Lg Hmc018kd1 Service Manual

Multi Type Room Air Conditioner
SERVICE MANUAL
MODEL: LM-1830C2L/M/N
LM-1830H2L/M/N LM-2430C2L/M/N LM-2430H2L/M L2-C243AL1
Refrigeration Cycle Diagram..................................................................................................... 11
Wiring Diagram .......................................................................................................................... 12
Operation Details ....................................................................................................................... 13
Display Function........................................................................................................................ 20
Self-diagnosis Function ............................................................................................................ 20
Installation.................................................................................................................................. 21
Operation.................................................................................................................................... 35
Disassembly of the parts (Indoor Unit).................................................................................... 37
2-way, 3-way Valve..................................................................................................................... 39
Cycle Troubleshooting Guide ....................................................................................................43
Electronic Parts Troubleshooting Guide.................................................................................. 45
Electronic Control Device ......................................................................................................... 52
Schematic Diagram.................................................................................................................... 55
Exploded View and Replacement Parts List............................................................................ 57
- 2 -
Contents
• Room temperature sensor. (THERMISTOR)
• Maintains the room temperature in accordance with the Setting Temp.
• Indoor fan is delayed for 5 seconds at the starting.
• Restarting is inhibited for approx. 3 minutes.
• High, Med, Low, Chaos
--- Lights up in operation
--- Lights up in Sleep Mode
--- Lights up in Timer Mode
--- Lights up in Deice Mode(for Heat pump model)
---
Lights up in Compressor operation(for Cooling model)
• Intermittent operation of fan at low speed.
• The fan is switched to low(Cooling), med(Heating) speed.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
• The fan is switched to intermittent or irregular operation
The fan speed is automatically switched from high to low speed.
• The louver can be set at the desired position or swing up and down automatically.
- 3 -
Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Time Delay Safety Control
Indoor Fan Speed Control
Operation indication Lamps (LED)
OUT
DOOR
Health Dehumidification Operation
• Both the indoor and outdoor fan stops during deicing.
• Hot start after deice ends.
• The indoor fan stops until the evaporator piping temperature will be reached at 28°C.
Sleep Mode Auto Control
Natural Air Control by CHAOS Logic
Airflow Direction Control
Deice (defrost) control (Heating)
Hot-start Control (Heating)
Outdoor unit operation
Soft Dry Operation Mode
• The function will be operated while in any
operation mode with selecting the function.
• The function is to be stopped while it is
operating with selecting the function.
Intermittent operation of fan at low speed.
PLASMA
- 4 -
Remote Controller
JET COOL
Healthy Dehumidification Operation Mode.
()
Operation Mode Selection
(Cooling
model only)
(Heating
model only)
Cooling Operation Mode.( )
Heating Operation Mode.( )
Auto Operation Mode.( )
Sleep Operation
˚C To ˚F Swtiching Button
Room, Temperature Display
Setting the Time or Timer
Airflow Direction Control
Operation ON/OFF
Temperature Setting
TEMPERATURE
LOWHIGH
Timer Selection
ON OFF
˚C / ˚F
Timer Setting
SET
Timer Cancel
CANCEL
Fan Operation Mode
Reset
Fan Speed Selection
(Low) (Med) (High) (CHAOS)
Down to 18°C(64˚F) Up to 30°C(86˚F)
Cooling
: Cancel Sleep Mode, Timer ON or Timer OFF
: 1, 2, 3, 4, 5, 6, 7, Off Timer
: Fan Operates without cooling or heating.
