Lg Hmc018kd1 Service Manual

Multi Type Room Air Conditioner
SERVICE MANUAL
MODEL: LM-1830C2L/M/N
LM-1830H2L/M/N LM-2430C2L/M/N LM-2430H2L/M L2-C243AL1
Refrigeration Cycle Diagram..................................................................................................... 11
Wiring Diagram .......................................................................................................................... 12
Operation Details ....................................................................................................................... 13
Display Function........................................................................................................................ 20
Self-diagnosis Function ............................................................................................................ 20
Installation.................................................................................................................................. 21
Operation.................................................................................................................................... 35
Disassembly of the parts (Indoor Unit).................................................................................... 37
2-way, 3-way Valve..................................................................................................................... 39
Cycle Troubleshooting Guide ....................................................................................................43
Electronic Parts Troubleshooting Guide.................................................................................. 45
Electronic Control Device ......................................................................................................... 52
Schematic Diagram.................................................................................................................... 55
Exploded View and Replacement Parts List............................................................................ 57
- 2 -
Contents
• Room temperature sensor. (THERMISTOR)
• Maintains the room temperature in accordance with the Setting Temp.
• Indoor fan is delayed for 5 seconds at the starting.
• Restarting is inhibited for approx. 3 minutes.
• High, Med, Low, Chaos
--- Lights up in operation
--- Lights up in Sleep Mode
--- Lights up in Timer Mode
--- Lights up in Deice Mode(for Heat pump model)
---
Lights up in Compressor operation(for Cooling model)
• Intermittent operation of fan at low speed.
• The fan is switched to low(Cooling), med(Heating) speed.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
• The fan is switched to intermittent or irregular operation
The fan speed is automatically switched from high to low speed.
• The louver can be set at the desired position or swing up and down automatically.
- 3 -
Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Time Delay Safety Control
Indoor Fan Speed Control
Operation indication Lamps (LED)
OUT
DOOR
Health Dehumidification Operation
• Both the indoor and outdoor fan stops during deicing.
• Hot start after deice ends.
• The indoor fan stops until the evaporator piping temperature will be reached at 28°C.
Sleep Mode Auto Control
Natural Air Control by CHAOS Logic
Airflow Direction Control
Deice (defrost) control (Heating)
Hot-start Control (Heating)
Outdoor unit operation
Soft Dry Operation Mode
• The function will be operated while in any
operation mode with selecting the function.
• The function is to be stopped while it is
operating with selecting the function.
Intermittent operation of fan at low speed.
PLASMA
- 4 -
Remote Controller
JET COOL
Healthy Dehumidification Operation Mode.
()
Operation Mode Selection
(Cooling
model only)
(Heating
model only)
Cooling Operation Mode.( )
Heating Operation Mode.( )
Auto Operation Mode.( )
Sleep Operation
˚C To ˚F Swtiching Button
Room, Temperature Display
Setting the Time or Timer
Airflow Direction Control
Operation ON/OFF
Temperature Setting
TEMPERATURE
LOWHIGH
Timer Selection
ON OFF
˚C / ˚F
Timer Setting
SET
Timer Cancel
CANCEL
Fan Operation Mode
Reset
Fan Speed Selection
(Low) (Med) (High) (CHAOS)
Down to 18°C(64˚F) Up to 30°C(86˚F)
Cooling
: Cancel Sleep Mode, Timer ON or Timer OFF
: 1, 2, 3, 4, 5, 6, 7, Off Timer
: Fan Operates without cooling or heating.
: High: 39°C(102˚F) LOW : 11°C(52˚F)
Down to 16°C(60˚F) Up to 30°C(86˚F)
Heating
: OFF, ON, OFF ON
- 5 -
Product Specifications
1. LM-1830C2L/M
17,000/18,000 8,500/9,000 8,500/9,000 208/230V
––
2.4 1.2 1.2 at 230V 1Ø, 208/230V, 60Hz
Indoor 7.0 7.0
Outdoor 42
Indoor 39/37/35 39/37/35
at 230V
Outdoor 53
1,680/1,700 930/950 930/950
––
8.2/7.5 4.5/4.0 4.5/4.0 208/230V
––
10.1/10.6 9.1/9.5 9.1/9.5
––
Indoor 802 x 262 x 165
Outdoor 870 x 655 x 320
Indoor 7
Outdoor 61
Liquid 6.35(1/4")
Gas 9.52(3/8")
780 780 at 7.5m
O
L.C.D Wireless
O O
Operation
A-Unit
Only
B-Unit
Only
A-Unit + B-Unit
Remarks
Unit
Item
Cooling Capacity Heating Capacity Moisture Removal /h Power Source ø, V, Hz
Air Circulation /min
Noise Level dB(A)
Input W
A
E.E.R. Btu/h.w C.O.P. -
Dimensions(W x H x D)
mm
Net. Weight kg
Service Valve mm(Inch)
Refrigerant(R-22) g Airflow Direction Control(Up & Down) Remote Controller Type Sleeping Operation Drain Hose
Cooling Heating Cooling Heating
Cooling
Heating
Running
Current
Btu/h(kcal/h)
( Hi / Med / Low )
- 6 -
2. LM-1830H2L/M
17,000/18,000 8,500/9,000 8,500/9,000
208/230V
17,000/18,000 8,500/9,000 8,500/9,000
2.4 1.2 1.2 at 230V 1Ø, 208/230V, 60Hz
Indoor 7.0/7.6 7.0/7.6
Cooling/Heating
Outdoor 42
Indoor 39/37/35 39/37/35
at 230V
Outdoor 53
1,680/1,700 930/950 930/950 1,680/1,700 930/950 930/950
8.2/7.5 4.5/4.0 4.5/4.0 208/230V
8.2/7.5 4.5/4.0 4.5/4.0
10.1/10.6 9.1/9.5 9.1/9.5
2.97/3.10 2.68/2.78 2.68/2.78
Indoor 802 x 262 x 165
Outdoor 870 x 655 x 320
Indoor 7
Outdoor 63
Liquid 6.35(1/4")
