LG AS-H0966KA2, F09AHJ, AS-H126RKA2, F12AHJ, AS-H186TKA2 User Manual

...
Page 1
Room Air Conditioner
SVC MANUAL(Exploded View)
MODEL : AS-H0966KA2 (F09AHJ)
AS-H126RKA2 (F12AHJ) AS-H186TKA2 (F18AHJ) AS-H246TKA2 (F24AHJ)
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel.
Internal Use Only
http://biz.lgservice.com
Page 2
- 2 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Air Conditioner Service Manual
TABLE OF CONTENTS
LG Model Name ...............................................................................................................................................3
Safety Precautions..........................................................................................................................................5
Dimensions....................................................................................................................................................10
Symbols Used in this Manual...................................................................................................................10
Indoor Unit................................................................................................................................................10
Outdoor Unit.............................................................................................................................................11
Product Specifications .................................................................................................................................14
Installation .....................................................................................................................................................15
Selection of the Best Location..................................................................................................................15
Piping Length and Elevation.....................................................................................................................15
How to Fix Installation Plate.....................................................................................................................16
Drill a Hole in the Wall..............................................................................................................................16
Drain hose junction...................................................................................................................................16
Flaring work and connection of piping .......................................................................................................17
Flaring work..............................................................................................................................................17
Connection of Piping Indoor.....................................................................................................................17
Connection of the Pipes-Outdoor.............................................................................................................21
Connecting the cable between indoor unit and outdoor unit ...................................................................22
Connect the Cable to the Indoor Unit.......................................................................................................22
Connect the Cable to the Outdoor Unit ....................................................................................................23
Checking the drainage and forming the pipings........................................................................................24
Checking the Drainage.............................................................................................................................24
Form the Piping........................................................................................................................................24
AIR PURGING ................................................................................................................................................25
Air purging................................................................................................................................................25
Air purging with vacuum pump.................................................................................................................25
Test Running .................................................................................................................................................27
Operation .......................................................................................................................................................28
Function of Controls .................................................................................................................................28
Display Function ......................................................................................................................................32
Self-diagnosis Function............................................................................................................................32
Remote Control Operations......................................................................................................................33
Disassembly ..................................................................................................................................................34
Indoor Unit................................................................................................................................................34
Schematic Diagram.......................................................................................................................................37
Electric Control Device.............................................................................................................................37
Wiring Diagram.........................................................................................................................................38
Components Location ..............................................................................................................................39
Troubleshooting Guide.................................................................................................................................41
Refrigeration Cycle Diagram ....................................................................................................................41
2-way, 3-way Valve .................................................................................................................................42
Cycle Parts...............................................................................................................................................48
Electronic Parts ........................................................................................................................................49
Exploded View...............................................................................................................................................56
Page 3
- 3 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
LG Model Name
2003
12 - 345678910
Code Type Code of Model Meaning
1 Producing Center, A~Z L: Chang-won R22 N: India
Refrigerant A: Chang-won R410A Z: Brazil
C: Chang-won R407C D: Indonesia T: China M: Mexico K: Turkey R22 V: Vietnam E: Turkey R410A S: Out Sourcing H: Thailand
2 Product Type A~Z S: Split Type Air Conditioner
3 Cooling/Heating/Inverter A~Z C: Cooling only
H: Heat pump X: C/O + E/Heater Z: H/P + E/Heater
V: AC Inverter C/O N: AC Inverter H/P Q: DC Inverter C/O W: DC Inverter H/P
4, 5 Capacity 0~9 Cooling/Heating Capacity
Ex. "09" 9,000 Btu/h
6 Electric Range 1~9 1: 115V/60Hz, A: 220V, 50Hz, 3Phase
A~Z 2: 220V/60Hz B: 208~230V, 60Hz, 3Phase
3: 208-230V/60Hz C: 575V, 50Hz, 3Phase 5: 200-220V/50Hz D: 440~460, 60Hz, 3Phase 6: 220-240V/50Hz E: 265V, 60Hz 7: 110V, 50/60Hz F: 200V, 50/60Hz 8: 380-415V/50Hz 9: 380-415V/60Hz
7 Chassis A~Z Name of Chassis of Unit
Ex. LSP SP Chassis
8 Look A~Z Look,
Color (Artcool Model)
9 Function A~Z
10 Serial No. 1~9 LG Model De
* ARTCOOL COLOR
velopment Serial No.
