LG LP-F8081CL, LP-F8081HL, LP-F8081ZL Service manual

Page 1
1. Preface
–3–
This service manual provides various service information, containing the mechanical and electrical parts and etc. This package air conditioner was manufactured and assembled under the strict quality control system. The refrigerant is charged at the factory. Be sure to read the safety precautions prior to servicing the unit.
1.1 Safety Precautions
¤ When servicing the unit, set the main SWITCH to OFF and remove the POWER SUPPLY cables. ¤Ł Observe the original lead dress. If a short circuit is found, replace all parts which have been overheated or
¤Ø After servicing the unit, make an insulation resistance test to protect the customer from being exposed to
shock hazards.
1.2 Features
¤ Design for cooling and heating ¤ŁSuper energy efficiency ¤ØMicom Control ¤ŒWhisper quiet operation ¤ºRemovable air filter ¤ 3 minute delay circuit ¤ 7 hour timer ¤ 3 step speeds for cooling/heating ¤ Auto Restart
Page 2
1.3 Product Specifications
–4–
POWER SOURCE (ø, V, Hz)
COOLING CAPACITY Btu/h
W
INPUT W
CURRENT A
HEATING CAPACITY Btu/h
(W)
W
(W)
INPUT W
(W)
CURRENT A
(A)
MAKER
TYPE
COMPRESSOR MODEL
INPUT W CURRENT A CAPACITY Kcal/h
NOISE INDOOR dB(A)
LEVEL(1m) OUTDOOR
AIR INDOOR CMM
VOLUME OUTDOOR
REFRIGERANT R-22 Kg
HEAT INDOOR R/C/FPI
EXCHANGER OUTDOOR R/C/FPI
FAN INDOOR TYPE
OUTDOOR
ROOM TEMPERATURE CONTROL
NET INDOOR Kg
WEIGHT OUTDOOR
DIMENSIONS INDOOR mm
(W × H × D) OUTDOOR
SVC LIQUID Inch
VALVE GAS (mm)
3,380 – 415,50 3,380 – 415,50
71,400 71,400 20,927 20,927
6,900 7,000
12.0 13.0
74,000 (8,000)
21,680 (8,000)
6,500
(8,000)
12.5
(12.0)
COPELAND COPELAND
SCROLL SCROLL
ZR94KC – TFD ZR94KC – TFD
6,990 6,990
13.6 13.6
19,732 19,732
56 56 65 65 35 35
104 104
5.9 7.2 3/33/17 3/33/17 2/18/17 2/18/17
SIROCO SIROCO
PROPELLER PROPELLER
MICOM CONTROL MICOM CONTROL
132 132 150 150
1,050 ×1,880 ×495 1,050 ×1,880 ×495
1,000
×
965 ×370 1,000 ×965 ×370
5/8 5/8
1 1
MODEL
LP-F8081CL
LP-F8081HL LP-F8081ZL
(Including Electric
heater)
Page 3
–5–
1.4 Functions
Indoor Unit
Power Switch ON/OFF
Operation Mode Control
Sensing the room temperature
Controlling the room temperature
Starting Current Control
Sensing Heat Exchanger Temperature
Timer Delay Safety Control
Indoor Fan Speed Control
Operation Indication lamps
Temperature Setting
Airflow Direction Control
Room temperature Display
Timer Control
• Cooling, Soft Dry, Auto, Fan ➔ Cooling Model
Cooling, Heating, Soft Dry, Fan➔ Heat Pump Model
• Room temperature sensor (Thermistor)
• Maintains the room temperature in accordance with the setting temperature.
• Indoor fan is delayed for 3 sec at the starting.
• Heat exchanger temperature sensor (Thermistor)
• Restarting is inhibited for approx. 3 minutes.
• High, Low, Duct
• Up : up to 30°C
• Down : down to 16°C
• Airflow direction Manual control
• Low, 10° ~ 35°C, Hi
• Off Timer (1, 2, 3....7 hour)
Page 4
–6–
Outdoor Unit
Deice Control
Outdoor Fan Speed Control
Sensing Heat Exchanger Temperature
• De-ice PCB
• One speed
• Heat exchanger temperature sensor (Thermistor)
Page 5
2. Dimensions
–7–
Indoor Unit
Outdoor Unit
268568990
1890
1051
496
75
130 121
75
193
951
36
36
60
345
93.8
131
36
75
525
109.5
58.5
145.8
93.8
Air Outlet Vent
Air Inlet Vent
Window Display
Earth Screw
700
650
963
930
582
185
125
546
1245
700
50
260
95 80
Air Outlet Vent
Air Inlet Vent
Page 6
3. Wiring Diagram
Indoor & Outdoor Unit Circuit Diagram
(1) LD-F8081CL
–8–
INDOOR UNIT CIRCUIT DIAGRAM
OR BK BL RD
BR
YL
RY3
CN2
CN3
DISPLAY
PCB ASM
CN1
RD
GN/YL
CONNECT TO OUTDOOR UNIT
WH BK
BK
GN/YL
BL BR
YL BL
CONNECT TO CONTACT "R" "N" OF OUTDOOR TERMINAL BLOCK "Tmo1"
NOTE
BL BK BR OR RD WH YL GN/YL
BLUE BLACK BROWN ORANGE RED WHITE YELLOW GREEN/YELLOW
: : : : : : : :
RY3
1
MAIN PCB ASM
RY2
FUSE (10A)
RY1
SUB PCB ASM
CAPACITOR
INDOOR
FAN MOTOR
ROOM
TH
EVA
TH
2 3 4
3 2 1
FIELD WIRING
NOTE
1. This product is 3ø,4W,380-415V,50Hz.
2. "Check List" before test run. 1st: Reconfirm the wiring connecting of compressor, outdoor unit motor. 2nd: Fasten the screw of "Terminal Block Tmo1,2" once more.
Tmo1,2 52C 51C 63H CH FMo1,2 Co1,2
TERMINAL BLOCK MAGNETIC CONTACTOR EOCR(COMP.) HIGH PRESSURE SWITCH CRANKCASE HEATER OUTDOOR FAN MOTOR RUN CAPACITOR FOR FAN(OUTDOOR)
NOTE
BL
BLUE
:
BK
BLACK
:
BR
BROWN
:
OR
ORANGE
:
RD
RED
:
WH
WHITE
:
YL
YELLOW
:
GN
GREEN
:
GN/YL
GREEN/YELLOW
:
BK
Tmo1
R S T N
3Ø, 4W
380-415V, 50Hz
POWER SUPPLY
CONNECT TO INDOOR UNIT
WH
WH
OR
OR
BK
Co1
Co2
YLBRORBKYLBROR
FMo2FMo1
RD
WH
52C
BK
BK
L1 L2
WH
BK
T1
1 3 5 31
2 4 6 32
WH
T3
COMP
FUSE(5A)
B
51C
Ta
Tb
Tc
RD
T2
FUSE(5A)
WH
BK
A
BK
BK
RD
WH
63H
CH
BK
BK
WH
GN/YL
BK
CONNECT TO INDOOR UNIT
BR
1
BL
2
BK
3
GN/YL
4 5 6
Tmo2
Page 7
–9–
(2) LD-F8081HL/ZL
INDOOR UNIT CIRCUIT DIAGRAM
CAPACITOR
BR
OR BK
BL
RD
YL
INDOOR
FAN MOTOR
RY3 RY2
RY1
SUB PCB ASM
FUSE (10A)
DISPLAY
PCB ASM
MAIN PCB ASM
CN1
CN2
ROOM
TH
EVA
TH
CN3
Tmi
YL BL
3 2 1
CONNECT TO CONTACT "T" "N" OF OUTDOOR TERMINAL BLOCK "A"
Ry3
Ry6
Ry7
BKBKBK
TF
TF
BK
BL
BK
BKWHRD
POWER SUPPLY
3Ø 380~415V
50Hz
L1 L2 L3
a
T1 T2 T3
b
EH
1 2 3 4 5 6
5 4
Tmi
CONNECT TO OUTDOOR
(HOUSING ASM)
TP
Option part
DEF TH EH EVA TH ROOM TH
Ry3 Ry6 Ry7 THi
Tmi TP TF
TERMINAL BLOCK(INDOOR) BIMETAL SWITCH FOR HEATER THERMAL FUSE
RELAY FOR COMP RELAY FOR HEATER RELAY FOR HEATING THERMISTOR FOR INDOOR TEMP
THERMISTER FOR DISCHARGE AIR ELECTRIC HEATER THERMISTER FOR EVA TEMP. THERMISTER FOR EVA INDOOR TEMP
NOTE
BK:BLACK BL:BLUE BR:BROWN
YL :YELLOW WH:WHITE
OUTDOOR UNIT WIRING DIAGRAM
F2
RD RD RD
TM
R S T N
POWER SUPPLY 3ø,380-415V,50Hz TERMINAL(4P)
CRANKCASE HEATER
CH
FUSE (250V, 5A)
F1,2
RUN CAPACITOR FOR FMo
Co
OUTDOOR FAN MOTOR
FMo
GN/YL
YLBRORBKYLBROR
YLBRORBKYLBROR
FMo
49FMo
63H2
BK
F2
BK BK
WH RD RD
63H1
52C
BK
BK
FMo
49FMo
D.P C TH 20SV 49FMo
BKWHRD
L1
COMP
DEICER PCB THERMISTOR FOR PIPE TEMP.(OUTDOOR) REVERSING COIL INERNAL T.P FOR FMo
BK BK
1 3 5 31 A
2 4 6 32 B
L3
L2
BK
R
A B
YL
BK
52F1 63H1 63H2 49C
WH
3.P.D
S T
WH WH
WH
BK WH BK
20SV
RELAY FOR FMo HIGH PRESSURE SWITCH HIGH PRESSURE SWITCH FOR HEATING INTERNAL O.L.P FOR COMP.
