Lg Lbne4880hl, Lbue4880hl Installation Guide

Page 1
ENGLISH
CEILING DUCT TYPE AIR CONDITIONERS
INSTALLATION INSTRUCTIONS
• Please read this instruction sheet completely before installing the product.
• When the power cord is wanted to replace, replacement work shall be performed by authorized personnel only.
• Installation work must be performed in accordance with national wiring standards by authorized personnel only.
Air filters
Remote Controller
(Side)
(Rear)
Air intake vents
Air intake vents
Air outlet vents
Piping Drain hose
Connecting wire
Control cover
Air outlet vents
(Side)
(Rear)
Air outlet
vents
Air intake
vents
Connecting Wire
Drain Hose
Connection Pipe
Control Cover
Indoor Unit
Outdoor Unit
ENGLISH ITALIANO ESPAÑOL FRANÇAIS DEUTSCH
(1)A30021V(· ˘ fi¿ ) 1994.12.31 2:11 PM ˘`1
Page 2
1.The following should be always observed for safety...............................3
2. Installation of Indoor, Outdoor unit
3. Connecting Pipes to the Indoor Unit
4. Connecting Pipes to the Outdoor Unit
5. Checking the Drainage..............................................................................14
6. Connecting Cables between Indoor Unit and Outdoor Unit
7. Air Purging of the Connecting Pipes and the Indoor Unit ....................18
OUT-LINE OF INSTALLATION
Installation works Installation Parts Required tools
1)
Selection of the best location
............................4
2) Indoor unit installation....5
Four Type “A” screws
Connecting cable
Level
Screw driver
Electric drill
Hole core drill (ø70mm)
1) Preparation of Piping...12
Pipes: Gas side .....
1
/2", 5/8", 3/4"
Liquid side .............
1
/4", 3/8", 1/2"
Insulated drain hose
Insulation materials
Flaring Tools set
1) Connecting the pipes to
the Outdoor Unit..........14
Additional Drain hose
(Inner Dia...............25mm)
1) Connecting cables to the
Indoor Unit...................15
2) Connecting cables to the
Outdoor Unit ................16
3) Form the pipings..........17
Screw driver
Hexagonal Wrench (4mm/5mm)
Gas-leak Detector
2
(1)A30021V(· ˘fi¿ ) 1994.12.31 2:11 PM ˘`2
Page 3
ENGLISH
3
1. The following should be always observed for safety
• Please report to or take consent by the supply authority before connecting to the system.
• Be sure to read "THE FOLLOWING SHOULD BE ALWAYS OBSERVED FOR SAFETY" before installing the air conditioner.
• Be sure to observe the cautions specified here as they include important items related to safety.
• The indications and meanings are as follows.
• After reading this manual, be sure to keep it together with the instruction manual in a handy place .
Could lead to death, serious injury, etc.
Do not install it yourself (customer).
Perform the installation securely referring to the installation manual.
Install the unit securely in a place which can bear the weight of the unit.
Perform electrical work according to the installation manual and be sure to use an exclusive circuit.
Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely.
Be sure to use the part provided or specified parts for the installation work.
Check that the refrigerant gas do not leak after installation is completed.
Perform the drainage/piping work securely according to the installation manual.
Use the specified wires to connect the indoor and the outdoor units securely and attach the wires firmly to the terminal board connecting sections so the stress of the wires is not applied to the sections.
• Incomplete installation could cause injury due to fire, electric shock,
the unit falling or a leakage of water. Consult the dealer from whom you purchased the unit or special installer.
• Incomplete installation could cause a personal injury due to fire, electric shock, the unit falling or a leakage of water.
• When installed in an insufficient strong place, the unit could fall causing injured.
• Incomplete connecting and fixing could cause fire.
• If the capacity of the power circuit is insufficient or there is incomplete electrical work, it could result in a fire or an electric shock.
• The use of defective parts could cause an injury or leakage of water due to a fire, electric shock, the unit falling, etc.
• If there is a defect in the drainage/piping work, water could drop from the unit and household goods could be wet and damaged.
Do not install the unit in a place where an inflammable gas leaks.
• If gas leaks and accumulates in the area surrounding the unit, it could cause an explosion.
• If the electrical part cover if the indoor unit and/or the service panel if the outdoor unit are not attached securely, it could result in a fire or electric shock due to dust, water, etc.
Could lead to serious injury in particular environments when operated incorrectly.
