LG LS-J0762YL, LS-J0762YLAC, LS-L1262YL, LS-L1262YLAC, LS-Q096BUL Service Manual

...
MODEL : LS-J0762YL(AC)
LS-L1262YL(AC) LS-Q096BUL(DC) LS-R126CUL(DC) LS-L12632L(AC)
Room Air Conditioner
SERVICE MANUAL
-BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
-ONLY FOR AUTHORIZED SERVICE PERSONNEL.
WEBSITE http://biz.LGservice.com E-MAIL http://www.LGEservice.com/techsup.html
Contents
Functions
.................................................................................................................................
3
Product Specification (Cooling & Heating)
...........................................................................
6
Dimensions
..............................................................................................................................
7
Refrigeration Cycle Diagram
..................................................................................................
9
Wiring Diagram
......................................................................................................................
10
Operation Details
..................................................................................................................
11
Installation
.............................................................................................................................
25
Operation
...............................................................................................................................
38
Disassembly of the parts (Indoor Unit)
...............................................................................
40
2-way, 3-way Valve
.................................................................................................................
43
Cycle Troubleshooting Guide
...............................................................................................
50
Self-diagnosis function
.........................................................................................................
51
Electronic Parts Troubleshooting Guide
.............................................................................
53
Electronic Control Device
.....................................................................................................
63
Schematic Diagram
...............................................................................................................
66
Exploded View and Replacement Parts List
.......................................................................
69
-2-
Functions
• Room temperature sensor. (Thermistor)
• Pipe temperature sensor. (Thermistor)
• Maintain the room temperature in accordance with the Setting Temp.
• Indoor fan is delayed for 5 sec at the starting.
• Restarting is for approx. 2 minutes.
• Super High, High, Med, Low
--- Lights up in operation
--- Lights up in Sleep Mode
--- Lights up in Timer Mode
--- Lights up in Preheat Mode (for Heating Model)
--- Lights up in Plasma Air Clean Mode
• Intermittent Operation of fan at low speed or off.
• The fan is switched to low(Cooling), low(Heating) speed.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
• The fan is switched to intermittent or irregular operation
The fan speed is automatically switched from high to low speed.
• The louver can be set at the desired position or swing up and down automatically.
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting the Current Control
Time Delay Safety Control
Indoor Fan Speed Control
Operation indication Lamps (LED)
Soft Dry Operation Mode
• Both the indoor and outdoor fan stops during defrosting.
• The indoor fan stops until the evaporator pipe temperature will be reached at 34°C.
Sleep Mode Auto Control
Natural Air Control by CHAOS Logic
Airflow Direction Control
PLASMA
-3-
Defrost(Deice) control (Heating)
Hot-start Control (Heating)
• The function will be operated while in any operation mode with selecting the function.
• The function is to be stopped while it is operating with selecting the function.
PLASMA
-4-
• If power is on, it will operate to chage capacitor on controller and power relay will operate after about 2~5sec.
• If outdoor temp. is below 0°C, preheater is operating for 1~5min.
• At the initial, It will be operated compressor after 1min. for preheating.
• The active power filter is designed to correct power factor(cos θ) and to regulate DC link voltage.
• It will be operated PFC circuit when the compressor freq. is over 30Hz and wattage is over 450 watt.
• The final operating freq. of comp. is set the lowest freq. that limited outdoor temp., discharge pipe temp., heat-sink temp., target freq., owing to CT.
• When the temp. of power module increases to 85°C, controller decreases Freq. of Comp.
• It will be changed the drive freq. of comp. according to temp. of indoor and outdoor.
• It will be changed the drive voltage of comp. according to operating frequency.
• It is only operated in the heating operation mode except defrosting operation.
• High speed
- Although fan motor speed is middle, it will change high speed in case of below AC193V, over 45°C of
outdoor temp., and over fc, fh of comp. Freq.