BL BL
BK
NOTE
BL BK BR OR
BK
D.P
52F1
1 2 3 4 5 6 7 8
OR
BLUE
:
BLACK
:
BROWN
:
ORANGE
:
TM 52C
3.P.D
1 2 3 4 5 6
C TH
BL
BR BL BR BL
GN/YL
NC
NO NC NO
YL
RD
RED
:
WH
WHITE
:
YL
YELLOW
:
GN/YL : GREEN/YELLOW
MAIN TERMINAL BLOCK MAGNETIC CONTACTOR 3 PHASE DETECTOR
Page 8
– 10 –
4. OPERATION DETAILS
(1) The function of main control
1. Time Delay Safety Control
• 3min
...
The compressor is ceased for 3 minutes to balance the pressure in the refrigeration cycle.
(Protection of compressor)
• 3sec
...
The indoor fan is ceased for 1~3 seconds to prevent relay noise. (Protection of fan relay and micro chip)
• 1min
...
The 4-way valve is ceased for 30 sec. to prevent the refrigerant-gas abnormal noise when the Heating operation is OFF or switched to the other operation mode.
2. Cooling Mode Operation
• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the controller and the operation diagram is as following
Intake Air temp.
Setting Temp. +1°C
(Compressor ON)
Setting Temp. -1°C
(Compressor OFF)
Indoor Fan Speed
Selecting
fan speed
Selecting
fan speed
Selecting
fan speed
Selecting
fan speed
Selecting
fan speed
3 minutes 3 minutes
Compressor ON OFF ON OFF ON
Page 9
– 11 –
3. Auto Operation (Cooling Model only)
ƒUThe operation procedure is as following.
ƒƒUU
Auto Operation for Cooling
Press Start/Stop Button
Select Auto Operation Mode
Check the Room temperature
Operation Condition Intake-air Temperature Setting temperature Fan speed
Over 26°C 25°C
Over 24°C~below 25.5°C Intake air -1.0°C Over 22°C~below 23.5°C Intake air -0.5°C
below 21.5°C Intake air Temperature(18°C, MAX)
When Switch to
Auto Operation
Controlled
by Fuzzy logic
Intake Air Temp.
Indoor Fan Speed
Compressor ON OFF
Fuzzy Speed
ON OFF
Setting Temp. +1°C
(Compressor ON)
Setting Temp. -1°C
(Compressor OFF)
3 minutes 3 minutes
Page 10
– 12 –
4. Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Intake Air Temp.
Setting Temp.
(Compressor ON)
Setting Temp. -1°C
Indoor Fan Speed
Compressor
Electric Heater(Option)
ON
ON
OFF ON OFF OFFOFF ON OFF
OFF
LOW
Hot
Start
minimum
10sec.
minimum
1min
minimum
10sec.
OFF
A A
OFFLOW LOW
Setting Temp. +1°C (Compressor OFF)
Selecting
fan speed
Selecting
fan speed
• A point: The indoor pipe temperature to be less then 35°C or Discharge air Temperature to be less than 29°C. The indoor fan operates for minimum 10sec. even if the indoor pipe temperature falls lower than35°C or the discharge air Temperature falls lower than 29°C.
Low(V)Stop(VI)
39˚C
Discharge Air Temp.
Indoor Pipe Temp.
34˚C
28˚C 26˚C
Selecting Fan Speed(IV)
Low(II)Stop(I)
(Hot-Start Operating)
Heating Start
(Hot-Start Release Point)
Selecting Fan Speed(III)
¡ During heating operation, the operating procedure of the indoor fan is as the following.
Step Indoor fan speed Pipe temp. Air discharge temp.
¥ Off 28°C(Hot start operating) ¥– Low 28°C <39°C ¥† Selecting speed 28°C 39°C ¥‡ Selecting speed 28°C >34°C ¥· Low 26°C 34°C ¥ Off 26°C
Page 11
– 13 –
5. Hot-Start Control
• The indoor fan stops until the evaporator piping temperature will be reached to 28°C.
• During heating operation, if piping temperatures fall below 26°C fan stops.
• The operation diagram is as following.
6. Defrost Control
• Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
• The first defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes passed from starting of heating operation and more than.
• Defrost ends after 10 minutes pass from starting of defrost operation or when the outdoor pipe temperature rises over 12°C even if before 10 minutes.
• The second defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes pass from ending of the first defrost and more than.
INDOOR PIPE
TEMP.
INDOOR FAN
SPEED
Selecting
fan speed
OFF OFFLOW
1min
Maximum
COMPRESSOR ON
28°C
26°C
More than 45 minutes of
heating operation
Outdoor Pipe Temp.
Indoor Fan
Compressor 4-Way Valve
ON ON
ON ON
OFF
ON
OFF
HOT-
START
ON
ON OFF OFFON
12°C
(Defrost OFF)
-6°C
(Defrost ON)
Within
10minutes
Defrost
Defrost
More than 45 minutes of
heating operation
Less than 5 minutes
Page 12
9. Child Lock function
This function is to operate Air conditioner only by Remocon. The procedure is as the following 1st: Press the 2 buttons of the temperature control simultaneously, to raise-to lower on the Display Panel of the
product for more 3 seconds.
2nd: The buzzer sounds and then the window of Display Panel shows
LLOOCC
(LOC) mark. 3rd: To release this function, the reverse again the operating procedure could be done. ¡ During this function is operating, any buttons of Display Panel don't work. But it is possible to operate with
Remote controller.
10. Off Timer Function
This function is to set the time of stopping the unit operation. The procedure is as the following.
1st: Press the timer set button on the Remocon. 2nd:
The buzzer sounds and then the display window shows the Off-Time to be set as 1:00¡
...
¡ 7:00 ¡ 0:00.
- The Off-Time is shifted as the following by each press.
- If you select '0:00', the Off-Timer function will be cancelled.
- During Off-Timer Operation, if you repress the timer set button, the rest time will be displayed.
– 14 –
8. Protection of the evaporator pipe from frosting
• Compressor and outdoor fan stop when indoor pipe temperature is below -2°C and restart at the pipe temperature is above 12°C.
7. Soft Dry Operation Mode
• During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 2°C, the compres­sor OFF temperature is the setting temperature minus 1°C.
• When the room temperature rises over the compressor ON temperature, the operation mode is switched to the Cooling mode.
• When the room temperature falls between the compressor ON temperature and OFF temperature, the opera­tion mode is switched to the Soft Dry Operation.
• The operation diagram is shown below.
Intake Air Temp.
Indoor Fan Speed
LOW
Selecting
fan speed
Selecting
fan speed
LOW LOW LOW LOW
Compressor OFFON ONON OFF OFF ON
LOW
OFF
Setting Temp. +2°C
(Compressor ON)
Setting Temp. -1°C
(Compresso OFF)
Operation
Cooling
Cooling
operation
Dry operation
3 min. 3 min.
10 min.
maximum
7 min.
maximum
10 min.
1:00 2:00 3:00 4:00 5:00 6:00 7:00 0:00
Page 13
11. Alarm mode display / only displayed while operating.
CCHH 00
: The sensor for sensing room temperature is open or short.
CCHH 11
: The sensor for sensing piping temperature of evaporator is open or short.
12. Function for test operation.
This function shall be operated while the set not operating and start while set temperature set button() down and start/stop buttons pressing continuously for 3 seconds. If you press start/stop button continuously for 3 seconds while set temp down button pressing once more test
operation and the set shall be stopped. After test operation operating and 18 minutes, test operation and the set shall be stopped. If you press start/stop button while test operation operating, test operation shall be stopped and the set shall
start. When test operation operating, the display of
8888::8888
shall be shifted to tESt
4-way valve is always off when test operation. Fan speed is high, air purifying system and auto air flow operations are off when test operation.
Regardless of outside temperature, the set operates when test operation. All but start/stop and air purifying system buttons cannot be set.
13. Function of changing set temperature when re-operation after stop.
Heating operation is set to the previous set temperature when re-operation after stop. Cooling operation is set to the previous set temperature when re-operation with start/stop button.
1.Operation mode. Cooling/soft dry mode Cooling mode
Heating mode Heating mode
2. Setting the set temperature when cooling operation.
Room temperature > Set temperature: to be set to the previous set temperature. Room temperature Set temperature a) Room temperature 26°C: to be set to 24°C b) 22°C Room temperature 25°C: to be set to 21°C c) Room temperature 21°C:to be set to -1°C less than room temperature.
3. Setting the set temperature when heating operation.
Set the previous set temperature when stopped.