Basic A Basic+4Way B Plasma Filter C Plasma Filter+4 Way D Tele+LCD E Tele+LCD+Nano plasma+4Way F Nano Plasma F+(A/changeove)+A/clean+Low A G Nano Plasma F+(A/changeove)+A/clean+4way+Low A H Tele+LED+4way I Internet J Plasma F+4Way+Oxy generator K Nano Plasma F+(A/changeove)+A/clean L Nano Plasma F+(A/changeove)+A/clean+4way M Nano Plasma F+(A/changeove)+A/clean+PTC N Nano Plasma F+(A/changeove)+Autoclean+4way+PTC P Nano Plasma F+(A/changeove)+A/clean+4way+Low A+PTC Q Negative ION+A/Clean R (Nano)Plasma+Negative ION+A/Clean S 4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean
T
Nano Plasma F+4Way+(A/changeove)+A/clean+ U
R Mirror W White B Blue D Wood M Metal C Cherry
Page 4
- 4 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
2004~
12 - 345678910
Code Type Code of Model Meaning
1 Producing Center, A~Z L: Chang-won R22 N: India
Refrigerant A: Chang-won R410A Z: Brazil
C: Chang-won R407C D: Indonesia T: China M: Mexico K: Turkey R22 V: Vietnam E: Turkey R410A S: Out Sourcing H: Thailand
2 Product Type A~Z S: Split Type Air Conditioner
3 Cooling/Heating/Inverter A~Z C: Cooling only
H: Heat pump X: C/O + E/Heater Z: H/P + E/Heater
V: AC Inverter C/O N: AC Inverter H/P Q: DC Inverter C/O W: DC Inverter H/P
4, 5 Capacity 0~9 Cooling/Heating Capacity
Ex. "09" 9,000 Btu/h
6 Electric Range 1~9 1: 115V/60Hz, A: 220V, 50Hz, 3Phase
A~Z 2: 220V/60Hz B: 208~230V, 60Hz, 3Phase
3: 208-230V/60Hz C: 575V, 50Hz, 3Phase 5: 200-220V/50Hz D: 440~460, 60Hz, 3Phase 6: 220-240V/50Hz E: 265V, 60Hz 7: 110V, 50/60Hz F: 200V
CHASSIS Look
D K
L G M N D P
Division Panel Type(Deluxe) Fighting 'Look'
(LG1) (LG2)-SEMI PANEL OEM1 OEM2 Panel Type(Deluxe) LG3
, 50/60Hz 8: 380-415V/50Hz 9: 380-415V/60Hz
7 Chassis A~Z Name of Chassis of Unit
Ex. LSP SP Chassis
8 Look A~Z Look,
Color (Artcool Model)
9 Function A~Z
10 Serial No. 1~9 LG Model De
* ARTCOOL COLOR
velopment Serial No.
Basic A Basic+4Way B Plasma Filter C Plasma Filter+4 Way D Tele+LCD E Tele+LCD+Nano plasma+4Way F Nano Plasma F+(A/changeove)+A/clean+Low A G Nano Plasma F+(A/changeove)+A/clean+4way+Low A H Tele+LED+4way I Internet J Plasma F+4Way+Oxy generator K Nano Plasma F+(A/changeove)+A/clean L Nano Plasma F+(A/changeove)+A/clean+4way M Nano Plasma F+(A/changeove)+A/clean+PTC N Nano Plasma F+(A/changeove)+Autoclean+4way+PTC P Nano Plasma F+(A/changeove)+A/clean+4way+Low A+PTC Q Negative ION+A/Clean R (Nano)Plasma+Negative ION+A/Clean S 4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean
T
Nano Plasma F+4Way+(A/changeove)+A/clean+ U
R Mirror W White B Blue D Wood M Metal C Cherry
S4/S5
S6 SQ SR
ST
ST2
Page 5
- 5 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
Do not use damaged power cords, plugs, or a loose socket.
Always use the power plug and socket with the ground terminal.
• There is risk of fire of electric shock. • There is risk of electric shock.
Install the panel and the cover of control box securely.
.Do not modify or extend the power cord.
• There is risk of fire of electric shock. • No grounding may cause electric shock.
Installation
Page 6
- 6 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Safety Precautions
Do not install the product on a defective instal­lation stand.
Be sure the installation area does not deteriorate with age.
• It may cause injury, accident, or damage to the
product.
• If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
• Sharp edges could cause injury. Be especially care­ful of the case edges and the fins on the condenser and evaporator.
There is risk of fire, electric shock, explosion, or injury.
Be cautious when unpacking and installing the product.
For installation, always contact the dealer or an Authorized service center
For re-installation of the installed product, always contact a dealer or an authorized ser­vice center.
Do not install, remove, or re-install the unit by yourself.
• There is risk of fire, electric shock, explosion, or injury.
• There is risk of fire, electric shock, explosion, or injury.
Page 7
- 7 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Safety Precautions
Operation
Do not turn the air-conditioner ON or OFF by plugging or unplugging the power plug.
Use a dedicated outlet for this appliance.
• There is risk of fire or electrical shock. • There is risk of fire or electrical shock.
Grasp the plug to remove the cord from the outlet. Do not touch it with wet hands.
Do not place a heater or other appliances near the power cable.
• There is risk of fire or electrical shock. • There is risk of fire and electric shock.
Do not allow water to run into electrical parts. Do not store or use flammable gas or com-
bustibles near the air conditioner.
• There is risk of fire, failure of the product, or electric shock.
• There is risk of fire or failure of product.
Wax
Thinner
Page 8
- 8 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Always check for gas (refrigerant) leakage after installation or repair of product.
Install the drain hose to ensure that water is drained away properly.
• Low refrigerant levels may cause failure of product. • A bad connection may cause water leakage.
Keep level even when installing the product. Use two or more people to lift and transport
the air conditioner.
• To avoid vibration or water leakage. • Avoid personal injury.
Installation
90˚
Unplug the unit if strange sounds, odors, or smoke comes from it.
Be cautious that water could not enter the product.
