LG LM360HE Schematic

Page 1
LG
Multi Type Air Conditioner
SERVICE MANUAL
LG
CAUTION
website http://www.lgservice.com e-mail http://www.lgeservice.com/techsup.html
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
• ONLY FOR AUTHORIZED SERVICE PERSONNEL.
MODEL: L3-C363LA0
L3-C363MA0 L3-C363NA0 L3-H363LA0 L3-H363MA0 L3-H363NA0
Page 2
2 MPS Multi Air Conditioner
Multi Air Conditioner Service Manual
TABLE OF CONTENTS
Safety Precautions......................................................................................................................................3
About MPS...............................................................................................................................
....................7
Product Specifications
...............................................................................................................................
.......8
Dimensions
...............................................................................................................................
.........................10
Refrigeration Cycle Diagram.............................................................................................................................12
Wiring Diagram...................................................................................................................................................13
Electronic Control Device..................................................................................................................................14
Schematic Diagram ...........................................................................................................................................17
Functions ............................................................................................................................................................20
Operation Details................................................................................................................................................23
2-way, 3-way Valve..............................................................................................................................................30
Cycle Troubleshooting Guide............................................................................................................................34
Electronic Parts Troubleshooting Guide..........................................................................................................42
Operation ............................................................................................................................................................56
Disassembly of the parts (Indoor unit).............................................................................................................58
Exploded View and Replacement Parts List....................................................................................................60
Page 3
Service Manual 3
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbol used in this manual are as shown below.
WARNING
CAUTION
This symbol indicates the possibility of death or serious injury. This symbol indicates the possibility of injury or damage.
WARNING
Installation
Be sure not to do.
Be sure to follow the instruction.
Do not use a defective or underrated circuit breaker. Use this appliance on a dedi­cated circuit.
• There is risk of fire or electric shock.
Do not let the air conditioner runforalongtimewhenthe humidity is very high and a door or a window is left open.
• Moisture may condense and wet or damage furniture.
Always ground the product.
• There is risk of fire or electric shock.
Install the panel and the cover of control box securely.
•Thereisriskoffireorelectricshock.
Always install a dedicated cir­cuit and breaker.
• Improper wiring or installation may cause fire or electric shock
Use the correctly rated break­er or fuse.
• There is risk of fire or electric shock.
Page 4
4 MPS Multi Air Conditioner
Safety Precautions
Operational
Do not modify or extend the power cable.
• There is risk of fire or electric shock.
Do not install, remove, or re­install the unit by yourself (customer).
• There is risk of fire, electric shock, explosion, or injury.
Be cautious when unpacking and installing the product.
• Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator.
For installation, always con­tact the dealer or an Authorized Service Center.
• There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
• It may cause injury, accident, or dam­age to the product.
Be sure the installation area does not deteriorate with age.
• If the base collapses, the air condition­er could fall with it, causing property damage, product failure, and personal injury.
Do not touch(operate) the product with wet hands.
• There is risk of fire or electrical shock.
Donotplaceaheaterorother appliances near the power cable.
• There is risk of fire and electric shock.
Do not allow water to run into electric parts.
• It may cause There is risk of fire, fail­ure of the product, or electric shock.
Page 5
Service Manual 5
Safety Precautions
Do not open the inlet grille of the product dur­ing operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
• There is risk of physical injury, electric shock, or product fail­ure.
Be cautious that water could not enter the product.
• There is risk of fire, electric shock, or product damage.
Do not store or use flammable gas or com­bustibles near the product.
• There is risk of fire or failure of product.
If strange sounds, or smell or smoke comes from product. Turn the breaker off or discon­nect the power supply cable.
• There is risk of electric shock or fire.
Gasolin
Page 6
6 MPS Multi Air Conditioner
Operational
Safety Precautions
Use two or more people to lift and transport the product.
• Avoid personal injury.
Useasoftclothtoclean.Do not use harsh detergents, sol­vents, etc.
• There is risk of fire, electric shock, or damage to the plastic parts of the prod­uct.
Do not touch the metal parts of the product when removing the air filter. They are very sharp!
• There is risk of personal injury.
Do not step on or put anyting on the product. (outdoor units)
• There is risk of personal injury and failure of product.
Do not insert hands or other objects through the air inlet or outlet while the product is oper­ated.
• There are sharp and moving parts that could cause personal injury.
CAUTION
Installation
check for gas (refrigerant) leakage after installation or repair of product.
• Low refrigerant levels may cause fail­ure of product.
Install the drain hose to ensure that water is drained away properly.
• A bad connection may cause water leakage.
Keep level even when installing the product.
• To avoid vibration or water leakage.
90˚
Thinner
Wax
Page 7
About MPS
About MPS
Conventional (On/Off Operation)
• During a Conventional Air Conditioning Cycle, the Compressor must turn on and off to reach desired Temperature setting.
• A large portion of power is used during Restart. This causes unnecessary power consumption.
27 25 23 21 19
0
0:05 0:10 0:15 0:20
Operation time (min)
Indoor Temp (°C)
ON OFF ON OFF
MPS
• MPS(Multi Power System) is a power saving system With Two rotary compressors of different capacity (60% & 40%) Operating an A/C at high power until it reaches desired temperature.
• And when it reaches the temperature, only the 40% Capacity rotary compressor operates.
27 25 23 21 19
0
0:05
100% operation 40% operation
0:10 0:15 0:20
Operation time (min)
Indoor Temp (°C)
Service Manual 7
MPS (Multi Power System)
Page 8
8 MPS Multi Air Conditioner
Product Specifications
Product Specifications
1. L3-C363LA0, L3-C363MA0, L3-C363NA0
34,200/36,000 22,800/24,000 11,400/12,000 208/230V
----
3.6 2.4 1.2 at 230V 1Ø, 208/230V, 60Hz
Indoor ––8
Outdoor 63
Indoor ––40/38/36
at 230V
Outdoor 54
4,020/4,020 2,530/2,530 1,340/1,340
––
17.9/17.9 11.6/11.6 5.9/5.9 208/230V
––
8.5/8.9 9.0/9.5 8.5/8.9
––
Indoor 888x287x170
Outdoor 870 x 1060 x 320
Indoor 9
Outdoor 78
Liquid 6.35(1/4)
Gas 12.7(1/2)
2,500 ––at 7.5m
O
L.C.D Wireless
O O
Operation
2-Unit On 1-Unit On
3-Unit On
Remarks
Unit
Item
Cooling Capacity Heating Capacity Moisture Removal /h Power Source ø,V,Hz
Air Circulation /min
Noise Level dB(A)
Input W
A
E.E.R. Btu/h.w C.O.P. -
Dimensions(WxHxD)
mm
Net. Weight kg
Service Valve mm(Inch)
Refrigerant(R-22) g Airflow Direction Control(Up & Down) Remote Controller Type Sleeping Operation Drain Hose
Cooling Heating Cooling Heating
Cooling
Heating
Runnig
Current
Btu/h(kcal/h)
( Hi / Med / Low )
Page 9
2. L3-H363LA0, L3-H363MA0, L3-H363NA0
Product Specifications
Operation
Item
Cooling Capacity
Heating Capacity
Moisture Removal ℓ/h
Power Source ø, V, Hz
Air Circulation m
Noise Level dB(A) ( Hi / Med / Low )
Input W
Runnig
Current
E.E.R. Btu/h.w
C.O.P. -
Cooling
Heating
Cooling
Heating
Cooling
Heating
Unit
Btu/h(kcal/h)
3
/min
A
3-Unit On
34,600/36,000 23,040/24,000 11,500/12,000 208/230V
––
3.6 2.4 1.2 at 230V
1Ø, 208/230V, 60Hz
Indoor 8
Outdoor 63
Indoor 40/38/36
Outdoor 54
3,920/3,920 2,660/2,660 1,500/1,500
––
17.5/17.5 12.2/12.2 6.7/6.7
––
8.8/9.2 8.7/9.0 7.7/8
––
2-Unit On 1-Unit On
Remarks
at 230V
208/230V
Dimensions(W x H x D)
Net. Weight kg
Service Valve mm(Inch)
Refrigerant(R-22) g
Airflow Direction Control(Up & Down)
Remote Controller Type
Sleeping Operation
Drain Hose
mm
Indoor 888 x 287 x 170
Outdoor 870 x 1060 x 320
Indoor 9
Outdoor 78
Liquid 6.35(1/4)
Gas 12.7(1/2)
2,500 780 780 at 7.5m
O
L.C.D Wireless
O
O
Service Manual 9
Page 10
10 MPS Multi Air Conditioner
Dimensions
1. Indoor Unit
Dimensions
Installation plate
A
A
ø70mm
Center
Center
ø70mm
Left rear piping Right rear piping
A
A
D
H
W
Tubing hole cover
W mm 888
H mm 287 D mm 170
L3-C363LA0, L3-C363MA0, L3-C363NA0 L3-H363LA0, L3-H363MA0, L3-H363NA0
MODEL
DIM
Page 11
Service Manual 11
Dimensions
2. Outdoor Unit
L6L7 L8
L9
L4
H
L5
W
D
L1
L3
L2
L10 L11L11 L11L11L11
Gas side 3-way valve
Liquid side 2-way valve
L3-C363LA0, L3-C363MA0, L3-C363NA0 L3-H363LA0, L3-H363MA0, L3-H363NA0
MODEL
DIM
W mm 870
H mm 1038
D mm 320 L1 mm 360 L2 mm 340 L3 mm 25 L4 mm 1035 L5 mm 25 L6 mm 546 L7 mm 160 L8 mm 160 L9 mm 44
L10 mm 64.5 L11 mm 50
Page 12
Indoor Side Outdoor Side
B
A
4- WAY Valve
COMP B
COMP A
Accum.
C
Indoor Side Outdoor Side
B
A
COMP B
COMP A
Accum.
C
ex)
Solenoid Valve L.E.V 3-Way Valve
2-Way Valve
Capillary
12 MPS Multi Air Conditioner
Refrigeration Cycle Diagram
Refrigeration Cycle Diagram
1. L3UH363LA0, L3UH363MA0, L3UH363NA0
2.