: High: 39°C(102˚F) LOW : 11°C(52˚F)
Down to 16°C(60˚F) Up to 30°C(86˚F)
Heating
: OFF, ON, OFF ON
- 5 -
Product Specifications
1. LM-1830C2L/M
17,000/18,000 8,500/9,000 8,500/9,000 208/230V
––
2.4 1.2 1.2 at 230V 1Ø, 208/230V, 60Hz
Indoor 7.0 7.0
Outdoor 42
Indoor 39/37/35 39/37/35
at 230V
Outdoor 53
1,680/1,700 930/950 930/950
––
8.2/7.5 4.5/4.0 4.5/4.0 208/230V
––
10.1/10.6 9.1/9.5 9.1/9.5
––
Indoor 802 x 262 x 165
Outdoor 870 x 655 x 320
Indoor 7
Outdoor 61
Liquid 6.35(1/4")
Gas 9.52(3/8")
780 780 at 7.5m
O
L.C.D Wireless
O O
Operation
A-Unit
Only
B-Unit
Only
A-Unit + B-Unit
Remarks
Unit
Item
Cooling Capacity Heating Capacity Moisture Removal /h Power Source ø, V, Hz
Air Circulation /min
Noise Level dB(A)
Input W
A
E.E.R. Btu/h.w C.O.P. -
Dimensions(W x H x D)
mm
Net. Weight kg
Service Valve mm(Inch)
Refrigerant(R-22) g Airflow Direction Control(Up & Down) Remote Controller Type Sleeping Operation Drain Hose
Cooling Heating Cooling Heating
Cooling
Heating
Running
Current
Btu/h(kcal/h)
( Hi / Med / Low )
- 6 -
2. LM-1830H2L/M
17,000/18,000 8,500/9,000 8,500/9,000
208/230V
17,000/18,000 8,500/9,000 8,500/9,000
2.4 1.2 1.2 at 230V 1Ø, 208/230V, 60Hz
Indoor 7.0/7.6 7.0/7.6
Cooling/Heating
Outdoor 42
Indoor 39/37/35 39/37/35
at 230V
Outdoor 53
1,680/1,700 930/950 930/950 1,680/1,700 930/950 930/950
8.2/7.5 4.5/4.0 4.5/4.0 208/230V
8.2/7.5 4.5/4.0 4.5/4.0
10.1/10.6 9.1/9.5 9.1/9.5
2.97/3.10 2.68/2.78 2.68/2.78
Indoor 802 x 262 x 165
Outdoor 870 x 655 x 320
Indoor 7
Outdoor 63
Liquid 6.35(1/4")
Gas 9.52(3/8")
780 780 at 7.5m
O
L.C.D Wireless
O O
Operation
A-Unit
Only
B-Unit
Only
A-Unit + B-Unit
Remarks
Unit
Item
Cooling Capacity Heating Capacity Moisture Removal /h Power Source ø, V, Hz
Air Circulation /min
Noise Level dB(A)
Input W
A
E.E.R. Btu/h.w C.O.P. -
Dimensions(W x H x D)
mm
Net. Weight kg
Service Valve mm(Inch)
Refrigerant(R-22) g Airflow Direction Control(Up & Down) Remote Controller Type Sleeping Operation Drain Hose
Cooling
Heating
Cooling
Heating Cooling
Heating
Running
Current
Btu/h(kcal/h)
( Hi / Med / Low )
- 7 -
3. LM-2430C2L/M
23,600/24,000 11,800/12,000 11,800/12,000 208/230V
––
3.4 1.7 1.7 at 230V 1Ø, 208/230V, 60Hz
Indoor 8.0 8.0
Outdoor 42
Indoor 40/38/36 40/38/36
at 230V
Outdoor 54
2,400/2,400 1,300/1,300 1,300/1,300
––
11.0/10.0 6.2/5.7 6.2/5.7 208/230V
––
9.8/10.0 9.1/9.2 9.1/9.2
––
Indoor 888 x 287 x 170
Outdoor 870 x 655 x 320
Indoor 7
Outdoor 61
Liquid 6.35(1/4")
Gas 12.7(1/2")
880 880 at 7.5m
O
L.C.D Wireless
O O
Operation
A-Unit
Only
B-Unit
Only
A-Unit + B-Unit
Remarks
Unit
Item