• There is risk of electric shock or fire. • There is risk of fire, electric shock, or product dam­age.
Safety Precautions
Page 9
- 9 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
Do not touch the metal parts of the product when removing the air filter. They are very sharp!
• There is risk of fire, electric shock, or damage to the plastic parts of the product.
• There is risk of personal injury.
Do not step on or put anyting on the product. (outdoor units)
Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
• There is risk of personal injury and failure of product. • There are sharp and moving parts that could cause
personal injury.
Operation
Wax
Safety Precautions
Page 10
- 10 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Dimensions
Dimensions
Installation plate
D
H
W
W mm 758 900 1,090
H mm 260 285 314
D mm 155 156 172
Model
Dimension
9K Btu Series 12K Btu Series 18K, 24K Btu Series
Indoor Unit
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the air conditioner.
This symbol indicates special notes.
NOTICE
Symbols Used in this Manual
Page 11
W
L2
L3
L1
D
H
L4
L5
Gas side
(3-way valve)
Liquid side
(2-way valve)
MODEL
9K Btu Series 12K Btu Series
DIM unit
W mm 575 717
H mm 525 481
D mm 260 228
L1 mm 301 270
L2 mm 73 56
L3 mm 392 464
L4 mm 35 17
L5 mm 100 130
Dimensions
Outdoor Unit
- 11 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Dimensions
Page 12
- 12 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Outdoor Unit
MODEL
DIM
W
L2
L3
L1
D
H
L4
L5
Gas side
(3-way valve)
Liquid side
(2-way valve)
W mm 840
H mm 577
D mm 276 L1 mm 337 L2 mm 64 L3 mm 611 L4 mm 16 L5 mm 156
18K But Series
Dimensions
Page 13
- 13 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Dimensions
Outdoor Unit
W
L7 L6 L8 L9
D
L1
L2
L3
L10L11
L4L5
H
Gas side
Liquid side
MODEL
DIM
W mm 870
H mm 655
D mm 320
L1 mm 370
L2 mm 340
L3 mm 25
L4 mm 630
L5 mm 25
L6 mm 546
L7 mm 162
L8 mm 162
L9 mm 54
L10 mm 74.5
L11 mm 79
24K Btu Series
Page 14
- 14 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Model Name
Item Unit
Cooling Capacity
kW
Heating Capacity
Moisture Removal l/h
Power Source Ø, V, Hz
Air Circulation
Indoor
m3/min
Outdoor
Noise Level
Indoor
dB (A)±3
Outdoor
Input
Cooling
W
Heating
Running
Cooling
A
Current
Heating
E.E.R. Cooling
W/W
C.O.P Heating
Motor Output
Indoor
W
Outdoor
Dimensions
Indoor
mm
(W x H x D)
Outdoor
Net. Weight
Indoor
kg
Outdoor
Refrigerant (R410A) g
Airflow Direction Control (Up & Down)
Airflow Direction Control (Left & Right)
Chaos Wind
Timer
Self Diagnosis
Remocon Type
Service Valve
Liquid
inch(mm)
Gas
Sleeping Operation
Drain Hose
Connecting Cable
Power Cord
Product Specifications
Product Specifications
Table-1
2.48 3.52 5.28 6.74
2.56 3.52 5.28 6.74
1.2 1.2 2.2 2.9
1Ø,220-240V,50Hz 1Ø,220-240V,50Hz 1Ø,220-240V,50Hz 1Ø,220-240V,50Hz
5.8/6.6 8.8/9.5 13.4 15.1
20 22 42 42
37 40 40 47
49 52 54 57
950 1270 1900 2350
900 1120 1950 2350
4.2 5.8 8.5 10.5
4.2 5.2 8.7 10.5
2.61 2.77 2.78 2.87
2.84 3.14 2.71 2.87
7 9.5 22 22
18 - 72 82.9
756x260x155 900x285x156 1090x314x172 1090x314x172
575x525x260 717x481x228 870x577x276 870x655x320
5.3 7.2 12 12
26 30 50 60
710g 720g 1270g 1500g
OOOO
----
OOOO
7Hr OFF 7Hr OFF 7Hr OFF 7Hr OFF
OOOO
L.C.D wireless L.C.D wireless L.C.D Wireless L.C.D Wireless
1/4"(6.35) 1/4"(6.35) 1/4"(6.35) 3/8(9.52)
3/8"(9.52) 1/2"(12.7) 1/2"(12.7) 5/8(15.88)
----
OOOO
1.0mm2x 3, 0.75mm2x 2 1.0mm2x 3, 0.75mm2x 2 1.5mm2x 3, 0.75mm2x 2 2.5mm2x 3, 0.75mm2x 2
3 x 1.0mm
2
3 x 1.0mm
2
3 x 1.5mm
2
3 x 2.5mm
2
AS-H0966KA2
(F09AHJ)
AS-H126RKA2
(F12AHJ)
AS-H186TKA2
(F18AHJ)
AS-H246TKA2
(F24AHJ)
Page 15
Installation
Installation
Indoor unit
Do not have any heat or steam near the unit.
Select a place where there are no obstacles in front of the
unit.
Make sure that condensation drainage can be conveniently routed away. Do not install near a doorway.