L3UC363LA0, L3UC363MA0, L3UC363NA0
Page 13
Wiring Diagram
MOTOR
PILLAR TERMINAL
STEP
MOTOR
MAIN PCB ASSY
FORCED OPERATION AUTO RESTART
REMOTE CONTROL
THERMISTOR (OUT PIPE)
THERMISTOR (IN PIPE/AIR)
3854A24002C
CN-MOTOR
CN-DISP1
DISPLAY PCB ASSY
INDOOR WIRING DIAGRAM
TO OUTDOOR UNIT
C
RD BK BR BL
GV S
CN-POWER
CN-U/D
CN-TH1
CN-TH2
SW01F
Indoor Unit
L3-C363LA0, L3-C363MA0, L3-C363NA0 L3-H363LA0, L3-H363MA0, L3-H363NA0
Wiring Diagram
Outdoor Unit
L3-C363LA0, L3-C363MA0, L3-C363NA0
L3-H363LA0, L3-H363MA0, L3-H363NA0
Service Manual 13
Page 14
14 MPS Multi Air Conditioner
Electronic Control Device
Electronic Control Device
Indoor Unit
• MAIN P.C.B DC ASM
Page 15
Service Manual 15
Electronic Control Device
Outdoor Unit
ASM P/N : 6871A20479A
PCB P/N : 6870A90186A
CN_OOO
C51M
R22M
D05M
ZD03M
TRANS6
2003.11.10
CN_POWER2
-
~
R36M
+
~
R11M
BD01M
NTC
SMPS
C12M
C10D
1
3
6
5
R34M
C28M
C30M
C19M
C07M
Q06M
C22M
R35M
Q09M
R24M
ZD02M
D06M
R37M
C32M
C33M
R25M
ZD01M
R23M
R12M
R10M
Q03M
D04M
C23M
C10M
R13M
D02M
TRANS5
L10M
TRANS3
TRANS4
L011M
L12M
13
12
L09M
C29M
978
C17M
TRANS2
TRANS1
L02M
L08M
L07M
L06M
L05M
C18M
D03M
R09M
L01M
C06M
D01M
IC01A
C08D
R02D
C04D
C01D
L01D
Q08M
D01D
C31M
C25M
L02D
R33M
IC04D
C02D
C03D
C07D
C05D
R30M
R31M
Q07M
CN_LEV(C)
C52M
L01H
C02A
RY_FAN(L)
IC01K
C26M
R32M
C27M
R28M
Q05M
IC05M
C14M
C21M
R20M
C16M
C15M
R21M
R16M
IC04M
IC03M
C02M
R29M
R27M
R26M
R19M
C24M
CN_COM3
C13M
R18M
R14M
R17M
R15M
CN_COM1
Q04M
CN_COM2
RY_4WAY
R08M
Q02M
R04M
R03M
C09M
C05M
R07M
C04M
R06M
RY_LIQ
R02M
C03M
RY_GAS
R01M
Q01M
C01M
IC03K
L4(D)
L3(C)
L2(B)
L1(A)
IC02K
Q01Z
OSC01B
CN_RY_FAN
CN_POWER1
RY_FAN(H)
R05M
3
RY_COMP(B)
C11M
L03M
L04M
NF03M
CN_RY_SV
NF05M
NF04M
NF02M
NF01M
SW01F
CN_LEV(B)
CN_LEV(A)
C50M
LED01T
CN_TH1
CN_JIG
CN_TH2
RY_COMP(A)
4
4
PCB P/N : 6870A90195A ASM P/N : 6871A20500
C04J
R01J
NF01J
C07J
C05J
C06J
NF02J
C09J
C03J
C01J
GND1
D01J
C02J
CN_TAB1(N)
ZNR01J
CN_POWER2
C08J
GND2
FUSE(250V/T5A)
CN_TAB2(L)
CN_POWER1
• MAIN P.C.B DC ASM
Page 16
16 MPS Multi Air Conditioner
Electronic Control Device
Display P.C.B ASM
Page 17
Service Manual 17
Schematic Diagram
Schematic Diagram
Indoor Unit
PKM13EPP-4002
OSC01B
3.6V
CST-8.00MTW
R21H~R25H
50V
8
R11H~R14H
R02F
12.1K
C06D
103
AUTO RESTART
REMOTE CONTROL
FORCED OPERATION
SWITCH
LIMIT
CN-SW
COM
NO
NC
123
123
Option
1
423
SW01F
5V
5V
6.2K
R06F
R04F
6.2K
470uF
25V
C05D +
DC5V
7805
1N4148
D99
IC02D
O
I
470uF
25V
C03D
104
50V
C04D
+
DC12V
7812
IC01D
O
I
CDS
Q
ST93C46CB6
R13H
R12H
20K
R11H
OJ2HOJ1H OJ3H
R14H
5
93C46B
EEPROM
Vss
7
6
DU
ORG
Vcc
OJ4H
4
3
2
1
2
10K
+
50V
C02D
104
680uF
25V
C01D
10K
R97
KA393
IC9-1
-
4
OR2HOR5H
DC 5V
R96
20K
OR3H~0R5H
OR4H OR3H
DC12V
3
1
+
8
10K
OR1H
56K
R95
10K
R21H
R24H
R25H
5V
12.1K
1%
55
Operation
RECEIVER
Vcc
GND
Vout
Sleep
CMP
Timer
11
220
10V
C02L
LED2
LED1
LED4
LED3
44
526
5
6
2
CN-DISP
7
3
3
7
RDPKOR
YL
22
11
4
3
4
3
receiver
R01G~R04G
220
STEPPING MOTOR
(UP/DOWN)
BL
CN-U/D
4
104
C02D
5V
11
10
7
6
5V
45
48
35
46 47
13
14
33 34
2
64
63
37
32
57
56
1
KID65004AF
IC01G
KID65004AF
14
12
13
3
5
4
9
15
16
8
1
2
HVB OUT
IC01M
9
7
8
4
6
5
18
55
54
50
51
52
53
17
16
19
20
21 61 62
10
7
R01B,1M
R01T~R05T
8
5V
12
3
11
9 10
6 7
40
5
43
42
29
41
31
30
44
38
220
0.01
R22H
R23H
25V
10V
R02A,20K
C01A
5V
C02A
2
1
3
KID65004AF
59
24
22
23
15 60
25
26
36
28
27
39 49 58
15
2
12
5
11
6
13
4
14
3
5V
16
1
9
8
IC02M
R02L,1K
C01L 680pF
R81 1K
R02B,10K
50V
C81
103
5V
receiver
R02E,20
R01E
5.1K
R01L
1K
BZ01E
PK
3
2
1
2
2
STEPPING MOTOR
(LEFT/RIGHT)
BL
3
3
4
4
5
5
1
1
CN-L/R
OR YL
RD
Option
PIPE-TH
2
3
4
DC12V
CN-MOTOR
4
4
INDOOR
FAN
MOTOR
3
3
2
2
1
1
DC 5V
+
11
CN-DC/DC
104,50V
C07D
RXE250
POLY SW
~
100uF
63V
C92
4 4
5 5
2
3
2
3
1/4W
750
R99
11
11
4
2
3
HVB OUT
+
7
KSC7536
IC01A
KIA7036P
5V
C91
103
1%
6.2K
R04H
KA393
IC9-2
R90 1K
R93 10K
-
5
DC 5V
R92 10K
R91
4.7K
6
1%
CN-TH1
1%
5V
12.1K
R02H
2433
4
2
11
CN-TH2
5V
6.2k
R26H
3
22
3
PIPE-TH
ROOM-TH
12V
1
2
1
2
CN-HVB
Option
33
HVB OUT
Page 18
18 MPS Multi Air Conditioner
Schematic Diagram
Outdoor Unit
P07
SW01F
OR2H,OR7H,OR10H:91K,OR3H-4H,OR8H-9H,OR11H-12H:15K(ETC:20K)
R03T
11
DC 5V
56K
R04T
1K
1
2
7036P
IC01A
CN-JIG
3
4
3
4
22
JIG_RX
JIG_TX
DC 5V
10K
R01T
1K
R02T
C01H-C04H : 103
P21
21
JIG_RX
26
OSC01B
CST-8.00MGW
JIG_TX
+
3
C02A
10
R03A,100
50V
25V
0.01
C01A
R02A,4.7K
R01A,1K
Xin
Vss
Xout
R01B,1M
25
24
P22
RESET
23
22
P20
19
R01F,1K
R02F,10K
R02G,10K
R01G,10K
R04G,10K
R03G,10K
P32
29
30
P33
28
27
P31
P30
L4(C)
L3(C)
L1(A)
L2(B)
PWM(A)
PWM(C)
PWM(B)
P53
P54
46
47
P52
45
51
P60
50
P62
P63
P61
52
53
31
P37
343536
P41
P40
33
32
P36
P35
RX(C)
RX(B)
TX(C)
RX(A)
TX(B)
14
13
P13
P12
P34
111012
P10
P11
TX(A)
CN-LEV(C)
CN-LEV(B)
DC 5V
+
C52M
220
50V
231
231
5
4
5
4
IC03M
44
220
50V
+
C51M
1 132
3
2
50V
55
1
+
220
C50M
1
22
11
OUT_PIPE
OUT_TH
22
33
44
CN-TH2
SUCTION
33
44
DC 5V
R05H-R20H
(ETC: 12.1K 1%)
(R05H,R06H,R07H:6.2K 1%)
DISCHARGE
CN-TH1
11
41
R01H,1K
60
P71
P66
P65
P64
555654
P70
P67
59
57
63
P73
P72
R04H,1K
62
61
P76
P74
P75
R02H,1K
R03H,1K
1
64
7 8 9
P05
P06
5
6
P02
P04
P03
P51
44 4 3
P00
P01
42
43
P47
P50
MICOM
TMP87CM41F
58
TEST
P77
20
2
VSS
AVDD
49
48
VDD
Q01Z
KRA107M
39
40
P44
P46
P45
38
37
P42
P43
DC 5V
CN-LEV(A)
IC02M
423
423
5 5
RY-COMP(A)
RY-FAN(H)
RY-COMP(B)
IC01M
R01Z-R07Z : 4.7K
RY-LIQ
RY-FAN(L)
RY-GAS
RY-4WAY
DC 15V
Page 19
Service Manual 19
Schematic Diagram
23.2K
8.06K
8.06K
23.2K
23.2K
8.06K
1%
1%
51.1K
102
100V
C25M
1%
9.1k
R27M
100uf
C24M
+
2
5
4
6
100uF
25V
C26M
R28M
13K
1%
1
5
+
R29M,2K,1%
4
22
51.1K
10K
1
2.94K
6
7
4.7K
PWM(C)
35.7K
4.3K
R26M
10.2K
3
2
1
21.5K
6.04K
KRA101M
Q07M
DC 5V
7
3K 5.23K39.2K 13K
20 20
9
8
R04S
20K
14
51.1K
102
C14M
100V
R15MC13M+1%
100uf 9.1k
2
5
4
6
C15M
25V
100uF
R16M
1
5
+
1%
13K
R17M,2K,1%
4
22 10K
1
51.1K
2.94K
6
7
4.7K
PWM(B)
35.7K
4.3K
10.2K
R14M
2
3
1
21.5K
6.04K
Q04M
KRA101M
DC 5V
7
3K 5.23K39.2K 13K
20
8
20
9
R04S
14
20K
51.1K
102
100V
C02M
R02M
9.1k
1%
100uf
C01M
+
2
5
4
6
100uF
25V
C03M
1
5
R03M
13K
1%
+
R04M,2K,1%
4
22 10K
1
51.1K
6
7
2.94K
PWM(A)
4.7K
35.7K
4.3K
R01M
10.2K
1%
2
3
1
21.5K
6.04K
KRA101M
Q01M
7
DC 5V
3K 5.23K39.2K 13K
R04S
8
20 20
9
14
20K
51.1K
RY-COMP(B)
RY-COMP(A)
51.1K
2SD2220
Q08M
51.1K
R31M
220
3
34K
100K
R33M
1.5K103K
100V
R34MC31M
Vm(C)
MT 15V
94
S/W TRANS6
2
3 7
Q09M
30,1W
R37M
ZD03M
12V
200
R36M
472/250V
C30M
100V
473K
C27M
2
8
10K
R32M
IC06M
63V
680uF
C28M
+
821K
C29M
1KV
L10M
L09M
FMX12S
D05M
Q05M
2SD2220
R19M
51.1K
220
3
34K
R21M
100K
1.5K103K
100V
R22MC21M
Vm(B)
ERB-44-08
D06M
8 4
6
S/W TRANS5
L12M
L11M
11 2
1KV
222K
C33M
3W
68K
R35M
C32M
MT 15V
94
S/W TRANS4
2
3 7
Q06M
R25M
30,1W
12V
200
R24M
ZD02M
u-POWER MODULE
NF02J
C09J~C10J
1uF
C08J
222*2
25V
ZNR01J~ZNR02J
uRM1515-2B
302
D01J
C04J
1M
C06J~C07J
C05J
9mH
472*3
R01J
1mH
NF01J
1uF
1uF
C03J
35V
C10D
102M
561*2
C04D
35V
470UF
12uH
L01D
1000UF
35V
220uF
C05D
10V
220uF
C03D
DC 5V
DC 15V
IC04D
C06D
50V
103
7805
C07D
50V
+
+
103
C02D
470uF
+
2K
R02D
1/2W
MT 15V
C08D
103
50V
L02D
12uH
D101
FB
12
OUT
R202
9
7
+
C01D
GND
PC201
D201
R201
D202
268
C102
BP
TNY
S
D
13
+
C101
R102
OUT
GND
3
NC
DC 0V
6
5
PC201
GND
NC
DC 310V
1
IN
R101
D01D
1N4937
RY-FAN(L)
RY-FAN(H)
RY-GAS
LIVE1
3 3
CN-POWER
NEUTRAL
1
FUSE
ZNR01J
250V/T5A
INR14D471K
SVC561D-14A
1
COMP B
COMP A
43
LIVE2
43
NF01M
HOT GAS
FAN LOW
FAN HI
1
1
NF02M
1
1
1
NF04M
NF03M
1
CN-FAN
COM(A)
COM(B)
COM(C)
DKS-10D-22
1/2W
560K
R11M
51.1K
472/250V
C19M
C16M
100V
473K
8
2
10K
R20M
IC05M
63V
C17M
680uF
+
C18M
821K
1KV
L06M
L05M
FMX12S
D03M
Q02M
2SD2220
51.1K
R06M
220
3
34K
R08M