Gas 9.52(3/8")
780 780 at 7.5m
O
L.C.D Wireless
O O
Operation
A-Unit
Only
B-Unit
Only
A-Unit + B-Unit
Remarks
Unit
Item
Cooling Capacity Heating Capacity Moisture Removal /h Power Source ø, V, Hz
Air Circulation /min
Noise Level dB(A)
Input W
A
E.E.R. Btu/h.w C.O.P. -
Dimensions(W x H x D)
mm
Net. Weight kg
Service Valve mm(Inch)
Refrigerant(R-22) g Airflow Direction Control(Up & Down) Remote Controller Type Sleeping Operation Drain Hose
Cooling
Heating
Cooling
Heating Cooling
Heating
Running
Current
Btu/h(kcal/h)
( Hi / Med / Low )
- 7 -
3. LM-2430C2L/M
23,600/24,000 11,800/12,000 11,800/12,000 208/230V
––
3.4 1.7 1.7 at 230V 1Ø, 208/230V, 60Hz
Indoor 8.0 8.0
Outdoor 42
Indoor 40/38/36 40/38/36
at 230V
Outdoor 54
2,400/2,400 1,300/1,300 1,300/1,300
––
11.0/10.0 6.2/5.7 6.2/5.7 208/230V
––
9.8/10.0 9.1/9.2 9.1/9.2
––
Indoor 888 x 287 x 170
Outdoor 870 x 655 x 320
Indoor 7
Outdoor 61
Liquid 6.35(1/4")
Gas 12.7(1/2")
880 880 at 7.5m
O
L.C.D Wireless
O O
Operation
A-Unit
Only
B-Unit
Only
A-Unit + B-Unit
Remarks
Unit
Item
Cooling Capacity Heating Capacity Moisture Removal /h Power Source ø, V, Hz
Air Circulation /min
Noise Level dB(A)
Input W
A
E.E.R. Btu/h.w C.O.P. -
Dimensions(W x H x D)
mm
Net. Weight kg
Service Valve mm(Inch)
Refrigerant(R-22) g Airflow Direction Control(Up & Down) Remote Controller Type Sleeping Operation Drain Hose
Cooling
Heating
Cooling
Heating Cooling
Heating
Running
Current
Btu/h(kcal/h)
( Hi / Med / Low )
- 8 -
4. LM-2430H2L/M
23,600/24,000
11,800/12,000 11,800/12,000
208/230V
23,600/24,000
11,800/12,000 11,800/12,000
3.4 1.7 1.7 at 230V 1Ø, 208/230V, 60Hz
Indoor 8.0/8.6 8.0/8.6
Cooling/Heating
Outdoor 42
Indoor 40/38/36 40/38/36
at 230V
Outdoor 54
2,400/2,400 1,300/1,300 1,300/1,300 2,400/2,400 1,300/1,300 1,300/1,300
11.0/10.0 6.2/5.7 6.2/5.7 208/230V
11.0/10.0 6.2/5.7 6.2/5.7
9.8/10.0 9.1/9.2 9.1/9.2
2.89/2.93 2.66/2.70 2.66/2.70
Indoor 888 x 287 x 170
Outdoor 870 x 655 x 320
Indoor 7
Outdoor 63
Liquid 6.35(1/4)
Gas 12.7(1/2)
880 880 at 7.5m
O
L.C.D Wireless
O O
Operation
A-Unit
Only
B-Unit
Only
A-Unit + B-Unit
Remarks
Unit
Item
Cooling Capacity Heating Capacity Moisture Removal /h Power Source ø, V, Hz
Air Circulation /min
Noise Level dB(A)
Input W
A
E.E.R. Btu/h.w C.O.P. -
Dimensions(W x H x D)
mm
Net. Weight kg
Service Valve mm(Inch)
Refrigerant(R-22) g Airflow Direction Control(Up & Down) Remote Controller Type Sleeping Operation Drain Hose
Cooling
Heating
Cooling
Heating Cooling
Heating
Runnig
Current
Btu/h(kcal/h)
( Hi / Med / Low )
- 9 -
Dimensions
Installation plate
Installation plate
Right rear piping
Left rear piping
ø70mm
ø70mm
50mm
20mm
20mm
80mm
A
A
ø70mm
Center
Center
ø70mm
Left rear piping Right rear piping
A
A
D
H
W
Tubing hole cover
W mm 802 888
H mm 262 287 D mm 165 170
LM-1830C2L/M, LM-1830H2L/M
LM-2430C2L/M, LM-2430H2L/M
MODEL
DIM
( LM-1830C2L/M, LM-1830H2L/M ) ( LM-2430C2L/M, LM-2430H2L/M )
1. Indoor Unit
Pipe Hole
Fix Hole
Hanger Hole
H
W
D
Capacity W H D
SP1 Ch. 9K/12K 570 568 137
- 10 -
W
D
L1
L2
L9
L4
L3
H
L10
L10
L10
L8
Gas side 3-Way valve
Liquid side 2-Way valve
L7L5L6
2. Outdoor Unit
W mm 870 H mm 655 D mm 320 L1 mm 370 L2 mm 25 L3 mm 630 L4 mm 25 L5 mm 546 L6 mm 160 L7 mm 160 L8 mm 64 L9 mm 76.5 L10 mm 50
LM-1830C2L/M, LM-1830H2L/M, LM-2430C2L/M, LM-2430H2L/M,L2-C243AL1
MODEL
DIM
- 11 -
Refrigeration Cycle Diagram
HEAT EXCHANGER
COOLING HEATING DEICE
HEAT
EXCHANGER
CAPILLARY TUBE
COMPRESSOR-B
COMPRESSOR-A
CAPILLARY TUBE
2-WAY VALVE
4-WAY VALVE
B-UNITA-UNIT
3-WAY VALVE
4-WAY VALVE
Indoor Unit Outdoor Unit
Pipe Size (Diameter : inch)
Max.
piping length
(m)
Max.
piping elevation
(m)
Gas
Btu/h
Liquid
1/2" 1/4" 15 8
3/8"
24K
18K 1/4" 15 8
ex)
Capillary Cooling & Deice
A-UNIT B-UNIT
CAPILLARY TUBE
LIQUID SIDE
2-WAY VALVE
GAS SIDE
3-WAY VALVE
HEAT EXCHANGER (EVAPORATOR)
HEAT
EXCHANGER
(CONDENSER)
COMPRESSOR
B
COMPRESSOR
A
1. LM-1830C2L/M, LM-2430C2L/M,L2-C243AL1 (Cooling only models)
2. LM-1830H2L/M, LM-2430H2L/M (Cooling & Heating modes)
MOTOR
STEP
MOTOR
CN-MOTOR
RD
CGVS
PILLAR TERMINAL
BKBRBL
SW01F
FORCED OPERATION
AUTO RESTART
REMOTE CONTROL
THERMISTOR
CN-TH
CN-U/D
CN-DISP1
MAIN PCB ASSY
INDOOR WIRING DIAGRAM
3854A20075M
DISPLAY PCB ASSY
TO OUTDOOR UNIT
CN-POWER
BK
CAPACITOR
TRANS­FORMER
CN-SV
CN-POWER CN-COMP1 CN-COMP2
FUSE T3.15A
CN-TRANAS
RY-COMP A
RY-COMP B
RY-FAN1
RY-SV3
RY-SV4
CN-TH1
MAIN DC PCB ASSY
MAIN AC PCB ASSY
PILLAR TERMINAL
TO INDOOR UNIT
B INDOORA INDOOR
CAPACITOR
A 4-WAY
B 4-WAY
THERMISTOR
BK BK
BK
BK
BK
BK BL YL
BK
BK
YL
BK
"A"
COMP
"B"
COMP
RD
RDBL
WH WH
44
33
OLP
OLP
H
S
C
C
S
R
R
CF
BK OR
OR
BR
YL
MOTOR
BK
T/B1
BK
BK
YL
RD
BK
BK
BR
BL
OR
RD
CGVSCGVS
CGVS
CGVS
BK BR BLRD BK BR BL
BKBKBR BL
WH
BL
BL
GN/YL
L2L1
MAIN
POWER
FUS250V 2.5A
FUS250V 2.5A
FUS250V 2.5A
FUS250V 2.5A
OUTDOOR WIRING DIAGRAM
3854A20075K
BK
CAPACITOR
TRANS­FORMER
CN-SV
CN-POWER CN-COMP1
CN-COMP2
FUSE T3.15A
CN-TRANAS
RY-COMP A
RY-COMP B
RY-FAN1
MAIN DC PCB ASSY
MAIN AC PCB ASSY
PILLAR TERMINAL
TO INDOOR UNIT
B INDOORA INDOOR
CAPACITOR
BK
BK
BK
YL
BK
"A"
COMP
"B"
COMP
RD
RD
BL
WH WH
4
4 33
OLP
OLP
H
S
C
C
S
R
R
C
F
BK OR
OR
BR
YL
MOTOR
BK
T/B1
BK
BK
YL
RD
BK
BK BR
BL
OR
RD
CGVSCGV S
CGVS
CGVS
BK BR BLRD BK BR BL
BKBKBR BL
WH
BL
BL
GN/YL
L2L1
MAIN
POWER
FUS250V 2.5A
FUS250V 2.5A
FUS250V 2.5A
FUS250V 2.5A
OUTDOOR WIRING DIAGRAM
3854A20075L
- 12 -
Wiring Diagram
1. INDOOR UNIT: LM-1830C2L/M, LM-1830H2L/M, LM-2430C2L/M, LM-2430H2L/M
2. OUTDOOR UNIT
• LM-1830C2L/M
• LM-2430C2L/M
• LM-1830H2L/M
• LM-2430H2L/M
Operation Details
1. MAIN UNIT FUNCTION
• DISPLAY
1) C/O Model Operation Indicator
On while in appliance operation, off while in appliance pause
Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on)
Sleep Timer Indicator
On while in sleep timer mode, off when sleep timer cancel or appliance operation pause
Timer Indicator
On while in timer mode (on/off), off when timer mode is completed or canceled.
