Lg Ls-d1832cn Installation Guide

Page 1
P/No.: 3828A90005G
ENGLISH
ITALIANO
Le mod e "Froid et chauffage" est
uipÈ d'un
ROOM AIR CONDITIONERS
• Please read this instruction sheet completely before installing the product.
• When the power cord is wanted to replace, replacement work shall be performed by authorized personnel only.
• Installation work must be performed in accordance with national wiring standards by authorized personnel only.
1. Type "A" screw
3. Type "B" screw
4. Holder Remote-Controller
2. Installation Plate
more than 5cm
1cm
5. Copper pipe (Liquid side)
6. Copper pipe (Gas side)
7. Power supply cord(power connecting cable)
8. Connecting cable(except 18K cooling only model)
more than 10cm
more than 10cm
more than 70cm
Cooling & Heating Model has included Drain Elbow
more than
5cm
Page 2
2 ENGLISH
OUT-LINE OF INSTALLATION
Installation works
Installation Parts
Required Tools
2. Installation of indoor, outdoor Unit
1.The following should always be observed for safety
...................................................
3
1) Selection of the best location
...
4
2) Indoor unit Installation
..............
5
• Installation plate
• Four type "A" screws
• Connecting cable
• Level
• Screw driver
• Electric drill
• Hole core drill(ø70mm)
3. Piping and drainage of indoor unit
1) Preparation of pipings
............
6
2) Connection of pipings ......7~11
• For right rear piping
• For the left piping
• Pipes: Gas side
.............
1
/2",5/8"
Liquid side
.........
1
/4",3/8"
(different depending on model No.)
• Insulated drain hose
• Insulation materials
• Flaring tools set
• Specified torque wrenches
1.8 kg.m, 4.2 kg.m, 5.5 kg.m,
6.6 kg.m (different depending on model No.) Spanner
.........................
Half union
4. Connecting pipings and the cable to outdoor unit
1) Connection of pipings to the outdoor unit
............................
12
2) Connection of the cable
.........
12
• Additional drain hose (Outer Dia
.....................
15.5 mm)
• Specified torque wrenches
1.8 kg.m, 4.2 kg.m, 5.5 kg.m,
6.6 kg.m
(different depending on model No.)
5. Checking the drainage and connecting the cable to Indoor unit
1) Checking the drainage
..........
14
2) Connecting of the cable
.........
15
3) Forming the pipings
...............
16
• A glass of water
• Screw driver
6. Air Purging
7. Maximum length of pipe and freon extra change
...........................................................
19
1) Air Purging
............................
17
2) Checking a gas-leakage
........
18
• Hexagonal wrench (4mm)
• Gas-leak detector
8. Test running
1) Connection of power supply
...............................................
20
2) Evaluation performance
..............................................
20
• Tow type "B" screws • Owner's manual
• Thermometer
Page 3
ENGLISH 3
ENGLISH
1. The following should be always be observed for safety
• Please report to or take consent by the supply authority before connection to the system.
• Be sure to read "THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY" before installing the air conditioner.
• Be sure to observe the cautions specified here as they include important items related to safety.
• The indications and meanings are as follows.
• After reading this manual, be sure to keep it together with the instruction manual in a handy place on the customer's site.
Could lead to death, serious injury, etc.
Donotinstall it yourself(customer).
Performthe installationsecurely referring to the installationmanual.
Installthe unitsecurelyina placewhichcan bear the weight ofthe unit.
Performelectricalworkaccordingtothe installation manual andbe sureto useanexclusivecircuit.
Attach theelectrical partcoverto the indoor unit andthe servicepanelto the outdoorunitsecurely.
Besure to usethe part provided orspecifiedparts for theinstallation work.
Check that the refrigerant gas due not leak after installation is completed.
Performgrounding
Donot install theunit ina place where an inflammable gasleaks.
Performthe drainage/piping work securely according to theinstallation manual.
Usethe specified wires to connect theindoor and outdoorunitssecurely andattach the wires firmly tothe terminalboard connectingsectionsso the stress ofthe wires is notapplied to thesections.
• Incomplete installation couldcause injury due tofire, electricshock,the unit falling or a leakage of water. Consult the dealer from whom you purchasedtheunitor specialinstaller.
• Incomplete installation could cause a personal injury due to fire, electric shock, the unit falling or a leakage of water.
• When installed in an insufficient strong place, the unit could fall causing injured.
• Incomplete connecting and fixing could cause fire.
• If the capacity of the power circuit is insufficientor there is incomplete electrical work,it couldresult in a fireor an electric shock.