100K
1.5K103K
100V
R09MC09M
Vm(A)
ERB-44-08
D04M
8 4
6
S/W TRANS3
L08M
L07M
11 2
C23M
1KV
222K
R23M3W68K
C22M
MT 15V
94
S/W TRANS2
3
2
7
Q03M
30,1W
R13M
ZD01M
12V
200
R12M
472/250V
C07M
C04M
473K
100V
8
2
R07M
10K
IC04M
C05M+63V
680uF
C06M
821K
1KV
L02M
L01M
D01M
FMX12S
ERB-44-08
D02M
8 4
6
S/W TRANS1
L03M
L04M
11 2
1KV
C11M
222K
3W
68K
R10M
C10M
+
NTC
450V
330UF
C12M
COM(B)
3
20TX(B)
1K
R14K
102
C03K
TX(C)
RX(C)
RX(B)
RY-LIQ
RY-4WAY
R15K
10K
R12K
10K
R16K
3
2
1
8
4
20
8
4
7
5
6
R10K
1K
C02K
102
2
1
4
IC03K
4
7
5
6
8
COM(C)
DC 15V
Vm(C)
Vm(B)
DC 15V
DC 0V
BD01M
D15XB60
DC 310V
RX(A)
DC 15V
TX(A)
DC 5V
R13K
1K1K
R01K
1K
R09K
10K
R07K
R05K
R11K
10K
C01K
1K
102
8
4
7
5
6
10K
R06K
IC02K
10K
R08K
8
R02K
R04K
10K
R03K
IC01K
2
3
1
8
4
20
COM(A)
Vm(A)
DC 15V
LIQUID
1
NF05M
1
1
1
4WAY
324
324
314
3
1
CN-COM3
4
412
412
CN-COM2
231
CN-COM1
231
Page 20
20 MPS Multi Air Conditioner
Functions
Functions
Room temperature sensor. (THERMISTOR)
Maintains the room temperature in accordance with the Setting Temp.
Indoor fan is delayed for 5 seconds at the starting.
Restarting is inhibited for approx. 3 minutes.
High, Med, Low, Chaos
--- Lights up in operation
--- Lights up in Sleep Mode
--- Lights up in Timer Mode
--- Lights up in Deice Mode(for Heat pump model)
--- Lights up in Compressor operation(for Cooling model)
Intermittent operation of fan at low speed.
The fan is switched to low(Cooling), med(Heating) speed.
The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
The fan is switched to intermittent or irregular operation
The fan speed is automatically switched from high to low speed.
The louver can be set at the desired position or swing up and down automatically.
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Time Delay Safety Control
Indoor Fan Speed Control
Operation indication Lamps (LED)
OUT
DOOR
Health Dehumidification Operation
Both the indoor and outdoor fan stops during deicing.
Hot start after deice ends.
The indoor fan stops until the
evaporator piping temperature will be reached at 28°C.
Sleep Mode Auto Control
Natural Air Control by CHAOS Logic
Airflow Direction Control
Deice (defrost) control (Heating)
Hot-start Control (Heating)
Page 21
Service Manual 21
Functions
Remote Controller
JET COOL
Healthy Dehumidification Operation Mode.
()
Operation Mode Selection
(Cooling
model only)
(Heating
model only)
Cooling Operation Mode.( )
Heating Operation Mode.( )
Auto Operation Mode.( )
Sleep Operation
˚C To ˚F Swtiching Button
Room, Temperature Display
Setting the Time or Timer
Airflow Direction Control
Operation ON/OFF
Temperature Setting
TEMPERATURE
LOWHIGH
Timer Selection
ON OFF
˚C / ˚F
Timer Setting
SET
Timer Cancel
CANCEL
Fan Operation Mode
Reset
Fan Speed Selection
(Low) (Med) (High) (CHAOS)
Down to 18°C(64˚F) Up to 30°C(86˚F)
Cooling
: Cancel Sleep Mode, Timer ON or Timer OFF
: 1, 2, 3, 4, 5, 6, 7, Off Timer
: Fan Operates without cooling or heating.
: High: 39°C(102˚F) LOW : 11°C(52˚F)
Down to 16°C(60˚F) Up to 30°C(86˚F)
Heating
: OFF, ON, OFF ON
Page 22
Display Function
• Cooling, Soft Dry, Fan, Heating
• Cooling, Soft Dry, Fan
• Sleep Mode
• Sleep Mode
• Timer Mode
• Timer Mode
• Hot-start, Defrost
Operation Indicator
Timer Indicator
Sleep Timer Indicator
Defrost Indicator
Operation Indicator
Timer Indicator
Sleep Timer Indicator
Compressor on Indicator
OUT
DOOR
Display Function
1. Heating Model 2. Cooling Model
Self-diagnosis Function
Error Indicator
• The function is to self-diagnosis air conditioner and express the troubles if there is any trouble.
• Error mark is displayed on display window of indoor units and wired-remote controller, and LED of outdoor unit control board.
• If more than two troubles occur simultaneously, lower number of error code is first displayed.
• After error occurs, if error is released, error LED is also released simultaneously.
(Operation LED)
Error code
Inlet pipe sensor02
Communication(Indoor Outdoor)05
Indoor ErrorOutdoor Error
06
Different mode operation07
Contents
1 digit
Open / ShortAir sensor (open/short)01
Open / Short
Communication Poorly
Open / ShortOutlet pipe sensor
Different mode operation
10 digit
(Sleep LED)
Case of error
Operation
Led
1 time
2 time
5 time
6 time
7 time
Indoor Status
Sleep
Indoor
Led
On or stop
off
On or stop
off
off
On or stop
off
off
Fan
Off
Off
Vane
Open
Open
Close
Open
Close
Comp &
On or stop
On or stop
On or stop
Outdoor Status
Fan
Off
Off
LEV
Open
or Close
Open
or Close
Close
Open
or Close
Close
22 MPS Multi Air Conditioner
Open / ShortOutdoor Air sensor44
Open / ShortCond. Pipe sensor45
Total Indoor capacity overCapacity over Error51
4 time
5 time
1 time
4 time
4 time
5 time
Off
Off
Off
Close
Close
Close
Off
Off
Off
Close
Close
Close
Page 23
Service Manual 23
Operation Details
Operation Details
Main Unit Function
1) C/O Model Operation Indicator
On while in appliance operation, off while in appliance pause
Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on)
Sleep Timer Indicator
On while in sleep timer mode, off when sleep timer cancel or appliance operation pause
Timer Indicator
On while in timer mode (on/off), off when timer mode is completed or canceled.
Comp. Running Incidator
While in appliance operation, on while in outdoor unit compressor running, off while in compressor off
2) H/P Model Operation Indicator
On while in appliance operation, off while in appliance pause
Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on)
Sleep Timer Indicator
On while in sleep timer mode, off when sleep timer cancel or appliance operation pause
Timer Indicator
On while in timer mode (on/off), off when timer mode is completed or canceled
Defrost Indicator
Off except when hot start during heating mode operation or while in defrost control
Cooling Mode Operation
When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan stop.
When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp Setting Temp+0.5°C Compressor OFF Temp Setting Temp-0.5°C
While in compressor running, operating with the airflow speed set by the remote control. While in compressor not running, operating with the low airflow speed regardless of the setting.
Healthy Dehumidification Mode
When the dehumidification operation input by the remote control is received, the intake air temperature is detected and the setting temp is automatically set according to the intake air temperature.
26°C Intake Air Temp 25°C 24°C Intake Intake Air Temp<26°C Intake Air Temp-1°C 18°C Intake Intake Air Temp<24°C Intake Air Temp-0.5°C Intake Air Temp<18°C 18°C
Page 24
24 MPS Multi Air Conditioner
Operation Details
While in compressor off, the indoor fan repeats low airflow speed and pause.
While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidifica-
tion operation and 4-min compressor off repeat. Compressor ON Temp. Setting Temp+0.5°C Compressor OFF Temp. Setting Temp-0.5°C
In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
Heating Mode Operation(H/P model)
When the intake air temp reaches +3°…above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on. Compressor ON Temp. Setting Temp. Compressor OFF Temp. Setting Temp.+3°C
While in compressor on, the indoor fan is off when the indoor pipe temp. is below 20
°C, when above 28°C,it
operates with the low or setting airflow speed. When the indoor pipe temp is between 20°C and 28°C, it oper­ates with Super-Low(while in sleep mode, with the medium airflow speed).