• Middle speed
- Nomal mode
• Low speed
- Although fan motor speed is middle, it will change Low speed in case of over AC 270V, over 21°C
(Heating Mode) of outdoor temp. below 24°C (Cooling Mode) of outdoor temp.
Outdoor Unit
Power relay control
Stand by control at low temp.
Active power filter control(PSC)
Comp. Freq. control
Overheatng. Protection(Power module)
Freq. speed control(up/down speed)
V/F control
Total current control (over current protection)
DC peak current control
4 way valve control
Outdoor fan motor control
Discharge pipe temp. control
-5-
Healthy Dehumidification Operation Mode.
( )
Remote Control
Operation ON/OFF
Reset
Operation Mode Selection
Temperature Setting
Timer Selection
Timer Setting
JET COOL
Timer Cancel
Sleep Operation
Airflow Direction Control
(Cooling
model only)
(Heating
model only)
TEMPERATURE
LOW HIGH
Cooling Operation Mode.( )
Heating Operation Mode.( )
Auto Operation Mode.( )
Horizontal Airflow Direction Control Button(Optional)
Room, Temperature Display
Setting the Time or Timer
PLASMA(Optional)
ON OFF
SET
PLASMA
CANCEL
Fan Speed Selection
(Low) (Med) (High) (CHAOS)
Power Save Cooling Button
: (High:39°C Low:11°C)
: OFF, ON, OFF ON
: Cancel Sleep Mode, Timer ON or Timer OFF
: 1, 2, 3, 4, 5, 6, 7, Off Timer
: Used to set Preheat mode.
Cooling
Down to 18°C Up to 30°C
Heating
Down to 16°C Up to 30°C
7K Series(AC) 12K Series(AC) 9K Series(DC) 12K Series(DC)
at 230V
7,000(4,700-8,300) 12,000(6,500-13,200) 9,000(3,700-9,700) 12,000(3,750-13,700)
9,000(5,000-10,000) 14,400(6,500-15,900) 11,250(1,750-12,500) 14,400(2,450-15,900)
1
1Ø, 220-240V, 50Hz
5.6 9 7.2 9 25 31 31 31 33 36 36 39 48 49 49 49
770 1,330 879 1,050 920 1,580 1,125 1,440
3.5 5.9 4 4.5
4.1 7 5 6.5
7.5 8.7 8.4 14.4
35.8 29 29 29 802*262*165 888*287*170 824*260*165 900*285*156 575*525*260 770*540*245 770*540*245 770*540*245
7 9.5 7 9.5
27 38 34 38
580(R22) 950(R22) 620(R410A) 950(R410A)
Up & Down Up & Down Up & Down
Up & Down, Right & Left
L.C.D Wireless
1/4(6.35)
3/8(9.52) 1/2(12.7) 3/8(9.52) 3/8(9.52)
O
O 1 1.5 1 1.5 1 1.5 1 1.5
Cooling Capacity Btu/h Heating Capacity Moisture Removal l/h Power Source Ø, V, Hz
Air Circulation
Indoor
m
3
/min
Outdoor
Noise Level
Indoor
dB (A)±3
Outdoor
Input
Cooling
W
Heating
Running
Cooling
A
Current
Heating
Motor Output
Indoor
W
Outdoor
Dimensions
Indoor
mm
(W x H x D)
Outdoor
Net. Weight
Indoor
kg
Outdoor Refrigerant (R22) g Airflow Direction Control (Up & Down) Remocon Type
Service Valve