• The use of defective parts could cause an injury or leakage of water dueto a fire, electric shock,the unit falling, etc.
• If gas leaksand accumulates in the area surrounding the unit,it could causean explosion.
• If there is a defect in the drainage/piping work, water could drop from the unit and household goods could be wet and damaged.
•Do not connect the ground wire to a gas pipe, water pipe arrester or telephonegroundwire. Defectivegroundingcouldcauseanelectricshock.
• If the electrical part cover if the indoor unit and/or the service panel if the outdoor unit are not attached securely, it could result in a fire or electric shockdue to dust,water, etc.
Could leadto serious injury in particular environmentswhen operatedincorrectly.
WARNING
WARNING
CAUTION
CAUTION
Page 4
4 ENGLISH
2. Installation of Indoor, Outdoor unit
1) Selection of the best location
1. Indoor unit
2. Outdoor unit
3.Piping length and the elevation
There should not be any heat source or
steam near the unit.
• There should not be any obstacles to prevent the air circulation.
• A place where air circulation in the room will be good.
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles.
• If an awning is built over the unit to prevent direct sunlight or rain exposure, be careful that heat radiation from the condenser is not restricted.
• There should not be any animals or plants which could be affected by hot air discharged.
• Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles.
More than
5 cm
More than 5 cm
More than
5 cm
More than eye-level
More than 10 cm
More than 10 cm
More than 70 cm
Indoor unit
Outdoor unit
Pipe Size
MODEL
GAS LIQUID
Max. length A (m)
Max.
Elevation
B (m)
18K 1/2" 1/4" 30 15
24K 5/8" 1/4" 30 15
A
B
Page 5
ENGLISH 5
ENGLISH
2) Indoor Unit Installation
The mounting wall should be strong and solid enough to protect it from the vibration.
1. Mount the installation plate on the wall with four Type "A" screws.
(if mounting the unit on the concrete wall, consider using anchor bolts.)
• Always mount the Installation plate
horizontally by aligning the marking-off line by means of the thread and a level.
2. Drill the piping hole with 70mm dia. holecore drill.
• For right rear piping and left rear piping,
draw a line in the direction of the arrow marked "D". The meeting point of the two lines is the center of the hole.
• Drill the piping hole with a ø70mm hole
core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
Type "A" screw
Installation Plate
marking-off line
Thread
Weight
The lower left and right side of Installation Plate
Left rear piping
Right rear piping
Indoor
Hole Center
Installation plate
Outdoor
WALL
C
B,D
A
C A,B,D
D
C
A,B
D
A,B,C
ø70mm
5-7mm
Page 6
6 ENGLISH
3. Piping and Drainage of Indoor Unit
1) Preperation of Pipings
1. Cut the pipes and the cable.
• Use the accessory piping kit or the pipes purchased locally.
• Measure the distance between the indoor and the outdoor unit.
• Cut the pipes a little longer than measured distance.
• Cut the cable 1.5m longer than the length of the pipe.
2. Remove burrs.
• Remove burrs from cut edges of pipes.
• Turn the pipe end toward down to avoid the
metal powder entering the pipe.
Caution:
If burrs are not removed, they may cause a gas leakage.
3. Flaring the pipes.
• Insert the flare nuts, mounted on the connection ports of both indoor and outdoor unit, onto the copper pipes. Some gas may leak, when the flare nuts are removed from the indoor unit, as some gas is charged to prevent the inside of the pipe from rusting.
• Fit the copper pipe end into the Bar of flare tool about 0.5~1.0mm higher. (See illustration)
• Flare the pipe ends.
4. Tape the flaring portion to protect it from the dust or damages.
When properly flared, the internal surface of the flare will evenly shine and be of even thickness. After the flare part comes into contact with the connectors, carefully check the flare finish.
Pipecutter
Slanted
Rough
Pipe
Point down
Reamer
Handle
"A"; ø15.88 mm (5/8") 0~1.0 mm
ø12.7 mm (1/2")
0~0.5 mm
ø9.52 mm (3/8")
0~0.5 mm
ø6.35 mm (1/4")
0~0.5 mm
Cone
Red arrow mark
Clamp handle
Yoke
Bar
Bar
Copper pipe
= Improper flaring =
Inclined
Surface
damaged
Cracked
Uneven
thickness
"A"
Page 7
ENGLISH 7
ENGLISH
2) Connection of Pipings
1. Remove the indoor tubing with Drain hose from the hole
• Remove tubing holder and pull the tubing out
of the chassis.
2. Replace the tubing holder into original position.
For right rear piping
3. Route the tubing and the drain hose straight backwards.
4. Insert the connecting cable into the indoor unit through the piping hole.
• Do not connect the cable to the indoor unit.