Ensure that the space around the left and right of the unit is more than "A". The unit should be installed as high on the wall as possible, allowing a minimum of "B" from ceiling.
Use a stud finder to locate studs to prevent unnecessary damage to the wall.
Outdoor unit
If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
Ensure that the space around the back and sides is more than 10cm. The front of the unit should have more than 70cm of space.
Do not place animals and plants in the path of the warm air.
Take the air conditioner weight into account and select a
place where noise and vibration are minimum.
Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
Rooftop Installations:
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location.
Consult local codes regarding rooftop mounting.
More than "A"
More than "B"
More than 2.3m
More than "B"
Capacity is based on standard length and maxi­mum allowance length is on the basis of reliability.
Oil trap should be installed every 5~7 meters.
Grade
Clearance(cm)
AB
5K~28K 10 5
30K~38K 30 12
Pipe Size
Capacit
y
(Btu/h)
GAS LIQUID
Max.
Length
A (m)
Additional
Refrigerant
(g/m)
Max.
Elevation
B (m)
Standard
Length
(m)
5k~14k
3/8"(Ø9.52) 1/4"(Ø6.35) 4 or 7.5 7 15 20
1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 7 15 20
1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 15 30 20
18k~28k 5/8"(Ø15.88) 1/4"(Ø6.35) 4 or 7.5 15 30 20
5/8"(Ø15.88) 3/8"(Ø9.52) 4 or 7.5 15 30 30
30k~38k
5/8"(Ø15.88) 3/8"(Ø9.52) 7.5 15 30 30
3/4"(Ø19.05) 3/8"(Ø9.52) 7.5 15 30 50
If case more than 5m
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
I
Selection of the Best Location
Piping Length and Elevation
Install the indoor unit on the wall where the height from the floors more than 2.3 meters.
More than 10cm More than 10cm
More than 60cm
More than 60cm
More than 70cm
- 15 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Page 16
- 16 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Installation
The wall you select should be strong and solid enough to prevent vibration
1. Mount the installation plate on the wall with four type A screws. If mounting the unit on a concrete wall, use anchor bolts.
Mount the installation plate horizontally by aligning the centerline using a level.
2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typi­cally. Drilling the hole through the wall for pip­ing connections must be done safely.
Drill the piping hole with a ø70mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
Open the Front Grille.
Pass Telephone Control Cord Wire through the hole
which the power cord goes through.
Connect Telephone Control Cord Wire to the phone jack
of telephone PCB of Control Box.
Fix Telephone Control Cord Wire inside Control box so
as not to disconnect.
Close the Front Grille.
Installation Plate
Type "A" screw
5-7mm
(3/16"~5/16")
Indoor
WALL
Outdoor
Installation plate
Ø70mm
Left rear piping Right rear piping
C
D
B
A
Ø70mm
ABCD
S6(9k) 75 12 80 12
SR2(12k) 0 40 20 40
ST2(18k/24k) 105 0 210 0
CHASSIS
(Grade)
Distance (mm)
How to Fix Installation Plate Drill a Hole in the Wall
Drain hose junction
Remove the rubber stopple in the desired drain direc­tion.
Insert drain hose into the handle of drain pan, and join drain hose and connecting hose according to the figure by.
Only the desired direction
Connecting
part
Adhesive
Drain hose
Page 17
- 17 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Flaring work and connection of piping
Flaring work and connection of piping
Flaring work
Flaring work
Main cause for refrigerant leakage is due to defect in the flaring work. Carry out correct flaring work using the follow­ing procedure.
Cut the pipes and the cable.
Use the piping kit accessory or pipes purchased locally.
Measure the distance between the indoor and the outdoor unit.
Cut the pipes a little longer than the measured distance.
Cut the cable 1.5m longer than the pipe length.
Check
Compare the flared work with figure below.
If flare is noted to be defective, cut off the flared sec-
tion and re-flare it.
Preparing the indoor unit's piping and drain hose for instal­lation through the wall.
Remove the plastic tubing retainer(see illustration below) and pull the tubing and drain hose away from chassis.
Replace the plastic tubing holder in the original position.(Optional)
Carry out flaring work using flaring tool as shown below.
Burr removal
Completely remove all burrs from the cut cross section of pipe/tube.
Put the end of the copper tube/pipe in a downward direc­tion as you remove burrs in order to avoid dropping burrs into the tubing.
Putting nut on
Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)
Flaring work
Firmly hold copper pipe in a die in the dimension shown in the table above.
Copper
pipe
90°
Slanted Uneven Rough
Pipe
Reamer
Point down
Flare nut
Copper tube
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
mm inch mm
Ø6.35 1/4 0~0.5
Ø9.52 3/8 0~0.5
Ø12.7 1/2 0~0.5
Ø15.88 5/8 0~1.0
Ø19.05 3/4 1.0~1.3
Outside diameter A
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Connection of piping -- Indoor
Tubing holder
When install, make sure that the remaining parts must be removed clearly so as not to damage the pip­ing and drain hose, especially power cord and connecting cable.
Page 18
- 18 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Flaring work and connection of piping
Route the indoor tubing and the drain hose in the direction of rear right.
Drain hose
Insert the connecting cable into the indoor unit from the out­door unit through the piping hole.
