Exploded View & Replacement Parts List .............40
2Room Air Conditioner
Preface
Preface
This SERVICE MANUAL provides various service information, including the mechanical and electrical parts
etc. This room air conditioner was manufactured and assembled under a strict quality control system.
The refrigerant is charged at the factory. Be sure to read the safety precautions prior to servicing the unit.
Electronic Type
1. Unplug the power cord and connect a jumper between 2 pins (black and white).
2. The grounding conductor (green or green and yellow) is to be open.
3. Measure the resistance value with an ohm meter between the jumpered lead and each exposed metallic part on
the equipment at all Mode [except POWER OFF].
4. The value should be over 1MΩ.
Mechanical Type
1. Unplug the power cord and connect a jumper between 2 pins (black and white).
2. The grounding conductor (green) is to be open.
3. Measure the resistance value with an ohm meter between the jumpered lead and each exposed
metallic part on the equipment at all the positions (except OFF) of the ROTARY SWITCH.
4. The value should be over 1MΩ.
Service Manual 3
Safety Precautions
WARNING
CAUTION
WARNING
Gasolin
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must
be followed.
■ Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
■ Meanings of symbols used in this manual are as shown below.
Be sure not to do.
Be sure to follow the instruction.
■ Installation
Don’t use a power cord, a plug or
a loose socket which is damaged.
• Otherwise, it may cause a fire or
electrical shock.
Do not disassemble or modify
products.
• It may cause failure and electric
shock.
Always plug into a grounded
outlet.
• Otherwise, it may cause a fire or
electrical shock.
Be caution when unpacking and
installing.
• Sharp edges may cause injury.
Do not modify or extend the
power cord length.
• It will cause electric shock or fire
due to heat generation.
Do not use the power cord near flammable gas or combustibles such as
gasoline, benzene, thinner, etc.
• It may cause explosion or fire.
4Room Air Conditioner
■ Installation
Safety Precautions
Install the product so that the noise or hot wind
from the outdoor unit may not cause any damage
to the neighbors.
• Otherwise, it may cause dispute with the neighbors.
Keep level parallel in installing the product.
• Otherwise, it may cause vibration or water leakage.
Service Manual 5
Product Specifications
Product Specifications
FOR
LC6000/LC8000/LC1000Y3/LC1200Y3/LC6000Y4/LC8000Y4/LC1000Y4/LC1200Y4/LEA0610ACL/
LEA0810ACL/LEA1010ACLY3/LEA1210ACL/HBLG1000CY3
2 ROW 16 STACKS, SLIT FIN TYPE3 ROW 16 STACKS, SLIT FIN TYPE
1 ROW 23 STACKS,
SLIT FIN TYPE
LC6000Y4
6,0008,00010,00012,000
6308401,0501,260
5.87.79.611.5
LC8000
LEA0810ACL
LC8000Y4
115V, 60Hz
26.7(DB)* 19.4(WB)**
35(DB)* 23.9(WB)**
TURBO FAN
AXIAL FAN
LC1000Y3
LEA1010ACLY3
HBLG1000CY3
9.5
2 ROW 23 STACKS,
LOUVER FIN TYPE
2/3
LC1000Y4
LC1200Y3
LEA1210ACL
LC1200Y4
FAN MOTOR
OPERATION CONTROL
ROOM TEMP. CONTROL
AIR DIRECTION CONTROL
CONSTRUCTION
PROTECTOR
POWER CORD
DRAIN SYSTEM
NET WEIGHT(lbs/kg)
OUTSIDE DIMENSION(inch)
(W x H x D) (mm)
* DB:Dry Bulb
**
WB:Wet Bulb
COMPRESSOR
FAN MOTOR
6 POLES
ROTARY SWITCH
THERMOSTAT
VERTICAL LOUVER (RIGHT & LEFT)
HORIZONTAL LOUVER (UP & DOWN)
TOP-DOWN CHASSIS
OVERLOAD PROTECTOR
INTERNAL THERMAL PROTECTOR
3 WIRE WITH GROUNDING
ATTACHMENT PLUG (CORD-CONNECTED TYPE)
DRAIN PIPE SPLASHED BY FAN SLINGER
57/2666/3077/3579/36