While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C, when above 35°C,it operates with the low airflow speed.
If overloaded while in heating mode operation, in order to prevent the compressor from OLP operation, the outdoor fan is turned on/off according to the indoor pipe temp.
While in defrost control, both of the indoor and outdoor fans are turned off.
Defrost Control(H/P model)
Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
The first defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes passed from
starting of heating operation and more than 10 minutes operation of compressor.
Defrost ends after 9/6 minutes passed from starting of defrost operation or after the outdoor fan operates within max. 2 minutes 30 seconds when the outdoor pipe temperature rises over 12°C even it before 12 min­utes.
The second defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes passed from ending of the first defrost and more than 10 minutes operation of compressor.
Heating overload(H/P models)
Outdoor fan ON/OFF by sensing outdoor pipe temperature.
Outdoor fan is OFF if pipe temperature is over 6.5°C and outdoor fan is ON if pipe temperature is below 0°C.
Outdoor fan is off if any one part is heating overload condition.
Page 25
Service Manual 25
Operation Details
Fuzzy Operation (C/O Model)
According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp Setting Temp + 0.5°C Compressor OFF Temp Setting Temp + 0.5°C
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time.
26°C Intake Air Temp 25°C 24°C Intake Air Temp < 26°C Intake Air Temp + 1°C 22°C Intake Air Temp < 24°C Intake Air Temp + 0.5°C 18°C Intake Air Temp < 22°C Intake Air Temp Intake Air Temp<18°C 18°C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
Fuzzy Operation (H/P Model)
When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since the operation off, the operation mode is selected.
When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air temp at that moment as follows.
24°C Inatake Air Temp Fuzzy Operation for Cooling 21°C Inatake Air Temp<24°C Fuzzy Operation for Dehumidification Inatake Air Temp<21°C Fuzzy Operation for Heating
If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10 sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.
1) Fuzzy Operation for Cooling
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp Setting Temp +0.5°C Compressor OFF Temp Setting Temp + 0.5°C
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time.
26°CIntake Air Temp 25°C 24°CIntake Air Temp<26°C Intake Air Temp + 1°C 22°CIntake Air Temp<24°C Intake Air Temp + 0.5°C 18°CIntake Air Temp<22°C Intake Air Temp Intake Air Temp<18°C 18°C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the tem­perature.
Page 26
26 MPS Multi Air Conditioner
Operation Details
2) Fuzzy Operation for Dehumidification
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp ➲ Setting Temp + 0.5°C Compressor OFF Temp ➲ Setting Temp+0.5°C
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time.
26°C Intake Air Temp 25°C 24°C Intake Air Temp<26°C Intake Air Temp+1°C 22°C Intake Air Temp<24°C Intake Air Temp+0.5°C 18°C Intake Air Temp<22°C Intake Air Temp Intake Air Temp<18°C 18°C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in dehumidification operation.
3) Fuzzy Operation for Heating
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C or more above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on.
Compressor ON Temp ➲ Setting Temp Compressor OFF Temp ➲ Setting Temp + 3°C
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time.
20°CIntake Air Temp Intake Air Temp + 0.5°C Intake Air Temp<20°C 20°C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the intake air temperature and the setting temperature.
Airflow Speed Selection
The airflow speed of the indoor fan is set to high, medium, low, or chaos (auto) by the input of the airflow speed selection key on the remote control.
On-Timer Operation
When the set time is reached after the time is input by the remote control, the appliance starts to operate.
The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
If the appliance is operating at the time set by the timer, the operation continues.
Page 27
Service Manual 27
Operation Details
Off-Timer Operation
When the set time is reached after the time is input by the remote control, the appliance stops operating.
The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
If the appliance is on pause at the time set by the timer, the pause continues.
Off-Timer <=> On-Timer Operation
When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation is carried out according to the set time.
Sleep Timer Operation
When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appli­ance operation, the operation of the appliance stops.
While the appliance is on pause, the sleep timer mode cannot be input.
While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature increases by 1°C. After another 30 min elapse, it increases by 1°C again.
When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to
the low.
When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to the medium.
Chaos Swing Mode
By the Chaos Swing key input, the upper/lower vane automatically operates with the Chaos Swing or they are fixed to the desired direction.
While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.
Chaos Natural Wind Mode
When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air­flow mode is operated for 2~15 sec. randomly by the Chaos Simulation.
Jet Cool Mode Operation (C/O Model)
If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
Jet Cool Mode Operation (H/P Model)
While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the other
mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C.
When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
Page 28
28 MPS Multi Air Conditioner
Operation Details
Auto Restarting Operation
When the power is restored after a sudden power failure while in appliance operation, the mode before the power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
The slide switch on the main unit of the appliance should be on the Auto Restarting position in order that the Auto Restarting operation is available.
Operation Mode that is kept on the memory
- State of Operation ON/OFF
- Operation Mode/Setting Temp/Selected Airflow Speed
- Sleep Timer Mode/Remaining Time of Sleep Timer (unit of hour)
Slide Switch
FORCED OPERATION
AUTO RESTART
REMOTE CONTROL
Forced Operation (C/O Model)
To operate the appliance by force in case that the remote control is lost, the forced operation selection switch is on the main unit of the appliance to operate the appliance in the standard conditions.
When the power is supplied while the slide switch is on the forced operation position, or when the slide switch position is switched to the Auto Restarting position (or test operation) or switched from the remote control posi­tion to the forced operation position while the power is on, the forced operation is carried out.
When the slide switch position is switched from the forced operation position to the Auto Restarting position or the remote control position, the forced operation is canceled and the appliance stops operating.
The forced operation is carried out in cooling mode with the setting temperature 22°C and the high speed of airflow.
While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to indicate the forced operation.
Forced Operation (H/P Model)
To operate the appliance by force in case that the remote control is lost, the forced operation selection switch is on the main unit of the appliance to operate the appliance in the standard conditions.
When the power is supplied while the slide switch is on the forced operation position, or when the slide switch position is switched to the Auto Restarting (or test operation) position or switched from the remote control posi­tion to the forced operation position while the power is on, the forced operation is carried out.
When the slide switch position is switched from the forced operation position to the Auto Restarting position or the remote control position, the forced operation is canceled and the appliance stops operating.
The forced operation is carried out in cooling mode with the setting temperature 22°C and the high speed of airflow.
In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the operation
condition is set according to the intake air temperature as follows.
24°CIntake Air Temp Cooling Mode Operation, 22°C, High Speed 21°CIntake Air Temp<24°C Dehumidification Operation, 23°C, High Speed Intake Air Temp<21°C Heating Mode Operation, 24°C, High Speed
While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to indicate the forced operation.
Page 29
Service Manual 29
Operation Details
Remote Control Operation Mode
When the remote control is selected by the slide switch on the main unit, the appliance operates according to the input by the remote control.
Protection of the evaporator pipe from frosting
If the indoor pipe temp is below 0°C in 7 min. after the compressor operates without any pause while in cool­ing cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor evaporator pipe from frosting.
When the indoor pipe temp is 7°C or higher after 3 min. pause of the compressor, the compressor and the outdoor fan is turned on according to the condition of the room temperature.
Buzzer Sounding Operation
When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.
When the appliance-pause key is input by the remote control, the long "beep" sounds.
When a key is input by the remote control while the slide switch on the main unit of the appliance is on the
forced operation position, the error sound "beep-beep-beep-beep-beep-" is made 10 times to indicate that the remote control signal cannot be received.
Page 30
30 MPS Multi Air Conditioner
2-way, 3-way Valve
2-way, 3-way Valve
2-way Valve (Liguid Side) 3-way Valve (Gas Side)
Works Shaft position Shaft position Service port
Shipping Closed Closed Closed
(with valve cap) (with valve cap) (with cap)
Air purging Open Closed Open
(Installation) (counter-clockwise) (clockwise) (push-pin or with
vacuum pump)
Operation Open Open Closed
(with valve cap) (with valve cap) (with cap)
Pumping down Closed Open Open
(Transfering) (clockwise) (counter-clockwise) (connected
manifold gauge)
Evacuation Open Open Open (Servicing) (with charging
cylinder)
Gas charging Open Open Open
(Servicing) (with charging
cylinder)
Pressure check Open Open Open
(Servicing) (with charging
cylinder)
Gas releasing Open Open Open
(Servicing) (with charging
cylinder)
3.
2.
1.
4.
5.
6.
Flare nut
To piping connection
Open position Closed position
Flare nut
Valve cap
To piping connection
Open position Closed position
Hexagonal wrench (4mm)
To outdoor unit
Pin
Service port
Service port cap
To outdoor unit
Page 31
Service Manual 31
2-way, 3-way Valve
Procedure
1. Confirm that both the gas side and liquid side valves are set to the open position.
- Remove the valve stem caps and confirm that the valve stems are in the raised position.
- Be sure to use a hexagonal wrench to operate the valve stems.
2. Operate the unit for 10 to 15 minutes.
3. Stop operation and wait for 3 minutes, then con­nect the manifold gauge to the service port of the gas side valve.
- Connect the hose of the gauge with the push pin to the service port.
4. Air purging of the charge hose.
- Open the Low-handle valve on the gauge slightly to air purge from the hose.
5. Set the liquid side valve to the closed position.
6. Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 1kg/cm2g.
7. Immediately set the gas side valve to the closed position.
- Do this quickly so that the gauge ends up indi­cating 1kg/ g.
8. Disconnect the charge set, and mount the liquid side and gas side valve caps and the service port nut.
- Use torque wrench to tighten the service port nut to a torque of 1.8kg.m.(4.2kg*m/5.5kg*m)
- Be sure to check for gas leakage.
Indoor unit
Outdoor unit
Liquid side
Close
Gas side
2-Way
valve
Open
3-Way
valve
manifold gauge
Indoor unit
Liquid side
Close
Gas side
2-Way
valve
Open
3-Way
valve
Hi- handle (CLOSE)
Low­handle (CLOSE)
(1) Pumping down
Page 32
32 MPS Multi Air Conditioner
2-way, 3-way Valve
(2) Evacuation
(All amount of refrigerant leaked)
Procedure
1. Confirm that both the liguid side valve and gas side valve are set to the opened position.
2. Connect the vaccum pump to the center hose of the manifold gauge.
3. Connect the service port of the gas side valve to the low side of the gauge.
4. Connect power supply to outdoor unit.
5. Evacuation for approximately one hour.
- Confirm that the gauge needle has moved toward-76 cmHg (vacuum of 4 mmHg or less).
6. Close the Low handle of the gauge turn off the vacuum pump, and confirm that the gauge nee­dle does not move(approximately 5 minutes after turning off the vacuum pump).
7. Disconnect the charge hose from the vacuum pump.
- Vacuum pump oil. If the vacuum pump oil becomes dirty or deplet­ed,replenish as needed.