Liquid
inch(mm)
Gas Sleeping Operation Drain Hose Connecting Cable mm
2
Power Cord mm
2
-6-
Product Specifications (Cooling & Heating)
Model Name
Item Unit
-7-
Dimensions
(1) Indoor Unit
Tubing hole cover
D
H
W
Installation plate
Tubing hole cover
Installation plate
Right rear piping
Left rear piping
ø70mm
ø70mm
50mm
20mm
20mm
80mm
ø70mm
A
A
A
A
Center
Right rear pipingLeft rear piping
Center
ø70mm
MODEL
DIM Unit
W mm 820 888 824 900
H mm 262 287 260 285 D mm 165 170 165 156
7k Btu Series(AC) 12k Btu Series(AC) 9k Btu Series(DC) 12k Btu Series(DC)
(7k, 12k)
( 7k) ( 12k )
( 7k ) ( 12k )
-8-
(2) Outdoor Unit
W
L2
L3
L1
D
H
L4
L5
Gas side
(3-way valve)
Liquid side
(2-way valve)
MODEL
7K Btu Series(AC) 12K Btu Series(AC) 9K Btu Series(DC) 12K Btu Series(DC)
DIM unit
W mm 564 770 770 770
H mm 525 540 540 540
D mm 265 245 245 245 L1 mm 294 287 287 287 L2 mm 66 64 64 64 L3 mm 374 518 518 518 L4 mm 17 10 10 10 L5 mm 270 100 100 100
Pipe size(Diameter:Ø)
MAX. Max
MODEL Piping length Elevation
Gas(inch) Liquid(inch)
(m) (m)
7k Btu Series(AC) 3/8" 1/4" 15 7 12k Btu Series(AC) 1/2" 1/4" 15 7 9k Btu Series(AC) 3/8" 1/4" 15 7 12k Btu Series(AC) 3/8" 1/4" 15 7
Refrigeration Cycle Diagram
-9-
INDOOR UNIT OUTDOOR UNIT
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
COMPRESSOR
ACCUMU LATOR
GAS SIDE
3-WAY VALVE
LIQUID SIDE
2-WAY VALVE
CAPILLARY TUBE
COOLING HEATING
REVERSING VALVE (Heating Model Only)
Wiring Diagram
-10-
(1) Indoor Unit
Model: LS-_YL/UL Series Model: LS-_NM/NN Series
Model: LS-L12632L
(2) Outdoor Unit
Model: LS-L12632L
CN-COIL2
CN-COIL1
REACTOR
CN-COMP CN-FAN
WCN-NOISE1
TERMINAL
BLOCK
CN-4WAY
RY­4WAY
BR BL
GN/YL
RD
RD BL BR
BR BL
FUSE
AC 250V/15A
GN/YL
RD
4WAY VALVE
1(L
)
2(N
)
3
TO INDOOR UNIT
MAIN PWB ASM
OUTDOOR WIRING DIAGRAM
3854A20157L
YL
YL
COMP-
RESSOR
YL
W(C
)
V(S
)
U(R
)
BL RD
YL BL RD
SSR
COMPRESSOR
THERMISTOR
HEAT SINK
THERMISTOR
INTAKE/PIPE
THERMISTOR
CN-TH2 CN-TH1
WH
BK
BK
BK
GR
RD BL YL
FAN
MOTOR
CN-COIL2
CN-COIL1
REACTOR
CN-COMP CN-FAN
WCN-NOISE1
TERMINAL
BLOCK
CN-4WAY
RY­4WAY
BR BL
GN/YL
RD
RD BL BR
BR BL
FUSE
AC 250V/15A
GN/YL
RD
4WAY
VALVE
1(L
)
2(N
)
3
TO INDOOR UNIT
MAIN PWB ASM
OUTDOOR WIRING DIAGRAM
3854A20051V
YL
YL
COMP-
RESSOR
YL
W(C
)
V(R
)
U(S
)
BL RD
YL BL RD
SSR
COMPRESSOR
THERMISTOR
HEAT SINK
THERMISTOR
INTAKE/PIPE
THERMISTOR
CN-TH2 CN-TH1
WH
BK
BK
BK
GR
YL BL RD
FAN
MOTOR
POWER
BR
BRBLRD
GN/YL
BL
1(L) 2(N)
3
MOTOR
CN-MOTOR
CN-TAB1
CN-AC/DC
CN-AC/DC
STEP
MOTOR
STEP
MOTOR
H.V.