Do not connect the cable to the indoor unit.
Make a small loop with the cable for easy connection later.
Tape the tubing, drain hose, and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.
NOTE: If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors.
*Foamed polyethylene or equivalent is recommended.
Indoor unit installation
Hook the indoor unit onto the upper portion of the installa­tion plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installa­tion plate by moving it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(click­ing sound).
Connecting the pipings to the indoor unit and drain hose to drain pipe.
Align the center of the pipes and sufficiently tighten the flare nut by hand.
Tighten the flare nut with a wrench.
When extending the drain hose at the indoor unit, install the
drain pipe.
Wrap the insulation material around the con­necting portion.
Overlap the connection pipe insulation material and the
indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.
Wrap the area which accommodates the rear piping hous-
ing section with vinyl tape.
Connecting pipe
Connecting cable
Tape
Drain hose
Drain hose
Connecting
cable
Indoor unit tubing Flare nut Pipes
Wrench
Indoor unit tubing
Open-end wrench (fixed)
Connection pipe
Flare nut
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
Plastic bands
Insulation material
Vinyl tape(narrow)
Connection pipe
Connecting cable
Vinyl tape (wide)
Wrap with vinyl tape
Indoor unit pipe
Pipe
For right rear piping
Page 19
- 19 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Flaring work and connection of piping
Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where they fit into the rear piping housing section.
Connecting the pipings to the indoor unit and the drain hose to drain pipe.
Align the center of the pipes and sufficiently tighten the flare nut by hand.
Tighten the flare nut with a wrench.
When extending the drain hose at the indoor unit, install the
drain pipe.
Wrap the insulation material around the con­necting portion.
Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap.
Route the indoor tubing and the drain hose to the required piping hole position.
Insert the piping, drain hose, and the connect­ing cable into the piping hole.
Insert the connecting cable into the indoor unit.
Don't connect the cable to the indoor unit.
Make a small loop with the cable for easy connection later.
Indoor unit installation
Hang the indoor unit from the hooks at the top of the instal­lation plate.
Insert the spacer etc. between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall.
Tape the drain hose and the connecting cable.
Connecting cable
Wrap with vinyl tape
Drain hose
Pipe
Vinyl tape(wide)
For left rear piping
Drain pipe
Connecting cable
Installation plate
Spacer
Indoor unit
8cm
Indoor unit tubing Flare nut Pipes
Wrench
Indoor unit tubing
Connection pipe
Flare nut
Open-end wrench (fixed)
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
Vinyl tape
Adhesive
Drain hose
Indoor unit drain hose
(narrow)
Plastic bands
Insulation material
Page 20
- 20 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Installation Information (For left piping)
Good case For left piping. Follow the instruction below.
Press on the upper side of clamp. ( )
Flaring work and connection of piping
Wrap the area which accommodates the rear piping hous­ing section with vinyl tape.
Indoor unit installation
Remove the spacer.
Ensure that the hooks are properly seated on the installa-
tion plate by moving it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
Bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section.
Reroute the pipings and the drain hose across the back of the chassis.
Set the pipings and the drain hose to the back of the chassis with the tubing holder.
Hook the edge of tubing holder to tap on chassis and push the bottom of tubing holder to be engaged at the bottom of chassis.
Vinyl tape(narrow)
Connection pipe
Connecting cable
Indoor unit piping
Pipe
Vinyl tape (wide)
Wrap with vinyl tape
Drain hose
Vinyl tape(narrow)
Pipe
Wrap with vinyl tape(wide)
Piping for passage through piping hole
Tubing holder
Drain hose
Connecting
cable
Unfold the tubing to downward slowly. ( )
Bend the tubing to the left side of chassis.
Page 21
- 21 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Flaring work and connection of piping
Align the center of the pipings and sufficiently tighten the flare nut by hand.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
Bad case
Following bending type from right to left could cause
problem of pipe damage.
Connection of the pipes-Outdoor
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
Outdoor unit
Gas side piping (Bigger diameter)
Liquid side piping (Smaller diameter)
Torque wrench
Page 22
- 22 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Connect the cable to the Indoor unit.
Connecting the cable between indoor unit and outdoor unit
Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of the indoor unit.). The earth wire should be longer than the common wires. The above circuit diagram is subject to change without notice. When installing, refer to the circuit diagram on the control box inside Indoor Uint.
Air
Conditioner
Main power source
Circuit Breaker
Use a circuit breaker or time delay fuse.
NORMAL CROSS-SECTIONAL AREA 0.75mm
2
The power connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (Type "B" approved by HAR or SAA).
The power cord connected to the "A" unit should be complied with the following specifications(Type "B" approved by HAR or SAA).
(mm2)
The above circuit diagram is subject to change without notice.
Be sure to connect wires according to the wiring diagram.
Connect the wires firmly, so that not to be pulled out easily.
Connect the wires according to color codes by referring the
wiring diagram.
If a power plug is not to be used, provide a circuit breaker between power source and the unit as shown below.
Connecting the cable between indoor unit and outdoor unit
When installing, refer to the circuit diagram on the Control Box of Indoor Unit.
When installing, refer to the wiring diagram on the Control Cover Inside Outdoor Unit.