8. Mount the valve caps and the service port caps.
Indoor unit
Outdoor unit
Liquid side
Open
Gas side
2-Way
valve
Open
3-Way
valve
manifold gauge
Indoor unit
Liquid side
Open
Gas side
2-Way
valve
Open
3-Way
valve
Vacuum pump
Hi- handle (OPEN)
Low­handle (OPEN)
Page 33
Service Manual 33
2-way, 3-way Valve
(3) Gas Charging
(After Evacuation)
Procedure
1. Connect the gauge to the charging cylinder.
- Connect the charge hose which you disconnect­ed from the vacuum pump to the valve at the bottom of the cylinder.
- If you are using a gas cylinder, also use a scale and reverse the cylinder so that the system can be charged with liquid.
2. Purge the air from the charge hose.
-
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air. (Be careful of the liquid refrigerant). The procedure is the same if using a gas cylinder.
3. Open the low handle on the gauge and charge the system with liquid refrigerant.
- If the system can not be charged with the speci­fied amount of refrigerant, it can be charged with a little at a time (approximately 150g each time) while operating the air conditioner in the cooling cycle; however, one time is not suffi­cient, wait approximately 1 minute and then repeat the procedure(pumping down-pin).
4. Immediately disconnect the charge hose from the gas side valve's service port.
- Stopping partway will allow the gas to be dis-
charged.
- If the system has been charged with liquid
refrigerant while operating the air conditioner turn off the air conditioner before disconnecting the hose.
5. Mount the valve stem nuts and the service port nut.
- Use torque wrench to tighten the service port nut to a torque of 1.8 kg.m.(4.2kg.m/5.5kg.m.)
- Be sure to check for gas leakage.
manifold gauge
Charging
cylinder
Hi- handle (OPEN)
Low-handle
(OPEN)
Check valve
Indoor unit
Outdoor unit
Liquid side
Open
Gas side
2-Way
valve
Open
3-Way
valve
Indoor unit
Liquid side
Open
Gas side
2-Way
valve
Open
3-Way
valve
This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner.
Page 34
34 MPS Multi Air Conditioner
Cycle Troubleshooting Guide
Cycle Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
All amount of refrigerant leaked out. Check refrigeration cycle.
Refrigerant leakage Clog of refrigeration cycle Defective compressor
Excessive amount of refrigerant
Normal
Notice:
Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
Notice:
1. The suction pressure is usually 4.5~6.0 kg/cm2G at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
Temp. difference : approx. 0°C Current :less than 80% of
rated current
Temp. difference : approx. 8°C Current :less than 80% of
rated current
Temp. difference : less than 8°C Current :over the rated
current
Temp. difference : over 8°C
Temp. Difference
Operating Current
Suction pressure Temperature
(Compared with (Compared with Cause of Trouble Description
the normal value) the normal value)
High Defective compressor Current is low.
Defective 4-way reverse valve
Normal Excessive amount of High pressure does not quickly
refrigerant rise at the beginning of operation. Insufficient amount of Current is low.
Lower Higher refrigerant(Leakage)
Clogging Current is low.
Higher
Page 35
Service Manual 35
Electronic Parts Troubleshooting Guide
Electronic Parts Troubleshooting Guide
(* Refer to Electronic Control Device drawing and Schematic diagram.)
Turn off Main Power
Turn on Main Power
Does "beeping" sound is made from the Indoor Unit?
Primarily, the operating condition of Micom is OK.
Check the voltage of power(About AC 220V/AC240V, 60Hz)
Main power's voltage
Voltage applied to the unit
Connecting method of Indoor/Outdoor connecting
cable
Check Fuse (Outdoor PCB Ass'y)
Check Varistor
ZNRØ1J(Outdoor PCB Ass'y)
Check the connection housing for contacting
Connector related to CN-DC/AC
Display PWB Ass'y Check
Check each load(Indoor/Outdoor Fan Motor, Compressor, Stepping Motor etc.) and contacting condition of related connector
PCB Board Operation Check
Items
Power Transformer (Outdoor unit)
- Input Voltage
- Output Voltage
IC01D(7812) Output (Indoor/Outdoor unit)
IC02D(7805) Output (Indoor/Outdoor unit)
IC01A(KIA7036, Reset IC) X01(8MHz)
Replace Trans
Replace IC01D
Replace IC02D
Replace faulty parts
- About AC220V/240V±10% - Check the power voltage
- About AC14±3V
DC+12V
DC+5V
Voltage of Micom No. 2,
(DC +4.5V over) and Soldering condition.
Content Remedy
NO
YES
(After 10 seconds)
1. The Outdoor Unit does not operate at all
Page 36
36 MPS Multi Air Conditioner
Electronic Parts Troubleshooting Guide
Turn on Main Power
While the compressor has been stopped, the compressor does not
operate owing to the delaying function for 3 minutes after stopped.
Caused by other parts except the remote control
Cause by the remote control
When the mark( ) is displayed in LCD screen, replace battery.
Check the contact of CN-DISPI connector.
When the compressor stopped Indoor Fan is driven by a low speed. At this point the wind speed is not controlled by the remote controller. (When operated in the Sleeping Mode, the wind speed is set to the low speed by force.)
Check DISP PWB Ass'y
- Voltage between CN DISP1 - :DC+5V
When the detect switch(double key) inside the remote controller door is fault, it is impossible to operate temperature regulating( / ) and wind speed selecting.
Check the connecting circuit between the remote con­troller MICOM (No. )-R17(2Ω)-IRLED-Q1- R16(2.2K).
Check point
Check the connecting circuit between PIN ­R01L(1K) - C01L(680PF) - MICOM PIN
Check Receiver Ass'y
2. The product is not operate with the remote controller.
Page 37
Service Manual 37
Electronic Parts Troubleshooting Guide
3. When cooling does not operate
Turn on Main Power
Operate "Cooling Mode( )" by setting the desired temperature of the remote controller is less than one of the indoor temperature by 1°C at least.
When in Air Circulation Mode, Compressor/Outdoor Fan is stopped.
Check the sensor for indoor temperature is attached as close as to be effected by the temperature of Heat Exchanger(EVA).
When the sensor circuit for indoor temperature and connector are in bad connection or are not engaged, Compressor/Outdoor Fan is stopped.
Check the related circuit of R02H(12.1K), R01H(1.0K), R04H(6.2K), R03H(1.0K) (Indoor unit).
Check the indoor temperature sensor is disconnected or not(About 10kΩ /at25°C).
Check if connection line (Indoor/Outdoor) is complied with Wiring Diagram.
Check Outdoor Unit
(PCB Ass'y)
Correct connection line
Good connection Bad connection
Page 38
38 MPS Multi Air Conditioner
Electronic Parts Troubleshooting Guide
4. When indoor Fan does not operate.(or "ON/OFF" led of display blinks 8 times)
Turn off Main power
Check it (Indoor/Outdoor)the connection line is complied with Wiring Diagram
Check the line fuse in the outdoor unit
Check the connection of CN-MOTOR
check the operation of blower by manual
Correct connection line
Check POLY S/W in indoor PCB Ass'y
If it is opened If it is shorted
Exchange Indoor PCB Ass'y
Check the outdoor PCB Ass'y
Bad connection Good connection
Page 39
Service Manual 39
Electronic Parts Troubleshooting Guide
5. When Vertical Louver does not operate.
Confirm that the Vertical Louver is normally geared with the shaft of Stepping Motor.
If the regular torque is detected when rotating the Vertical Louver with hands Normal
Check the connecting condition of CN-U/D Connector
Check the soldering condition(on PWB) of CN-U/D Connector
If there are no problems after above checks
Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver
Check the operating circuit of the Vertical Louver
Confirm that there is DC+12V between pin
(RED) of CN-U/D and
GND.
Page 40
40 MPS Multi Air Conditioner
Electronic Parts Troubleshooting Guide
6. When Heating does not operate
Operate Heating Mode( )by setting the desired temperature of the remote control is higher than one of the indoor temperature by 2°Cat least.
In heating Mode, the indoor fan operates in case the pipe temperature is higher than 28°C.
Check the connector of intake and pipe sensor(thermistors)
Check the related circuit of R02H(12.1K), R01H(1.0K), R04H(6.2K), R03H(1.0K).
Check the indoor room temperature is disconnected or not (about 10KΩ/at 25°C).
Check the indoor pipe temperature is disconnected or not (about 5K/at 25°C).
Turn ON Main Power
Check if connection line (Indoor/Outdoor) is complied with Wiring Diagram.
Check Outdoor Unit
(PCB Ass'y)
Correct connection line
Good connection Bad connection
Page 41
Service Manual 41
Electronic Parts Troubleshooting Guide
7. Outdoor unit does not operate at all.
8. Communication error
PCB Board Operation Check in Outdoor
Items
Power Transformer (Outdoor unit)
- Input Voltage
- Output Voltage
IC01D(7812) Output (Indoor/Outdoor unit)
IC02D(7805) Output (Indoor/Outdoor unit)
IC01A(KIA7036, Reset IC) X01(8MHz)
Replace Trans
Replace IC01D
Replace IC02D
Replace faulty parts
- About AC220V/240V±10% - Check the power voltage
- About AC14±3V
DC+12V
DC+5V
Content Remedy
The control data can be transmitted or received between indoor and outdoor unit with one signal cable.
If the data be disturbed by any noise level and misconnection, the unit will be operated incorrectly. In this
case, the indoor unit blinks the operation and operation LED on display and indoor fan, outdoor fan, COMP are not operated.
The unit can be reoperated by On/Off control of Remocon.
Check Outdoor Unit
Turn off Main Power
Check the electrical wiring diagram of outdoor side.
Check the abnormal condition for the component of
Compressor/Outdoor Fan Motor/4-way.
Check the openor shortof connecting wires between indoor and outdoor.
Page 42
42 MPS Multi Air Conditioner
Installation
Installation
(1) Installation of Indoor, Outdoor unit
Front
Right Rear right
Rear left
Down right
Left
1) Selection of the best location
1. Indoor unit
There should not be any heat source or steam near the unit.
There should not be any obstacles to prevent the air circulation.
A place where air circulation in the room will be good.
A place where drainage can be easily obtained.
A place where noise prevention is taken into
consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from
the wall, ceiling, fence, or other obstacles.
2. Outdoor unit
If an awning is built over the unit to prevent direct sunlight or rain exposure, be careful that heat radiation from the condenser is not restricted.
There should not be any animals or plants which could be affected by hot air discharged.
Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles.
3. Piping length and the elevation
Pipe Size
GAS LIQUID
Max. piping
length
A(m)
Max.
Elevation
B(m)
1/2"(3/8") 1/4" 15 7.5
More than 5 cm
More than
5 cm
More than
5 cm
More than eye-level
more than 30cm
(11.8 inch)
more than 30cm
(11.8 inch)
more than 70cm
(27.6 inch)
Indoor unit
A
B
Outdoor unit
Page 43
Service Manual 43
Installation
2) Indoor Unit Installation
The mounting wall should be strong and solid enough to protect it from the vibration.