ASM
RD
AIR CLEAN
(
PLASMA
)
SAFETY S/W1
SAFETY S/W2
BK
BK BK
BK BK
CN-U/D
CN-L/R
CN-DISP1
DISPLAY PWB ASM
INDOOR WIRING DIAGRAM
3854A20142G
SW(FORCE)
T/BLOCK
TO OUTDOOR UNIT
SSR
AC PWB ASM DC PWB ASM
OR BK
BR
4
RY-POWER
FUSE AC 250V T2A
3
YL
SH-CAPA
GN/YL
CN-DISP2
BR
BL
CN-TH
THERMISTOR
POWER
BR
BRBLRD
GN/YL
BL
1(L) 2(N)
3
MOTOR
CN-MOTOR
CN-TAB1
CN-AC/DC
CN-AC/DC
STEP
MOTOR
STEP
MOTOR
H.V.
ASM
RD
AIR CLEAN
(
PLASMA
)
SAFETY S/W1
SAFETY S/W2
BK
BK BK
BK BK
CN-U/D
CN-L/R
CN-DISP1
DISPLAY PWB ASM
INDOOR WIRING DIAGRAM
3854A20142V
SW(FORCE)
T/BLOCK
TO OUTDOOR UNIT
SSR
AC PWB ASM DC PWB ASM
OR BK
BR
4
RY-POWER
FUSE AC 250V T2A
3
YL
SH-CAPA
GN/YL
BR
BL
CN-TH
THERMISTOR
POWER
BR
BRBLRD
GN/YL
BL
1(L) 2(N)
3
MOTOR
CN-MOTOR
CN-TAB1
CN-AC/DC
CN-AC/DC
STEP
MOTOR
STEP
MOTOR
H.V. ASM
RD
AIR CLEAN
(
PLASMA
)
SAFETY S/W1
BK
BK BK
CN-U/D
CN-L/R
CN-DISP1
DISPLAY PWB ASM
INDOOR WIRING DIAGRAM
3854A20305B
SW(FORCE)
T/BLOCK
TO OUTDOOR UNIT
SSR
AC PWB ASM DC PWB ASM
OR BK
BR
4
RY-POWER
FUSE AC 250V T2A
3
YL
SH-CAPA
GN/YL
CN-DISP2
BR
BL
CN-TH
THERMISTOR
Operation Details
1. LED display of indoor unit
LS-_YL/UL Series
LS-_NM/NN Series
-11-
Operation
indicator
Shape of
display
Setting
temp.
Standard Too hot Hot Cold Too cold
Jet
(Cool, Heat)
Test
operation
Comfortable
A.I operation mode
Cooling heating
dehumidifi-
cation
Energy save
in cooling
mode
Operation Indicator
Sleep Timer Indicator
Timer Indicator
Preheat Indicator
Setting Temp.
On while in appliance operation, off while in appliance pause.
Blinking(3sec off/0.5sec on) according to Error Code as long as the system mal-
functions.
On while in sleep timer mode, off when sleep timer cancel or appliance operation pause.
On while in timer mode(on/off), off when timer mode is completed or canceled.
Off except when hot start during heating mode operation or while in defrost control.
Cooling/heating/dehumidification mode : setting temperature from remote control
Fuzzy operation mode : fuzzy key data(5sec on) AI
Operation Indicator
Power Saving Indicator
Timer Indicator
Preheat Indicator
On while in appliance operation, off while in appliance pause.
Flashing while in disconnection or short in Thermistor. (3 sec off/0.5 sec on)
On while in power saving cold mode, off when power saving cold cancel.
On while in timer mode(on/off) and sleep timer mode (on), off when timer mode is
completed or canceled.
Off except when hot start during heating mode operation or while in defrost control.