Cooling Capacity Heating Capacity Moisture Removal /h Power Source ø, V, Hz
Air Circulation /min
Noise Level dB(A)
Input W
A
E.E.R. Btu/h.w C.O.P. -
Dimensions(W x H x D)
mm
Net. Weight kg
Service Valve mm(Inch)
Refrigerant(R-22) g Airflow Direction Control(Up & Down) Remote Controller Type Sleeping Operation Drain Hose
Cooling
Heating
Cooling
Heating Cooling
Heating
Running
Current
Btu/h(kcal/h)
( Hi / Med / Low )
- 8 -
4. LM-2430H2L/M
23,600/24,000
11,800/12,000 11,800/12,000
208/230V
23,600/24,000
11,800/12,000 11,800/12,000
3.4 1.7 1.7 at 230V 1Ø, 208/230V, 60Hz
Indoor 8.0/8.6 8.0/8.6
Cooling/Heating
Outdoor 42
Indoor 40/38/36 40/38/36
at 230V
Outdoor 54
2,400/2,400 1,300/1,300 1,300/1,300 2,400/2,400 1,300/1,300 1,300/1,300
11.0/10.0 6.2/5.7 6.2/5.7 208/230V
11.0/10.0 6.2/5.7 6.2/5.7
9.8/10.0 9.1/9.2 9.1/9.2
2.89/2.93 2.66/2.70 2.66/2.70
Indoor 888 x 287 x 170
Outdoor 870 x 655 x 320
Indoor 7
Outdoor 63
Liquid 6.35(1/4)
Gas 12.7(1/2)
880 880 at 7.5m
O
L.C.D Wireless
O O
Operation
A-Unit
Only
B-Unit
Only
A-Unit + B-Unit
Remarks
Unit
Item
Cooling Capacity Heating Capacity Moisture Removal /h Power Source ø, V, Hz
Air Circulation /min
Noise Level dB(A)
Input W
A
E.E.R. Btu/h.w C.O.P. -
Dimensions(W x H x D)
mm
Net. Weight kg
Service Valve mm(Inch)
Refrigerant(R-22) g Airflow Direction Control(Up & Down) Remote Controller Type Sleeping Operation Drain Hose
Cooling
Heating
Cooling
Heating Cooling
Heating
Runnig
Current
Btu/h(kcal/h)
( Hi / Med / Low )
- 9 -
Dimensions
Installation plate
Installation plate
Right rear piping
Left rear piping
ø70mm
ø70mm
50mm
20mm
20mm
80mm
A
A
ø70mm
Center
Center
ø70mm
Left rear piping Right rear piping
A
A
D
H
W
Tubing hole cover
W mm 802 888
H mm 262 287 D mm 165 170
LM-1830C2L/M, LM-1830H2L/M
LM-2430C2L/M, LM-2430H2L/M
MODEL
DIM
( LM-1830C2L/M, LM-1830H2L/M ) ( LM-2430C2L/M, LM-2430H2L/M )
1. Indoor Unit
Pipe Hole
Fix Hole
Hanger Hole
H
W
D
Capacity W H D
SP1 Ch. 9K/12K 570 568 137
- 10 -
W
D
L1
L2
L9
L4
L3
H
L10
L10
L10
L8
Gas side 3-Way valve
Liquid side 2-Way valve
L7L5L6
2. Outdoor Unit
W mm 870 H mm 655 D mm 320 L1 mm 370 L2 mm 25 L3 mm 630 L4 mm 25 L5 mm 546 L6 mm 160 L7 mm 160 L8 mm 64 L9 mm 76.5 L10 mm 50
LM-1830C2L/M, LM-1830H2L/M, LM-2430C2L/M, LM-2430H2L/M,L2-C243AL1
MODEL
DIM
- 11 -
Refrigeration Cycle Diagram
HEAT EXCHANGER
COOLING HEATING DEICE
HEAT
EXCHANGER
CAPILLARY TUBE
COMPRESSOR-B
COMPRESSOR-A
CAPILLARY TUBE
2-WAY VALVE
4-WAY VALVE
B-UNITA-UNIT
3-WAY VALVE
4-WAY VALVE
Indoor Unit Outdoor Unit
Pipe Size (Diameter : inch)
Max.
piping length
(m)
Max.