1. Mount the installation plate on the wall with four Type "A" screws.
(If mounting the unit on the concrete wall, consid­er using anchor bolts.)
Always mount the Installation plate horizontally
by aligning the marking-off line by means of the thread and a level.
2. Drill the piping hole with 70mm dia. holecore drill.
Line according to the arrows marked on lower
the left and the rght side of the Installation Plate. The meeting point of the extended line is the center of the hole.
Drill the piping hole at either the right or the left
and the hole should be slightly slant to the out­door side.
Installation Plate
marking-off line
Thread
Weight
Type "A" screw
The lower left and the right side of Installation Plate
Left rear piping Right rear piping
A
A
ø70mm ø70mm
Indoor Outdoor
A
A
Wall
5~7mm
Page 44
44 MPS Multi Air Conditioner
Installation
1) Preparation of pipings
1. Cut the pipes and the cable.
Use the accessory piping kit or the pipes pur­chased locally.
Measure the distance between the indoor and the outdoor unit.
Cut the pipes a little longer than the measured distance.
Cut the cable 1.5m longer than the length of the pipe.
2. Remove burrs.
Remove burrs from cut edges of pipes.
Turn the pipe end toward down to avoid the
metal powder entering the pipe.
Caution:
If burrs are not removed, they may cause a gas leakage.
3. Flaring the pipes.
Insert the flare nuts, mounted on the connection ports of both indoor and outdoor unit, onto the copper pipes. Some refrgerant gas may leak, when the flare nuts are removed from the indoor unit, as some gas is charged to prevent the inside of the pipe from rusting.
Fit the copper pipe end into the Bar of flare tool about 0~0.5mm higher. (See illustration)
Flare the pipe ends.
4. Tape the flaring portion to protect it from the dust or damages.
90
Slanted
Pipe cutter
Rough
"A"
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Bar
Yoke
Handle
When properly flared, the internal surface flare will evenly shine and be of even thickness. Since the flare part comes into contact with the connec­tors, carefully check the flare finish.
"
A"; ø12.7mm(1/2")→0~0.5 mm
ø9.52mm (3/8")
0~0.5 mm
ø6.35mm (1/4")
0~0.5 mm
(2) Piping and Drainage of Indoor Unit
Point down
Pipe
Reamer
= Improper flaring =
Inclined Cracked Uneven
Surface
damaged
thickness
Page 45
Service Manual 45
Installation
2)
Connection of Pipings
1. Remove the installation plate
Pull the two '∆' marked portion of bottom of the chassis and pull the installation plate out of chas­sis.
2. Route the drain hose and the indoor tubing.
For left rear piping
3. Route the tubing and the drain hose straight
backwards(see figure).
4. Insert the connecting cable into the indoor
unit through the piping hole.
Do not connect the cable to the indoor unit.
Make a small loop with the cable for easy con-
nection later.
5. Tape the tubing, drain hose and the connecting
cable. Be sure that drain hose locates at the lowest side of the bundle. Locating at the upper side can be a reason that drain water overflows drain pan inside the unit.
Installation plate
Pull
Pull
To remove the holder, press the bottom of the chassis near the holder upwards and the tab is clear of its hole.
Turn it clockwise approx. 90° and remove it.
Tubing holder
Press
Connecting cable
Gas side piping
Liquid side piping Drain hose
Page 46
46 MPS Multi Air Conditioner
Installation
Connecting cable
Drain hose
Press the lower left and right side of the unit against the Installation Plate until the hooks engage with their slots (sound click).
6. Indoor unit installation.
Hook the indoor unit onto the upper position of the installation plate. (Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure the hooks are properly seated on the installation plate by moving it in left and right.
7. Connecting the pipings to the indoor unit.
Align the center of the pipings and sufficiently tighten the flare nut with fingers.
Finally, tighten the flare nut with torque wrench until the wrench clicks. Wrench tightening the flare nut with forque wrench, ensure the direction for tightening fol­lows the arrows on the wrench.
8. Wrap the insulation material around the con­necting portion.
CAUTION: Take care to arrange the pipings,
drain hose and cables as the right upper picture for inserting it into the indoor unit and refixing the tubing holder easily.
Pipe Size Torque
Liquid Side (1/4") 1.8kg m
Gas Side (3/8") 4.2kg m Gas Side (1/2") 5.5kg m
Wrap the insulation material around the connecting portion.
Indoor unit tubing Flare nut Pipings
Spanner
Torque wrench
Plastic bands
Insulation material
Page 47
Service Manual 47
Installation
9. Set the pipings and the connecting cable to the back of the chassis with the tubing holder.
Hook the edge of tubing holder to tap on chas-
sis and push the bottom of tubing holder to be engaged in the bottom of chassis.
10. Indoor unit installation.
Hook the indoor unit onto the upper portion of
installation plate. (Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure the hooks are properly seated on the installation plate by moving it in left and right.
Press the lower left and right side of the unit against the Installation Plate until the hooks engages with their slots (sound click).
Drain hose
Taping
Piping
2
Push
Tubing holder
Hook
1
Connecting cable
Drain hose
Page 48
48 MPS Multi Air Conditioner
Installation
Gas side piping
Gas side piping
Evaporator side piping
Evaporator side piping
Torque wrench
B-UNIT
C-UNIT
A-UNIT
Outdoor unit
A
B
C
1) Connecting the pipings to the Outdoor unit
1. Align the center of the pipings and sufficiently
tighten the flare nut with fingers.
2. Finally, tighten the flare nut with torque
wrench until the wrench clicks.
When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
Pipe Size Torque
Liquid Side (1/4") 1.8kg.m
Gas Side (3/8") 4.2kg.m Gas Side (1/2") 5.5kg.m
(3) Connecting Pipings and the cable to Outdoor unit
Page 49
Service Manual 49
Installation
Outdoor unit
GN/YL
20mm
GN/YL
20mm
AWG 18
AWG 12
WARNING
WARNING
NOTE
NOTE
Over 5mm
Holder for
power supply
cord
Connecting
cable
Cover control
Terminal block
Power supply
cable
A-UNIT
SVGC
B-UNIT
SVGC
C-UNIT
SVGC
Terminal BLOCK
SVGC
Terminal BLOCK
SVGC
L1 L2
Power Source
208/230V AC
(High voltage)
Indoor A-UNIT Indoor B-UNIT
Terminal BLOCK
SVGC
Indoor C-UNIT
Connecting cable(Low voltage)Connecting cable(Low voltage)Connecting cable(Low voltage)
Connection of the cable
1. Remove the cover control from the unit by loosening the screw.
2. Dismount caps on the conduit panel.
3. Temporarily mount the conduit tubes on the conduit panel.
4. Connect the wires to the terminals on the control board individually as the following.
5. Secure the cable onto the control board with the holder (clamper).
6. Ground the unit in accordance with local codes.
7. Refix the cover control to the original position with the screw.
8. Use lock nuts to secure the conduit tubes.
1. Separately wire the high and low voltage line.
2. Use heat-proof electrical wiring capable of withstanding temperature up to 167˚F.
3. Use outdoor and waterproof connection cable rated more than 300V for the connection between indoor and outdoor unit. (For example, Type SJO-WA)
Be sure to comply with local codes while running the wire from the indoor unit to the outdoor unit(size of wire and wiring method, etc).
Every wire must be connected firmly.
No wire should be allowed to touch refrigerant tubing,
the compressor or any moving parts.
The power cable connected to the outdoor unit should be complied with the following specifications. (UL recognized and CSA certified)
CAUTION
The connecting cable connected to the indoor and outdoor unit should be complied with the following specifications. (UL recognized and CSA certified)
Page 50
50 MPS Multi Air Conditioner
Installation
Connection method of the connecting cable(Example)
(1) Dismount two-caps on the conduit panel. (2) Make a hole appropriate for the passage of connec-
tion cable through on cap by tool.
(for low voltage line) (3) Pass the connecting cable through the hole. (4)
Properly connect the cable on the terminal block. (5) Fix the connection cable with clamp cord provided on
the unit not to have strain at the terminal when the
connection cable is pulled outside up to a 35 pound
weight. (6) Wind the vinyl tape round the connecting cable for
sealing between the surface of the connection cable
and cap. (7) Mount the taped part of cable on the cap. (8) Finally, mount the holed cap with the wound cable on
the conduit panel.
When connecting each power wire to the corresponding terminal, follow instructions "How to connect wiring to the terminals" and fasten the wire tightly with the fixing screw of the terminal plate.
How to connect wiring to the terminals
For solid core wiring (or F-cable)
(1) Cut the wire end with a wire cutter of wire-cutting pli-
ers, then strip the insulation to expose the solid wire
about 25mm(15/16") (2) Using a screwdriver, remove the terminal screw(s) on
the terminal plate. (3) Using pliers, bend the solid wire to from a loop suit-
able for the terminal screw. (4) Shape the loop wire properly, place it on the terminal
plater and tighten securely with the terminal screw
using a screwdriver.
For strand wiring
(1) Cut the wire end with a wire cutter or wire-cutting pli-
ers, then strip the insulation to expose the strand
wiring about 10mm(3/8"). (2) Using a screwdriver, remove the terminal screw(s) on
the terminal plate. (3) Using a round terminal fastener or pliers, securely
clamp each stripped wire end with a round terminal. (4) Position the round terminal wire, and replace and
tighten the terminal screw using a screwdriver.
Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
WARNING
G
Terminal block
Lock nut
Power supply line
(1ø, 230/208V)
Conduit panel
Cap(Reuse)
Clamp cord
Hole (for low voltage line)
Cap(Remove) Taping
(for sealing)
Low voltage line (connecting cable)
Loop
Strip 25mm(15/16")
Insulation
Solid wire
High voltage
Low voltage
Strip 10mm(3/8")
Round terminal
Connecting cable
Loosening the terminal block screw
Fastening the wire tightly
Strand wire
Page 51
Service Manual 51
Installation
Connect the cable to the indoor unit
1. Connect the wires to the terminals on the control board individually according to the outdoor unit con­nection.
Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respec­tively. (Refer to Wiring diagram on page11.)
2. Attach the Grille onto the cabinet.
Grasp lower the left and right side of the Grille and engage four tabs on the top inside edge of the chassis.
Press the Grille toward the chassis until it will be back into place.
CAUTION
CAUTION
Air
Conditioner
Circuit Breaker
Use a circuit breaker or time delay fuse.
Connecting cable
Main power source
If a power plug is not to be used, provide a circuit breaker between power source and the unit as shown below.
Model
18k 1ø,230/208V 15A 24k 1ø,230/208V 20A 36k 1ø,230/208V 30A
Power source
Fuse or breaker
Capacity
Be sure to refer to the wiring diagram label inside the cover control and carry out the correct field wiring. Wrong wiring can cause the unit to misoperate to result in a fire hazard.
Check local electrical codes and any specified wiring instructions or limitations.