5k~9k 12k 14K~18k 24k~28k 30k, 32k 36k, 38k
0.75 1.0 1.5 2.5 2.5 5.5
Unit(A) Indoor Indoor Indoor Indoor Outdoor Outdoor
Cable Type(B) H05VV-F H05VV-F H05VV-F H05VV-F H05RN-F H05RN-F
NORMAL CROSS
-SECTIONAL AREA
Grade
5k~12k 14k~18k 24k~28k
1.0 1.5 2.5
Cable Type(B) H07RN-F H07RN-F H07RN-F
NORMAL
CROSS
-SECTIONAL AREA
Grade
(mm2)
30k, 32k 36k, 38k
0.75 0.75
Cable Type(B) H07RN-F H07RN-F
NORMAL CROSS
-SECTIONAL AREA
Grade
(mm2)
Page 23
- 23 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Connecting the cable between indoor unit and outdoor unit
Remove the control cover from the unit by loosening the screw.
Connect the wires to the terminals on the con­trol board individually.
Secure the cable onto the control board with the cord clamp.
Refix the control cover to the original position with the screw.
Use a recognized circuit breaker "A" between the power source and the unit. A disconnecting device to adequately discon­nect all supply lines must be fitted.
Outdoor Unit
Cover control
Cord clamp
1(L) 2(N) 34 1(L) 2(N) 34
CASE 1 CASE 2
Connecting cable
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
6) Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness. (Refer to page 22))
7) Always install an earth leakage circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal func-
tion of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductors.
Connect the cable to the outdoor unit
5k~14k 18k 24k~28k 30k, 32k 36k, 38k
15 20 30 30 40
Circuit
Breaker
(A)
Grade
Page 24
- 24 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Checking the drainage and forming the pipings
Checking the drainage and forming the pipings
Checking the drainage Form the piping
To remove the front panel from the indoor unit.
Set the air direction louvers up-and-down to the position(horizontally) by hand.
Remove the securing screws that retain the front panel. Pull the lower left and right sides of the grille toward you and lift it off.
Form the piping by wrapping the connecting portion of the indoor unit with insulation mate­rial and secure it with two kinds of vinyl tapes.
If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.
In cases where the outdoor unit is installed below the indoor unit perform the following.
Tape the piping, drain hose and connecting cable from down to up.
Secure the tapped piping along the exterior wall using sad­dle or equivalent.
To check the drainage.
Pour a glass of water on the evaporator.
Ensure the water flows through the drain hose of the indoor
unit without any leakage and goes out the drain exit.
In cases where the Outdoor unit is installed above the Indoor unit perform the following.
Tape the piping and connecting cable from down to up.
Secure the taped piping along the exterior wall. Form a trap
to prevent water entering the room.
Fix the piping onto the wall by saddle or equivalent.
Drain piping
The drain hose should point downward for easy drain flow.
Do not make drain piping.
Pull the right and the left side.
Downward slope
Do not raise
Accumulated drain water
Tip of drain hose dipped in water
Air
Waving
Water leakage
Water leakage
Ditch
Less than 50mm gap
Water leakage
Taping
Drain hose
Pipings
Connecting cable
Trap is required to prevent water from entering into electrical parts.
Seal small openings around pipings with a gum type sealer.
Seal a small opening around the pipings with gum type sealer.
Trap
Trap
Page 25
- 25 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Air purgingd
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
Pressure in the system rises.
Operating current rises.
Cooling(or heating) efficiency drops.
Moisture in the refrigerant circuit may freeze and block cap-
illary tubing.
Water may lead to corrosion of parts in the refrigeration system.
Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the system.
Do a leak test of all joints of the tubing(both indoor and out­door) and both gas and liquid side service valves. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
Preparation
Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been complet­ed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
Leak test
Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.
Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylinder valve when the gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap.
AIR PURGING
Air purging
Air purging with vacuum pump
Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The "Hi" knob of the manifold valve must always be kept close.
To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
Lo Hi
Indoor unit
Outdoor unit
Manifold valve
Charge hose
Nitrogen gas cylinder(in vertical standing position)
Pressure gauge
Page 26
- 26 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Air purgingd
Evacuation
Connect the charge hose end described in the preceding
steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with tubing length and capacity of the pump. The following table shows the time required for evacuation.
When the desired vacuum is reached, close the "Lo" knob
of the manifold valve and stop the vacuum pump.
Finishing the job
With a service valve wrench, turn the valve stem of liquid
side valve counter-clockwise to fully open the valve.
Turn the valve stem of gas side valve counter-clockwise to
fully open the valve.
Loosen the charge hose connected to the gas side service
port slightly to release the pressure, then remove the hose.
Replace the flare nut and its bonnet on the gas side service
port and fasten the flare nut securely with an adjustable wrench. This process is very important to prevent leakage from the system.
Replace the valve caps at both gas and liquid side service
valves and fasten them tight.
This completes air purging with a vacuum pump. The air conditioner is now ready to test run.
(1) Remove the caps from the 2-way and 3-way valves.
(2) Remove the service-port cap from the 3-way valve.
(3) To open the 2-way valve turn the valve stem counter-
clockwise approximately 90°, wait for about 2~3 sec, and close it.
