LG LM360CE Schematic

ENGLISH
IMPORTANT! Please read this instruction sheet completely before installing the product.
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
CAUTION
The weight of the condensing unit requires caution and proper handling procedures when lifting or moving to avoid personal injury. Use care to avoid contact with sharp or pointed edges.
Safety Precautions
• Always wear safety eye wear and work gloves when installing equipment.
• Never assume electrical power is disconnected. Check with meter and equipment.
• Keep hands out of fan areas when power is connected to equipment.
• R-22 causes frostbite burns.
• R-22 is toxic when burned.
NOTE TO INSTALLING DEALER: The Owners Instructions and Warranty are to be given to the owner
or prominently displayed near the indoor Furnace/Air Handler Unit.
P/No: 3828A22013N
DELUXE HIGH WALL MINI SPLIT
INSTALLATION INSTRUCTIONS
When wiring:
Electrical shock can cause severe personal injury or death. Only a qualified, experienced electrician should attempt to wire this system.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When transporting:
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your finger.
When installing...
... in a wall: Make sure the wall is strong enough to hold the unit's weight.
It may be necessary to construct a strong wood or metal frame to provide added support.
... in a room: Properly insulate any tubing run inside a room to prevent "sweating" that can cause
dripping and water damage to wall and floors.
... in moist or uneven locatinons: Use a raised concrete pad or concrete blocks provide a solid,
level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
... in an area with high winds: Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.
... in a snowy area(for Heat Pump Model): Install the outdoor unit on a raised platform that is
higher than drifting snow. Provide snow vents.
When connecting refrigerant tubing
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Check carefully for leaks before starting the test run.
When servicing
• Turn the power OFF at the main power box(mains) before opening the unit to check or repair
electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have
been left inside the unit being serviced.
Special warnings
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with local building codes or, in the absence of local codes, with the National Electrical Code NFPA 70/ANSI C1-1993 or current edition and Canadian Electrical Code Part1 CSA C.22.1.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
FRANÇAIS ESPAÑOL
2 Room Air Conditioner
Room Air Conditioner Installation Manual
TABLE OF CONTENTS
The following should be
always observed for safety ....................................3~6
Installation of indoor, outdoor unit .......................7~9
Flaring work and connection of piping.............10~13
Connecting the Cable between Indoor Unit and
Outdoor Unit ........................................................14~17
Checking the Drainage, Forming the Pipings
and Long pipe Setting ........................................18~19
Air Purging...........................................................20~21
Charging.....................................................................22
Test running...............................................................23
Level gaugeScrew driverElectric drillHole core drill (ø50mm)Horizontal meter
Flaring tool setSpecified torque wrenches
1.8kg.m, 4.2kg.m, 5.5kg.m, 6.6kg.m (different depending on model No.)
Spanner .................Half union
A glass of waterScrew driver
Hexagonal wrench(4mm)Gas-leak detectorVacuum pumpGauge manifold
Owner's manualThermometerHolder Remote Control
Installation Requirements
Required Tools
Installation Manual 3
ENGLISH
Installation Parts Provided
Installation Parts Provided
Type "A" screws and plastic anchors
Type "B" screws
Holder Remote Control
Installation plate
Standard Type
more than
70cm
(27.6 inch)
more than
30cm
(11.8 inch)
more than
30cm
(11.8 inch)
Air Outlet
Air Intake
(side, rear)
Connection pipe Drain hose
Connecting wire
Control cover
more than 30cm
(11.8 inch)
4 Room Air Conditioner
Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
Do not disassemble or repair the product. There is risk of fire or electric shock.
Always ground the product.
There is risk of fire or electric shock.
Install the panel and the cover of control box securely.
There is risk of fire or electric shock.
Always install a dedicated circuit and breaker.
Improper wiring or installation may cause fire or electric shock.
Use the correctly rated breaker or fuse.
There is risk of fire or electric shock.
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage.
WARNING
Be sure not to do.
Be sure to follow the instruction.
Safety Precautions
Installation
WARNING
CAUTION
Installation Manual 5
ENGLISH
Safety Precautions
Do not store or use flammable gas or combustibles near the product.
There is risk of fire or failure of product.
Do not modify or extend the power cable.
There is risk of fire or electric shock.
Be cautious when unpacking and installing the product.
Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator.
For installation, always contact the dealer or an Authorized Service Center.
There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
It may cause injury, accident, or damage to the product.
Be sure the installation area does not deteriorate with age.
If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
Moisture may condense and wet or damage furniture.
Operation
Gasolin
6 Room Air Conditioner
Safety Precautions
CAUTION
Installation
Always check for gas (refrigerant) leakage after installation or repair of product.
Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained away properly.
A bad connection may cause water leakage.
Keep level even when installing the product.
To avoid vibration or water leakage.
Do not install the product where the sound or hot air from the outdoor unit could be offensive to neighbors.
It may cause a problem for your neighbors.
Use two or more people to lift and transport the product.
Avoid personal injury.
Do not install the product where it will be exposed to salt spray directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
90°
Installation Manual 7
ENGLISH
Installation of Indoor, Outdoor Unit
Installation of Indoor, Outdoor Unit
Read completely, then follow step by step.
Indoor unit
1. Do not have any heat or steam near the unit.
2. Select a place where there are no obstacles in front of the unit.
3. Make sure that condensation drainage can be conveniently routed away.
4. Do not install near a doorway.
5. Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
6. Use a stud finder to locate studs to prevent unnecessary damage to the wall.
Outdoor unit
1. If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
2. Ensure that the spaces indicated by arrows around front, back and side of the unit.
3. Do not place animals and plants in the path of the warm air.
4. Take the air conditioner weight into account and select a place where noise and vibration are minimum.
5.
Select a place so that the warm air and sound from the air conditioner do not disturb neighbors.
Rooftop Installations:
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop mounting.
Select the best location
More than 5cm
(2.0 inch)
More than 5cm
(2.0 inch)
More than 2.3m
(90.6 inch)
More than 5cm
(2.0 inch)
CAUTION: Install the indoor unit on the wall where the height from the floors more than 2.3m(7.5ft).
more than 30cm
(11.8 inch)
more than 30cm
(11.8 inch)
more than 70cm
(27.6 inch)
8 Room Air Conditioner
Installation of Indoor, Outdoor Unit
Multi Piping Type
Piping length and elevation
36k
45m 15m 3m 7.5m 7.5m
(150ft) (50ft) (10ft) (25ft) (25ft)
Capacity(Btu/h)
Max total length
of all pipes
(A+B+C)
Max length of
each pipe
(A/B/C)
Min length of
each pipe
(A/B/C)
Max Elevation between each
indoor unit and
outdoor unit (h1)
Max elevation
between indoor
units (h2)
h2
h2
h1
h1
A
BC
Oil trap
h1
CAUTION: Capacity is based on standard length and maximum allowance length is on the basis of reliability. Oil trap should be installed every 5~7 meters (16.4~23.0ft).
12K 1/2" 1/4"
7.5m 30g/m
(25ft) (0.32oz/ft)
Gas Liquid Standard Length
Additional
Refrigerant
Indoor Capacity
(Btu/h)
Pipe Size
Loading...
+ 16 hidden pages