141/2 x 201/2 x 233/5
368 x 521 x 607
6Room Air Conditioner
FOR
LV080CE/LV100CE/LV120CE/HBLG1004C
Product Specifications
MODELS
ITEMS
POWER SUPPLY
COOLING CAPACITY(Btu/h)
INPUT(W)
RUNNING CURRENT(A)
E.E.R(BTU/W.h)
OPERATING
CONDITION
INDOOR(°C)
OUTDOOR (°C)
REFRIGERANT (R-22) CHARGE
EVAPORATOR
CONDENSER
FAN, INDOOR
FAN, OUTDOOR
FAN SPEEDS, FAN/COOLING
FAN MOTOR
LV080CE
LV100CE
HBLG1004C
LV120CE
115V, 60Hz
8,00010,00012,000
8401,0501,260
7.79.611.5
9.5
26.7(DB)* 19.4(WB)**
35(DB)* 23.9(WB)**
300g(10.6 oz)445g(15.7 oz)510g(18.0 oz)
2 ROW 16 STACKS, SLIT FIN TYPE
3 ROW 16 STACKS, SLIT FIN TYPE
2 ROW 23 STACKS,
LOUVER FIN TYPE
TURBO FAN
AXIAL FAN
3/3
6 POLES
OPERATION CONTROL
ROOM TEMP. CONTROL
AIR DIRECTION CONTROL
CONSTRUCTION
PROTECTOR
COMPRESSOR
FAN MOTOR
POWER CORD
DRAIN SYSTEM
NET WEIGHT(lbs/kg)
OUTSIDE DIMENSION(inch)
(W x H x D) (mm)
* DB:Dry Bulb
**
WB:Wet Bulb
REMOTE CONTROLLER
THERMISTOR
VERTICAL LOUVER (RIGHT & LEFT)
HORIZONTAL LOUVER (UP & DOWN)
TOP-DOWN CHASSIS
OVERLOAD PROTECTOR
INTERNAL THERMAL PROTECTOR
3 WIRE WITH GROUNDING
ATTACHMENT PLUG (CORD-CONNECTED TYPE)
DRAIN PIPE SPLASHED BY FAN SLINGER
66/3077/3579/36
1
141/
2 x 20
/
2 x 23
3
/
5
368 x 521 x 607
Service Manual 7
NOTICE
Operation
VENTCLOSE
OPEN
Inlet Grille
Operation
Features
• Designed for COOLING ONLY.
• Powerful and whispering cooling.
• Simple installation and service.
• Low air-intake, top cooled-air discharge.
Control Locations
MECHANICAL TYPE MODEL
• VENTILATION
The ventilation lever must be in the CLOSE position
in order to maintain the best cooling conditions.
When a fresh air is necessary in the room, set the
ventilation lever OPEN position.
The damper is opened and room air is exhausted.
• TEMP
Thermostat will automatically control the temperature
of the room. Select a higher number for a cooler temperature in the room. The temperature is selected by
moving the knob to the desired position.
The 5 or 6 position is a normal setting for average
conditions.
• Built-in adjustable THERMOSTAT or THERMISTOR
• Washable one-touch filter
• Compact size
• Reliable and efficient rotary compressor is equipped.
• MODE
- Turns air conditioner off.
- Med speed fan operation without cooling.
- Low speed fan operation without cooling.
- Cooling with high speed fan operation.
- Cooling with med speed fan operation.
- Cooling with low speed fan operation.
Before using the air conditioner
secure the front grille with two screws
enclosed with the owner’s manual.
1. Open the inlet grille downward and remove the
air filter.
2. Fasten the front grille with screws.
3. Reinstall the air filter.
4. Close the inlet grille.
8Room Air Conditioner
ELECTRONIC TYPE MODEL
Power
Temp
Fan Speed
Timer Mode
1
2
4
3
5
°C
Dry
2
6
1
45
3
Operation
Precaution: The Remote Control unit will not function properly if bright light strikes the sensor window of the air conditioner or
if there are obstacles between the Remote Control unit and the air conditioner.
1. POWER
• To turn the air conditioner ON, push this button. To turn the
air conditioner OFF, push the button again.
4.
FAN SPEED
• Every time you push this button, it advances the setting as
follows: {High(F3) → Low(F1) → Med(F2) → High(F3)}
• This button takes priority over any other button.
• When you first turn it on, the unit is in cool mode, high fanspeed, temperature setting at 22˚C(72˚F).
5. TIMER
- SHUT-OFF TIME
• You will usually use shut-off time while you sleep.