(4) Apply a soap water or a liquid neutral detergent on the
indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping.
(5) If bubbles come out, the pipes have leakage.
Soap water method
Gas side
Liquid side
Cap
Hexagonal wrench
2-way valve
(Open)
3-way valve
(Close)
Required time for evacuation when 30 gal/h vacuum
pump is used
10 min. or more 15 min. or more
If tubing length is less than 10m (33 ft)
if tubing length is longer than 10m (33 ft)
Indoor unit
Outdoor unit
Lo Hi
Manifold valve
Vacuum pump
Pressure gauge
Open
Close
Page 27
- 27 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Test running
TEST RUNNING
1. Check that all tubing and wiring have been properly con-
nected.
2. Check that the gas and liquid side service valves are fully
open.
Settlement of outdoor unit
Anchor the outdoor unit with a bolt and nut(ø10mm) tightly and horizontally on a concrete or rigid mount.
When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake.
In the case when the vibration of the unit is conveyed to the hose, secure the unit with an anti-vibration bushing.
NOTE: If the actual pressure is higher than shown, the system is
most likely over-charged, and charge should be removed. If the actual pressure are lower than shown, the system is most likely undercharged, and charge should be added.
The air conditioner is now ready for use.
Power-Failure Compensation Function User Selection ON/OFF
1) Operation Sequence
Press the forced switch until BUZZER sounds 2 times (beep~beep~).
Release the forced switch if BUZZER sounds.
Check the function selection ON/OFF with the operation LED.
2) Checking function-selection ON/OFF
- Function-Selection ON: One time blinking of operation LED would repeat 4 times.
- Function-Selection OFF: Two times blinking of operation LED would repeat 4 times.
Evaluation of the performance
Operate unit for 15~20 minutes, then check the system refrigerant charge:
1. Measure the pressure of the gas side service valve.
2. Measure the temperature of the intake and discharge of air.
3. Ensure the difference between the intake temperature and the discharge is more than 8°C(46°F) (Cooling) or (Heating).
4. For reference; the gas side pressure of optimum condition is as below.(Cooling)
Bolt
Tubing connection
Discharge temperature
Discharge air
Intake temperature
R-22 35°C (95°F) 4~5kg/cm2G(56.8~71.0 P.S.I.G.)
R-410A 35°C (95°F) 8.5~9.5kg/cm2G(120~135 P.S.I.G.)
Outside ambient
TEMP.
Refrigerant
The pressure of the gas side
service valve.
This is performed when the unit is to be relocated or the refrigerant circuit is serviced.
Pump Down means collecting all refrigerant in the outdoor unit without loss in refrigerant gas.
CAUTION:
Be sure to perform Pump Down procedure with the unit cooling mode.
Pump Down Procedure
1. Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve.
2. Open the gas side service valve halfway and purge the air from the manifold hose using the refrigerant gas.
3. Close the liquid side service valve(all the way in).
4. Turn on the unit's operating switch and start the cooling operation.
5. When the low-pressure gauge reading becomes 1 to
0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the gas side valve stem and then quickly turn off the unit. At that time, Pump Down has been completed and all refrigerant gas will have been collected in the outdoor unit.
PUMP DOWN
Power button
Open the front panel upward
Page 28
- 28 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Operation
Function of Controls
Operation
• DISPLAY
1) C/O Model
Operation Indicator
ON while in appliance operation, OFF while in appliance pause.
Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Comp. Running Incidator
While in appliance operation, ON while in outdoor unit compressor running, OFF while in compressor off.
2) H/P Model
Operation Indicator
ON while in appliance operation, OFF while in appliance pause.
Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Defrost Indicator
OFF except when hot start during heating mode operation or while in defrost control.
Cooling Mode Operation
When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan stop.
When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp Setting Temp+0.5°C Compressor OFF Temp Setting Temp-0.5°C
While in compressor running, operating with the airflow speed set by the remote control. While in compressor not running, operating with the low airflow speed regardless of the setting.
Healthy Dehumidification Mode
When the dehumidification operation input by the remote control is received, the intake air temperature is detected and the setting temp is automatically set according to the intake air temperature.
26°C Intake Air Temp 25°C 24°C Intake Air Temp<26°C Intake Air Temp-1°C 18°C Intake Air Temp<24°C Intake Air Temp-0.5°C Intake Air Temp<18°C 18°C
Page 29
- 29 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Operation
While in compressor off, the indoor fan repeats low airflow speed and pause.
While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat. Compressor ON Temp. Setting Temp+0.5°C Compressor OFF Temp. Setting Temp-0.5°C
In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
Heating Mode Operation
When the intake air temp reaches +3°…above the setting temp, the compressor is turned off. When below
the setting temp, the compressor is turned on. Compressor ON Temp. Setting Temp. Compressor OFF Temp. Setting Temp.+3°C
While in compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C, when above 28°C , it
operates with the low or setting airflow speed. When the indoor pipe temp is between 20°C and 28°C, it oper­ates with Super-Low(while in sleep mode, with the medium airflow speed).
While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C, when above 35°C , it
operates with the low airflow speed.
If overloaded while in heating mode operation, in order to prevent the compressor from OLP operation, the
outdoor fan is turned on/off according to the indoor pipe temp.