How to operate the power display (LS-_YL/UL Series)
It must be displayed the power level that will be operating frequency of compressor.
It indicates power levels that compressor operating frequency is controlled to depend on indoor and outdoor
conditions.
It is displayed as below.
Heat mode operation
- Power level 1: below Step 2 of COMP. operating frequency
- Power level 2: below Step 4 of COMP. operating frequency
- Power level 3: Equal Step 5 of COMP. operating frequency
- Power level 4: below Step 7 of COMP. operating frequency
Operation mode except heat mode operation
- Power level 1: below Step 2 of COMP. operating frequency
- Power level 2: below Step 4 of COMP. operating frequency
- Power level 3: Equal Step 5 of COMP. operating frequency
- Power level 4: below Step 7 of COMP. operating frequency
-12-
Power Level 1
Power Level 2
Power Level 3
Power Level 4
-13-
2. Protection of the evaporator pipe from frosting
If the indoor pipe temperaure is below 0°C in 7 min. after the compressor operates without pause while in cooling cycle operation mode, compressor, outdoor fan are turned off.
When indoor pipe temp. is 7°C or higher after 2 min pause of compressor compressor, outdoor fan is turned on according to the condition of the room temperature.
3. Protection of the indoor fan from droplet formation (Enclosure sweat and condensed disposal test)
• Control condition : The system operates standard operation without this condition as follows.
Setting temperature <25°C Indoor fan speed low speed Outdoor temperature < 30°C
• Control method
In operation for 5~20 minutes in , , conditions, return to the previous COMP STEP after operation for 5~40 minutes at the COMP STEP 3.
Comp. free
Comp. Step 4 Comp. Step 2
Comp. off
0˚C
3˚C
6˚C
7˚C
Indoor pipe temp.
-14-
4. Cooling mode operation
Operating frequency of compressor depend on the difference of the temperature.
(= intake air Temp.- Compressor off Temp.
Compressor off temp.= setting temp. -0.5°C
on temp. = setting temp. +0.5°C
If compressor operates at some operating frequency, the operating frequency of compressor cannot be
changed within 30 seconds.
Condition of compressor turned off
- When intake air temperature stay at the temperature between setting temp.
-
0.5°C and setting temp.
-
1.0°C for 3 minutes continuously.
- When intake air temperature reaches below the temperature of setting temp.
-
1.0°C.
Compressor 2 minutes delay
- The compressor can restart minimum 2 minutes later after compressor off.
Temp. differences Comp. Operating frequency
over 3.0°C Step 7 over 2.5°C Step 6
2.0~2.49°C Step 5
1.5~1.99°C Step 4
1.0~1.49°C Step 3
0.5~0.99°C Step 2
0.0~0.49°C Step 1
[The operating freq. step of comp.]
[The targeting operating freq. of comp. each model]
Model
7K Series(AC) 35 41 45 56 64 68 78
12K Series(AC) 30 40 45 55 61 67 72
9K Series(DC) 15 22 32 40 51 54 58
12K Series(DC) 15 28 40 53 66 71 76
Comp. Operating frequency
Step 1 Step 2 Step 3 Step 4 Step 5(Fr) Step 6 Step 7
-15-
5. Healthy Dehumidification mode operation
When the dehumidification operation is set by the remote controller the intake air temperature is detected and the setting temp. is automatically set according to the intake air temperature.
When intake air temp reaches above the temp of setting +1.0°C, condition of compressor same as cooling mode operation.
When intake air temperature reaches bolow the temp of setting –1.0°C, compressor operate step1~step3 and indoor fan speed repeatly operate low or stop.
Intake air Temp.
32°C intake air temp.
26°C intake air temp. < 32°C
24°C intake air temp.< 26°C
18°C < intake air temp. < 24°C
intake air temp. ≤ 18°C
Setting Temp.