2. TEMPERATURE SETTING
• Use this button to automatically control the temperature of
the room.
The temperature can be set within a range of 16˚C(60°F) to
30˚C(86°F) by increments of 1˚C(1°F).
• With unit running, use Timer to set number of hours until
shut-off.
• For your sleeping comfort, once Time is set, the
Temperature setting will raise 1°C(2°F) after 30 min, and
1°C(2°F) after another 30 min.
• Every time you push Timer button, it advances the Timer
3. MODE
- Every time you push this button, it will cycle through the following modes: COOL, ENERGY SAVER, FAN and DRY.
- ENERGY SAVER
• The fan stops when the compressor stops cooling.
Approximately every 3 minutes the fan will turn on and the
unit will check the room air to determine if cooling is needed.
AUTO RESTART
When power is restored after an electrical power failure, the unit will begin to run at its last setting.
setting as follows: 1 Hour → 2 Hours → etc. → 12 Hours
maximum.
- START TIME
• With unit not running, use timer to set number of hours
before unit starts.
• Every time you push Timer button, it advances the Timer
setting as follows: 1 Hour → 2 Hours → etc. → 12 Hours
maximum.
6. REMOTE CONTROL SENSOR
Service Manual 9
Disassembly Instructins
Inlet GrilleInlet Grille
Disassembly Instructions
— Before the following disassembly, set POWER SWITCH to OFF and disconnect the power cord.
Mechanical Parts
FRONT GRILLE
1. Open the inlet grille downward and remove the air
filter.
2. Remove the screws which fasten the front
grille.(See Figure 1)
3. Pull the front grille from the right side.
4. Remove the front grille.(There are 4 hooks.)
5. Re-install the components by referring to the
removal procedure, above.
CABINET
1. After disassembling the FRONT GRILLE, remove
the 6 screws which fasten the cabinet at both
sides.(See Figure 2)
2. Remove the 4 screws which fasten the cabinet at
back.
3. Remove the cabinet.
4. Re-install the components by referring to the
removal procedure, above.
Figure 1
CONTROL BOX
1. Remove the front grille. (Refer to section 2.1.1)
2. Remove the cabinet. (Refer to section 2.1.2)
3. Remove the 1 screw which fasten the power cord.
(See Figure 3)
4. Disconnect the grounding screw from the evaporator channel.
5. Remove the 2 screws which fasten the control
box.(See Figure 3)
6. Remove the housing which connects motor wire
in the control box.
7. Remove three leads which connect compressor.
8. Discharge the capacitor by placing a 20,000 ohm
resistor across the capacitor terminals.
9. Raise the control box upward completely.
10. Re-install the components by referring to the
removal procedure, above.
(Refer to the circuit diagram found on pages
29~32 in this manual and on the control box.)
Figure 2
10Room Air Conditioner
Figure 3
Air Handling Parts
AIR GUIDE AND TURBO FAN
1. Remove the front grille. (Refer to section 2.1.1)
2. Remove the cabinet. (Refer to section 2.1.2)
3. Remove the control box. (Refer to section 2.1.3)
4. Remove the 4 screws which fasten the brace.
5. Remove the brace.
6. Remove the 2 screws which fasten the upper air
guide. (See Figure 4)
7. Remove the upper air guide.
8. Remove the 2 screws which fasten the evaporator.
9. Move the evaporator forward and pulling it upward
slightly. (See Figure 5)
10. Remove orifice by pulling two taps.
11. Remove the clamp with a hand plier which
secures the turbo fan.
12. Remove the turbo fan. (See Figure 6)
13. Remove the motor. (Refer to section 2.3.7)
14. Remove the 2 screws which fasten the lower air
guide from the base pan.
15. Remove the 2 screws which fasten the motor
mount from the base pan.
16. Remove the 2 screws which fasten the lower air
guide and motor mount.
17. Move the lower air guide backward and pull out
from the base pan. (Move the lower air giude
carefully.)
18. Re-install the components by referring to the
removal procedure, above.
Disassembly Instructins
Figure 4
Figure 5
FAN
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the brace (Refer to section 2.2.1)
3. Remove 6 screws which fasten the condenser.
4. Move the condenser to the right carefully.
5. Remove the clamp with a hand plier which secures the
fan.