• Make a small loop with the cable for easy
connection later.
• Connecting cable
5. Tape the tubing, drain hose and the connecting cable. Be sure that drain hose locates at the lowest side of the bundle. Locating at the upper side can be a reason that drain water overflows drain pan inside the unit.
Pull
Press
To remove the holder, press the bottom of chassis near the holder upward and pull the tab outof its hole.
Tubing holder
Connecting cable
Gas side piping
Liquid side piping Drain hose
Taping Indoor/Outdoor
Connecting cable
18K
CoolingModel
Heat PumpModel
24K
Page 8
8 ENGLISH
6. Indoor unit installation
• Hook the indoor unit onto the upper portion of installation plate. (Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure the hooks are properly seated on the installation plate by moving it left and right.
7. Connecting the pipings to the indoor unit.
• Align the center of the pipings and sufficiently tighten the flare nut with fingers.
• Finally, tighten the flare nut with torque wrench until the wrench clicks.
When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
8. Wrap the insulation material around the connecting portion.
CAUTION: Take care to arrange the pipings,
drain hose and cables as the picture on page 7 for inserting it into the indoor unit and refixing the tubing holder easily.
Connecting cable
Drain hose
Press the lower left and right side of the unit against the Installation Plate until the hooks engage with their slots (sound click).
Flare nut
Pipings
Torque wrench
Spanner
Indoor unit tubing
Plastic Bands
Insulation material
Wrap the insulation material around the connecting portion.
Pipe Size Torque Liquid Side(1/4") 1.8kg.m Liquid Side(3/8") 4.2kg.m
Gas Side(1/2") 5.5kg.m Gas Side(5/8") 6.6kg.m
Page 9
ENGLISH 9
ENGLISH
For the left pipings
3. Route the indoor tubing with the drain hose to the piping hole as desired position.
4. Insert the pipings, power supply cord and connecting cable into the piping hole.
5. Insert the connecting cable into the indoor unit.
• Don't connect the cable to the indoor unit.
• Make a small loop with the cable for easy
connection later.
6. Tape the tubing, drain hose and the connecting cable.
• Connecting cable
IndoorOutdoor
Drain pipe
Connecting cable
Connecting piping
Pull
Toremovetheholder, press thebottomof chassisneartheholder upwardandpullthetab outof its hole.
Tubing holder
Press
Indoor/outdoor
connecting cable
Connecting cable
Taping
Gas side piping
Liquid side piping Drain hose
18K
CoolingModel
Heat PumpModel
24K
Page 10
10 ENGLISH
7. Indoor unit installation
• Hook the indoor unit onto the upper portion of installation plate. (Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure the hooks are properly seated on the installation plate by moving it in left and right.
8. Connecting the pipings to the indoor unit.
• Align the center of the pipings and sufficiently tighten the flare nut with fingers.
• Finally, tighten the flare nut with torque wrench until the wrench clicks.
When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
Flare nut
Pipings
Torque wrench
Spanner
Indoor unit tubing
Plastic Bands
Insulation material
Wrap the insulation material around the connecting portion.
9. Wrap the insulation material around the connecting portion.
CAUTION: Take care to arrange the pipings,
drain hose and cables as the right upper picture for inserting it into the indoor unit and refixing the tubing holder easily.
Connecting cable
Drain hose
Press the lower left and right side of the unit against the Installation Plate until the hooks engage with their slots(sound click).
Pipe Size Torque Liquid Side(1/4") 1.8kg.m Liquid Side(3/8") 4.2kg.m
Gas Side(1/2") 5.5kg.m Gas Side(5/8") 6.6kg.m
Page 11
ENGLISH 11
ENGLISH
10. Set the pipings and the connecting cable to the back of the chassis with the tubing holder
• Hook the edge of tubing holder to tap on chassis and push the bottom of tubing holder to be engaged in the bottom of chassis.
11. Indoor unit installation
• Hook the indoor unit onto the upper portion of installation plate. (Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure the hooks are properly seated on the installation plate by moving it in left and right.
Piping
Taping
Drain hose
Tubing holder
Hook
Push
Connecting cable
Drain hose
Press the lower left and right side of the unit against the Installation Plate until the lower hooks engage with their slots (sound click).
Page 12
12 ENGLISH
4. Connecting Pipings and the cable to Outdoor unit
1) Connecting the pipings to the Outdoor unit
1. Align the center of the pipings and
sufficiently tighten the flare nut with fingers.
2. Finally, tighten the flare nut with torque
wrench until the wrench clicks.