WARNING
WARNING
CAUTION
CAUTION
(1)A30021V(· ˘fi¿ ) 1994.12.31 2:11 PM ˘`3
Page 4
4
Indoor unit
Outdoor unit
B
A
H
600600
Top view
(unit: mm)
Front view
Front
Inspection hole
(600X600)
Control box
1000
1. Selection of the best location
1) Indoor unit
Select location
Install the air conditioner in the location that satisfies the following conditions.
• The place shall easily bear a load exceeding four times the indoor unit’s weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.(Suitable dimension “H” is necessary to get a slope to drain as figure.)
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical noise.
• The place where air circulation in the room will be good .
• There should not be any heat source or steam near the unit.
2) Outdoor unit
• If an awning is built over the unit to prevent direct sunlight or rain exposure, be careful that heat radiation from the condenser is not restricted.
• There should not be any animals or plants which could be affected by hot air discharged.
• Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
3) Piping length and the elevation
2. Installation of Indoor, Outdoor Unit
• If 18K Model is installed at a distance of 15m, 400g of refrigerant should be added (15-5) x 40g = 400g
• Capacity is based on standard length and maximun allowance length is on the basis of reliability.
Capacity
18K BTU/h 5/8" 1/4" 5 15 24K BTU/h 5/8" 3/8" 5 15 36K BTU/h 5/8" 3/8" 5 25 48K BTU/h 3/4'' 1/2'' 5 30 60K BTU/h 3/4'' 1/2'' 5 30
Gas Liquid
5 8 40 5 8 60 5 15 70 5 30 70 5 30 70
Elevation B(m)
Length A(m)
* Additional
refrigerant
(g/m)
Pipe Size
(Diameter: Ø)
Standard
Standard
Max.
Max.
(1)A30021V(· ˘fi¿ ) 1994.12.31 2:11 PM ˘`4
More than 30cm
Fence or
obstacles
Sunroof
More than 30cm
More than 70cm
Page 5
ENGLISH
2. Indoor unit installation
Installation of Unit
Install the unit above the ceiling correctly.
• Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
• Apply a filter Accessory at air return hole.
• Install the unit leaning to a drainage hole side as a figure for easy water drainage.
• A place where the unit will be leveled and that can support the weight of the unit.
• A place where the unit can withstand its vibration.
• A place where service can be easily performed.
5
CASE 1
POSITION OF SUSPENSION BOLT
CASE 2
POSITION OF CONSOLE BOLT
(Unit:mm)
Drainage hole
M10 Nut M10 SP. washer M10 washer
X 4 X 4
(Local supply)
X 4
M10 Nut
M10 SP. washer
M10 washer
X 4 X 4
(Local supply)
X 4
A B
C
1-3 mm
D
(G)
H
I
EF
A B C D E F (G) H I
18K BTU/h
942 880 466 54 575 30 87 750 186
24K BTU/h
942 880 466 54 575 30 87 750 186 1072 1010 492 54 600 30 87 750 186 1242 1180 492 54 600 30 87 830 186 1292 1230 650.5 54 760 30 120 1006 294 1292 1230 570.5 54 680 30 120 1006 294 1292 1230 650.5 54 760 30 120 1006 294 1292 1230 570.5 54 680 30 120 1006 294
Dimension
Capacity
36K BTU/h
(LB-C36)
36K BTU/h
(LB-F36)
48K BTU/h
(LB-B48)
60K BTU/h
(LB-B60)
48K BTU/h
(LB-E48)
60K BTU/h
(LB-E60)
(1)A30021V(· ˘fi¿ ) 1994.12.31 2:11 PM ˘`5
Page 6
6
• Select and mark the position for fixing bolts.
• Drill the hole for set anchor on the face of ceiling.
• Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling.
• Mount the suspension bolts to the set anchor firmly.
• Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.
1 Set anchor
Old building New building
2 Plate washer 3 Spring washer
4 Nut 5 Suspension
bolts
Tighten the nut and bolt to prevent unit falling
CAUTION
• Local supply
¤ Set anchor ¤Ł Plate washer - M10 ¤Ø Spring washer - M10 ¤Œ Nut - W3/8 or M10 ¤º Suspension bolt - W3/8 or M10
(1)A30021V(· ˘fi¿ ) 1994.12.31 2:11 PM ˘`6
Page 7
ENGLISH
Ceiling
CAUTION
1~3mm
Drainage hole
Drainage holeMake sure to be closed.
Unit
Drainage pipe (Local supply)
Thermal insulator
(Local supply)
Drainage hole
7
Front of view
CAUTION FOR GRADIENT OF UNIT AND DRAIN PIPING
Lay the drain hose with a downward inclination so water will drain out.