piping elevation
(m)
Gas
Btu/h
Liquid
1/2" 1/4" 15 8
3/8"
24K
18K 1/4" 15 8
ex)
Capillary Cooling & Deice
A-UNIT B-UNIT
CAPILLARY TUBE
LIQUID SIDE
2-WAY VALVE
GAS SIDE
3-WAY VALVE
HEAT EXCHANGER (EVAPORATOR)
HEAT
EXCHANGER
(CONDENSER)
COMPRESSOR
B
COMPRESSOR
A
1. LM-1830C2L/M, LM-2430C2L/M,L2-C243AL1 (Cooling only models)
2. LM-1830H2L/M, LM-2430H2L/M (Cooling & Heating modes)
MOTOR
STEP
MOTOR
CN-MOTOR
RD
CGVS
PILLAR TERMINAL
BKBRBL
SW01F
FORCED OPERATION
AUTO RESTART
REMOTE CONTROL
THERMISTOR
CN-TH
CN-U/D
CN-DISP1
MAIN PCB ASSY
INDOOR WIRING DIAGRAM
3854A20075M
DISPLAY PCB ASSY
TO OUTDOOR UNIT
CN-POWER
BK
CAPACITOR
TRANS­FORMER
CN-SV
CN-POWER CN-COMP1 CN-COMP2
FUSE T3.15A
CN-TRANAS
RY-COMP A
RY-COMP B
RY-FAN1
RY-SV3
RY-SV4
CN-TH1
MAIN DC PCB ASSY
MAIN AC PCB ASSY
PILLAR TERMINAL
TO INDOOR UNIT
B INDOORA INDOOR
CAPACITOR
A 4-WAY
B 4-WAY
THERMISTOR
BK BK
BK
BK
BK
BK BL YL
BK
BK
YL
BK
"A"
COMP
"B"
COMP
RD
RDBL
WH WH
44
33
OLP
OLP
H
S
C
C
S
R
R
CF
BK OR
OR
BR
YL
MOTOR
BK
T/B1
BK
BK
YL
RD
BK
BK
BR
BL
OR
RD
CGVSCGVS
CGVS
CGVS
BK BR BLRD BK BR BL
BKBKBR BL
WH
BL
BL
GN/YL
L2L1
MAIN
POWER
FUS250V 2.5A
FUS250V 2.5A
FUS250V 2.5A
FUS250V 2.5A
OUTDOOR WIRING DIAGRAM
3854A20075K
BK
CAPACITOR
TRANS­FORMER
CN-SV
CN-POWER CN-COMP1
CN-COMP2
FUSE T3.15A
CN-TRANAS
RY-COMP A
RY-COMP B
RY-FAN1
MAIN DC PCB ASSY
MAIN AC PCB ASSY
PILLAR TERMINAL
TO INDOOR UNIT
B INDOORA INDOOR
CAPACITOR
BK
BK
BK
YL
BK
"A"
COMP
"B"
COMP
RD
RD
BL
WH WH
4
4 33
OLP
OLP
H
S
C
C
S
R
R
C
F
BK OR
OR
BR
YL
MOTOR
BK
T/B1
BK
BK
YL
RD
BK
BK BR
BL
OR
RD
CGVSCGV S
CGVS
CGVS
BK BR BLRD BK BR BL
BKBKBR BL
WH
BL
BL
GN/YL
L2L1
MAIN
POWER
FUS250V 2.5A
FUS250V 2.5A
FUS250V 2.5A
FUS250V 2.5A
OUTDOOR WIRING DIAGRAM
3854A20075L
- 12 -
Wiring Diagram
1. INDOOR UNIT: LM-1830C2L/M, LM-1830H2L/M, LM-2430C2L/M, LM-2430H2L/M
2. OUTDOOR UNIT
• LM-1830C2L/M
• LM-2430C2L/M
• LM-1830H2L/M
• LM-2430H2L/M
Operation Details
1. MAIN UNIT FUNCTION
• DISPLAY
1) C/O Model Operation Indicator
On while in appliance operation, off while in appliance pause
Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on)
Sleep Timer Indicator
On while in sleep timer mode, off when sleep timer cancel or appliance operation pause
Timer Indicator
On while in timer mode (on/off), off when timer mode is completed or canceled.
Comp. Running Incidator
While in appliance operation, on while in outdoor unit compressor running, off while in compressor off
2) H/P Model Operation Indicator
On while in appliance operation, off while in appliance pause
Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on)
Sleep Timer Indicator
On while in sleep timer mode, off when sleep timer cancel or appliance operation pause
Timer Indicator
On while in timer mode (on/off), off when timer mode is completed or canceled
Defrost Indicator
Off except when hot start during heating mode operation or while in defrost control
Cooling Mode Operation
When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan stop.
When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp Setting Temp+0.5°C Compressor OFF Temp ➲ Setting Temp-0.5°C
While in compressor running, operating with the airflow speed set by the remote control. While in compressor not running, operating with the low airflow speed regardless of the setting.
