. Refer to the installation manual for the outdoor unit.
• Vertical Air Handling Unit can be installed for upflow and horizontal-left positions.
More than 350
(13-25/32)
More than 600(23-5/8) clearance from access panels for Service
More than 350
(13-25/32)
NOTE : The primary and secondary drain line must be trapped to allow proper drainage of condensate
water, If the secondary drain line is not used, it must be capped.
!
CAUTION
In the case of sea coast installation, salt residue may cause corrosion of cabinet and component parts. Please take appropriate anti-corrosion measures.
8 Vertical Air Handling Unit
More than
250(9-27/32)
More than
250(9-27/32)
Unit : mm(inch)
Installation
Upflow Installation
• Position unit for plenum installation.
• The plenum should be secured in order to support the installation of adapter callers accommodate the installation of any duct work.
• Seal all duct work according to local codes to prevent air leakage. Ensure that filter access is unobstructed.
• The air handler support platform should be sturdy enough to support the cabinet plus any accessory components including filter box.
• The minimum height clearance is 14 inches(350 mm) to maintain proper air flow.
• Vibration isolators (purchased locally) must be placed between the unit and the pedestal.
• An illustration showing an example of where a vibration isolator should be added would clarify what the installing contractor should do to properly position the isolator.
Field Supplied Supply Duct
Field Supplied Return Plenum
ENGLISH
More than 1 inch (25 mm)
More than 6 screws (M4*25 L)
!
CAUTION
Do not connect the screws on Front and Rear side, it may cause the filter can not be mounted.
Installation Manual 9
Installation
Downflow Installation
Downflow installation requires various changes to the air handling unit from original configuration. There are additional kits required in order to convert the air handling unit to the downflow configuration.
1) Please remove the panels and Brackets from
the unit.
A
D
B
E
C
2) Please remove the thermistor from a coil. Also remove a coil and Drain pan from the unit
Deletion
3) Rotate the cabinet. 4) Please assemble the downflow bracket as below. Install the bracket in the order shown and fix with screw.
10 Vertical Air Handling Unit
Bracket Installation
ڼ
ڻ
D
ں
ڸ
ڽ
ڹ