• Alway lay the drain with downward inclination (1/50 to 1/100). Prevent any upward flow or reverse flow in any part.
• 5mm or thicker formed thermal insulator shall always be provided for the drain pipe.
1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 5mm.
• The unit must be horizontal or declined to the drain hose connected when finished
installation.
CORRECT
CORRECT
INCORRECT
INCORRECT
• Upward routing not allowed
(1)A30021V(· ˘fi¿ ) 1994.12.31 2:11 PM ˘`7
Page 8
8
• Drill the piping hole with 70mm dia, hole core drill.
• Piping hole should be slightly slant to the outdoor side.
INSULATION, OTHERS
Insulate the joint and tubes completely.
All thermal insulation must comply with local requirement.
INDOOR UNIT
REFRIGERANT PIPE
• Insulate and tape both the gas piping and liquid piping.
After all workings are finished, check the working and operation.
• Air distribution Is the air circulation good?
• Drain Is the drainage smoothly and no sweating?
• Gas leakage Is the piping connection correctly?
• Wiring Is the wiring connection correctly?
• Lock-bolt Is the lock-bolt of compressor loosened?
THERMAL INSULATION
TEST AND CHECK
Make sure that there is no clearance here.
Overlap with thermal insulator for piping.
Thermal insulator for refrigerant pipe (Local supply)
Thermal insulator for piping(Local supply)
Hose crip for thermal insulator(Local supply)
Union for liquid pipe
Refrigerant pipe and thermal insulator(Local supply)
Union for gas pipe
Thermal insulator for refrigerant pipe (Local supply)
Hose crip for thermal insulator (Local supply)
Power cable
Liquid pipe
Thermal insulator
Gas pipe
Tape
(1)A30021V(· ˘fi¿ ) 1994.12.31 2:11 PM ˘`8
Indoor Outdoor
WALL
5~7mm
Page 9
ENGLISH
9
INSTALLATION OF REMOTE CONTROL BOX
Install the remote control box and cord correctly.
• Although the room temperature sensor is in the indoor unit, the remote control box should be installed in such places away from direct sunlight and high humidity.
INSTALLATION OF THE REMOTE CONTROL BOX
• Select places that is not splashed by water.
• Select control position after receiving customer approval.
• The room temperature sensor of the thermostat for temperature control is built in the indoor unit.
• This remote controller equipped with liquid crystal display. If this position is higher or lower, display is difficult to see. (The standard height is 1.2~1.5m high)
ROUTING OF THE REMOTE CONTROL CORD
• Keep the remote control cord away from the refrigerant piping and the drain piping.
• To protect the remote control cord from electrical noise, place the cord at least 5cm away from other power cables. (Audio equipment, Television set, etc)
• If the remote control cord is secured to a wall, provide a trap at the top of the cord to prevent water droplets from running.
POINT OF REMOTE CONTROLLER INSTALLATION
DISASSEMBLING OF THE REMOTE CONTROLLER
ELECTRICAL WIRING TO THE INDOOR UNIT
FIXING OF REMOTE CONTROL CORD
1. Fix the cord clamps on the wall by ø3 tapping screws(Local supply).
2. Fix the remote control cord.
PROCEDURE OF INSTALLATION
1. Fix the under plate on the switch box by screws(Local supply). In this case, fit the under plate on the wall, and be careful of deformation.
2. Receive the remote control cord in the switch box.
3. Hook the remote control unit on the under plate.
WHEN THE REMOTE CONTROL BOX IS
INSTALLED WITH THE CORD BURIED.
PROCEDURE OF INSTALLATION
1. Fix the under plate on the wall by self tapping screws (accessory).
2. Make a slit (Part A) at the top side of the remote control box by nipper.
3.Rout the cord as shown in the following figure. In
this case, push the cord into the around of case(Part B).
4. Hook the remote control unit on the under plate.
WHEN THE REMOTE CONTROL BOX IS INSTALLED WITH THE CORD EXPOSED.
(1)A30021V(· ˘fi¿ ) 1994.12.31 2:11 PM ˘`9
Remote controller
Yellow, Red, Brown
If the length of the cord exceeds 50m, use a wire size greater than 0.5mm
The lower part
Lever carefully
the box open
using a screw
driver, etc.
Face of wall Upper notch
Under plate Remote
control unit Screw
(Local supply) Remote
control cord Lower notch Switch box
(Local supply)
Be sure to connect the wires to CN REMO
The maximum length of the cord is 100m.
