Lg Lmu366hv Owner's Manual

Multi Air Conditioner
SVC MANUAL(Exploded View)
Model : A4UW363FA1(LMU366HV)
CAUTION
Before Servicing the unit, read the safety precautions in Standard SVC manual. Only for authorized service personnel.
Internal Use Only
http://biz.lgservice.com
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
1. Specification
Note :
1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 26.7°C(80°F) DB/19.4°C(67°F) WB
- Outdoor Temperature 35°C(95°F) DB/23.9°C(75°F) WB
Heating: - Indoor Temperature 21.1°C(70°F) DB/15.6°C(60°F) WB
- Outdoor Temperature 8.3°C(47°F) DB/6.1°C(43°F) WB
Piping Length - Interconnecting Piping Length 7.5m(24.6 ft.)
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
4. At least two indoor units should be connected.
5. For more Capacity(*),refer to the combination table
Conversion Formula kW = Btu/h class X 0.0002931 cfm = CMM x 35.3
Capacity(*) Btu/h Class Power Input Cooling kW (Min._Rated~ Max.) Heating kW Running Current (Rated) Cooling A
Heating A Starting Current Cooling/Heating A Power Supply Ø / V / Hz Power Supply Cable (Outdoor) No.x AWG Transmission Cable (Outdoor to Indoor unit ) No.x AWG Dimensions W x H x D mm(inch) Net Weight kg(lbs) Max. Number of Connectable Indoor Units
Type
Qty x Model Compressor Motor type
Oil charge volume cc
Oil Type
Cycle A Charge (at 7.5m) g(oz) Refrigerant Cycle B Charge (at 7.5m) g(oz)
Type
Control Heat Exchanger (Rows x Column x FPI) x No.
Coil tube dia. mm(inch)
Defrosting Method
Capacitor μ/Vac Fan motor Drive
Discharge Direction(Side/Top)
Air Flow Rate x No. of Fan CMM(CFM) Sound Level(H/L) Sound Pressure dB(A)+3
Liquid(Cycle A) mm(inch) Piping Connections Gas(Cycle A) mm(inch)
Liquid(Cycle B) mm(inch)
Gas(Cycle B) mm(inch) Piping length spec. Max. total piping m(ft.)
Max. OD~ID piping m(ft.)
Piping Length (no add'l refrigerant) m(ft.) Max. Elevation Outdoor Unit~Indoor Unit m(ft.) Difference Indoor Unit~Indoor Unit m(ft.) Operation Range Cooling ˚C(˚F) (Outdoor) Heating ˚C(˚F)
36,000
0.72~3.75~ 3.92
0.72~3.70~4.10
3.0~17.4~18.2
4.5~17.2~18.8
-
1/208~230/60
3 x 12
4 x 18 (Including Earth)
870x808x320(34 1/4x31 13/16x12 9/16)
65(143.3)
4
Twin-Rotary
5KD240X
BLDC
900
FV50S
2,550(89.95)
-
R410A
EEV
(2Rx36Cx18) x1
7(0.276)
Reversing cycle
-
Direct (DC)
Side
60(2,118)
52
6.35(1/4) x 4EA
9.52(3/8) x 4EA
-
-
75(246.1)
25(82.0)
37.5(123.0) 15(49.2)
7.5(24.6)
-10 ~ 46 (14 ~114.8)
-15 ~ 24 (5~75.2)
A4UW363FA1(LMU366HV)
Outdoor Unit
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
2. List of Functions
Note :
O : Applied, X : Not applied, – : No relation Option: Model name & price are different according to options, and assembled in factory with main unit. Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Defrost / Deicing High Pressure Switch Low Pressure Switch Phase protection Restart Delay (3-minutes) Self Diagnosis Soft Start Test Function Auto operation(Artificial intelligence) Auto Restart Operation Central control(LGAP) PDI(Power Distribution Indicator) PI485 Low ambient operation Thermistor
O X X X O O O X O O
O PQNUD1S00 PMNFP14A0
O
-
FunctionCategory
A4UW363FA1(LMU366HV)
Reliability
Convenience
Others
Special function kit
CAC Network Function