Comp. Running Incidator
While in appliance operation, on while in outdoor unit compressor running, off while in compressor off
2) H/P Model Operation Indicator
On while in appliance operation, off while in appliance pause
Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on)
Sleep Timer Indicator
On while in sleep timer mode, off when sleep timer cancel or appliance operation pause
Timer Indicator
On while in timer mode (on/off), off when timer mode is completed or canceled
Defrost Indicator
Off except when hot start during heating mode operation or while in defrost control
Cooling Mode Operation
When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan stop.
When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp Setting Temp+0.5°C Compressor OFF Temp ➲ Setting Temp-0.5°C
While in compressor running, operating with the airflow speed set by the remote control. While in compressor not running, operating with the low airflow speed regardless of the setting.
Healthy Dehumidification Mode
When the dehumidification operation input by the remote control is received, the intake air temperature is detected and the setting temp is automatically set according to the intake air temperature.
26°C Intake Air Temp 25°C 24°C Intake Intake Air Temp<26°C Intake Air Temp-1°C 18°C Intake Intake Air Temp<24°C Intake Air Temp-0.5°C Intake Air Temp<18°C 18°C
-13-
While in compressor off, the indoor fan repeats low airflow speed and pause.
While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidifica-
tion operation and 4-min compressor off repeat. Compressor ON Temp. Setting Temp+0.5°C Compressor OFF Temp. ➲ Setting Temp-0.5°C
In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
Heating Mode Operation(H/P model)
When the intake air temp reaches +3°…above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on. Compressor ON Temp. Setting Temp. Compressor OFF Temp. ➲ Setting Temp.+3°C
While in compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C, when above 28°C , it operates with the low or setting airflow speed. When the indoor pipe temp is between 20°C and 28°C, it oper­ates with Super-Low(while in sleep mode, with the medium airflow speed).
While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C, when above 35°C , it operates with the low airflow speed.
If overloaded while in heating mode operation, in order to prevent the compressor from OLP operation, the outdoor fan is turned on/off according to the indoor pipe temp.
While in defrost control, both of the indoor and outdoor fans are turned off.
Defrost Control(H/P model)
Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
The first defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes passed from
starting of heating operation and more than 10 minutes operation of compressor.
Defrost ends after 9/6 minutes passed from starting of defrost operation or after the outdoor fan operates within max. 2 minutes 30 seconds when the outdoor pipe temperature rises over 12°C even it before 12 min- utes.
The second defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes passed from ending of the first defrost and more than 10 minutes operation of compressor.
Heating overload(H/P models)
Outdoor fan ON/OFF by sensing outdoor pipe temperature.
Outdoor fan is OFF if pipe temperature is over 6.5°C and outdoor fan is ON if pipe temperature is below 0°C.
Outdoor fan is off if any one part is heating overload condition.
-14-
-15-
Fuzzy Operation (C/O Model)
According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp ➲ Setting Temp + 0.5°C Compressor OFF Temp ➲ Setting Temp + 0.5°C
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time.
26°C Intake Air Temp 25°C 24°C Intake Air Temp < 26°C Intake Air Temp + 1°C 22°C Intake Air Temp < 24°C Intake Air Temp + 0.5°C 18°C Intake Air Temp < 22°C Intake Air Temp Intake Air Temp<18°C 18°C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
Fuzzy Operation (H/P Model)
When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since the operation off, the operation mode is selected.
When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air temp at that moment as follows.
24°C Inatake Air Temp Fuzzy Operation for Cooling 21°C Inatake Air Temp<24°C Fuzzy Operation for Dehumidification Inatake Air Temp<21°C Fuzzy Operation for Heating
If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10 sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.
1) Fuzzy Operation for Cooling
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp ➲ Setting Temp +0.5°C Compressor OFF Temp ➲ Setting Temp + 0.5°C
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time.
26°CIntake Air Temp 25°C 24°CIntake Air Temp<26°C Intake Air Temp + 1°C 22°CIntake Air Temp<24°C Intake Air Temp + 0.5°C 18°CIntake Air Temp<22°C Intake Air Temp Intake Air Temp<18°C ➲ 18°C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the tem­perature.
-16-
2) Fuzzy Operation for Dehumidification
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp Setting Temp + 0.5°C Compressor OFF Temp ➲ Setting Temp+0.5°C
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time.
26°C Intake Air Temp 25°C 24°C Intake Air Temp<26°C Intake Air Temp+1°C 22°C Intake Air Temp<24°C Intake Air Temp+0.5°C 18°C Intake Air Temp<22°C Intake Air Temp Intake Air Temp<18°C ➲ 18°C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in dehumidification operation.
3) Fuzzy Operation for Heating
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C or more above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on.
Compressor ON Temp Setting Temp Compressor OFF Temp ➲ Setting Temp + 3°C
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time.
20°CIntake Air Temp Intake Air Temp + 0.5°C Intake Air Temp<20°C 20°C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the intake air temperature and the setting temperature.
Airflow Speed Selection
The airflow speed of the indoor fan is set to high, medium, low, or chaos (auto) by the input of the airflow speed selection key on the remote control.
On-Timer Operation
When the set time is reached after the time is input by the remote control, the appliance starts to operate.
The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
If the appliance is operating at the time set by the timer, the operation continues.
-17-
Off-Timer Operation
When the set time is reached after the time is input by the remote control, the appliance stops operating.
The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
If the appliance is on pause at the time set by the timer, the pause continues.
Off-Timer <=> On-Timer Operation
When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation is carried out according to the set time.
Sleep Timer Operation
When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appli­ance operation, the operation of the appliance stops.
While the appliance is on pause, the sleep timer mode cannot be input.
While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature increases by 1°C. After another 30 min elapse, it increases by 1°C again.
When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to
the low.
When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to the medium.
Chaos Swing Mode
By the Chaos Swing key input, the upper/lower vane automatically operates with the Chaos Swing or they are fixed to the desired direction.
While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.
Chaos Natural Wind Mode
When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air­flow mode is operated for 2~15 sec. randomly by the Chaos Simulation.
Jet Cool Mode Operation (C/O Model)
If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
Jet Cool Mode Operation (H/P Model)
While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the other
mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C.
When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
-18-
Auto Restarting Operation
When the power is restored after a sudden power failure while in appliance operation, the mode before the power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
The slide switch on the main unit of the appliance should be on the Auto Restarting position in order that the Auto Restarting operation is available.
Operation Mode that is kept on the memory
- State of Operation ON/OFF
- Operation Mode/Setting Temp/Selected Airflow Speed
- Sleep Timer Mode/Remaining Time of Sleep Timer (unit of hour)
Slide Switch
FORCED OPERATION
AUTO RESTART
REMOTE CONTROL
Forced Operation (C/O Model)
To operate the appliance by force in case that the remote control is lost, the forced operation selection switch is on the main unit of the appliance to operate the appliance in the standard conditions.