6. Remove the fan. (See Figure 7)
7. Re-install by referring to the removal procedure.
Figure 6
Figure 7
Service Manual 11
Disassembly Instructins
SHROUD
1. Remove the fan. (Refer to section 2.2.2)
2. Remove the shroud. (See Figure 8)
3. Re-install the components by referring to the
removal procedure, above.
Electrical Parts
OVERLOAD PROTECTOR
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the nut which fastens the terminal cover.
3. Remove the terminal cover. (See Figure 9)
4. Remove all the leads from the overload protector.
5. Remove the overload protector.
6. Re-install the components by referring to the
removal procedure, above.
Figure 8
COMPRESSOR
1. Remove the cabinet. (Refer to section 2.1.2)
2. Discharge the refrigerant system using a Freon
Recovery System.
If there is no valve to attach the recovery system,
install one (such as a WATCO A-1) before venting
the FreonTM. Leave the valve in place after
servicing the system.
3. Remove the overload protector. (Refer to section
2.3.1)
4. After purging the unit completely, unbraze the suction and discharge tubes at the compressor connections.
5. Remove the 3 nuts and the 3 washers which
fasten the compressor.
6. Remove the compressor. (See Figure 10)
7. Re-install the components by referring to the
removal procedure, above.
TM
Figure 9
Figure 10
12Room Air Conditioner
CAPACITOR
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the screw and the clamp which fastens the
capacitor.
3. Disconnect all the leads of capacitor terminals.
4. Re-install the components by referring to the
removal procedure, above. (See Figure 11)
POWER CORD
1. Remove the cabinet. (Refer to section 2.1.2)
2. Disconnect the grounding screw from the control
box.
3. Disconnect the 2 receptacles.
4. Remove a screw which fastens the clip cord.
(See Figure 12)
5. Remove the power cord.
6. Re-install the component by referring to the above
removal procedure, above.
(Use only one ground-marked hole for ground
connection.)
7. If the supply cord of this appliance is damaged, it
must be replaced by the special cord. (The
special cord means the cord which has the same
specification marked on the supply cord attached at
the unit.)
Disassembly Instructins
Figure 11
Mechanical Type
Figure 12
THERMOSTAT(For Mechanical Type)
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the 2 screws which fasten the thermostat.
3. Disconnect 2 leads of thermostat terminals.
4. Remove the thermostat.
5. Re-install the components by refering to the above
removal procedure. (See Figure 13)
THERMOSTAT(For Electronic Type)
1. Plug out thermistor from the main PCB.
ROTARY SWITCH
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the 2 screws which fasten the rotary
switch.
3. Disconnect all the leads of the rotary switch terminals.
4. Remove the rotary switch.
5. Re-install the components by referring to the
above removal procedure. (See Figure 14)
Electronic Type
Figure 13
Figure 14
Service Manual 13
Disassembly Instructins
MOTOR
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the turbo fan. (Refer to section 2.2.1)
3. Remove the fan. (Refer to section 2.2.2)
4. Remove the 4 screws which fasten the motor from
the Motor Mount. (See Figure 15)
5. Remove the motor.
6. Re-install the components by referring to the
removal procedure, above.(See Figure 15)
Refrigerating Cycle
CONDENSER
CAUTION
Discharge the refrigerant system using a
FreonTMRecovery System.
If there is no valve to attach the recovery
system, install one (such as a WATCO A-1)
before venting the FreonTM. Leave the valve in
place after servicing the system.
Figure 15
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the 4 screws which fasten the brace.
3. Remove the 4 screws which fasten the condenser
and shroud. (See Figure 16)
4. Remove the 2 screws which fasten the condenser
and base pan.
5. After discharging the refrigerant completely,
unbraze the interconnecting tube at the condenser
connections.
6. Remove the condenser.
7. Re-install the components by referring to notes.
(See Figure 16)
EVAPORATOR
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the control box.(Refer to section 2.1.3)
3. Remove the upper air guide. (Refer to section
2.2.1)
4. Remove the 2 screws which fasten the evaporator
from lower air guide.
5. Move the evaporator sideways carefully.
(Refer to section 2.2.1)
6. After discharging the refrigerant completely,
unbraze the interconnecting tube at the evaporator
connections.
7. Remove the evaporator.
8. Re-install the components by referring to notes.
(See Figure 17)
Figure 16
Figure 17
14Room Air Conditioner
Loading...
+ 32 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.