• When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
Outdoor unit
Gas side piping (Bigger Dia.)
Liquid side piping (Smaller Dia.)
Torque wrench
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
4) Specification of power source.
5) Confirm that electrical capacity is sufficient.
6) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device.
• Proper starting power is not given to the compressor.
Pipe Size Torque Liquid Side(1/4") 1.8kg.m Liquid Side(3/8") 4.2kg.m
Gas Side(1/2") 5.5kg.m Gas Side(5/8") 6.6kg.m
Page 13
1(L)
1(L)
1(L)
2(N)
2(N)
2(N)
3
3
3
4
5
1(L)
2(N)
3
4
5
1(L)
2(N)
ENGLISH 13
ENGLISH
2)
Connection of the cable
1. Remove the cover control from the unit by loosening the screw. Connect the wires to the terminals on the control board individually as the following.
Outdoor unit
Terminal block
Connecting cable
Power cord (power connectingcable)
Cover control
Over 5mm
Power supply
2. Secure the cable onto the control board with the holder (clamper).
3. Refix the cover control to the original position with
the screw.
4. Use a recongnized circuit breaker 20A between the
power source and the unit. A disconnection device to adequately disconnect all supply lines must be fitted.
Terminals on theoutdoor unit
Terminals on theoutdoor unit
Terminals on theoutdoor unit
• 18K cooling only model
• 18K heat pump model
• 24K models
BROWN BLUE GN/YL BROWN
BROWN BLUE GN/YL BROWN
RED BLACK WHITE
RED BLACK WHITE
Terminals on theindoor unit
Terminals on theindoor unit
Terminals on theindoor unit
CAUTION
Ø10.0mm
(18K : Ø8.0mm)
Ø7.0mm
(18K : Ø5.0mm)
Ø8.0mm
The power cord connected to the indoor unit should be complied with the following specifications (Type H05VV-F(Indoor),H07RN-F(Outdoor) approved by HAR or SAA).
The connecting cable connected to theindoorandoutdoor unit should be complied with the following specifications (Type H07RN-Fapproved by HAR or SAA).
The powerconnecting cable
(18K)connected to the indoorand outdoor unit should be compliedwith thefollowing specifications (Type H07RN-Fapproved by HAR or SAA).
NORMAL CROSS-SECTIONAL AREA0.75mm
2
NORMAL CROSS-SECTIONAL AREA2.5mm
2
(18K : 1.5mm
2
)
NORMAL CROSS-SECTIONAL AREA 1.5mm
2
BROWN BLUE GN/YL
BROWN BLUE GN/YL
Page 14
14 ENGLISH
1) Checking the Drainage
1. Remove the Grille from the cabinet.
• Set the up-and-down air direction louver to open position (horizontally) by finger pressure.
• Remove 4 screws.
• To remove the Grille, pull lower the left and right side of the grille toward you (slightly tilted) and lift it straight upward (Four tabs on the top inside edge of chassis are clear of their slots).
2. Check the drainage.
• Pour a glass of water on the evaporator.
• Ensure if water flows drain hose of indoor unit without any leakage.
5.Checking the Drainage and Connecting the cable to Indoor unit
Grille
Chassis
Screw(3places)
Page 15
ENGLISH 15
ENGLISH
2) Connect the cable to the indoor unit
1. Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.
18K heat pump model
2. Attach the Grille onto the cabinet.
• Grasp lower the left and right side of the Grille and engage four tabs on the top inside edge of the chassis.
• Press the Grille toward the chassis until it will be back into place.
24K models
1(L)
1(L)
1(L)
2(N)
2(N)
2(N)
3
3
3
4
5
1(L)
2(N)
3
4
5
1(L)
2(N)
Power supply
Terminals on theoutdoor unit
Terminals on theoutdoor unit
Terminals on theoutdoor unit
• 18K cooling only model
• 18K heat pump model
• 24K models
BROWN BLUE GN/YL BROWN
BROWN BLUE GN/YL BROWN
RED BLACK WHITE
RED BLACK WHITE
Terminals on theindoor unit
Terminals on theindoor unit
Terminals on theindoor unit
BROWN BLUE GN/YL
BROWN BLUE GN/YL
Page 16
16 ENGLISH
3) Form the pipings
1. Wrap the connecting portion of indoor unit with the Insulation material and secure it with two Plastic Bands. (for the right pipings)
• If you want to connect an additional drain hose, the end of the drain-outlet should keep distance from the ground.(Do not dip it into water, and fix it on the wall to avoid swinging in the wind.)