When the power is supplied while the slide switch is on the forced operation position, or when the slide switch position is switched to the Auto Restarting position (or test operation) or switched from the remote control posi­tion to the forced operation position while the power is on, the forced operation is carried out.
When the slide switch position is switched from the forced operation position to the Auto Restarting position or the remote control position, the forced operation is canceled and the appliance stops operating.
The forced operation is carried out in cooling mode with the setting temperature 22°C and the high speed of airflow.
While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to indicate the forced operation.
Forced Operation (H/P Model)
To operate the appliance by force in case that the remote control is lost, the forced operation selection switch is on the main unit of the appliance to operate the appliance in the standard conditions.
When the power is supplied while the slide switch is on the forced operation position, or when the slide switch position is switched to the Auto Restarting (or test operation) position or switched from the remote control posi­tion to the forced operation position while the power is on, the forced operation is carried out.
When the slide switch position is switched from the forced operation position to the Auto Restarting position or the remote control position, the forced operation is canceled and the appliance stops operating.
The forced operation is carried out in cooling mode with the setting temperature 22°C and the high speed of airflow.
In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the operation condition is set according to the intake air temperature as follows.
24°CIntake Air Temp Cooling Mode Operation, 22°C, High Speed 21°CIntake Air Temp<24°C Dehumidification Operation, 23°C, High Speed Intake Air Temp<21°C Heating Mode Operation, 24°C, High Speed
While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to indicate the forced operation.
-19-
Remote Control Operation Mode
When the remote control is selected by the slide switch on the main unit, the appliance operates according to the input by the remote control.
Protection of the evaporator pipe from frosting
If the indoor pipe temp is below 0°C in 7 min. after the compressor operates without any pause while in cool­ing cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor evaporator pipe from frosting.
When the indoor pipe temp is 7°C or higher after 3 min. pause of the compressor, the compressor and the outdoor fan is turned on according to the condition of the room temperature.
Buzzer Sounding Operation
When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.
When the appliance-pause key is input by the remote control, the long "beep" sounds.
When a key is input by the remote control while the slide switch on the main unit of the appliance is on the
forced operation position, the error sound "beep-beep-beep-beep-beep-" is made 10 times to indicate that the remote control signal cannot be received.
Display Function
1. Heating Model 2. Cooling Model
Self-diagnosis Function
Error Indicator
The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.
Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.
If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.
After error occurrence, if error is released, error LED is also released simultaneously.
To operate again on the occurrence of error code 12, be sure to pull out power cord and then re-insert.
Having or not of error code is different from Model.
-20-
1
(3times)
3sec 3sec
(5times)
3sec
(twice)
3sec 3sec
(once)
3sec 3sec 3sec
2
3
5
8
Error Code
Error LED
(Indoor body operation LED)
Error contents SVC check point
Indoor suction temperature thermistor open/short.
Indoor pipe temperature thermistor open/short.
Indoor TH ass'y check
Outdoor TH ass'y
check
Resetting of remocon operating mode
Communication line/circuit check
Outdoor suction temperature thermistor open/short.
Outdoor pipe temperature thermistor open/short.
Abnormal operation of multi product. (Simultanueous operation of cooling and heating)
Indoor fan lock
Poor communication
Check indoor fan
motor and outdoor PCB ass'y
Cooling, Soft Dry, Fan, Heating
Cooling, Soft Dry, Fan
Sleep Mode
Sleep Mode
Timer Mode
Timer Mode
Hot-start, Defrost
Operation Indicator
Timer Indicator
Sleep Timer Indicator
Defrost Indicator
Operation Indicator
Timer Indicator
Sleep Timer Indicator
Compressor on Indicator
OUT
DOOR
- 21 -
Installation
Front
Right Rear right
Rear left
Down right
Left
1) Selection of the best location
1. Indoor unit
There should not be any heat source or steam
near the unit.
There should not be any obstacles to prevent the air circulation.
A place where air circulation in the room will be good.
A place where drainage can be easily obtained.
A place where noise prevention is taken into
consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from
the wall, ceiling, fence, or other obstacles.
2. Outdoor unit
If an awning is built over the unit to prevent direct sunlight or rain exposure, be careful that heat radiation from the condenser is not restricted.
There should not be any animals or plants which could be affected by hot air discharged.
Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles.
3. Piping length and the elevation
Pipe Size
GAS LIQUID
Max. piping
length
A (m)
Max.
Elevation
B (m)
1/2"(3/8") 1/4" 15 8
(1) Installation of Indoor, Outdoor unit
More than
5 cm
More than eye-level
More than 10 cm
More than 5 cm
More than
5 cm
More than 10 cm
More than 70 cm
Indoor unit
A
B
Outdoor unit
- 22 -
2) Indoor Unit Installation (Standard type)
The mounting wall should be strong and solid enough to protect it from the vibration.
1. Mount the installation plate on the wall with four Type "A" screws.
(If mounting the unit on the concrete wall, consid­er using anchor bolts.)
Always mount the Installation plate horizontally by aligning the marking-off line by means of the thread and a level.
2. Drill the piping hole with 70mm dia. holecore drill.
Line according to the arrows marked on lower the left and the rght side of the Installation Plate. The meeting point of the extended line is the center of the hole.
Drill the piping hole at either the right or the left and the hole should be slightly slant to the out­door side.
Installation Plate
marking-off line
Thread
Weight
Type "A" screw
The lower left and the right side of Installation Plate
LM-1830C2L/M, LM-1830H2L/M
LM-2430C2L/M, LM-2430H2L/M
Left rear piping Right rear piping
80mm
20mm
50mm
ø70mm
ø70mm
Left rear piping Right rear piping
A
A
A
A
20mm
ø70mm ø70mm
Wall
Indoor Outdoor
5~7mm
- 23 -
1) Preparation of pipings
1. Cut the pipes and the cable.
Use the accessory piping kit or the pipes pur­chased locally.
Measure the distance between the indoor and the outdoor unit.
Cut the pipes a little longer than the measured distance.
Cut the cable 1.5m longer than the length of the pipe.
2. Remove burrs.
Remove burrs from cut edges of pipes.
Turn the pipe end toward down to avoid the
metal powder entering the pipe.
Caution:
If burrs are not removed, they may cause a gas leakage.
3. Flaring the pipes.
Insert the flare nuts, mounted on the connection ports of both indoor and outdoor unit, onto the copper pipes. Some refrgerant gas may leak, when the flare nuts are removed from the indoor unit, as some gas is charged to prevent the inside of the pipe from rusting.
Fit the copper pipe end into the Bar of flare tool about 0~0.5mm higher. (See illustration)
Flare the pipe ends.
4. Tape the flaring portion to protect it from the dust or damages.
90
Slanted
Pipe cutter
Rough
"A"
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Bar
Yoke
Handle
When properly flared, the internal surface flare will evenly shine and be of even thickness. Since the flare part comes into contact with the connec­tors, carefully check the flare finish.
"
A"; ø12.7 mm (1/2") →0~0.5 mm
ø9.52 mm (3/8")
0~0.5 mm
ø6.35 mm (1/4")
0~0.5 mm
(2) Piping and Drainage of Indoor Unit
Point down
Pipe
Reamer
= Improper flaring =
Inclined Cracked Uneven
Surface
damaged
thickness
- 24 -
2)
Connection of Pipings (Standard type)
1. Remove the installation plate
Pull the two '∆' marked portion of bottom of the chassis and pull the installation plate out of chas­sis.
2. Route the drain hose and the indoor tubing.
For left rear piping
3. Route the tubing and the drain hose straight
backwards(see figure).
4. Insert the connecting cable into the indoor
unit through the piping hole.
Do not connect the cable to the indoor unit.