WARNING
Page 52
52 MPS Multi Air Conditioner
Installation
1. To remove the front panel from the indoor unit, remove the front panel from the indoor unit cabinet.
Set the air direction louvers up-and-down to the posi­tion(horizontally) by hand.
Remove the securing screws that retain the front panel. Pull the lower left and right sides of the grille
toward you and lift it off. (9K Btu models: 2EA,
12K Btu models: 3EA)
2. To check the drainage.
Pour a glass of water on the evaporator.
Ensure the water flows through the drain hose of the
indoor unit without any leakage and goes out the drain exit.
3. Drain piping
The drain hose should point downward for easy drain flow.
Do not make drain piping.
1. Form the piping by wrapping the connecting por­tion of the indoor unit with insulation material and secure it with two kinds of vinyl tapes.
If you want to connect an additional drain hose, the end of the drain outlet should be routed above the
ground. Secure the drain hose appropriately.
2. In cases where the outdoor unit is installed below the indoor unit perform the following.
Tape the piping, drain hose and connecting cable from down to up.
Secure the tapped piping along the exterior wall using saddle or equivalent
3. In cases where the Outdoor unit is installed above the Indoor unit perform the following.
Tape the piping and connecting cable from down to up.
Secure the taped piping along the exterior wall. Form a trap to prevent water entering the room.
Fix the piping onto the wall by saddle or equivalent.
Pull the right and the left side.
Screw
Trap is required to prevent water from entering into electrical parts.
Plastic band
Taping
Drain hose
Pipings Connecting
cable
Power supply cord
Seal a small opening around the pipings with gum type sealer.
Seal a small opening around the pipings with gum type sealer.
Trap
Trap
Downward slope
Do not raise
Accumulated drain water
Tip of drain hose dipped in water
Air
Waving
Water leakage
Water leakage
Ditch
Less than 50mm gap
Water leakage
(4) Checking the drainage
(5) Form the piping
Page 53
Service Manual 53
Installation
(6) Air Purging of the Pipings and indoor unit
The air which contains moisture remaining in the is refrigeration cycle may cause a malfunction on the compressor.
1. Confirm that both the liquid side valve and the gas side valve are set to the closed position.
2. After connecting the piping, check the joints for gas leakage with gas leak detector.
3. Remove the service port nut, and connect the gauge manifold and the vacuum pump to the service port by the charge hose.
4. Vacuum the indoor unit and the connecting pipes until the pressure in them lowers to below-76cmHg.
5. Disconnect the charge hose and fit the nut to the service port. (Tightening torque: 1.8kg.m)
6. Remove the valve stem nuts, and fully open the stems of the 2-way and 3-way valves with a hexagon wrench.
7. Tighten the valve stem nuts of the 2-way valve and 3-way valve.
Indoor unit
Outdoor unit
Liquid side
Closed
Gas side
2-Way
valve
Closed
3-Way
valve
manifold gauge
Indoor unit
Liquid side
Closed
Gas side
2-Way
valve
Closed
3-Way
valve
Vacuum pump
Hi- handle (OPEN)
Low­handle (OPEN)
Page 54
Installation
h2
h2
h1
h1
A
BC
Oil trap
h1
(7) Maximum Length of Pipe and Freon Extra Charge
Multi Piping Type
Capacity(Btu/h)
36k
Indoor Capacity
(Btu/h)
12K 1/2" 1/4"
Max total length
of all pipes
(A+B+C)
Max length of
each pipe
(A/B/C)
Min length of
each pipe
(A/B/C)
Max Elevation between each
indoor unit and
outdoor unit (h1)
between indoor
45m 15m 3m 7.5m 7.5m
(150ft) (50ft) (10ft) (25ft) (25ft)
Pipe Size
Gas Liquid Standard Length
Refrigerant
7.5m 30g/m
(25ft) (0.32oz/ft)
Max elevation
units (h2)
Additional
CAUTION: Capacity is based on standard length and maximum allowance length is on the basis of reliability. Oil trap should be installed every 5~7 meters (16.4~23.0ft).
54 MPS Multi Air Conditioner
Page 55
Service Manual 55
Installation
(8) Test running
Battery Cover
Settlement of Outdoor Unit
• Anchor the outdoor unit with a bolt and nut (ø10cm) tightly and horizontally on a concrete or rigid mount.
• When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earth­quake.
• In the case when the vibration of the unit is con­veyed to the house, settle the unit with an anti­vibration rubber.
2) Evaluation of the performance
1. Measure the temperature of the intake and
discharge air.
2. Ensure the difference between the intake
temperature and the discharge one is more than 8°C.
1) Connection of power supply
1. Connect the power supply cord to the inde-
pendent power supply.
2. Prepare the remote control.
• Insert two batteries provided. Remove the battery cover from the remote con­troller.
• Slide the cover according to the arrow direction. Insert the two batteries.
(Two "R03" or "AAA" dry-cell batteries or equiv­alent.)
• Be sure that the (+) and (-) directions are cor­rect.
• Be sure that both batteries are new. Re-attach the cover.
• Slide it back into position.
3. Operate the unit at cooling operation mode for fifteen minutes or more.
: Heating capacity decreases as outdoor temperature decreases. The unit can work below to 14F without unit out or system shut down.
NOTICE
Bolt
Tubing connection
Discharge air
Page 56
56 MPS Multi Air Conditioner
Operation
Operation
(1) Name and Function-Remote Control (Door Closed)
Signal transmitter
Transmits the signals to the room air conditioner.
REMOTE CONTROL
START/STOP BUTTON
Operationstartswhenthisbuttonispressedandstops when the button is pressed again.
OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
ROOM TEMPERATURE SETTING BUTTONS
Used to select the room temperature.
INDOOR FAN SPEED SELECTOR
Used to select fan speed in four steps low, medium, high, or CHAOS.
JET COOL
Used to start or stop the speed cooling. (Speed cooling operates super high fan speed in cooling mode.)
CHAOS SWING BUTTON
Used to stop or start louver movement and set the desired up/down airflow direction
.
1
234
5
6
Signal transmitter
5 4
6 1
3
Flip-up door
(closed)
2
Page 57
Service Manual 57
Operation
(2) Name and Function-Remote Control (Door Opened)
Signal transmitter
Transmits the signals
to the room air conditioner.
REMOTE CONTROL
ON/OFF TIMER BUTTONS
Used to set the time of starting and stopping operation.
TIME SETTING BUTTONS
Used to adjust the time.
TIMER SET/CANCEL BUTTONS
Used to set the timer when the desired time is obtained and to cancel the Timer operation.
SLEEP MODE AUTO BUTTON
Used to set Sleep Mode Auto operation.
AIR CIRCULATION BUTTON
Used to circulate the room air without cooling or heating (turns indoor fan on/off).
ROOM TEMPERATURE CHECKING BUTTON
Used to check the room temperature.
˚CTO˚F SWITCHING BUTTON
RESET BUTTON
Used prior to resetting time or after replacing batteries.
Signal transmitter
1
2
3
4
ON OFF
1 2 3
SET
CANCEL
˚C/˚F
4 5 6 7 8
5
6
7
8
Page 58
58 MPS Multi Air Conditioner
Disassembly of the parts (Indoor unit)
Disassembly of the parts (Indoor unit)
Warning :
Disconnect the unit from power supply before mak­ing any checks. Be sure the power switch is set to OFF.
To remove the Grille from the Chassis.
Set the up-and-down air discharge louver to open position (horizontally) by finger pressure.
Remove the securing screws
To remove the Grille, pull the lower left and right
side of the grille toward you (slightly tilted) and lift it straight upward.
1. To remove the sensor, housing connect, step
motor conductor with sensor holder, Motor, Evaporator & P.C.B.
Screw
Step Motor Conductor
Motor Conductor
Sensor Conductor
Page 59
Service Manual 59
Disassembly of the parts (Indoor unit)
2. To remove the Control Box.
Remove securing screws.
Pull the control box out from the chassis care-
fully.
3. To remove the Discharge Grille.
Pull the discharge grille out from the chassis carefully.
4. To remove the Evaporator.
Remove screws securing the evaporator and the holder eva.
Unhook the tab on the right inside of the chas­sis at the same time, slightly pull the evapora­tor toward you until the tab is clear of the slot.
5. To remove the Cross-Flow Fan
Loosen the screw securing the cross-flow fan to the fan motor (do not remove).
Lift up the right side of the cross-flow fan and the fan motor, separate the fan motor from the cross-flow fan.
Remove the left end of the cross-flow fan from the self-aligning bearing.
Page 60
60 MPS Multi Air Conditioner
Exploded View and Replacement Parts List
Exploded View and Replacement Parts List
135312
268712
267110
135311
354210
152313
249951
152302
135500
135314
159901
342800
131410 733010
346812
263230-1
263230-2
268714
352150
146811
35211B
359011
1. Indoor Unit
L3-C363LA0/C363MA0/C363NA0, L3-H363LA0/H363MA0/H363NA0
Page 61
Service Manual 61
Exploded View and Replacement Parts List
PART No.
L3-C363LA0 L3-C363MA0 L3-C363NA0 L3-H363LA0 L3-H363MA0 L3-H363NA0
131410 CHASSIS ASSEMBLY 3141A20003D 3141A20003D 3141A20003D 3141A20003D 3141A20003D 3141A20003D R 135311 GRILLE ASSEMBLY,DISCHARGE(INDOOR)3531A10023X 3531A10023X 3531A10023X 3531A10023X 3531A10023X 3531A10023X R 135312 GRILLE ASSEMBLY, FRONT 3531A10098B 3531A10098B 3531A10098B 3531A10098A 3531A10098A 3531A10098A R 135500 COVER 3550A10107A 3550A10107A 3550A10107A 3550A10107A 3550A10107A 3550A10107A R 146811 MOTOR ASSEMBLY, STEP 4681AR2727H 4681AR2727H 4681AR2727H 4681AR2727H 4681AR2727H 4681AR2727H R 152302 FILTER(MECH), A/C 5230A20004A 5230A20004A 5230A20004A 5230A20004A 5230A20004A 5230A20004A R 152313 DEODORIZER 5231AR2412T - - 5231AR2412T - -
Only in CND/Not in RMC 159901 VANE,HORIZONTAL 5990A30007A 5990A30007A 5990A30007A 5990A30007A 5990A30007A 5990A30007A R 249951 CONTROL BOX ASSEMBLY, INDOOR 4995A00003A 4995A00003A 4995A00003A 4995A00003A 4995A00003A 4995A00003A R
263230-1 THERMISTOR ASSEMBLY 6323A20003A 6323A20003A 6323A20003A 6323A20003A 6323A20003A 6323A20003A R 263230-2 THERMISTOR ASSEMBLY 6323A20024A 6323A20024A 6323A20024A 6323A20024A 6323A20024A 6323A20024A R
267110 REMOTE CONTROLLER ASSEMBLY 6711A20025N 6711A20025N 6711A20025N 6711A20026U 6711A20026U 6711A20026U R 268712 PWB(PCB) ASSEMBLY, DISPLAY 6871A30009Q 6871A30009Q 6871A30009Q 6871A30009Q 6871A30009Q 6871A30009Q R 268714 PWB(PCB) ASSEMBLY, MAIN 6871A20502B 6871A20502B 6871A20502B 6871A20502A 6871A20502A 6871A20502A R 342800 BEARING 3H02821B 3H02821B 3H02821B 3H02821B 3H02821B 3H02821B R 346812 MOTOR ASSEMBLY, DC 4681AR2295H 4681AR2295H 4681AR2295H 4681AR2295H 4681AR2295H 4681AR2295H R 35211B TUBE ASSEMBLY, TUBING 2H02449J 2H02449J 2H02449J 2H02449J 2H02449J 2H02449J R 352150 HOSE ASSEMBLY, DRAIN 5251AR2575H 5251AR2575H 5251AR2575H 5251AR2575H 5251AR2575H 5251AR2575H R 354210 EVAPORATOR ASSEMBLY, FIRST 5421A20032D 5421A20032D 5421A20032D 5421A20032D 5421A20032D 5421A20032D R 359011 FAN ASSEMBLY, CROSS FLOW 5901AR6141C 5901AR6141C 5901AR6141C 5901AR6141C 5901AR6141C 5901AR6141C R 733010 PLATE ASSEMBLY, INSTALL 1H00843A 1H00843A 1H00843A 1H00843A 1H00843A 1H00843A R 135314 GRILLE ASSY,INLET SUB 3531A10054R 3531A10054R 3531A10054R 3531A10054Q 3531A10054Q 3531A10054Q R
DESCRIPTION
SVC
CODE
LOCATION
No.