25°C 25°C
intake air temp. -1°C
intake air temp. -0.5°C
18°C
-16-
6. Heating mode operation
Operating frequency of compressor depend on the difference of the temperature (= compressor off temp. - intake air temp.)
Compressor off temp. = setting temp.+3.0°C
on temp. = setting temp.
If compressor operates at some operation frequency, the operating frequency of compressor cannot be changed within 30 seconds.
Condition of compressor turned off
- When intake air temperature reaches +3°C above the setting temperature.
Condition of indoor fan turned off
- While in compressor on:indoor pipe temp. < 30°C
While in defrost control, between the indoor and outdoor fans are turned off.
Compressor 2minutes delay
- After compressor off, the compressor can restart minimum 2 minutes later.
Temp. differences
over 3.0°C
2.5~3.0°C
2.0~2.49°C
1.5~1.99°C
1.0~1.49°C
0.5~0.99°C
0.0~0.49°C
Comp. Operating frequency
Step 7 Step 6 Step 5 Step 4 Step 3 Step 2 Step 1
[ The operating freq. step of comp]
[The targeting operating freq. of comp. each model]
Model
7K Series(AC) 35 48 56 68 80 85 90
12K Series(AC) 35 43 55 65 74 80 86
9K Series(DC) 15 25 40 52 63 66 70
12K Series(DC) 15 28 40 53 66 71 76
Comp. Operating frequency
Step 1 Step 2 Step 3 Step 4 Step 5(Fr) Step 6 Step 7
-17-
7. Fuzzy mode operation
When any of operation mode is not selected like the moment of the power on or when the unit turned off, the operation mode is selected.
When determining the operation mode, the compressor, outdoor fan are off and only the indoor fan is operat­ed for 15~20 seconds, then an operation mode is selected according to.
Basis of determining operating mode
Outdoor temp.
over 24°C
21~24°C 18~21°C
below 18°C
Operating Mode
Cooling
Healthy Dehumidification
intake air temp. ≥ 25°C Dehumidification
intake air temp. < 25°C Heating
Heating
7.1 Fuzzy operation for cooling
According to the setting temperature selected by Fuzzy rule, the operating frequency of compressor is deter­mined like cooling mode operation.
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temperature at that time.
When the Fuzzy key(=setting temp. key) is input after the initial setting temperature is selected, the Fuzzy key value and intake air temperature at that time are compared to select the setting temperature automatically according to the fuzzy rule.
While in Fuzzy operation, the air flow speed of the indoor fan is automatically operated by Fuzzy logic.
at beginning
during opertion
Intake air temp.
over 26°C
18~26°C
below 18°C
18~30°C
below 18°C
over 30°C
Setting temp.
25°C
intake air temp. -0.5°C
18°C
Fuzzy rule 18°C Fuzzy rule 30°C Fuzzy rule
Fan speed
Fuzzy airflow
-18-
7.2 Fuzzy operation for Heating
According to the setting temperature selected by Fuzzy rule, the operating frequency of compressor is deter­mined like heating mode operation.
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temperature at that time.
When the Fuzzy key(=setting temp. key) is input after the initial setting temperature is selected, the Fuzzy key value and intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically operated by Fuzzy logic.
at beginning
during opertion
Intake Air temp.
over 20°C
below -20°C
16~30°C
below 16°C
over 30°C
Setting temp.
intake air temp. +0.5°C
20°C
Fuzzy rule 16°C Fuzzy rule 30°C Fuzzy rule
Fan speed
Fuzzy airflow
7.3 Fuzzy operation for dehumidification
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temperature at that time.
According to the setting temperature selected by Fuzzy rule, the operating frequency of compressor is deter­mined like dehumidefication mode operation.
at beginning
during operation
Intake Air temp.
over 26°C
18~26°C
below 18°C
18~30°C
below 18°C
over 30°C
Setting temp.