Make a small loop with the cable for easy con-
nection later.
5. Tape the tubing, drain hose and the connecting
cable. Be sure that drain hose locates at the lowest side of the bundle. Locating at the upper side can be a reason that drain water overflows drain pan inside the unit.
Installation plate
Pull
Pull
To remove the holder, press the bottom of the chassis near the holder upwards and the tab is clear of its hole.
Turn it clockwise approx. 90° and remove it.
Tubing holder
Press
Pull
Connecting cable
Gas side piping
Liquid side piping Drain hose
- 25 -
Connecting cable
Drain hose
Press the lower left and right side of the unit against the Installation Plate until the hooks engage with their slots (sound click).
6. Indoor unit installation.
Hook the indoor unit onto the upper position of the installation plate. (Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure the hooks are properly seated on the installation plate by moving it in left and right.
7. Connecting the pipings to the indoor unit.
Align the center of the pipings and sufficiently tighten the flare nut with fingers.
Finally, tighten the flare nut with torque wrench until the wrench clicks. Wrench tightening the flare nut with forque wrench, ensure the direction for tightening fol­lows the arrows on the wrench.
8. Wrap the insulation material around the con­necting portion.
CAUTION: Take care to arrange the pipings,
drain hose and cables as the right upper picture for inserting it into the indoor unit and refixing the tubing holder easily.
Pipe Size Torque
Liquid Side (1/4") 1.8kg m
Gas Side (3/8") 4.2kg m Gas Side (1/2") 5.5kg m
Wrap the insulation material around the connecting portion.
Indoor unit tubing Flare nut Pipings
Spanner
Torque wrench
Plastic bands
Insulation material
- 26 -
9. Set the pipings and the connecting cable to the back of the chassis with the tubing holder.
Hook the edge of tubing holder to tap on chas­sis and push the bottom of tubing holder to be engaged in the bottom of chassis.
10. Indoor unit installation.
Hook the indoor unit onto the upper portion of installation plate. (Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure the hooks are properly seated on the installation plate by moving it in left and right.
Press the lower left and right side of the unit against the Installation Plate until the hooks engages with their slots (sound click).
Piping
Drain hose
Taping
Tubing holder
Hook
1
Push
2
Connecting cable
Drain hose
- 27 -
(3) Connecting Pipings and the cable to Outdoor unit
Outdoor unit
A-UNIT
Gas side piping
Liquid side piping
B-UNIT
Torque wrench
1) Connecting the pipings to the Outdoor unit
1. Align the center of the pipings and sufficiently
tighten the flare nut with fingers.
2. Finally, tighten the flare nut with torque
wrench until the wrench clicks.
When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
Pipe Size Torque
Liquid Side (1/4") 1.8kg.m
Gas Side (3/8") 4.2kg.m Gas Side (1/2") 5.5kg.m
- 28 -
Outdoor unit
Over 5mm
Holder for
power supply
cord
GN/YL
20mm
GN/YL
20mm
AWG 18
AWG 12
Connecting
cable
Cover control
Terminal block
Power supply
cable
A-UNIT
SVGC
B-UNIT
SVGC
Terminal BLOCK
SVGC
Terminal BLOCK
SVGC
L1 L2
Power Source
208/230V AC
(High voltage)
Indoor A-UNIT Indoor B-UNIT
Connecting cable(Low voltage)Connecting cable(Low voltage)
WARNING
WARNING
NOTE
NOTE
Connection of the cable
1. Remove the cover control from the unit by loosening the screw.
2. Dismount caps on the conduit panel.
3. Temporarily mount the conduit tubes on the conduit panel.
4. Connect the wires to the terminals on the control board individually as the following.
5. Secure the cable onto the control board with the holder (clamper).
6. Ground the unit in accordance with local codes.
7. Refix the cover control to the original position with the screw.
8. Use lock nuts to secure the conduit tubes.
1. Separately wire the high and low voltage line.
2. Use heat-proof electrical wiring capable of withstanding temperature up to 167˚F.
3. Use outdoor and waterproof connection cable rated more than 300V for the connection between indoor and outdoor unit. (For example, Type SJO-WA)
Be sure to comply with local codes while running the
wire from the indoor unit to the outdoor unit(size of wire and wiring method, etc).
Every wire must be connected firmly.
No wire should be allowed to touch refrigerant tubing,
the compressor or any moving parts.
The power cable connected to the outdoor unit should be complied with the following specifications. (UL recognized and CSA certified)
CAUTION
The connecting cable connected to the indoor and outdoor unit should be complied with the following specifications. (UL recognized and CSA certified)
- 29 -
Connection method of the connecting cable(Example)
(1) Dismount two-caps on the conduit panel. (2) Make a hole appropriate for the passage of connec-
tion cable through on cap by tool.
(for low voltage line) (3) Pass the connecting cable through the hole. (4)
Properly connect the cable on the terminal block. (5) Fix the connection cable with clamp cord provided on
the unit not to have strain at the terminal when the
connection cable is pulled outside up to a 35 pound
weight. (6) Wind the vinyl tape round the connecting cable for
sealing between the surface of the connection cable
and cap. (7) Mount the taped part of cable on the cap. (8) Finally, mount the holed cap with the wound cable on
the conduit panel.
When connecting each power wire to the corresponding terminal, follow instructions "How to connect wiring to the terminals" and fasten the wire tightly with the fixing screw of the terminal plate.
How to connect wiring to the terminals
For solid core wiring (or F-cable)
(1) Cut the wire end with a wire cutter of wire-cutting pli-
ers, then strip the insulation to expose the solid wire
about 25mm(15/16") (2) Using a screwdriver, remove the terminal screw(s) on
the terminal plate. (3) Using pliers, bend the solid wire to from a loop suit-
able for the terminal screw. (4) Shape the loop wire properly, place it on the terminal
plater and tighten securely with the terminal screw
using a screwdriver.
For strand wiring
(1) Cut the wire end with a wire cutter or wire-cutting pli-
ers, then strip the insulation to expose the strand
wiring about 10mm(3/8"). (2) Using a screwdriver, remove the terminal screw(s) on
the terminal plate. (3) Using a round terminal fastener or pliers, securely
clamp each stripped wire end with a round terminal. (4) Position the round terminal wire, and replace and
tighten the terminal screw using a screwdriver.
Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
WARNING
G
Terminal block
Lock nut
Power supply line
(1ø, 230/208V)
Conduit panel
Cap(Reuse)
Clamp cord
Hole (for low voltage line)
Cap(Remove) Taping
(for sealing)
Low voltage line (connecting cable)
Loop
Strip 25mm(15/16")
Insulation
Solid wire
High voltage
Low voltage
Strip 10mm(3/8")
Round terminal
Connecting cable
Loosening the terminal block screw
Fastening the wire tightly
Strand wire
- 30 -
Connect the cable to the indoor unit
1. Connect the wires to the terminals on the control board individually according to the outdoor unit con­nection.
Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respec­tively. (Refer to Wiring diagram on page11.)
2. Attach the Grille onto the cabinet.
Grasp lower the left and right side of the Grille and engage four tabs on the top inside edge of the chassis.
Press the Grille toward the chassis until it will be back into place.
CAUTION
CAUTION
Air
Conditioner
Circuit Breaker
Use a circuit breaker or time delay fuse.
Connecting cable
Main power source
If a power plug is not to be used, provide a circuit breaker between power source and the unit as shown below.
Model
18K 1ø,230/208V 15A 24K 1ø,230/208V 20A
Power source
Fuse or breaker
Capacity
Be sure to refer to the wiring diagram label inside the cover control and carry out the correct field wiring. Wrong wiring can cause the unit to misoperate to result in a fire hazard.