14. Auto Restart
In case the power comes on again a power failure, Auto Restarting Operation is the function to operate proce­dures automatically to the previous operating conditions.
– 15 –
Page 14
5-1.
Installation of Indoor, Outdoor unit
1) Selection of the best location Indoor unit
• There should not be any heat source or steam
near the unit.
• There should not be any obstacles to prevent the
air circulation.
• A place where air circulation in the room will be
good.
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into con-
sideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the
wall, ceiling, fence, or other obstacles.
Outdoor unit
• If an awning is built over the unit to prevent direct
sunlight or rain exposure, be careful that heat radiation from the condenser is not restricted.
• There should not be any animals or plants which
could be affected by discharged hot air.
• Ensure the space indicated by arrows from the
wall, ceiling, fence, or other obstacles.
–16–
5. Installation
5cm
A
B
Indoor unit
Outdoor unit
50cm
50cm
50cm
150cm
5cm
40cm
100cm
Piping length and the elevation
1" 5/8" 50 35
80K
(Btu/h)
PIPE SIZE
MODEL
GAS SIDE LIQUID SIDE
Max.
Length
A (m)
Max.
Elevation
B (m)
Page 15
–17–
2) Indoor Unit installation
The mounting floor should be strong and solid
enough to prevent it from vibration.
Drill the piping hole with 70mm diameter hole-
core drill at either the right or the left of indoor unit. The hole should be sightly slant to the out­door side.
3) Outdoor unit Installation
Install the outdoor unit on the concrete or any
solid base securely and horizontally.
If there is any vibration transmitted to the build-
ing, mount the rubber underneath the outdoor unit.
4) Refrigerant amount
Before shipment, this air conditioner is filled with the rated amount of refrigerant including additional amount required for air-purging, subject to 5m pip­ing length. (The rated amount of refrigerant is indi­cated on the name plate.) But when the piping length exceeds 5 meters, additional charge is required according to the following table.
(Unit: g)
Example) 72K~80K In case of 10m long pipe(one-way), the amount of refrigerant to be replenished is:
(10 - 5) × 80 = 400g
200mm
70mm
70mm
90mm
Wall
Core Drill
MODEL
80K
REFRIGERANT CHARGE
80 per 1m
Page 16
–18–
5-2. Installation Method
1) Procedure
No. Installation works Descriptions
1 Preparation of tools and installation parts Preparation of installation 2 Flaring the pipes To insert the flare nuts, mounted on the
connection parts of both indoor and
outdoor unit, onto the copper pipes. 3 Pipe bending To reduce the flow resistance of refrigerant. 4 Connection of installation parts Connection of long piping
(elbows, socket etc) 5 Tighten the flare nut (outdoor) Connecting the pipings of the outdoor unit. 6 Blowing the pipings To remove dust and scale in working. 7 Tighten the flare nut (indoor) Connecting the pipings of the indoor unit. 8 Check a gas-leakage of the connecting
part of the pipings. 9 Air purging of the piping and indoor unit The air which contains moisture and which
remains in the refrigeration cycle may cause a malfunction on the compressor
10 Open the 3-way (liquid side) and
3-way (gas side) valves.
1 1 Form the pipings To prevent heat loss and sweat 12 Checking the drainage (indoor unit) To ensure if water flow drain hose of indoor unit. 13 Connecting the cable between outdoor Preparation of the operating
and indoor unit 14 Connecting the main cable to outdoor unit 15 Supply the power to the crankcase heater To prevent the liquid back to the compressor.
(Before the operating the unit) (Heat pump only) 16 Cooling operation
(Use the remote control or display of the
indoor unit)
Page 17
–19–
2) Preparation of installation parts and tools
No. Installation Parts, Tools Use
1 Pipe cutter (MAX 35mm Copper pipe) Cutting the pipings 2 Remear Remove burrs from cut edges of pipes. 3 Wrench (H5, H4 hexagonal wrench) To open the service valve 4 Pipe bender Bending the pipings 5 Leak detector Check a gas-leakage of connecting part
of the pipings 6 Manifold gauge To measure the pressure, to charge the refrigerant 7 Charge-nipple To connect the bombe 8 Vacuum pump To remove the air in the pipe. 9 Charge cylinder balance To measure the refrigerant amount
10 Bombe (Freon-22) Gas charge
Air purge
Cleaning the pipe
11 Spanner To tighten the connecting parts of the pipings 12 Monkey spanner 13 Driver( , ) 14 Benchi (150mm) Cutting the wires 15 Tapeline To measure the length 16 Core drill To make holes through the concrete wall and blocks 17 Voltmeter, Amperemeter, Clampmeter To measure the current and voltage 18 Insulation resistance tester To measure the insulation resistance 19 Glass thermometer
To measure the intake and outlet air temperature of the indoor unit
20 Copper tubes To use the connecting pipings 21 Insulation material To cover the connecting pipings 22 Tape To finish the connecting pipings 23 Electrical Leakage Breaker To shut off the main power 24 Cable To connect the cable from outdoor unit to indoor unit 27 Drain hose sockets, elbows To remote the condensing water
Page 18
–20–
Cut the pipes and the cable
• Use the accessory piping kit or the pipes purchased locally.
• Measure the distance between the indoor and the outdoor unit.
• Cut the pipes a little longer than measured distance.
• Cut the cable 1.5m longer than the pipe length.
Remove burrs.
• Remove burrs from cut edges of pipes.
• Turn the pipe end down to avoid the metal pow­der entering the pipe.
Caution:
If burrs are not removed, they may cause a gas leakage.
2) Connection of piping
Move the indoor tubing and drain hose to the hole
• Remove tubing holder and pull the tubing out of the chassis.
Replace the tubing holder into original position Route the tubing and the drain hose staight backwards.Insert the connecting cable into the indoor unit through the hole.
• Do not connect the cable to the indoor unit
• Make a small loop with the cable for easy connection later.
Tape the tubing and the connecting cable.Indoor unit installation.Connecting the pipings to the indoor unit.
• Align the center of the pipings and suffciently tighten the flare nut with fingers.
• Finally, tighten the flare nut with troque wrench until the wrench clicks. When tightening the flare nut with troque wrench, ensure the direction for tightening follows the arrow on the wrench.
90°
Pipe cutter
Slanted Rough
Pipe
Point down
Reamer
5-3. Piping of Indoor Unit
1) Preparation of piping
Page 19
–21–
3) Precautions in bending
If it is necessary to bend or stretch the tubing, use the spring which is attached to the tubing in
stead of pipe bender.
• Please make a careful notice to make a smooth line.
• Hold the tubing with your two hands closely and then bend or stretch it slowly not to make any crack.
• Remember that the radius (R) should not exceed 70mm (Refer to Fig. 1)
Do not repeat the bending process to prevent the
tubing from cracking or crushing.
Keep in mind that the bending part should not be
cracked and make the radius (R) as long as possible (Refer to Fig. 2)`
Spring
R70mm
(Fig. 1)
(Fig. 2)
R
5-4. Connecting Piping to Outdoor Unit
1) Connecting pipings to the outdoor unit
Upon connecting 4-way valves, please weld connecting pipes using elbows instead of connecting pipes with
flare nuts.
5-5. Connecting the Cable
Open the control board cover from the outdoor unit by
removing the screws.
Connect wires to the terminals on the control board individually and secure the cables onto the control
board with clamp.
Page 20
MODEL Circuit breaker capacity
80K
50A
(BTU/h)
–22–
5-6. Power Supply and Wiring
Voltage
Time
Starting point
Power source voltage working voltage
Starting voltage
The unit is completely wired internally at the factory according to general rule of electrical technology, but local rules, if they are required, should be complied with.
1) Power Supply
Power source must fulfill the following conditions:
¤ The working voltage should be higher than
90% and lower than 110% of the rated voltage marked on the name plate.
¤Ł The starting voltage should be higher than
85% of the rated voltage marked on the name plate.
¤Ł Provide a recognized circuit breaker as below
between power source and unit. A disconnection device to adequately discon­nect all supply lines must be fitted. (for service operations)
¤Ø The screws which fasten the wiring in the cas-
ing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fas­tened. (If they are loose, it could give rise to burn-out of the wires.)
¤ŒSee to it that the starting voltage is maintained
at more than 90 percent of the rated voltage marked on the name plate.
¤ºThe following troubles would be caused by volt-
age drop-down. Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, distur­bance to the normal function of a overload pro­tection device.
2) Wiring
After the confirmation of the above conditions, pre­pare the wiring as follows:
¤ Use the power supply cord(Rubber insula-
tion, type Ho7RNF approved by HAR or SAA) suitable for the product's electriccal capacity.
MODEL
80K
(BTU/h)
VOLTS
Conductor
cross-sectional
area
450/ 750V 5.5mm
2
Page 21
–23–
5-7. Air Purging of the Piping and Indoor Unit
No leakage found leakage found
leakage ceased
leakage ceased
leakage persists
The air which contains moisture and which remains in the Refrigeration cycle may cause a malfunction on the compressor.
¤ Remove the caps from the 4-way(liquid side)
and 4-way(gas side) valves.
¤Ł Remove the service-port cap from the 3-way
(gas side) valve.