Healthy Dehumidification Mode
When the dehumidification operation input by the remote control is received, the intake air temperature is detected and the setting temp is automatically set according to the intake air temperature.
26°C Intake Air Temp 25°C 24°C Intake Intake Air Temp<26°C Intake Air Temp-1°C 18°C Intake Intake Air Temp<24°C Intake Air Temp-0.5°C Intake Air Temp<18°C 18°C
-13-
While in compressor off, the indoor fan repeats low airflow speed and pause.
While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidifica-
tion operation and 4-min compressor off repeat. Compressor ON Temp. Setting Temp+0.5°C Compressor OFF Temp. ➲ Setting Temp-0.5°C
In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
Heating Mode Operation(H/P model)
When the intake air temp reaches +3°…above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on. Compressor ON Temp. Setting Temp. Compressor OFF Temp. ➲ Setting Temp.+3°C
While in compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C, when above 28°C , it operates with the low or setting airflow speed. When the indoor pipe temp is between 20°C and 28°C, it oper­ates with Super-Low(while in sleep mode, with the medium airflow speed).
While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C, when above 35°C , it operates with the low airflow speed.
If overloaded while in heating mode operation, in order to prevent the compressor from OLP operation, the outdoor fan is turned on/off according to the indoor pipe temp.
While in defrost control, both of the indoor and outdoor fans are turned off.
Defrost Control(H/P model)
Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
The first defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes passed from
starting of heating operation and more than 10 minutes operation of compressor.
Defrost ends after 9/6 minutes passed from starting of defrost operation or after the outdoor fan operates within max. 2 minutes 30 seconds when the outdoor pipe temperature rises over 12°C even it before 12 min- utes.
The second defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes passed from ending of the first defrost and more than 10 minutes operation of compressor.
Heating overload(H/P models)
Outdoor fan ON/OFF by sensing outdoor pipe temperature.
Outdoor fan is OFF if pipe temperature is over 6.5°C and outdoor fan is ON if pipe temperature is below 0°C.
Outdoor fan is off if any one part is heating overload condition.
-14-
-15-
Fuzzy Operation (C/O Model)
According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp ➲ Setting Temp + 0.5°C Compressor OFF Temp ➲ Setting Temp + 0.5°C
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time.
26°C Intake Air Temp 25°C 24°C Intake Air Temp < 26°C Intake Air Temp + 1°C 22°C Intake Air Temp < 24°C Intake Air Temp + 0.5°C 18°C Intake Air Temp < 22°C Intake Air Temp Intake Air Temp<18°C 18°C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
Fuzzy Operation (H/P Model)
When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since the operation off, the operation mode is selected.
When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air temp at that moment as follows.
24°C Inatake Air Temp Fuzzy Operation for Cooling 21°C Inatake Air Temp<24°C Fuzzy Operation for Dehumidification Inatake Air Temp<21°C Fuzzy Operation for Heating
If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10 sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.
1) Fuzzy Operation for Cooling
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp ➲ Setting Temp +0.5°C Compressor OFF Temp ➲ Setting Temp + 0.5°C
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time.
26°CIntake Air Temp 25°C 24°CIntake Air Temp<26°C Intake Air Temp + 1°C 22°CIntake Air Temp<24°C Intake Air Temp + 0.5°C 18°CIntake Air Temp<22°C Intake Air Temp Intake Air Temp<18°C ➲ 18°C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the tem­perature.
-16-
2) Fuzzy Operation for Dehumidification
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp Setting Temp + 0.5°C Compressor OFF Temp ➲ Setting Temp+0.5°C
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time.
26°C Intake Air Temp 25°C 24°C Intake Air Temp<26°C Intake Air Temp+1°C 22°C Intake Air Temp<24°C Intake Air Temp+0.5°C 18°C Intake Air Temp<22°C Intake Air Temp Intake Air Temp<18°C ➲ 18°C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in dehumidification operation.
3) Fuzzy Operation for Heating
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C or more above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on.
Compressor ON Temp Setting Temp Compressor OFF Temp ➲ Setting Temp + 3°C
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time.
20°CIntake Air Temp Intake Air Temp + 0.5°C Intake Air Temp<20°C 20°C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the intake air temperature and the setting temperature.