Check local electrical codes and any specified wiring instructions or limitations.
WARNING
- 31 -
(4) Checking the drainage
1. To remove the front panel from the indoor unit, remove the front panel from the indoor unit cabi­net.
Set the air direction louvers up-and-down to the position(horizontally) by hand.
Remove the securing screws that retain the front panel. Pull the lower left and right sides of the grille
toward you and lift it off. (9K Btu models: 2EA,
12K Btu models: 3EA)
2. To check the drainage.
Pour a glass of water on the evaporator.
Ensure the water flows through the drain hose of the
indoor unit without any leakage and goes out the drain exit.
3. Drain piping
The drain hose should point downward for easy drain flow.
Do not make drain piping.
(5) Form the piping
1. Form the piping by wrapping the connecting por­tion of the indoor unit with insulation material and secure it with two kinds of vinyl tapes.
If you want to connect an additional drain hose, the end of the drain outlet should be routed above the
ground. Secure the drain hose appropriately.
2. In cases where the outdoor unit is installed below the indoor unit perform the following.
Tape the piping, drain hose and connecting cable from down to up.
Secure the tapped piping along the exterior wall using saddle or equivalent
3. In cases where the Outdoor unit is installed above the Indoor unit perform the following.
Tape the piping and connecting cable from down to up.
Secure the taped piping along the exterior wall. Form a trap to prevent water entering the room.
Fix the piping onto the wall by saddle or equivalent.
Seal a small opening around the pipings with gum type sealer.
Pull the right and the left side.
Screw
Trap is required to prevent water from entering into electrical parts.
Plastic band
Taping
Drain hose
Pipings Connecting
cable
Seal a small opening around the pipings with gum type sealer.
Trap
Downward slope
Do not raise
Accumulated drain water
Tip of drain hose dipped in water
Air
Waving
Water leakage
Water leakage
Ditch
Less than 50mm gap
Water leakage
- 32 -
(6) Air Purging of the Pipings and indoor unit
The air which contains moisture remaining in the is refrigeration cycle may cause a malfunction on the compressor.
1. Confirm that both the liquid side valve and the gas side valve are set to the closed position.
2. After connecting the piping, check the joints for gas leakage with gas leak detector.
3. Remove the service port nut, and connect the gauge manifold and the vacuum pump to the service port by the charge hose.
4. Vacuum the indoor unit and the connecting pipes until the pressure in them lowers to below-76cmHg.
5. Disconnect the charge hose and fit the nut to the service port. (Tightening torque: 1.8kg.m)
6. Remove the valve stem nuts, and fully open the stems of the 2-way and 3-way valves with a hexagon wrench.
7. Tighten the valve stem nuts of the 2-way valve and 3-way valve.
Indoor unit
Outdoor unit
Liquid side
Gas side
CLOSEOPEN
Vacuum pump
2-way valve
Closed
Closed
3-way valve
- 33 -
(7) Maximum Length of Pipe and Freon Extra Charge
INDOOR UNIT
INDOOR UNIT
OUTDOOR UNIT
B(Length)
D(Length)
A(Height)
C(Height)
Model
STANDARD
CONNECTION TYPE
Charge am't(g)
LENGTH(m)
ABCD
per 1m
LM-1830C2L/M
7.5 7 15 7 15 20
LM-1830H2L/M LM-2430C2L/M
7.5 7 15 7 15 20
LM-2430H2L/M
** A, B mean indoor unit higher located than outdoor unit.
C, D mean outdoor unit higher located than indoor unit.
Charge amount per 1m
- 34 -
(8) Test running
Battery Cover
Settlement of Outdoor Unit
Anchor the outdoor unit with a bolt and nut
(ø10cm) tightly and horizontally on a concrete or rigid mount.
When installing on the wall, roof or rooftop,
anchor the mounting base securely with a nail or wire assuming the influence of wind and earth­quake.
In the case when the vibration of the unit is con-
veyed to the house, settle the unit with an anti­vibration rubber.
2) Evaluation of the performance
1. Measure the temperature of the intake and
discharge air.
2. Ensure the difference between the intake
temperature and the discharge one is more than 8°C.
1) Connection of power supply
1. Connect the power supply cord to the inde-
pendent power supply.
2. Prepare the remote control.
Insert two batteries provided. Remove the battery cover from the remote con­troller.
Slide the cover according to the arrow direction. Insert the two batteries.
(Two "R03" or "AAA" dry-cell batteries or equiv­alent.)
Be sure that the (+) and (-) directions are cor­rect.
Be sure that both batteries are new. Re-attach the cover.
Slide it back into position.
3. Operate the unit at cooling operation mode for fifteen minutes or more.
Bolt
Tubing connection
Discharge air
-35-
Operation
(1) Name and Function-Remote Control (Door Closed, Standard Type)
Signal transmitter
Transmits the signals to the room air conditioner.
Remote Control
START/STOP BUTTON
Operation starts when this button is pressed and stops when the button is pressed again.
OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
ROOM TEMPERATURE SETTING BUTTONS
Used to select the room temperature.
INDOOR FAN SPEED SELECTOR
Used to select fan speed in four steps low, medium, high, or CHAOS.
JET COOL
Used to start or stop the speed cooling. (Speed cooling operates super high fan speed in cooling mode.)
CHAOS SWING BUTTON
Used to stop or start louver movement and set the desired up/down airflow direction
.
1
234
5
6
Signal transmitter
5 4
6 1
3
Flip-up door
(closed)
2
-36-
(2) Name and Function-Remote Control (Door Opened, Standard Type)
Signal transmitter
Transmits the signals to the room air conditioner.
Remote Control
ON/OFF TIMER BUTTONS
Used to set the time of starting and stopping operation.
TIME SETTING BUTTONS
Used to adjust the time.
TIMER SET/CANCEL BUTTONS
Used to set the timer when the desired time is obtained and to cancel the Timer operation.
SLEEP MODE AUTO BUTTON
Used to set Sleep Mode Auto operation.
AIR CIRCULATION BUTTON
Used to circulate the room air without cooling or heating (turns indoor fan on/off).
ROOM TEMPERATURE CHECKING BUTTON
Used to check the room temperature.
˚C TO ˚F SWITCHING BUTTON
RESET BUTTON
Used prior to resetting time or after replacing batteries.
Signal transmitter
1
2
3
4
ON OFF
1 2 3
SET
CANCEL
˚C/˚F
4 5 6 7 8
5
6
7 8
- 37 -
Disassembly of the parts (Indoor unit, Standard Type)
Warning :
Disconnect the unit from power supply before mak­ing any checks. Be sure the power switch is set to “OFF”.
To remove the Grille from the Chassis.
• Set the up-and-down air discharge louver to open position (horizontally) by finger pressure.
• Remove the securing screws
• To remove the Grille, pull the lower left and right side of the grille toward you (slightly tilted) and lift it straight upward.
1. To remove the sensor, housing connect, step
motor conductor with sensor holder, Motor, Evaporator & P.C.B.
Screw
Step Motor Conductor
Motor Conductor
Sensor Conductor
2. To remove the Control Box.
Remove securing screws.
Pull the control box out from the chassis care-
fully.
3. To remove the Discharge Grille.
Pull the discharge grille out from the chassis carefully.
4. To remove the Evaporator.
Remove screws securing the evaporator and the holder eva.
Unhook the tab on the right inside of the chas­sis at the same time, slightly pull the evapora­tor toward you until the tab is clear of the slot.
5. To remove the Cross-Flow Fan
Loosen the screw securing the cross-flow fan to the fan motor (do not remove).
Lift up the right side of the cross-flow fan and the fan motor, separate the fan motor from the cross-flow fan.