• Connecting cable
2. Tape the Pipings, drain hose and Connecting Cable from down to up.
3. Form the pipings gathered by taping along the exterior wall and fix it onto the wall by saddle or equivalent.
2. Tape the Pipings and Connecting cable from down to up.
3. Form the pipings gathered by taping along the exterior wall, make the Trap to be required to prevent water from entering into the room.
4. Fix the pipings onto the wall by saddle or equivalent.
In case of the Outdoor unit being installed below position of the Indoor unit.
In case of the Outdoor unit being installed above position of the Indoor unit.
Seal a small opening around the pipings with gum type sealer.
Taping
Pipings
Connectingcable
Powersupplycord
Plastic band
Trap is required to prevent water from entering
into electrical parts.
Seal a small opening around the pipings with gum type sealer.
Trap
Drain hose
18K
CoolingModel
Heat PumpModel
24K
Page 17
ENGLISH 17
ENGLISH
5. To open 2-way valve again, turn the valve stem counter-clockwise until it stops.
•Re-tighten the connecting portion with torque wrenches.
No leakage found
Ieakage found
Outdoor unit
Cover control
Gasside
To indoor unit Liquid side
Cap
Hexagonal wrench
Service port cap
3-way valve
(Close)
2-way valve
(Open)
leakage ceased
leakage persists
Repair
leakage ceased
6. To purge the air, push the pin on the service port of 3-way valve for three seconds with a hexagonal wrench and set it free for one minute. Repeat this three times.
Result
7. Set the both liquid and gas side valves to open position with the Hexagonal wrench for the unit operation.
6. Air Purging
1) Air purging
The air which contains moisture remaining in the refrigeration cycle may cause a malfunction on the compressor.
1. Remove the caps from the 2-way and 3-way valves.
2. Remove the service-port cap from the 3-way valve.
3. Turn the valve stem of liquid side valve counter-clockwise approx. 90 and hold it there for ten seconds, then close it.
4. Check a gas-leakage of the connecting portion of the pipings.
CAUTION: Do not leak the gas in the air
during air purging. Use vacuum pump as far as possible.
Page 18
18 ENGLISH
2) Checking a gas leakage
1. Connect the manifold gauge to the service port of 3-way valve. Measure the pressure.
2. Keep it for 5-10 minutes. Ensure if the pressure indicated on the gauge is as same as that of measured at first time.
NOTE:
The additional gas for air purping has been charged in the outdoor unit. However, if the flare connections have not been done correctly and there gas leaks, a gas cylinder
and the charge set will be needed.
CAUTION : Do not leak the gas in the air during air purging. Use vacuum pump as far as
possible.
Indoor unit
Liquid side
Closed
Outdoor unit
Gas side
Closed
CLOSE
CLOSE
Page 19
ENGLISH 19
ENGLISH
7. Maximum Length of Pipe and Freon Extra Charge
In case more than 5m
• Capacity is based on standard length and maximum allowance length is on the basis of reliability.
• Oil trap should be installed every 5~7 meters.
A
B
A
B
CAUTION
7K, 9K 3/8" 1/4" 5 7 15 20
12K 1/2" 1/4" 5 7 15 20 18K 1/2" 1/4" 5 15 30 20 24K 5/8" 1/4" 5 15 30 30
Pipe Size
Capacity
(Btu/h)
GAS LIQUID
Max.
length
A (m)
Additional
Refrigerant
(g/m)
Max.
Elevation
B (m)
Standard
Length
(m)
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Oil trap
Page 20
20 ENGLISH
Discharge air
(Cooling)
2) Evaluation of the performance
1. Measure the temperature of the intake and discharge air.
2. Ensure the difference between the intake temperature and the discharge one is more
than 8 C (Cooling) or reversely (Heating).
8. Test running
Settlement of Outdoor Unit
• Anchor the outdoor unit with a bolt and nut
(ø10cm) tightly and horizontally on a concrete or rigid mount.
• When installing on the wall, roof or rooftop,
anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake.
• In the case when the vibration of the unit is
conveyed to the house, settle the unit with an anti-vibration rubber.
Bolt
Tubing connection
1) Connection of power supply
1. Connect the power supply cord to the independent power supply.
• Circuitbreaker is required.
2. Prepare the remote control.
• Insert two batteries provided.
Remove the battery cover from the remote controller.
• Slide the cover according to the arrow
direction.
Insert the two batteries. (Two "R03" or "AAA" dry-cell batteries or equivalent.)
• Be sure that the (+) and (-) directions are
correct.
• Be sure that both batteries are new.
Re-attach the cover.
• Slide it back into position.
3. Operate the unit for fifteen minutes or more.
RESET
RESET
RESET
Loading...