¤ØTo open the valve, turn the valve stem of 3-way
(liquid side) valve counter-clockwise approx. 90° and hold it there for ten seconds, then close it.
¤ŒCheck a gas-leakage of the connecting portion
of the pipings.
¤ºTo open 3-way(liquid side) valve
again, turn the valve stem counter­clockwise until it stops.
¤ To purge the air, push the pin on the service port
of 3-way(gas side) valve for three seconds using with a hexagonal wrench and set it free for one minute.
• Repeat this three times.
Result
• Re-tighten the connecting portion with torque wrenches.
Outdoor unit
Service port cap
Hexagonal wrench
3-way valve cap (gas side)
3-way valve cap (liquid side)
To indoor unit
Page 22
–24–
¤
Set the both 3-way(liquid side) and 3-way(gas side) valves to open position with the Hexagonal wrench for the unit operation.
¤
Checking a gas leakage for the left piping
• Connect the manifold gauge to the service port of 3-way(gas side) valve. Measure the pressure.
• Keep it for 5 - 10 minutes. Ensure if the pressure indicated on the gauge is as same as that of measured at first time.
CLOSE CLOSE
Closed
Closed
Indoor unit
Outdoor unit
Liquid side
Gas side
Page 23
–25–
5-8. Checking the Drainage and Form the Piping
1) Checking the Drainage
¤ Remove the inlet grille.
¤Ł Check the drainage.
• Pour a glass of water into the drain pan.
• Ensure if water flows drain hose of indoor unit.
Page 24
–26–
2) Form the Piping
¤ Wrap the connecting portion of indoor unit with the
insulation material and secure it with two Plastic Bands. (for the right piping)
• If you connect an additional drain hose, the end of the drain-outlet should be kept distance from the ground. (Do not dip it into water, and fix it on the wall to avoid swinging in the wind.)
¤ŁTape the Piping, and Connecting Cable from down
to up.
¤ØForm the piping gathered by taping along the exteri-
or wall and fix it onto the wall by saddle or equiva­lent.
¤ Tape the piping and connecting cable from down to
up.
¤Ł In order to prevent water from entering the room,
form a trap and tape the piping.
¤Ø Fix the piping onto the wall with saddle or bracket.
In case of the outdoor unit is installed below position of the indoor unit.
In case of the outdoor unit is installed upper posi­tion of the indoor unit.
Main cable Gas side piping
Connecting Cable (For heater)
Connecting Cable
Tube PE Foam
Trap is required to prevent the electrical parts from entering the water.
Seal a small opening around the piping with gum type sealer.
Trap
Trap
Page 25
–27–
5-9 Final Check and Test Run
After installing the unit, perform the final check and run­ning test as follows: Final check points
¤ Is the unit securely mounted? ¤ŁIs the installation location adequate? ¤ØIs the water piping work adequately and without
leakage?
¤ŒAre trapped drain lines installed at condensate
drain connections?
¤ºHas the refrigeration cooling cycle been kept
sealed?
¤ Is the electrical wiring adequate and are the
screws tightened on terminals?
After the above final checkings, prepare the running test as follows:
¤ Connect compound gauges to the check joints at
discharge and suction sides of the compressor.
¤ŁTurn all switches "OFF". ¤ØTurn the main switch "ON".
Running test should be accomplished as follows:
¤ Set operation switch at "FAN" and the fan will
start. Check to ensure that the fan sounds nor­mal.
¤ŁNext, set it at "COOL" and the compressor will
start. Check to ensure that the compressor sounds normal.
¤ØCheck discharge and suction pressure on the
compound gauges.
¤ŒCheck working voltage, phase balance and run-
ning current.
¤ºCheck to ensure that the thermistor functions
properly.
¤ Check to ensure that the high pressure control
switch functions correctly.
Page 26
–28–
5-10 Installation Check List
1. Is the unit securely mounted and levelled?
Space for Evaporator Air Flow Space for Condenser Air Flow Space for Maintenance Work Noise and Vibration Appearance
2. Is electrical wiring system adequate?
Wire Size Tightened Connection Switch Size Operation Control Devices Fuse Size Safety Devices Voltage Hz
3. Does the refrigerant piping work adequately?
Pipe Size Leakage Insulation Refrigerant Charge Vibration Trap
4. Does the duct work adequately?
Pipe Size Sound-proof Insulation Vibration-Proof
Vibration
5. Are the condensate drain lines properly arranged?
Trap Drain Ditch
6. Are the service valves opened?
Page 27
–29–
5-11 Running Test and Maintenance Record
JOB NUMBER: POWER SUPPLY : Main Power_______ V, ________ Hz
Accessory Attached : CUSTOMER'S NAME AND ADDRESS : (PHONE NO.: ) INSTALLED BY: DATE: START UP BY: DATE:
1. Does the operation switch function properly?2. Is the rotating direction of the evaporator fan correct?3. Is the rotating direction of the condenser fan correct?4. Is the evaporator airflow sufficient?5. Are there any abnormal sounds?6. Has the unit been operated at least twenty (20) minutes?7. Check indoor temperatures :
Inlet : DB __________ °C, WB _______________°C Outlet : DB __________ °C, WB _______________°C
8. Check outdoor temperatures :
Inlet : DB __________ °C Outlet : DB __________ °C
9. Check pressures :
Discharge pressure:________kg/cm
2
Suction pressure: ____kg/cm
2
10. Check voltage :
Rated voltage:________ V Operating voltage:R-S __________ V, S-T _____ V, T-R ______V. Starting voltage: _____ V (0.85 x Rated Voltage) Phase unbalance : 1-V/V mean = ______ (-0.03 Imbalance +0.03)
11. Check running current:
packaged air conditioner: ____ A
12. Do the control devices function properly?13. Do the protective devices function correctly?14. Is the refrigerant charge adequate?15. Is the drain line draining properly?16. Is the air filter clean?17. Are the evaporator coil and condenser coil clean?18. Are all cabinet panels fixed?19. Are all cabinet panels free from rattles?
Indoor Unit Outdoor Unit
Model ( V, Hz) ( V, Hz)
Production No.
Page 28
6. Operation
–30–
Display
¤
START/STOP BUTTON
Operation starts when this button is pressed and stops when the button is pressed again.
¤Ł
OPERATION MODE SELECTION BUTTON
Used to select the operation Mode.
¤Ø
ROOM TEMPERATURE SETTING BUTTONS
Used to select the room temperature.
¤Œ
INDOOR FAN SPEED SELECTION
Used to select fan speed in three steps-low, med, high.
¤º
FAN OPERATION LAMP
¤
COOLING OPERATION LAMP
¤
SOFT DRY OPERATION LAMP
¤
HEATING OPERATION LAMP
¤
DEFROST OPERATION LAMP
¤
AUTO OPERATION LAMP
¤æ
DUCT AIR FLOW LAMP(OPTION)
¤
OUTDOOR UNIT OPERATION LAMP
¤
TIMER SETTING BUTTON (OPERATION STOPS AT ON)
¤
TIMER OPEATION LAMP
¤ı
ELECTRIC HEATER OPERATION LAMP
§
ELECTRIC HEATER OPERATION BUTTON (OPTION)
M
O
D
E
DUCT
OUT DOOR
ROOM TEMP. SET TEMP.
LH
M
O
D
E
DUCT
OUT DOOR
ROOM TEMP. SET TEMP.
LH
13
147
2 3 4 12
1
10
65 11713
2 3 4 12 116 8 9
65 14 11 15
Page 29
–31–
Works Shaft position Shaft position Service port
Shipping Closed Closed Closed
(with valve cap) (with valve cap) (with valve cap)
1. Air purging Open Closed Open (Installation) (counter-clockwise) (clockwise) (push-pin)
Operation Open Open Closed
(with valve cap) (with valve cap)
2. Pumping down Open Open Open
(transferring) (clockwise) (counter (connected
-clockwise) manifold gauge)
3. Evacuation Open Open Open
(Servicing) (with charging
cylinder)
4. Gas charging Open Open Open
(Servicing) (with charging
cylinder)
5. Pressure check Open Open Open
(Servicing) (with charging
cylinder)
6. Gas releasing Open Open Open
(Servicing) (with charging
cylinder)
3-Way Valve (Liquid Side) 3-Way Valve (Gas Side)
7. 3-Way Valve
Valve cap
Open position
Flare nut
To piping connection
To outdoor unit
Closed position
Service
cap
port
Pin
Service port
Flare nut
To piping connection
Valve cap
Open position Closed position
Service port
To outdoor unit
cap
Service port
Pin
Page 30
–32–
Gas side
Liquid side
Indoor unit
Outdoor unit
Closed
3-way valve
Closed
3-way valve
7.1 Air purging
Required tools: hexagonal wrench, adjustable wrench, torque wrench, and gas leak detector. The additional gas for air purging has been charged in the outdoor unit. However, if the flare connections have not been done correctly and there gas leaks, a gas cylinder and the charge set will be needed. The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration pipes, it will affect the compressor, reduce cooling capacity, and can lead to a malfunction.
• Procedure
¤ Recheck the piping connections. ¤ŁOpen the valve stem of the 3-way(liquid side) valve
counterclockwise approximately 90°, wait 10 seconds, and then set it to closed position.