Remove the left end of the cross-flow fan from the self-aligning bearing.
- 38 -
2-way Valve (Liguid Side) 3-way Valve (Gas Side)
Works Shaft position Shaft position Service port
Shipping Closed Closed Closed
(with valve cap) (with valve cap) (with cap)
Air purging Open Closed Open
(Installation) (counter-clockwise) (clockwise) (push-pin or with
vacuum pump)
Operation Open Open Closed
(with valve cap) (with valve cap) (with cap)
Pumping down Closed Open Open
(Transfering) (clockwise) (counter-clockwise) (connected
manifold gauge)
Evacuation Open Open Open
(Servicing) (with charging
cylinder)
Gas charging Open Open Open
(Servicing) (with charging
cylinder)
Pressure check Open Open Open
(Servicing) (with charging
cylinder)
Gas releasing Open Open Open
(Servicing) (with charging
cylinder)
- 39 -
2-way, 3-way Valve
3.
2.
1.
4.
5.
6.
Flare nut
To piping connection
Open position Closed position
Flare nut
Valve cap
To piping connection
Open position Closed position
Hexagonal wrench (4mm)
To outdoor unit
Pin
Service port
Service port cap
To outdoor unit
(1) Pumping down
Procedure
1. Confirm that both the gas side and liquid side valves are set to the open position.
- Remove the valve stem caps and confirm that the valve stems are in the raised position.
- Be sure to use a hexagonal wrench to operate the valve stems.
2. Operate the unit for 10 to 15 minutes.
3. Stop operation and wait for 3 minutes, then con­nect the manifold gauge to the service port of the gas side valve.
- Connect the hose of the gauge with the push pin to the service port.
4. Air purging of the charge hose.
- Open the Low-handle valve on the gauge slightly to air purge from the hose.
5. Set the liquid side valve to the closed position.
6. Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 1kg/cm
2
g.
7. Immediately set the gas side valve to the closed position.
- Do this quickly so that the gauge ends up indi­cating 1kg/ g.
8. Disconnect the charge set, and mount the liquid side and gas side valve caps and the service port nut.
- Use torque wrench to tighten the service port nut to a torque of 1.8kg.m.(4.2kg.m/5.5kg.m)
- Be sure to check for gas leakage.
9. Apply steps from 1 to 8 to each unit (A-unit, B­unit) by the same method.
- 40 -
Indoor unit
Outdoor unit
Liquid side
Close
Gas side
2-Way
valve
Open
3-Way
valve
manifold gauge
Indoor unit
Liquid side
Close
Gas side
2-Way
valve
Open
3-Way
valve
Hi- handle (CLOSE)
Low­handle (CLOSE)
(2) Evacuation
(All amount of refrigerant leaked)
• Procedure
1. Confirm that both the liguid side valve and gas side valve are set to the opened position.
2. Connect the vaccum pump to the center hose of the manifold gauge.
3. Connect the service port of the gas side valve to the low side of the gauge.
4. Evacuation for approximately one hour.
- Confirm that the gauge needle has moved toward-76 cmHg (vacuum of 4 mmHg or less).
5. Close the Low handle of the gauge turn off the vacuum pump, and confirm that the gauge nee­dle does not move(approximately 5 minutes after turning off the vacuum pump).
6. Disconnect the charge hose from the vacuum pump.
- Vacuum pump oil. If the vacuum pump oil becomes dirty or deplet­ed,replenish as needed.
7. Mount the valve caps and the service port caps.
8. Apply steps from 1 to 7 to each unit (A-unit, B­unit) by the same method.
- 41 -
Indoor unit
Outdoor unit
Liquid side
Open
Gas side
2-Way
valve
Open
3-Way
valve
manifold gauge
Indoor unit
Liquid side
Open
Gas side
2-Way
valve
Open
3-Way
valve
Vacuum pump
Hi- handle (OPEN)
Low­handle (OPEN)
(3) Gas Charging
(After Evacuation)
• Procedure
1. Connect the gauge to the charging cylinder.
- Connect the charge hose which you disconnect­ed from the vacuum pump to the valve at the bottom of the cylinder.
- If you are using a gas cylinder, also use a scale and reverse the cylinder so that the system can be charged with liquid.
2. Purge the air from the charge hose.
- Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air. (Be careful of the liquid refriger­ant). The procedure is the same if using a gas cylinder.
3. Open the low handle on the gauge and charge the system with liquid refrigerant.
- If the system can not be charged with the speci­fied amount of refrigerant, it can be charged with a little at a time (approximately 150g each time) while operating the air conditioner in the cooling cycle; however, one time is not suffi­cient, wait approximately 1 minute and then repeat the procedure(pumping down-pin).
4. Immediately disconnect the charge hose from the gas side valve's service port.
- Stopping partway will allow the gas to be dis­charged.
- If the system has been charged with liquid refrigerant while operating the air conditioner turn off the air conditioner before disconnecting the hose.
5. Mount the valve stem nuts and the service port nut.
- Use torque wrench to tighten the service port nut to a torque of 1.8 kg.m.(4.2kg.m/5.5kg.m.)
- Be sure to check for gas leakage.
6. Apply steps from 1 to 5 to each unit (A-unit, B­unit) by the same method.
- 42 -
manifold gauge
Charging
cylinder
Hi- handle (OPEN)
Low-handle
(OPEN)
Check valve
Indoor unit
Outdoor unit
Liquid side
Open
Gas side
2-Way
valve
Open
3-Way
valve
Indoor unit
Liquid side
Open
Gas side
2-Way
valve
Open
3-Way
valve
This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner.
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
All amount of refrigerant leaked out. Check refrigeration cycle.
Refrigerant leakage Clog of refrigeration cycle Defective compressor
Excessive amount of refrigerant
Normal
Notice:
Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
Notice:
1. The suction pressure is usually 4.5~6.0 kg/cm2G at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
- 43 -
Cycle Troubleshooting Guide
Temp. difference : approx. 0°C Current : less than 80% of
rated current
Temp. difference : approx. 8°C Current : less than 80% of
rated current
Temp. difference : less than 8°C Current : over the rated
current
Temp. difference : over 8°C
Temp. Difference
Operating Current
Suction pressure Temperature
(Compared with (Compared with Cause of Trouble Description
the normal value) the normal value)
High Defective compressor Current is low.
Defective 4-way reverse valve
Normal Excessive amount of High pressure does not quickly
refrigerant rise at the beginning of operation. Insufficient amount of Current is low.
Lower Higher refrigerant(Leakage)
Clogging Current is low.
Higher
- 44 -
Comp basic step.
Free joint outdoor unit has two compressor (TPS: Twin power system)
If overload Max. capacity, display error code in indoor unit.
Max. capacity
Step Step 1 Step 2 Step 3
Outdoor Operation Mode COMP 40%(B)only COMP 60%(A)only COMP 100%(A+B) together 18k(Max. 19k)
Cooling Qs<=7k Qs<=12k 12k<Qs Heating - Qs<=9k 12k<Qs
21k(Max. 23k)
Cooling Qs<=9k Qs<=12k 12k<Qs Heating - Qs<=9k 12k<Qs
30k(Max. 33k)
Cooling Qs<=12k Qs<=19k 19k<Qs Heating Qs<=12k Qs<=19k 19k<Qs
Outdoor Max capacity
14k 14k combination 18k 19kcombination 21k 23k combination 30k 33k combination
- 45 -
1. Product does not operate at all.
(* Refer to Electronic Control Device drawing and Schematic diagram.)
Electronic Parts Troubleshooting Guide
Turn off Main Power
Turn on Main Power
Does "beeping" sound is made from the Indoor Unit?
Primarily, the operating condition of Micom is OK.