PartsList-IndoorUnit
Page 62
62 MPS Multi Air Conditioner
Exploded View and Replacement Parts List
L3UC363LA0, L3UC363MA0, L3UC363NA0
546810
559010
552203-1
552203-2
554160-2
554160-1
567502
554031
447910
430410
435512
135301
437211
137213-2137213-1
135314
548490
552112
552113
552117
561411-1
561411-2
561411-3
263230-1
263230-2
649950
668711-2
668711-1
W0CZZ-1
W0CZZ-2
435511
2. Outdoor Unit
Page 63
Service Manual 63
Exploded View and Replacement Parts List
PART No.
L3-C363LA0 L3-C363MA0 L3-C363NA0
135301 GRILLE,DISCHARGE 3530A20006B 3530A20006B 3530A20006B R
135314 GRILLE,REAR 3530A10176B 3530A10176B 3530A10176B R 263230-1 THERMISTOR ASSEMBLY 6323A20028A 6323A20028A 6323A20028A R 263230-2 THERMISTOR ASSEMBLY 6323A20026A 6323A20026A 6323A20026A R
430410 BASE ASSEMBLY, OUTDOOR 3041AP7177D 3041AP7177D 3041AP7177D R
435511 COVER ASSEMBLY,CONTROL(OUTDOOR) 3551A10044B 3551A10044B 3551A10044B R
435512 COVER ASSEMBLY,TOP(OUTDOOR) 3H03266H 3H03266H 3H03266H R
437211 PANEL ASSEMBLY,FRONT(OUTDOOR) 3721A10109A 3721A10109A 3721A10109A R
447910 BARRIER ASSEMBLY,OUTDOOR 4791A10019B 4791A10019B 4791A10019B R
546810 MOTOR ASSEMBLY,OUTDOOR 4681AR1392X 4681AR1392X 4681AR1392X R
548490 ACCUMULATOR ASSEMBLY(MECH) 5211A21233B 5211A21233B 5211A21233B R
552112 TUBE ASSEMBLY,CONDENSER IN 5211A11010C 5211A11010C 5211A11010C R
552113 TUBE ASSEMBLY, CONDENSER OUT 5211A12001C 5211A12001C 5211A12001C R
552116 TUBE ASSEMBLY, REVERSING - - - R
552117 TUBE ASSEMBLY, SUCTION(OUTDOOR) 5211A10446C 5211A10446C 5211A10446C R
554031 CONDENSER ASSEMBLY, BENT 5403A20168C 5403A20168C 5403A20168C R
559010 FAN ASSEMBLY, PROPELLER 5901A10033A 5901A10033A 5901A10033A R 561410-1 COIL ASSEMBLY, REVERSING VALVE - - - R 561410-2 COIL ASSEMBLY, SOLENOID - - - R
649950 CONTROL BOX ASSEMBLY,OUTDOOR 4995A00002B 4995A00002B 4995A00002B R 668711-1 PWB(PCB) ASSEMBLY,MAIN(AC) 6871A20500B 6871A20500B 6871A20500B R 668711-2 PWB(PCB) ASSEMBLY,MAIN(OUTDOOR) 6871A20479B 6871A20479B 6871A20479B R 137213-1 PANEL ASSEMBLY, SIDE 3721A10110A 3721A10110A 3721A10110A R 137213-2 PANEL ASSEMBLY, SIDE 3721A10111C 3721A10111C 3721A10111C R 552203-1 VALVE,SERVICE 2H01890U 2H01890U 2H01890U R 552203-2 VALVE,SERVICE 2H02479R 2H02479R 2H02479R R 554160-1 COMPRESSOR 2520UHGK2EA 2520UHGK2EA 2520UHGK2EA R 554160-2 COMPRESSOR 2520UMMK2BA 2520UMMK2BA 2520UMMK2BA R 561411-1 COIL ASSEMBLY,EXPANSION 6141A20018D 6141A20018D 6141A20018D R 561411-2 COIL ASSEMBLY,EXPANSION 6141A20018E 6141A20018E 6141A20018E R 561411-3 COIL ASSEMBLY,EXPANSION 6141A20018F 6141A20018F 6141A20018F R
W0CZZ-1 CAPACITOR,DRAWING 0CZZA20007Q 0CZZA20007Q 0CZZA20007Q R W0CZZ-2 CAPACITOR,DRAWING 2H01451S 2H01451S 2H01451S R
567502 O.L.P 2H00599W 2H00599W 2H00599W R
DESCRIPTION
SVC
CODE
LOCATION
No.
Parts List - Outdoor Unit(L3UC363LA0, L3UC363MA0, L3UC363NA0)
Page 64
64 MPS Multi Air Conditioner
Exploded View and Replacement Parts List
L3UH363LA0, L3UH363MA0, L3UH363NA0
546810
559010
552203-1
552203-2
554160-2
554160-1
554031
447910
567502
430410
435512
135301
437211
137213-2137213-1
135314
263230-1
263230-2
649950
668711-2
668711-1
W0CZZ-1
W0CZZ-2
548490
552112
55211F
552113
552116
561410-1
561411-1
561411-2
561411-3
561410-2
435511
Page 65
Service Manual 65
Exploded View and Replacement Parts List
PART No.
L3-H363LA0 L3-H363MA0 L3-H363NA0
135301 GRILLE,DISCHARGE 3530A20006B 3530A20006B 3530A20006B R
135314 GRILLE,REAR 3530A10176B 3530A10176B 3530A10176B R 263230-1 THERMISTOR ASSEMBLY 6323A20028A 6323A20028A 6323A20028A R 263230-2 THERMISTOR ASSEMBLY 6323A20026A 6323A20026A 6323A20026A R
430410 BASE ASSEMBLY, OUTDOOR 3041AP7177D 3041AP7177D 3041AP7177D R
435511 COVER ASSEMBLY,CONTROL(OUTDOOR) 3551A10044A 3551A10044A 3551A10044A R
435512 COVER ASSEMBLY,TOP(OUTDOOR) 3H03266H 3H03266H 3H03266H R
437211 PANEL ASSEMBLY,FRONT(OUTDOOR) 3721A10109A 3721A10109A 3721A10109A R
447910 BARRIER ASSEMBLY,OUTDOOR 4791A10019B 4791A10019B 4791A10019B R
546810 MOTOR ASSEMBLY,OUTDOOR 4681AR1392X 4681AR1392X 4681AR1392X R
548490 ACCUMULATOR ASSEMBLY(MECH) 5211A21233A 5211A21233A 5211A21233A R
552112 TUBE ASSEMBLY,CONDENSER IN 5211A11010C 5211A11010C 5211A11010C R
552113 TUBE ASSEMBLY, CONDENSER OUT 5211A12001C 5211A12001C 5211A12001C R
552116 TUBE ASSEMBLY, REVERSING 5211A10448A 5211A10448A 5211A10448A R
552117 TUBE ASSEMBLY, SUCTION(OUTDOOR) - - - R
554031 CONDENSER ASSEMBLY, BENT 5403A20168A 5403A20168A 5403A20168A R
559010 FAN ASSEMBLY, PROPELLER 5901A10033A 5901A10033A 5901A10033A R 561410-1 COIL ASSEMBLY, REVERSING VALVE 6141A20021A 6141A20021A 6141A20021A R 561410-2 COIL ASSEMBLY, SOLENOID 6141A20022A 6141A20022A 6141A20022A R
649950 CONTROL BOX ASSEMBLY,OUTDOOR 4995A00002A 4995A00002A 4995A00002A R 668711-1 PWB(PCB) ASSEMBLY,MAIN(AC) 6871A20500B 6871A20500B 6871A20500B R 668711-2 PWB(PCB) ASSEMBLY,MAIN(OUTDOOR) 6871A20479A 6871A20479A 6871A20479A R 137213-1 PANEL ASSEMBLY, SIDE 3721A10110A 3721A10110A 3721A10110A R 137213-2 PANEL ASSEMBLY, SIDE 3721A10111C 3721A10111C 3721A10111C R 552203-1 VALVE,SERVICE 2H01890U 2H01890U 2H01890U R 552203-2 VALVE,SERVICE 2H02479R 2H02479R 2H02479R R 554160-1 COMPRESSOR 2520UHGK2EA 2520UHGK2EA 2520UHGK2EA R 554160-2 COMPRESSOR 2520UMMK2BA 2520UMMK2BA 2520UMMK2BA R 561411-1 COIL ASSEMBLY,EXPANSION 6141A20018D 6141A20018D 6141A20018D R 561411-2 COIL ASSEMBLY,EXPANSION 6141A20018E 6141A20018E 6141A20018E R 561411-3 COIL ASSEMBLY,EXPANSION 6141A20018F 6141A20018F 6141A20018F R W0CZZ-1 CAPACITOR,DRAWING 0CZZA20007Q 0CZZA20007Q 0CZZA20007Q R W0CZZ-2 CAPACITOR,DRAWING 2H01451S 2H01451S 2H01451S R
567502 O.L.P 2H00599W 2H00599W 2H00599W R
55211F TUBE ASSEMBLY, SOLENOIDE 5211A00007A 5211A00007A 5211A00007A R
DESCRIPTION
SVC
CODE
LOCATION
No.
Parts List - Outdoor Unit(L3UH363LA0, L3UH363MA0, L3UH363NA0)
Page 66
P/No.: 3828A20466A
August, 2004
Printed in Korea
Loading...