- Be sure to use a hexagonal wrench to operate the valve stem.
¤ØCheck for gas leakage.
-Check the flare connections for gas leakage.
¤ŒPurge the air from the system.
- Set the 3-way(liquid side) valve to the open position and remove the cap from the 3-way(gas side) valve's service port.
- Using the hexagonal wrench to press the valve core pin, discharge for three seconds and then wait for one minute. Repeat this three times.
¤ºUse torque wrench to tighten the service port nut. ¤ Set the 3-way (gas side) valve to the back seat.
¤ Mount the valve stem nuts to the 3-way (liquid
side)valve and 3-way (gas side) valves.
¤ Check for gas leakage.
• At this time, especially check for gas leakage from the 3-way (liquid side) valve and 3-way (gas side) valve's stem nuts, and from the service port nut.
Caution
If gas leakage is discovered in step
¤¤ØØ
above,
take the following measures:
If the gas leaks stop when the piping connections are tightened further, continue working from step ¤Œ. If the gas leaks do not stop when the connections are
retightened, repair the location of the leak, discharge all of the gas through the service port, and then recharge with the specified amount of gas from a gas cylinder.
Service port nut. Be sure, using a torque wrench to tighten the service port nut (after using the service port), so that it prevents the
gas leakage from the refrigeration cycle.
Page 31
7.2 Pump down
• Procedure
¤ Confirm that both 3-way(liquid side) and 3-
way(gas side) valves are set to the open position.
• Remove the valve stem caps and confirm that the valve stems are in the raised position.
• Be sure to use a hexagonal wrench to operate the valve stems.
¤ŁOperate the unit for 10 to 15 minutes.
¤ØStop operation and wait for 3 minutes, then
connect the charge set to the service port of the 3-way (gas side) valve.
- Connect the charge hose with the push pin to the service port.
¤ŒAir purging of the charge hose.
• Open the low-pressure valve on the charge equipment slightly to purge air from the charge hose.
¤ºSet the 3-way(liquid side) valve to the closed
position.
¤ Operate the air conditioner at the cooling cycle
and stop it when the gauge indicates 1 kg/cm2g
¤ Immediately set the 3-way(gas side) valve to the
closed position.
- Do this quickly so that the gauge ends up indicating 3 to 5kg/cm2g.
¤ Disconnect the charge set, and mount the
3-way(liquid side) and 3-way(gas side) valve's stem nuts and the service port nut.
- Use torque wrench to tighten the service port nut.
- Be sure to check gas leakage.
Lo
CLOSECLOSE
Purge the air
Gas side
Liquid side
Indoor unit
Outdoor unit
Closed
Open
3-Way valve
3-Way valve
–33–
Page 32
1) Re-airpurging
(Re-installation)
• Procedure
¤ Confirm that both the 3-way (liquid side) valve
and the 3-way(gas side) valve are set to the closed position.
¤ŁConnect the charge set and a gas cylinder to the
service port of the 3-way(gas side) valve.
• Leave the valve on the gas cylinder closed.
¤ØAir purging.
• Open the valves on the gas cylinder and the charge set. Purge the air by loosening the flare nut on the 3-way(liquid side) valve approximately 45° for 3 seconds then closing it for 1 minute; repeat 3 times.
• After purging the air, use a torque wrench to tighten the flare nut on liquid side valve.
¤ŒCheck gas leakage.
• Check the flare connections for gas leakage.
¤ºDischarge the refrigerant.
• Close the valve on the gas cylinder and discharge the refrigerant until the gauge indicates 3 to 5kg/cm2g
¤ Disconnect the charge set and the gas cylinder,
and set the 3-way(liquid side) and 3-way(gas side) valves to the open position.
• Be sure to use a hexagonal wrench to operate the valve stems.
¤
Mount the valve stem nuts and the service port nut.
• Use torque wrench to tighten the service port nut.
• Be sure to check gas leakage.
CLOSE
OPEN
R22
Gas side
Gas cylinder
Liquid side
Indoor unit
Outdoor unit
Closed
3-Way valve
Closed 3-Way valve
–34–
Page 33
2) Balance refrigerant of the 3-way(liquid side), 3-way(gas side) valves
(Gas leakage)
• Procedure
¤ Confirm that both the liquid side and gas side valves are set to the back seat.
¤ŁConnect the charge set to the 3-way(gas side) valve's port.
• Leave the valve on the charge set closed.
• Connect the charge hose with the push pin to the service port.
¤Ø Open the valve (Lo side) on the charge set and discharge the refrigerant until the gauge indicates 0 kg/cm
2
g.
- If there is no air in the refrigerant cycle (the pressure when the air conditioner is not running is higher than 1 kg/cm2g), discharge the refrigerant until the gauge indicates 0.5 to 1 kg/cm2g. In case of this, it will not be necessary to apply an evacuation.
- Discharge the refrigerant gradually; if it is discharged too suddenly, the refrigeration oil will also be discharged.
CLOSE
OPEN
Gas side
Liquid side
Indoor unit
Outdoor unit
Open
Open
3-Way valve
3-Way valve
–35–
Page 34
7.3 Evacuation
(All amount of refrigerant leaked)
• Procedure
¤ Connect the vacuum pump to the center hose of charge set.
¤ŁEvacuation for approximately one hour.
- Confirm that the gauge needle has moved toward -76cmHg (vacuum of 4 mmHg or less).
¤ØClose the valve (Lo side) on the charge set, turn off the vacuum pump, and confirm that the gauge needle
does not move (approximately 5 minutes after turning off the vacuum pump).
¤ŒDisconnect the charge hose from the vacuum pump.
- Vacuum pump oil. If the vacuum pump oil gets dirty or depleted, replenish as needed.
CLOSE
Lo
OPEN
Vacuum pump
Gas side
Liquid side
Indoor unit
Outdoor unit
Open
3-Way valve
Open
3-Way valve
–36–
Page 35
7.4 Gas Charging
1) Cooling mode (After Evacuation)
• Procedure
¤ Connect the charge hose to the charging cylinder.
• Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder.
• If you are using a gas cylinder, use a scale and reverse the cylinder so that the system can be charged with liquid.
¤ŁPurge the air from the charge hose.
• Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air. (Be careful of the liquid refrigerant). The procedure is the same if using a gas cylinder.
¤ØOpen the valve (Lo side) on the charge set and
charge the system with liquid refrigerant.
• If the system can not be charged with the specified amount of refrigerant, it can be charged with a little at a time (approximately 150g each time) while operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure (pumping down-pin).
¤ŒImmediately disconnect the charge hose from the
3-way(gas side) valve's service port.
• Stopping partway will allow the gas to be discharged.
• If the system has been charged with liquid refrigerant while operating the air conditioner turn off the air conditioner before disconnecting the hose.
¤º Mount the valve stem nuts and the service port
nut.
Use a torque wrench to tighten the service port nut.
• Be sure to check gas leakage.
This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner.
–37–
Charging cylinder
Indoor unit
Check valve
OPEN
(1)
Lo
Liquid side
Gas side
CLOSE
3-Way valve
3-Way valve
Open
Open
Outdoor unit
Page 36
–38–
2) Heating Mode
(After Evacuation)
CLOSE
Lo
OPEN
(1)
Gas side
Liquid side
Indoor unit
Check valve
Charging cylinder
Outdoor unit
Open
Open
3-Way valve
3-Way valve
• Procedure
¤ Connect the charge hose to the charge cylinder.
• Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder.
• If you are using a gas cylinder, use a scale and reverse the cylinder so that the system can be charged with liquid.
¤ŁPurge the air from the charge hose.
• Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air. (Be careful of the liquid refrigerant). The procedure is the same if using a gas cylinder.
¤Ø Open the valve (Lo side) on the charge set and
charge the system with liquid refrigerant.
• If the system can not be charged with the specified amount of refrigerant, it can be charged with a little at a time (approximately 150g each time) while operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure (pumping down-pin).
¤ŒImmediately disconnect the charge hose from the
3-way valve's service port.
• Stopping partway will allow the gas to be discharged.
• If the system has been charged with liquid refrigerant while operating the air conditioner turn off the air conditioner before disconnecting the hose.
¤º
Mount the valve stem nuts and the service port nut.
-
Use a torque wrench to tighten the service port nut.
- Be sure to check gas leakage.
This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner.
Page 37
8. Troubleshooting Guide
–39–
In general, possible trouble is classified as two causes. The one is so called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air
Conditioning caused by a defect in the refrigeration circuit and improper application. Unit runs but ineffective cooling
Ineffective Cooling or Heating
Check outdoor coil (heat exchanger) & fan operation.
Check gas leakage.
Repair gas leak.
Replacement of unit if the unit is beyond repair.
Satisfactory operation with temperature difference of inlet & outlet air ; COOLING : 7~10°C HEATING : 15~17°C
Check heat load rise at cooling operation.
Unexpected residue
Added electrical utensil
Check inside gas pressure.
Adjust refrigerant charge.
Malfunction of compressor.
Replacement of compressor
Check of cold (warm) air cir­culation for smooth flow.
Dirty indoor coil (heat exchanger.)
Malfunction of fan.