Airflow Speed Selection
The airflow speed of the indoor fan is set to high, medium, low, or chaos (auto) by the input of the airflow speed selection key on the remote control.
On-Timer Operation
When the set time is reached after the time is input by the remote control, the appliance starts to operate.
The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
If the appliance is operating at the time set by the timer, the operation continues.
-17-
Off-Timer Operation
When the set time is reached after the time is input by the remote control, the appliance stops operating.
The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
If the appliance is on pause at the time set by the timer, the pause continues.
Off-Timer <=> On-Timer Operation
When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation is carried out according to the set time.
Sleep Timer Operation
When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appli­ance operation, the operation of the appliance stops.
While the appliance is on pause, the sleep timer mode cannot be input.
While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature increases by 1°C. After another 30 min elapse, it increases by 1°C again.
When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to
the low.
When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to the medium.
Chaos Swing Mode
By the Chaos Swing key input, the upper/lower vane automatically operates with the Chaos Swing or they are fixed to the desired direction.
While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.
Chaos Natural Wind Mode
When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air­flow mode is operated for 2~15 sec. randomly by the Chaos Simulation.
Jet Cool Mode Operation (C/O Model)
If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
Jet Cool Mode Operation (H/P Model)
While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the other
mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C.
When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
-18-
Auto Restarting Operation
When the power is restored after a sudden power failure while in appliance operation, the mode before the power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
The slide switch on the main unit of the appliance should be on the Auto Restarting position in order that the Auto Restarting operation is available.
Operation Mode that is kept on the memory
- State of Operation ON/OFF
- Operation Mode/Setting Temp/Selected Airflow Speed
- Sleep Timer Mode/Remaining Time of Sleep Timer (unit of hour)
Slide Switch
FORCED OPERATION
AUTO RESTART
REMOTE CONTROL
Forced Operation (C/O Model)
To operate the appliance by force in case that the remote control is lost, the forced operation selection switch is on the main unit of the appliance to operate the appliance in the standard conditions.
When the power is supplied while the slide switch is on the forced operation position, or when the slide switch position is switched to the Auto Restarting position (or test operation) or switched from the remote control posi­tion to the forced operation position while the power is on, the forced operation is carried out.
When the slide switch position is switched from the forced operation position to the Auto Restarting position or the remote control position, the forced operation is canceled and the appliance stops operating.
The forced operation is carried out in cooling mode with the setting temperature 22°C and the high speed of airflow.
While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to indicate the forced operation.
Forced Operation (H/P Model)
To operate the appliance by force in case that the remote control is lost, the forced operation selection switch is on the main unit of the appliance to operate the appliance in the standard conditions.
When the power is supplied while the slide switch is on the forced operation position, or when the slide switch position is switched to the Auto Restarting (or test operation) position or switched from the remote control posi­tion to the forced operation position while the power is on, the forced operation is carried out.
When the slide switch position is switched from the forced operation position to the Auto Restarting position or the remote control position, the forced operation is canceled and the appliance stops operating.
The forced operation is carried out in cooling mode with the setting temperature 22°C and the high speed of airflow.
In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the operation condition is set according to the intake air temperature as follows.
24°CIntake Air Temp Cooling Mode Operation, 22°C, High Speed 21°CIntake Air Temp<24°C Dehumidification Operation, 23°C, High Speed Intake Air Temp<21°C Heating Mode Operation, 24°C, High Speed
While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to indicate the forced operation.
-19-
Remote Control Operation Mode
When the remote control is selected by the slide switch on the main unit, the appliance operates according to the input by the remote control.
Protection of the evaporator pipe from frosting
If the indoor pipe temp is below 0°C in 7 min. after the compressor operates without any pause while in cool­ing cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor evaporator pipe from frosting.
When the indoor pipe temp is 7°C or higher after 3 min. pause of the compressor, the compressor and the outdoor fan is turned on according to the condition of the room temperature.
Buzzer Sounding Operation
When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.
When the appliance-pause key is input by the remote control, the long "beep" sounds.
When a key is input by the remote control while the slide switch on the main unit of the appliance is on the
forced operation position, the error sound "beep-beep-beep-beep-beep-" is made 10 times to indicate that the remote control signal cannot be received.
Loading...
+ 42 hidden pages