Check the voltage of power(About AC 220V/AC240V, 60Hz)
Main power's voltage
Voltage applied to the unit
Connecting method of Indoor/Outdoor connecting
cable
Check Fuse (Outdoor PCB Ass'y)
Check Varistor
ZNRØ1J(Outdoor PCB Ass'y)
Check the connection housing for contacting
Connector related to CN-DC/AC
Display PWB Ass'y Check
Check each load(Indoor/Outdoor Fan Motor, Compressor, Stepping Motor etc.) and contacting condition of related connector
PCB Board Operation Check
Items
Power Transformer (Outdoor unit)
- Input Voltage
- Output Voltage
IC01D(7812) Output (Indoor/Outdoor unit)
IC02D(7805) Output (Indoor/Outdoor unit)
IC01A(KIA7036, Reset IC) X01(8MHz)
Replace Trans
Replace IC01D
Replace IC02D
Replace faulty parts
- About AC220V/240V±10% - Check the power voltage
- About AC14±3V
DC +12V
DC +5V
Voltage of Micom No. 2,
(DC +4.5V over) and Soldering condition.
Content Remedy
NO
YES
(After 10 seconds)
- 46 -
Turn on Main Power
While the compressor has been stopped, the compressor does not operate owing to the delaying function for 3 minutes after stopped.
Caused by other parts except the remote control
Cause by the remote control
When the mark( ) is displayed in LCD screen, replace battery.
Check the contact of CN-DISPI connector.
When the compressor stopped Indoor Fan is driven by a low speed. At this point the wind speed is not controlled by the remote controller. (When operated in the Sleeping Mode, the wind speed is set to the low speed by force.)
Check DISP PWB Ass'y
- Voltage between CN DISP1 - : DC +5V
When the detect switch(double key) inside the remote controller door is fault, it is impossible to operate temperature regulating( / ) and wind speed selecting.
Check the connecting circuit between the remote con­troller MICOM (No.
) - R17(2) - IR LED - Q1 -
R16(2.2K).
Check point
Check the connecting circuit between PIN
-
R01L(1K) - C01L(680PF) - MICOM PIN
Check Receiver Ass'y
2. The product is not operate with the remote control.
- 47 -
3. When cooling does not operate
Turn on Main Power
Operate "Cooling Mode( )" by setting the desired temperature of the remote controller is less than one of the indoor temperature by 1°C at least.
When in Air Circulation Mode, Compressor/Outdoor Fan is stopped.
Check the sensor for indoor temperature is attached as close as to be effected by the temperature of Heat Exchanger(EVA).
When the sensor circuit for indoor temperature and connector are in bad connection or are not engaged, Compressor/Outdoor Fan is stopped.
Check the related circuit of R02H(12.1K), R01H(1.0K), R04H(6.2K), R03H(1.0K) (Indoor unit).
Check the indoor temperature sensor is disconnected or not(About 10k Ω/ at 25°C).
Check if connection line (Indoor/Outdoor) is complied with Wiring Diagram.
Check Outdoor Unit
(PCB Ass'y)
Correct connection line
Good connection Bad connection
- 48 -
Turn off Main power
Check it (Indoor/Outdoor)the connection line is complied with Wiring Diagram
Check the line fuse in the outdoor unit
Check the connection of CN-MOTOR
check the operation of blower by manual
Correct connection line
4. When indoor Fan does not operate.(or "ON/OFF" led of display blinks 8 times)
Check POLY S/W in indoor PCB Ass'y
If it is opened If it is shorted
Exchange Indoor PCB Ass'y
Check the outdoor PCB Ass'y
Bad connection Good connection
- 49 -
Confirm that the Vertical Louver is normally geared with the shaft of Stepping Motor.
If the regular torque is detected when rotating the Vertical Louver with hands Normal
Check the connecting condition of CN-U/D Connector
Check the soldering condition(on PWB) of CN-U/D Connector
If there are no problems after above checks
Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver
5. When Vertical Louver does not operate.
Check the operating circuit of the Vertical Louver
Confirm that there is DC +12V between pin (RED) of CN-U/D and GND.
-50-
6. When Heating does not operate
Operate Heating Mode( ) by setting the desired temperature of the remote control is higher than one of the indoor temperature by 2°C at least.
In heating Mode, the indoor fan operates in case the pipe temperature is higher than 28°C.
Check the connector of intake and pipe sensor(thermistors)
Check the related circuit of R02H(12.1K), R01H(1.0K), R04H(6.2K), R03H(1.0K).
Check the indoor room temperature is disconnected or not (about 10K/at 25°C).
Check the indoor pipe temperature is disconnected or not (about 5K/at 25°C).
Turn ON Main Power
Check if connection line (Indoor/Outdoor) is complied with Wiring Diagram.
Check Outdoor Unit
(PCB Ass'y)
Correct connection line
Good connection Bad connection
-51-
PCB Board Operation Check in Outdoor
Items
Power Transformer (Outdoor unit)
- Input Voltage
- Output Voltage
IC01D(7812) Output (Indoor/Outdoor unit)
IC02D(7805) Output (Indoor/Outdoor unit)
IC01A(KIA7036, Reset IC) X01(8MHz)
Replace Trans
Replace IC01D
Replace IC02D
Replace faulty parts
- About AC220V/240V±10% - Check the power voltage
- About AC14±3V
DC +12V
DC +5V
Content Remedy
7. Outdoor unit does not operate at all.
8. Communication error
The control data can be transmitted or received between indoor and outdoor unit with one signal cable.
If the data be disturbed by any noise level and misconnection, the unit will be operated incorrectly. In this
case, the indoor unit blinks the operation and operation LED on display and indoor fan, outdoor fan, COMP are not operated.
The unit can be reoperated by On/Off control of Remocon.
Check Outdoor Unit
Turn off Main Power
Check the electrical wiring diagram of outdoor side.
Check the abnormal condition for the component of
Compressor/Outdoor Fan Motor/4-way.
Check the open or short of connecting wires between indoor and outdoor.
- 52 -
Electronic Control Device
1. Indoor
• MAIN P.C.B ASM
-53-
2. Outdoor
• MAIN P.C.B ASM
- 54 -
3. Display Ass'y
- 55 -
Schematic Diagram
1. Indoor
-56-
2. Outdoor
- 57 -
Exploded View and Replacement Parts List
1. Indoor Unit (LM-1830C2L/M/N, LM-1830H2L/M/N)
135312
268712
267110
135311
354210
152313
249951
152302
135511
159901
342800
131410 733010
346812
263230
268714
352150
146811
35211B
359011
- 59 -
2. Indoor Unit (LM-2430C2L/M/N, LM-2430H2L/M/N)
135312
268712
267110
135311
354210
249951
152302
135511
159901-1
159901-1
342800
131410 733010
346812
263230
268714
352150
146811
35211B
359011
152313
- 63 -
3. Outdoor Unit (LM-1830C2L/M/N, LM-2430C2L/M/N)
435512
554030
137213
435311
437210
W0CZZ-1
261704
W0CZZ-2
263230
268716
559010 346810
447910
435511
649950
268717
W52110-2
W52110-1
430410
349600
554160
552203-1
552203-2
552203-3
266310
- 65 -
4. Outdoor Unit (LM-1830H2L/M/N, LM-2430H2L/M/N)
435512
554030
435300
137213-1
137213-2
135301
349480 437210
559010 346811
447910
435511
561410-2
561410-1
430410
349600
554160
552202
552203-1
552203-2
552203-3
W0CZZ-1
261704
W0CZZ-2
263230
268716
649950
W52110-2
W52110-1
268717
266310
P/No.: 3828A20097A
July, 2005
Printed in Korea
Loading...