Clogging of air filter.
Obstruction at air outlet.
Stop of auto air-swing.
Countermeasure against above trouble.
Check clogging in refrigera­tion circuit.
Repair clogging in refrigera­tion circuit.
Page 38
–40–
Failures to Start
Check of circuit breaker and fuse.
Check control switch.
Fan only fails to start
Improper wiring
Defect of fan motor capacitor.
Irregular motor resistance
( )
Irregular motor insulation
( )
Replacement of fan motor.
Improper electric heater
Replacement of electric heater
Regular but fails to start.
Replacement of compressor
Electric heater is not energized
Loose terminal connection.
Improper wiring
Irregular motor resistance (
)
Irregular motor insulation (
)
Replacement of compressor
Drop of power voltage
Capacitor check
Replacement
Compressor only fails to start
Defect of compressor capacitor
Check power source.
Check control switch setting.
Page 39
–41–
PACKAGE AIR CONDITIONER VOLTAGE LIMITS
8.1 No cooling and heating operation performed
1) Both the blower and the compressor do not work
NAME PLATE RATING MINIMUM MAXIMUM
380 - 415 V 342 V 456 V
2) Only blowers do not work
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Other parts than the unit
Magnetic switch for compressor & fan motor
Operating switch
Protection devices
Electric supply interrupted Defective power wiring Cut of power fuse
Too low voltage
Control point is on condition of "OFF" due to trouble.
Troubled or defective contactor
Opened the contact point with trouble
Measure it with a tester in case that the same power source is supplied to other equipment than the unit, what and where trouble can be discovered by checking the operation of other equipment.
Measure it with a tester.
Make short-circuit, then measure it with a tester.
Check it with the eyes or tester.
Check it with the eyes or tester.
Repair a switch box and is relative instrument.
Replacement of fuse Request a power
supplier to repair.
Check the power source. Use a thick cable if necessary.
Replace it if necessary.
Repair or replace it.
Discover the trouble cause and push the rest button.
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Air volume change over switch
Capacitor
Troubled or defective contact point
Defected
Check it with the eyes or a tester
Check it with a tester.
Repair or replace it.
Replace it.
Page 40
–42–
3) Only outdoor fan does not work
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Motor
Electric Wiring
Over-heated Layer short
Open wire on operation Short circuited on
operation
Check how it is insulated.
Check it with a tester.
Repair or replace it.
Rewiring or repair.
4) Only compressor does not work
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Magnetic switch for compressor motor
Compressor motor
Compressor
High pressure switch
Electric circuit
Defective contact, magnetic coil troubled.
Troubled over-heated (layer short)
Troubled or over-heated (lock)
Troubled or defective contact or operating
Defective connection or disconnection of the circuit for compressor.
Check it with the eyes on with a tester.
Check how it is insulated.
Groaned noise of motor
Check it with a tester.
Check it with a tester.
Repair or replace it.
Replace or repair the compressor.
Repair or replace it.
Replace it if necessary.
Rewiring or push reset button.
Page 41
–43–
Note: Use an appropriate measuring instrument for readjustment.
*1: Check the High-pressure switch indication. *2: Check the Low- pressure switch indication.
8.2 The Units discontinue after the operation started
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Other parts than the unit
Outdoor coil
In-condensable gas blended.
High pressure switch
Refrigerant
Outdoor Fan
Improper opening of the service valves in the refrigerant line
Coil is dirty *1
Air intruded into the refrigerant pipe line *1
Improper adjustment
A shortage of refrigerant amount. * 2
Reverse rotation of fan Obstacle Air short circuit *1
Checking
Checking
In the event that difference between the saturating temperature corresponding to high pressure and the temperature of air discharged from the outdoor coil is more than 15°C, incondensable gas may be blended.
Check it with a pressure gauge.
Confirm the wind blowing out.
Check it with eyes.
Open it properly
Wash it by means of something like chemical washing.
Extract air by vacuum pump, then recharge the refrigerant.
Readjust it to normal operating pressure. (Note) Don't alternate the specified adjusting pressure. If the adjusted pressure exceeds the specified range, it will cause a great accident.
Recharge the refrigerant. Repair the spot where it leaks.
If reversed, connect interchanged wires to each terminal. Power wirings.
Page 42
–44–
8.3 The unit is working, but not cooling and heating sufficiently (Both blower and compressor are working)
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Load
Air flow
Short air volume
Refrigerant
Air passage
Air filter
Much heat load
Obstacle disturbs Intake of uniform wind.
Reverse rotation of blower.
Shortage in the charged refrigerant.
Improper or foreign bodies
Clogged with dust
Heat load increased. Window or door has many cracks or gaps.
Checking
Checking
Coil inlet pipe is frosted
Checking
Checking
Do necessary disposal respectively.
Correct it.
Correct it.
Replenish it. (Repair the leakage spot).
Correct or clear the foreign bodies.
Cleaning
8.4 All the functions are performed normally, but very noisily and
much vibratively.
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Compressor
Blower
Screws
• Checking
• Checking
Checking
Checking
• Remove the shipping bracket.
• Replace the
compressor
• Repair or replace it.
• Clear the other material
Repair
Liquid refrigerant flooding back from the evaporator.
Compressor shipping bracket is not removed.
Faulty discharge valve and suction valve.
Fan broken. Other materials intruded.
Looseness or fail-off of screws
• Check for refrigerant over-charge.
• Check to see if the intaking air temperature is extremely cold.
• Check for insufficient air flow quantity.
Page 43
–45–
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Electric troubles (Magnetic contactor)
Others
Defective contact. Defective contact point. Rusting and faults in the iron core contact face. Defective contact of the operating switch.
Improper installation
Checking
Checking
Repair and clean or replace it.
Correct it.
Fault Cause Check/Correcitve Action
High Discharge
Low Discharge
High Suction Pressure
Low Suction Pressure
Condenser cooling air extremely hot or insufficient air flow through the condenser
Inside of the condenser tube is clogged.
Air in the refrigeration cooling cycle.
Suction pressure is higher than standard.
Faulty discharge valves or suction valves of the compressor.
Refrigerant low-charge or leakage.
Suction pressure is lower than standard. Intake air extemely hot or excessive air flow
through the evaporator coil.
Refrigerant over-charge. Faulty discharge valve or suction valve of
the compressor. Discharge pressure is higher than standard
Intake air extremely cold or insufficient air flow through the evaporator coil.
Refrigerant short-charge or leakage.
Restricted liquid in the suction line.
1. Check the operation of the outdoor motor .
2. Check discharge and suction, air circulation.
Clean condenser coil.
Purge air from the cycle.
See "High Suction Pressure".
1. Check unit operation input
2. Check the suction pressure.
Add refrigerant: repair leakage if any.
See "Low Suction Pressure".
1. Check fresh air, intake or check for
leakage of the return air.
2. Check air flow quantity.
Purge the refrigerant. Check the operating input.
See "High discharge Pressure".
1. Check air flow quantity.
2. Check air filter .
3. Check evaporator coil frosting
Add refrigerant, repair leakage, if any.
Check the capillary tube and the strainer.
8.5 Trouble checking by protection devices
Page 44
–46–
Fault Cause Check/Correcitve Action
Internal Thermostat Cut-Off
Overcurrent Relay for Compressor Cut-Off
Overcurrent Relay for Fan Motor Cut-Off
Fuse Blown
Disconnection and Faulty Contact
Discharge pressure is lower than standard.
Single or three phases running.
High or low voltage or phase unbalance.
Refrigerant short charge or leakage.
Compressor frequently stops and starts.
Discharge and suction pressure are extremely high.
High or low voltage, or phase unbalance. Single or three phases running
Faulty compressor motor.
Loose connections. Compressor frequently stops and starts.
High or low voltage, or phase unbalance. Single or three phases running.
Faulty fan motor.
Loose connection. Faulty fan bearing. Loose connections. Single or three phase running.
Faulty motor.
Disconnection.
Faulty contact.
See "Low Discharge Pressure".
Check the power supply line and the contactor.
Check the voltage and phase unbalance.
Add refrigerant, repair leakage, if any.
Check thermistor operation, or any other cause for frequent stop and start operation.
See "High Discharge Pressure" or "High Suction Pressure".
Check the voltage and phase unbalance. Check the power supply line and the
contact. Check electric resistance among the
compressor terminals, and from the terminals to ground.
Check the electric connections. Check the operation of the thermistor, or
any other cause for frequent stop.
Check the voltage and electric wiring. Check the power supply line and the
contactor. Check the fan motor and wiring. Check the elelctric connections.
Check repair or replace the bearing. Check the electric connections.
Check the power supply line. Check electric resistance among motor
housing, and from the terminals to ground.
1. Check the wires and connect where necessary.
2. Check the contact holding coil.
Check the contact in the magnetic contact, the over-current relay, the pressure control switch, the operation switch, the auxiliary relay.
Page 45
–47–
8.6 Electronic Parts Troubleshooting Guide
1) No cooling operation performed.
YES
YES
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
Is the AC220V
(AC 240 V) between Connector(CN-
outunit) ¥Land ¥Nof Main
P.C.B
ON/OFF S/W ON
Is the unit operating?