Front case
Remote control
box body
(Main board)
CN REMO
Make sure that wire and terminal numbers are matched on unit side and remote controller side.
2
.
Face of wall
Remote
control cord
(Part A)
Remote
control unit
Upper notch
Under plate
Tapping screw
(Local supply)
Upper flange
Push hand
(Part B)
Lower notch
Cord
clamp
Page 10
10
Flared connection (Union)
Flared connection (Service valve, Ball valve)
Use a seemliness tube
Factory charged
Indoor
Outdoor
REFRIGERANT PIPING
INSTALLATION OF OUT DOOR UNIT
Perform the work according to the Service Manual or Installation Guide.
Select a location that satisfies the following conditions. Install the unit firmly in place.
Select the following location
• A place where the air conditioner can get good ventilation.
• A place where it shall not annoy the neighbors.
• A place where the unit shall be leveled and that can support the weight of unit and withstand its vibrations.
Keep a maintenance space
• Use two spanners when connect the refrigerant pipe to the unit.
• Make a bend with a radius as large as possible.
• Perform air purge with R-22 or vacuum drying.
• When piping work is finished, check all joints.
Add refrigerant if piping is over 5m.
Above 70Cm
Above 30Cm
Outdoor unit
Above 30Cm Above 50Cm
Face of wall
Capacity Addition volume 18K BTU/h 40 g/m 24K BTU/h 60 g/m 36K BTU/h 70 g/m 48K BTU/h 70 g/m 60K BTU/h 70 g/m
(1)A30021V(· ˘fi¿ ) 1994.12.31 2:11 PM ˘`10
Page 11
ENGLISH
Outdoor
Indoor
Control terminal board Control box
Control box cover
(On which the Electric
Wiring Connection is put)
Main terminal board Control terminal board
Cord clamper
Cover control
A A view
Remote control cord
Connection cord between the indoor unit and the outdoor unit
Cord clamper
1
1
Main power source
Switch box
Circuit Breaker
11
ELECTRICAL WIRING
INDOOR UNIT
• Remove the control box cover for electrical connection between the indoor and outdoor unit.(Remove two screws .)
• Use the cord clamper to fix the cord.
Perform the electrical wiring work according to the electrical wiring connection.
• All wiring must comply with local requirements.
• Select a power source that is capable of supplying the current required by the air conditioner.
• Use a recognized circuit breaker between the power source and the unit. A disconnection device to adequately disconnect all supply lines must be fitted.
• Capacity of circuit breaker
WIRING CONNECTION
OUTDOOR UNIT
• Remove the control cover for wiring
connection.
• Use the cord clamper to fix the cord.
• Earthing work
Connect the cable of diameter 1.6mm
2
or more to the earthing terminal provided in the control box and do earthing.
¡ Please check !!
Capacity 1 Phase 3 Phase 18K BTU/h 25A ­24K BTU/h 25A ­36K BTU/h 35A 25A 48K BTU/h 50A 35A 60K BTU/h 50A 35A
(1)A30021V(· ˘fi¿ ) 1994.12.31 2:11 PM ˘`11
Page 12
12
3-1. Preparation of Piping
3. Connecting Pipes to the Indoor Unit
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.
1) Cut the pipes and the cable.
Use the accessory piping kit or the pipes purchased locally.
Measure the distance between the indoor and the outdoor unit.
Cut the pipes a little longer than measured distance.
Cut the cable 1.5m longer than the pipe length.
2) Burrs removal
Completely remove all burrs from the cut cross section of pipe/tube.
Put the end of the copper tube/pipe to downward direction as you remove burrs in order to avoid to let burrs drop in the tubing.
3) Putting nut on
Remove flare nuts attached to indoor and outdoor units, than put them on pipe/tube having completed burr removal. (Not possible to put them on after flaring work)
4) Flaring work
Carry out flaring work using flaring tool as shown below.
Firmly hold copper tube in a bar(or die) as indicated dimension in the table above.
5) Check
Compare the flared work with figure.
If flare is noted to be defective, cut off
the flared section and do flaring work again.
Copper
tube
90°
Slanted Uneven Rough
Pipe
Reamer
Point down
Flare nut
Copper tube
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shining without scratches.