25°C
intake air temp. -0.5°C
18°C
Fuzzy rule 18°C Fuzzy rule 30°C Fuzzy rule
Fan speed
Fuzzy airflow
-19-
8. Jet cool mode operation
While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the other mode operation(cooling, dehumidification, ventilation), the Jet Cool mode is operated.
In the Jet Cool mode, the indoor fan is operated super-high speed for 30 min. at cooling mode operation.
In the Jet Cool mode, the room temperature is controlled to the setting temperature, 18°C.
When the sleep timer mode input while the Jet Cool mode operation, the Jet Cool mode has the priority.
When the Jet Cool key is input, the upper/lower vane is reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
9. Jet heat mode operation
While in cooling mode or Fuzzy operation, the Jet Heat key cannot be input. When it is input while in the Heating mode operation (dehumidification), the Jet Heat mode is operated.
In the Jet Heat mode, the indoor fan is operated super-high speed for 60 min. at Heating mode operation.
In the Jet Heat mode, the room temperature is controlled to the setting temperature, 30°C.
When the sleep timer mode input while the Jet Heat mode operation, the Jet Heat mode has the priority.
When the Jet Heat key is input, the upper/lower vane is reset to those of the initial Jet heating mode and
then operated in order that the air outflow could reach under flow.
10. Swing mode
10.1 Chaos swing mode
By the Chaos swing key input, the upper/lower vane automatically operates with the Chaos swing or it is fixed to the desired direction.
CLOSED
Chaos Swing On
Chaos Swing
The first path
Mode 9
Mode 8
Mode 7 Mode 6
Mode 5
Mode 4
Mode 3
Mode 2
Mode 1
OPEN
11.1 Sleep timer operation for cooling cycle
While in cooling mode operation, 30 min. later since the start of the sleep timer, the setting temperature increase by 1°C. After another 30min. elapse, it increases by 1°C again.
11.2 Sleep timer operation for heating cycle
While in heating mode operation, 60 min. later since the start of the sleep timer, the setting temperature decrease by 1°C. After another 60min. elapse, it decreases by 1°C again.
-20-
Setting temp. (˚C)
1.0˚C up
1.0˚C up
Cooling ON temp. (Setting temp. +0.5˚C)
Cooling OFF temp. (Setting temp. -0.5˚C)
0.5 1 Sleep time (hr
)
Setting temp. (˚C)
Heating ON temp. (Setting temp)
Heating OFF temp. (Setting temp. +3.0˚C)
1 2 Sleep time (hr
)
0.5˚C down
1.0˚C down
11. Sleep timer operation
When the sleep time is reached after [1,2,3,4,5,6,7hr] is input by the remote control during the operation, the operation of the appliance stops.
When the appliance is on pause, the sleep timer mode cannot be input.
12. Auto restarting operation
When the power is restarted after a sudden power failure while in appliance operation, the mode before the power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
Operation mode that is kept on the memory
- State of operation ON/OFF
- Operation mode/setting temp./selected airflow speed
- Sleep timer mode/remaining time of sleep timer
- Chaos Swing
13. Forced operation
To operate the appliance by force in case that the remote control is lost, the forced operation selection switch is on the main unit of the appliance to operate the appliance in the standard conditions.
The operation condition is set according to the outdoor temp. and intake air temperature as follows.
The unit select before operating mode in 3 hours.
14. Trial Operation
Press the Tact Switch for compulsory operation of the main body for 3 seconds in order to operate in the trial operation mode.
- Operation mode: Cold
- Indoor pan: Strong wind
- COMP frequency: Step 5
- COMP compulsorily operates for about 18 minutes irrespective of indoor temperature.
-21-
Outdoor temp.
over 24°C
21~24°C 18~21°C
below 18°C
Setting temp.
22°C 23°C 23°C 24°C 24°C
Setting speed of
indoor fan
High speed
Operating Mode
Cooling
Healthy Dehumidification
Intake air temp. ≥ 25°C Dehumidification
Intake air temp. < 25°C Heating
Heating
15. Power relay control
Power relay turns on 1 second later after the power is input to the outdoor unit.