Is the input power
AC220V (AC240V) at COMP
Magnetic coil?
Check the magnetic contactor of outdoor unit.
Is it Cooling mode?
Room temp, > Set temp?
Is the DC5V at 14
pin of IC1(MICOM)
Replacement ICO2M, RY-Comp
Replacement (MICOM)
Room temp, >set temp setting
Select the cooling operation mode.
Check the wiring diagram.
Page 46
–48–
2) Indoor fan does not operate.
YES
YES
YES
YES YES YES
YES YES YES
YES
NO
NO
NO
NO
NONONO
NO NO NO
Is the unit
operating?
Is the DC5V at 20 pin
of MICOM?
Is the DC12V at each
terminal of RY1 coil of
SUB PCB ASM?
Replacement IC03M
Is the AC220V (240V)
between "C" and "H" of
SUB P.C.B?
Replacement RY1 of
SUB PCB
Check the motor winding
Replacement RY2 of
SUB PCB
Replacement RY3 of
SUB PCB
Is the AC220V (240V)
between "C" and "M" of
SUB P .C.B?
Is the AC220V (240V)
between "C" and "L" of
SUB P.C.B?
Is the DC12V at each
terminal of RY2 of SUB
PCB ASM?
Is the DC12V at each
terminal of RY3 of SUB
PCB ASM?
Is the DC5V at 21 pin
of MICOM?
Is the DC5V at 22 pin
of MICOM?
Replacement
MICOM and check
the EVA-Th
ON/OFF S/W ON
Page 47
–49–
3) The unit does not operate.
YES
NO
YES
NO
YES
NO
YES
NO
4) Timer control does not operate.
Replacement
MICOM
Is the AC220V
(240V) at Trans input terminal?
Is the AC12-18V at
Trans (2nd)?
Is the connector of
Main/Display correct?
Is the DC5V between PIN64
and PIN 32 of MICOM?
Replacement Main PCB ASM
1. Replacement IC03D
2. Replacement Main PCB ASM
Check the connector of Main/Display
Replacement Trans
1. Check the electric connections
2. Check the fuse of Main PCB ASM
Page 48
–50–
4) No heating operation performed.
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
ON/OFF S/W ON
Is the AC220V
(AC 240 V) between connector
(CN-outunit) ¥Land ¥Nof Main
P.C.B
Is the input power AC220V
(AC240V) at COMP magnetic coil
contactor?
Is it heating mode?
Room temp <Set temp?
Is the DC5V
at 14 pin of MICOM
Is the DC5V at 18 pin of
MICOM
Is the DC12V
at each terminal?
(RY-4way COIL)
Is the
AC220V (AC 240 V) between
connector(4WAY) and CN-outunit ¥L of
Main P.C.B
Is the DC12V at
each terminal? (RY -Comp)
Replacement RY -4way
Replacement IC02M
Replacement RY3
Is the AC220V
(AC 240 V) between connector(CN-outunit)
¥Land ¥N of Main
P.C.B
Check the wiring diagram.
Replacement MICOM
Replacement IC02M
Room temp. < Set temp. Setting
Replacement MICOM
Select the heating operation mode.
Check the COMP magnetic contactor of outdoor unit.
Check the wiring
connection
Is the unit operating?
Page 49
–51–
5) No heater operation performed.
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
Is the heating operating?
Is the Heat S/W of Main
PCB "ON"?
Heat S/W "ON"
Heater S/W "ON"
Replacement MICOM
Replacement IC02M
Replacement RY -Heater
Is the heater S/W of Main
PCB"ON"?
Is the DC 5V at 58 pin of
MICOM
Is the DC 12V at eack terminal?
(RY-Heater)
Is the
AC220V (AC 240 V) between
connector(HEA TER) and CN-outunit ¥Lof
Main P.C.B
Check the heater wiring
Select the heating operation mode.
Page 50
9. Electronic Control Device
–52–
9.1 Main P.C.B ASSY
Page 51
–53–
9.2 DISPLAY P.C.B ASSY
9.3 SUB P.C.B ASSY
PWB: 6870AQ2241 ASM: 6871AQ2242
CN-INPUT
CN-RELAY
CN-MOTOR
FUSE
250V/T10A
RY1 (HIGH)
RY2 (MIDDLE)
RY3 (LOW)
9.4 DE-ICER P.C.B ASSY
Page 52
10. Schematic Diagram
–54–
Circuit and Troubleshooting
Page 53
11. Exploped View and Replacement Parts List
–55–
45-3
38
40
41
42
39
36
34
35
47
43
44
45-2
45
43-2
43-1
37
46
48
49
32
47
45-3
45-1
31
33
30
23
28
26
27
25 29
24
28
31-1
27-1
36
Indoor Unit
Exploded View
Page 54
–56–
22
55
19
10
4
5
1
12
21
20
15
13
16
2
9
8
7
18
17
6
3
11
14
Page 55
–57–
1 BASE PAN 3040AP2624P 3040AP2624P 3040AP2624P 1 2 PANEL ASSY SIDE 3721AP3446A 3721AP3446A 3721AP3446A 1 3 PANEL ASSY SIDE 3721AP3446B 3721AP3446B 3721AP3446C 1 4 PANEL ASSY SIDE 3721AP3465E 3721AP3465A 3721AP3465C 1 5 PANEL ASSY SIDE 3721AP3465F 3721AP3465B 3721AP3465D 1 6 PANEL ASSY REAR-L 3720AP2221A 3720AP2221A 3720AP2221A 1 7 PANEL ASSY, SIDE 3721AP3466A 3721AP3466A 3721AP3466A 1 8 PANEL ASSY, SIDE 3721AP3466B 3721AP3466B 3721AP3466B 1
9 PANEL ASSY, REAR 3721AP3447A 3721AP3447A 3721AP3447C 1 10 COVER ASSY, TOP(INDOOR)" 3551AP2388A 3551AP2388B 3551AP2388B 1 11 DRAIN PAN ASS'Y 3087AP2281A 3087AP2281A 3087AP2281A 1 12 BRACKET 4810AP3333P 4810AP3333P 4810AP3333P 1 13 BRACKET 4810AP2296B 4810AP2296B 4810AP2296B 1 14 BRACKET 4810AP2298A 4810AP2298A 4810AP2298A 1 15 EVAPORATOR ASSY 5420AP2380A 5420AP2380A 5420AP2380A 1
15-1 EVAPORATOR ASSY, FINAL 5421AP2980A 5421AP2980B 5421AP2980B 1
16 TUBE ASSY 5211AP2678A 5211AP2678A 5211AP2678A 1 17 TUBE ASSY 5211AP3959B 5211AP3959B 5211AP3959B 1 18 TUBE CAPILLARY 5424AP3074G 5424AP3074G 5424AP3074G 15 19 EVA. BRACKET TOP 5420AP3302A 4811A30016A 4811A30016A 1 20 DOOR ASSY 3A02221A 3A02221A 3A02221A 1 21 MOTOR ASSY, AC 4681AP2411G 4681AP2411G 4681AP2411G 1 22 MOUNT ASSY, MOTOR 3G00788U 3G00788U 3G00788U 1 23 GRILLE ASSY INLET 5237AP2386A 5237AP2386A 5237AP2386A 1 24 GRILLE ASSY INLET 3530AP1109A 3530AP1109A 3530AP1109A 2 25 "FILTER ASSY, A/C" 5231AP3330A 5231AP3330A 5231AP3330A 1 26 BRACKET 5236AP3294A 5236AP3294A 5236AP3294A 1 27 GUIDE FILTER 4974AP2225A 4974AP2225A 4974AP2225A 1
27-1 GUIDE FILTER 4974AP2225B 4974AP2225B 4974AP2225B 1
28 BRACKET 4810AP3298A 4810AP3298A 4810AP3298A 2 29 BRACKET 4810AP4051A 4810AP4051A 4810AP4051A 1 30 BOARD CONTROL(INDOOR) 3500AP2293A 3500AP2293A 3500AP2293A 1 31 PWB(PCB)ASSY, MAIN 6871A20040U 6871A20040R 6871A20040R 1
31-1 PWB(PCB) ASSY, SUB 6871AQ2242A 6871AQ2242A 6871AQ2242A 1
32 CONTROL BOX(INDOOR) 4994AP2291A 4994AP2291A 4994AP2291A 1 33 HOUSING ASS'Y(MECH) 3661AP1139A 3661AP1139A 3661AP1139A 1 34 HOUSING ASS'Y(MECH) 3661AP1139B 3661AP1139B 3661AP1139B 1 35 FAN ASSY, BLOWER 2A00578R 2A00578R 2A00578R 2 36 CUT OFF 4A00085A 4A00085A 4A00085A 2 37 PANEL ASSY FRONT 3720AP1136P 3720AP1136P 3720AP1136P 1 38 HOLDER ASSY DISPLAY 4930AP1133C 4930AP1133C 4930AP1133C 1 39 DISPLAY ASSY(MECH) 3545A20004D 3545A20004M 3545A20004L 1 40 PWB(PCB) ASSY, DISPLAY 6871AQ3143Q 6871AQ3143R 6871AQ3143R 1 41 HOLDER, DISPLAY 3070AP2292K 3070AP2292K 3070AP2292K 1 42 WINDOW DISPLAY 3790AP3936Q 3790AP3936Q 3790AP7356C 1
No. DESCRIPTION Q’TY REMARK
PART No.