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Outside Diameter
" A "
Gas Liquid Gas
Liquid 60K BTU/h 3/4" 1/2" 1.0~1.3 0.5~0.8 48K BTU/h 3/4" 1/2" 1.0~1.3 0.5~0.8 36K BTU/h 5/8" 3/8" 0.8~1.0 0.5~0.8 24K BTU/h 5/8" 3/8" 0.8~1.0 0.5~0.8 18K BTU/h 5/8" 1/4" 0.5~0.8 0~0.5
Capacity
(1)A30021V(· ˘fi¿ ) 1994.12.31 2:12 PM ˘`12
Page 13
ENGLISH
6) Pipe bending
Annealed copper pipe with small diameter (ø6.35 or ø9.52) can be easily bent manually. In this case, secure large R(radius) for the bend section and gradually bend pipe. If annealed copper pipe is large in diameter (ø15.88 or ø19.05), bend pipe with bender. Use bender appropriate for the pipe diameter.
7)
Brazing
In refrigerant piping, bending (in particular, acute bending) must be minimized to reduce piping resistance. Bending is, however, necessary in some places by virtue of the installation position of devices auxiliary to the packaged air conditioner, or of the building structure, piping distance or finsishing appearance. If a more acute bend is required than that attainable by pipe bender, perform brazing using ready-made elbow. Aside from this function, brazing also serves to connect straight pipes, generally using ready-made sockets. While brazing, protect piping against heat with wet cloth to avoid damaging valve packing or burning thermal insulator with burner heat. While brazing, blow inert gas (nitrogen gas or carbonic gas) to prevent formation of oxidation film in copper piping; otherwise, the refrigerant circuit will clog. The blowing of nitrogen gas (or carbonic gas) through 3-way valves is described in the following:
8)
Refrigerant piping(Flare piping)
When connecting piping, be sure to keep piping dry(keep piping away from water), clean (keep piping away from dust) and airtight (avoid refrigerant leakage). When connecting piping on rainy days or making a through-hall in wall, take due care to prevent water or plaster from entering piping.
13
CAUTION
a. This procedure is designed to prevent
formation of oxidation film by filling piping with inert gas. Note that excessive gas pressure will generate pinholes at brazed points. (Nitrogen gas: Supply pressure
0.05~0.1kg/cm
2
G)
b. When supplying inert gas, be sure to open
one end of piping.
Water enters Plaster enters
(1)A30021V(· ˘fi¿ ) 1994.12.31 2:12 PM ˘`13
Page 14
1) Connecting the pipes to the Outdoor unit
1. Align the center of the pipings and
sufficiently tighten the flare nut with fingers.
2. Finally, tighten the flare nut with torque
wrench until the wrench clicks.
• When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
1) Checking the Drainage
1. Remove the Air Filter.
2. Check the drainage.
• Spray one or two glasses of water upon the evaporator.
• Ensure that water flows drain hose of indoor unit without any leakage.
4. Connecting Pipes to the Outdoor Unit
5. Checking the Drainage
14
Liquid side piping (Smaller Dia.)
Gas side piping (Bigger Dia.)
Torque wrench
Outdoor unit
Pipe size Torque
1/4" 1.8kg.m 3/8" 4.2kg.m 1/2" 5.5kg.m
Gas Side 5/8" 6.6kg.m
3/4" 6.6kg.m
Liquid Side
(1)A30021V(· ˘fi¿ ) 1994.12.31 2:12 PM ˘`14
Page 15
ENGLISH
1) Connecting cables to the Indoor Unit
Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as
those of indoor unit respectively
60K/48K/36K Btu
24K/18K Btu
2) Clamping of cables
1) Arrange 2 power cables on the control panel.
2) First, fasten the steel clamp with a screw to the inner boss of control panel.
3) For the cooling model, fix the other side of the clamp with a screw strongly.
For the heat pump model, put the 0.75mm2cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control panel.
4) In Australia, the length of power supply cord measured from the entry of the power supply
cord to the middle of live pin on the power plug should be over 1.8m.
POWER INPUT
• Cooling & Heating type
• Cooling only type (380-415V3N~) (220/240V~)
Terminals on the indoor unit
1 2 4 53
Terminals on the outdoor unit
1 2 4 53
POWER INPUT
POWER INPUT
• Cooling only type
Terminals on the indoor unit
1(L) 2(N) 4(N) 53(L)
Terminals on the outdoor unit
4(N) 5 63(L)
1(L) 2(N) 4(N) 5 6 7 83(L)
4(N) 5 6 73(L)
Terminals on the indoor unit
1 2 4 53
• Cooling & Heating type
Terminals on the indoor unit
Terminals on the outdoor unit
Terminals on the outdoor unit
1 2 4 53
1(L) 2(N)
POWER INPUT
R S T N
Capacity 18K BTU/h 24K BTU/h 36K BTU/h 48K BTU/h 60K BTU/h
1 Phase
2.5mm
2
2.5mm
2
5.5mm
2
8.5mm
2
8.5mm
2
3 Phase
-
-
2.5mm
2
3.5mm
2
5.5mm
2
The power cord connected to the outdoor unit should be complied with the following specifications (Rubber insulation, type H05RN-F approved by HAR or SAA).
The connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (Rubber insulation, type H05RN-F approved by HAR or SAA).
CAUTION
20mm
GN/YL
NORMAL CROSS-SECTIONAL AREA
NORMAL CROSS-SECTIONAL AREA 0.75mm
2
(18K/24K/36K)
1.25mm
2
(48K/60K)
20mm
GN/YL
15
6. Connecting Cables between Indoor Unit and Outdoor Unit
If the supply cord is damaged, it must be replaced by a special cord or assembly availible from the manufacturer of its service agent.
Make sure that the screws of the terminal are free from looseness.
(1)A30021V(· ˘fi¿ ) 1994.12.31 2:12 PM ˘`15
WARNING
Page 16
3) Connecting the cable to the Outdoor Unit
1. Remove the Cover control from the unit
by loosening a screw. Connect the wires to the terminals on the control board individually as following.
2. Secure the cable onto the control board
with the holder (clamper).
3. Refix the cover control to the original
position with the screw.
16
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device.
• Proper starting power is not given to the compressor.
(1)A30021V(· ˘fi¿ ) 1994.12.31 2:12 PM ˘`16
Outdoor unit
Over 5mm
Terminal block Cord Clamper
Power supply cord
Cover control
Page 17
ENGLISH
4) Form the pipings
1. Wrap the connecting portion of indoor unit with the Insulation material and secure it with two Plastic Bands. (for the right pipings)
• If you want to connect an additional drain hose, the end of the drain-outlet should keep distance from the ground. (Do not dip it into water, and fix it on the wall to avoid swinging in the wind.)
2. Tape the Pipings, drain hose and Connecting Cable from bottom to top.
3. Form the pipings gathered by taping along the exterior wall and fix it onto the wall by saddle or equivalent.
2. Tape the Pipings and Connecting cable from bottom to top.
3. Form the pipings gathered by taping along the exterior wall, and make the trap prevent water from entering into the room.
4. Fix the pipings onto the wall by saddle or equivalent.
17
In case of the Outdoor unit being installed below position of the Indoor unit.
In case of the Outdoor Unit being installed above position of the Indoor Unit.
(1)A30021V(· ˘fi¿ ) 1994.12.31 2:12 PM ˘`17
Seal a small opening around the pipings with gum type sealer.
Drain hose
Taping
Pipings
Connecting cable
Power supply cord
Trap is required to prevent water from entering into electrical parts.
Seal a small opening around the pipings with gum type sealer.
Trap
Page 18
The air which contains moisture remaining in the refrigeration cycle may cause a malfunction on the compressor.
1. Remove the caps from the gas side and liquid side valves.
2. Remove the service-port cap from the gas side valve.
3. Turn the valve stem of liquid side valve counterclockwise approx. 90° and hold it there for ten seconds, then close it.
4. Check a gas-leakage of the connecting portion of the pipings.
CAUTION : Do not leak the gas in the air
during air purging. Use vacuum pump as far as possible.
7. Air Purging of the Connecting Pipes and the Indoor Unit
18
No leakage found leakage foundResult
leakage persists
leakage ceased
leakage ceased
Outdoor unit
Cover control
To indoor unit Liquid side
Gas side
2-way valve or
3-way valve
(open)
3-way valve
(Close)
Cap
Service port cap
Hexagonal wrench
5. To open liquid side valve again, turn the valve stem counterclockwise until it stops.
6. To purge the air, push the pin on the service port of gas side valve for three seconds with a hexagonal wrench and set it free for one minute. Repeat this three times.
• Re-tighten the connecting portion with torque wrenches.
Repair
7. Set the both liquid and gas side valves to open position with the hexagonal wrench for the unit operation.
NOTE:
The additional gas for air purging has been charged in the outdoor unit. However, if the flare connections have not been done correctly and there gas leaks, a gas cylinder and the charge set will be needed.
CAUTION : Do not leak the gas in the air during air purging.
(1)A30021V(· ˘fi¿ ) 1994.12.31 2:12 PM ˘`18
Loading...