Control sequence : power on
PTC operating power relay on
16. Protection from total current control
CT1 control
If the operating current reaches I1, the operating frequency of the compressor decrease.
After decreasing the operating frequency by 1step, if operating current is below I1 for 60 seconds continuous-
ly, the operating frequency of compressor increase by 1step.
CT2 control
If the operating current of the appliance reaches I2, the compressor stop instantly and 2 minutes later the compressor restart again.
If CT2 occurs 5 times within 1hour, the appliance turn off and display ERROR CODE 7.
-22-
Model
7K Btu Series(AC) 12K Btu Series(AC) 7K Btu Series(DC) 12K Btu Series(DC)
Cooling Heating
5A 6A
8.5A
5.5A 6.5A
8.5A
Cooling Heating
5.5A 7.5A 10A
6A 8A
10A
Cooling Heating
7.5A 5.5A 12A
8A 10A
12A
Cooling Heating
7.5A 9.5A 12A
8A 10A
12A
Operating mode
below 38°C
(outdoor temp.)
I1 I2 I1 I2
over 38°C
(outdoor temp.)
Condition
I1:Current of operating frequency down
I2: Current of compressor cut off
cf. I1 is set the lowest level between intial value and in case dectection of dc paeak current.
Control table
17. Protection from DC Peak Current
DC Peak Current Error by a fault signal of IPM
If the operating current of IPM reaches 35A ±3A, the compressor stop instantly.
If DC PEAK occurs 5 times within 1 hour, the appliance turns off and display ERROR CODE 6.
DC Peak Current Error by the compressor lock
If the DC LINK voltage below DC 140V occurs 5 times within 1 hour while the compressor is operating, the appliance turns off and display ERROR CODE 6.
DC Peak Current Error by the Outdoor Fan Lock
If its 5 times within 1 hour in case of the temperature of outdoor pipe TH is over 65°C while the compressor is operating, the appliance turns off and display ERROR CODE 6.
18. Portection from overheating of power module
If the temperature of the heat sink TH. reaches over Toff, the Compressor stop instantly.
It will be limited the compressor operating frequency according to the heat sink TH.(refer to below FIG.)
It will be blink 4 times, when the thermistor is open or short, also the temperature is over Toff.
19. Portection from overheating of compressor
If the temperature of the discharge pipe of compressor reaches over 130°C or below -30°C the compressor
stop instantly.
It will be limited the compressor operating frequency according to the compressor dome TH.(Refer to below
Fig.)
Temperature range by COMP SPEC varies by 10°C.
-23-
Comp. off
Comp. free
Fc-1
Fc-2
Target frequency
Toff (95°C)
Ton + 3°C (88°C)
Ton + 6°C (91°C)
Ton (85°C)
130°C 118°C
111°C 108°C
-13°C
-30°C
101°C 93°C
Fhmin
OFF
OFF
0Hz
Fc-2 Fc-1
Setting frequency
[The control graph from heat–sink TH]
20 . Defrosting control
While in heating mode operation in order to protect the evaporator pipe of the outdoor unit from freezing, reversed to cooling cycle to defrost the evaporator pipe of the outdoor unit.
Defrosting control is available 50 minutes later since heating cycle started and the pipe temperature of out­door unit reaches below -6°C.
-24-
50 min
Setting frequency
Setting speed
Setting
speed
OFF OFF
ON
OFF
OFF(Cooling cycle)
Setting
frequency
15 sec
Fh min step
Operating frequency of compressor
4 Wa y valve
Outdoor fan
Indoor fan
Preheat LED
Fh min
Fh+1
OFF
ON ON(Heating cycle)
ON ON
Low
(FhMAX-2 or
FhMAX-3)
15 sec 30 sec
8 min or
over 30˚C(120sec)
30 sec 1 min