LP-F8081CL LP-F8081HL LP-F8081ZL
Page 56
–58–
43 KNOB 4940AP3422C 4940AP3422C 4940AP3422C 1
43-1 KNOB 4940AP3166E 4940AP3166E 4940AP3166E 1 43-2 KNOB 4940AP3326E 4940AP3326E 4940AP3326E 1
4940A30006A 4940A30006A 4940A30006A 1
44 KNOB
4940A30006B 4940A30006B 4940A30006B 1 4940A30006C 4940A30006C 4940A30006C 1 4940A30006D 4940A30006D 4940A30006D 1
45 GRILLE ASSY, DIFFUSER 3023AP2387B 3023AP2387B 3023AP2387B 1
45-1 GRILLE 4A01317Z 4A01317Z 4A01317Z 5 45-2 LOUVER, VERTICAL 3A00752Y 3A00752Y 3A00752Y 12 45-3 DECORATION 3508AP3328A 3508AP3328C 3508AP3328C 2
46 BARRIER ASSY 4791AP2300A 4791AP2300B 4791AP2300B 1 47 BARRIER INDOOR 4790AP3217A/B 4790AP3217A/B 4790AP3217A/B 1 48 CAPACITOR 2A00986S 2A00986S 2A00986S 1 49 CLAMP, CAPACITOR 4H00930D 4H00930D 4H00930D 1 50 ELECTRIC HEATER - - 5301A10001A 1
No. DESCRIPTION Q’TY REMARK
PART No.
LP-F8081CL LP-F8081HL LP-F8081ZL
Page 57
–59–
Outdoor Unit
Exploded View
4-1
4-2
4-4
4-3
12-8
Page 58
–60–
1 BASE ASSY 3041AP2606Q 1
2 COMPRESSOR 5417AP2982A 1
4-1 5403AP2618H 1 4-2
CONDENSER ASSY
5403AP2618H 1 4-3 5403AP2618H 1 4-4 5403AP2618H 1
5 LINK SHEET 4520AP4095A 2 6 BRACKET COND 4810A30028A 2 7 TUBE ASSY, (MANIFOLD IN) 5211A30050A 1 8 TUBE ASSY, (MANIFOLD IN) 5211A30050B 1
9 TUBE ASSY, (MANIFOLD OUT) 5211AP3868A 1 10 TUBE ASSY, (MANIFOLD OUT) 5211AP3868B 1 11 MESH(COVER FIN) 2A00191R 2 12 CONTROL BOX ASSY 4995AP2854D 1
12-1 CASE CONTROL 3110AP2592A 1 12-2 BOARD CONTROL 3500AP2591A 1 12-3 MAGNATIC CONTACTOR 2A01031C 1 12-4 PROTECTION RELAY 2A00999C 1 12-5 TERMINAL BLOCK 3A00493A 1 12-6 SH-CAPACITOR 2H00841J 2 12-8 TERMINAL BLOCK 4G00103A 1
13 REBBER MOUNTING 4022AP9183A 4 14 BRACKET 4H01811C 4 15 BUSHING 4830AP4182A 1 16 SUPPORT VALVE 4980AP2621A 1 17 VALVE SERVICE 2A00469C 1 18 VALVE SERVICE 2A00468B 1 19 COVER TUBING 3550AP2844P 1 20 SUPPORTER REAR 4980AP1265Q 1 21 SUPPORTER REAR 4980AP1265P 1 22 SUPPORTER FRONT 4980AP1264P 1 23 SUPPORTER FRONT 4980AP1263P 1 24 ORIFICE ASSY 4948AP1242P 1 25 MOUNT MOTOR ASSY 3A00434A 2 26 MOTOR 4680AP2610B 2 27 BUSHING BASE COMP 4A00077A 11 28 NUT 4H00947C 12 29 FAN ASSY 0A00026B 2 30 FAN LOCKER 4A01387A 2 31 SPRING LOCK WASHER 1WSD1000030 2 32 HEXAGON NUTS 1NHA1001206 2 33 GRILLE COVER 2A00144P 2
34-1 PANEL ASSY FRONT 3721AP2913P 1 34-2 PANEL ASSY FRONT 3721AP2913Q 1
35 COVER ASSY CONTROL 3551AP7047Z 1 36 PANEL INSTALL-U 3720AP3810P 1 37 BRACKET INSTALL-L 3720AP3814P 1 39 BRACKET F.P 4810AP7078A 1 40 COVER FAN 3550AP3912A 1 41 HUB FAN 3250AP3964A 2 43 HIGH PRESSURE SWITCH 6600AG3057A 1 44 TUBE ASSY,DISCHARGE 5211A30104A 1 45 TUBE ASSY,CONDENSER 5211A30105A 1
No. DESCRIPTION Q’TY REMARK
PART No.
LP-F8081CL
Page 59
–61–
Outdoor Unit
Exploded View
14
7
8
4
4-6
4-4
4-7
4-9
4-9
4-8
4-3
3
2
28
27
20
20-2
52
51
16
15
37
25
26
33
35
36
44
39
1
9
22
5
29
31
30
43
40
41
42
34
49
32
45
47
48
46
15
38
4-2
4-5
4-1
6
19
21-1
131118
17
10
12
Page 60
–62–
1 BASE ASSY 3041AP2606V 1
2 COMPRESSOR 5417AP2982A 1
3 ACCUMULATOR 3A02139U 1
4 CONTROL BOX ASSY 4995A20002B 1
4-1 CASE CONTROL 3110AP2592A 1 4-2 BOARD CONTROL 3500AP2591A 1 4-3 TERMINAL BLOCK 3A00493A 1 4-4 TERMINAL BLOCK 4G00103A 1 4-5 MAGNATIC CONTACTOR 2A01031C 1 4-6 SH-CAPACITOR 2H00841J 2 4-7 RELAY 3A00261C 1 4-8 TERMINAL BLOCK 3H00390A 1 4-9 DEICER PCB ASSY 6871A20015T 1
4-10 3 PHASE DETECTOR 6871A30015D 1
5 CONDENSER ASSY 5403A20030E 1
6 CONDENSER ASSY 5403A20030F 1
7 CONDENSER ASSY 5403A20030G 1
8 CONDENSER ASSY 5403A20030H 1
9 LINK SHEET 4520AP4095A 2 10 BRACKET COND 4810AP3697A 2 11 TUBE ASSY, (MANIFOLD IN) 5211A30269A 1 12 TUBE ASSY, (MANIFOLD IN) 5211A30269B 1 13 TUBE ASSY, (MANIFOLD OUT) 5211A30270C 1 14 TUBE ASSY, (MANIFOLD OUT) 5211A30270D 1 15 TUBE ASSY REVER SING 5211A20078B 1 16 COIL ASYS REVERSING 3A02028B 1 17 TUBE ASSY CHECK VALVE 5211A30271A 1 18 TUBE ASSY CHECK VALVE 5211A30271B 1 19 TUBE ASSY CAPILLIARY 5211A20129B 2 20 CORE VALVE 3A01902A 1
21-1 HIGH PRESSURE SWITCH 6600AG3057A 1 21-2 HIGH PRESSURE SWITCH 3A01100A 1
22 MESH 2A00191Q 1 25 SUPPORT VALVE 4980AP2621A 1 26 BRACKET FRONT 4810AP7078A 1 27 VALVE SERVICE 2A00469H 1 28 VALVE SERVICE 2A00468E 1 29 COVER TUBING 3550A20003P 1 30 SUPPORTER REAR 4980AP1265Q 1 31 SUPPORTER REAR 4980AP1265P 1 32 SUPPORTER FRONT 4980AP1264P 1 33 SUPPORTER FRONT 4980AP1263P 1 34 ORIFICE ASSY 4948AP1242P 1 35 MOUNT MOTOR ASSY 3A00434A 2 36 MOTOR 4680AP2610B 2 37 BUSHING BASE COMP 4A00077A 8 38 NUT 4H00947C 8 39 FAN ASSY 0A00026B 2
No. DESCRIPTION Q’TY REMARK
PART No.
LP-F8081HL/ZL
Page 61
–63–
40 FAN LOCKER 4A01387A 2 41 SPRING LOCK WASHER 1WSD1000030 2 42 HEXAGON NUTS 1NHA1001206 2 43 GRILLE COVER 2A00144P 2 44 PANEL ASSY FRONT 3721AP2913P 1 45 PANEL ASSY FRONT 3721AP2913Q 1 46 COVER ASSY CONTROL 3551AP7047Z 1 47 PANEL INSTALL-U 3720AP3810P 1 48 BRACKET INSTALL-L 3720AP3814P 1 49 COVER FAN 3550AP3912A 1 51 TUBE ASSY,CONDENSER 5211A30219A 1 52 TUBE ASSY,CONNECTOR 5211A30272A 1
No. DESCRIPTION Q’TY REMARK
PART No.
LP-F8081HL/ZL
Page 62
P/No.: 3828A30074P
February, 2000
Printed in Korea
Loading...