While in defrost control, both of the indoor and outdoor fans are turned off.
Defrost Control
While in heating mode operation in order to protect the evaporator pipe of the outdoor unit from freezing, reversed to cooling cycle to defrost the evaporator pipe of the outdoor unit.
After 40 min heating mode operation, at 4 min interval, whether to carry out defrost control or not and the time of defrost control are determined according to the following conditions.
1) While in heating mode operation, the maximum of the indoor pipe temperature is measured and it is com-
pared with the present indoor pipe temperature to get the difference of the indoor pipe temperatures (=the maximum temperature of indoor pipe ? the present temperature of indoor pipe), according to which, whether to carry out defrost control or not is determined.
2) According to the need of defrost control shown above and the elapsed time of heating mode operation at that
moment, the defrost control time is determined.
3) When the determined time of defrost control is below 7 min, heating mode operation continues without carry-
ing out defrost control. According to the procedure stated above, the determination is made again. When the defrost control time is 7 min or longer, defrost control is then carried out.
While in defrost control, the minimum temp of the indoor pipe is measured and it is compared with the present temp of the indoor pipe to get the difference of the indoor pipe temperatures (=the present temperature of the indoor pipe ? the minimum temperature of the indoor pipe). When the difference is 5°C or higher, defrost con­trol is completed and heating mode operation is carried out.
While in defrost control, if the defrost time determined before the start of defrost control is completed, defrost control stops and heating mode operation is carried out regardless of the above condition.
When the indoor pipe temp is 42°C or above, defrost control is not carried out even if the condition is one of the defrost conditions above.
While in defrost control, the compressor is on and the indoor fan, the outdoor fan, and the 4 way valve are off.
Page 30
- 30 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Operation
Airflow Speed Selection
The airflow speed of the indoor fan is set to high, medium, low, or chaos (auto) by the input of the airflow speed selection key on the remote control.
Sleep Timer Operation
When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appli­ance operation, the operation of the appliance stops.
While the appliance is on pause, the sleep timer mode cannot be input.
While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature increases by 1°C. After another 30 min elapse, it increases by 1°C again.
When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to
the low.
When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to the medium.
Chaos Natural Wind Mode
When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air­flow mode is operated for 2~15 sec. randomly by the Chaos Simulation.
Jet Cool Mode Operation (C/O Model)
If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
Jet Cool Mode Operation (H/P Model)
While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C.
When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
Forced Operation
Operation procedures when the remote control can't be used.
The operation will be started if the power button is pressed.
If you want to stop operation, re-press the button.
While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to
indicate the forced operation.
Heat pump Model
Cooling Model
Room Temp. ≥ 24°C 21°C ≤ Room Temp. < 24°C Room Temp. < 21°C
Operating mode Cooling Cooling Healthy Dehumidification Heating
Indoor FAN Speed
High High High High
Setting Temperature
22°C22°C23°C24°C
Page 31
- 31 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Operation
Test operation
During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room tem­perature and resets in 18±1 minutes.
During test operation, if remote controller signal is received, the unit operates as remote controller sets. If you want to use this operation, open the front panel upward and Press the power button let it be pressed for about 3 seconds.
If you want to stop the operation, re-press the button.
Auto restart
In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate procedures automatically to the previous operating conditions.
Protection of the evaporator pipe from frosting
If the indoor pipe temp is below 0°C in 7 min. after the compressor operates without any pause while in cool­ing cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor evaporator pipe from frosting.
When the indoor pipe temp is 7°C or higher after 3 min. pause of the compressor, the compressor and the outdoor fan is turned on according to the condition of the room temperature.
Buzzer Sounding Operation
When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.
When the appliance-pause key is input by the remote control, the long "beep" sounds.
When a key is input by the remote control while the slide switch on the main unit of the appliance is on the
forced operation position, the error sound "beep-beep-beep-beep-beep-" is made 10 times to indicate that the remote control signal cannot be received.
Page 32
- 32 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Self-diagnosis Function
Operation
Display Function
1. Heating Model 2. Cooling Model
Cooling, Soft Dry, Fan, Heating Cooling, Soft Dry, Fan
Hot-start, Deice
Operation Indicator
Deicer Indicator
Operation Indicator
Compressor on Indicator
OUT
DOOR
3sec 3sec 3sec
(once)
Error
Code
1
Error Display LED
(Indoor body operation LED)
Error contents
Indoor room temperature thermistor open/short
Indoor pipe temperature thermistor open/short.
Indoor Thermistor assembly check
SVC check point
Page 33
- 33 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Remote Control Operations
The remote control transmits the signals to the system.
Operation
Page 34
- 34 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Disassembly
Disassembly
Indoor Unit
Disconnect the unit from power supply before mak­ing any checks. Be sure the power switch is set to OFF.
To remove the Grille from the Chassis.
Set the up-and-down air discharge louver to open position (horizontally) by finger pressure.
Remove the securing screws.
To remove the Grille, pull the lower left and right
side of the grille toward you (slightly tilted) and lift it straight upward.
1. Before removing the control box, be sure to
take out the wire screwed at the other end.
Earth Conductor
Page 35
- 35 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Disassembly
2. To remove the Control Box.
Remove securing screws.
Pull the control box out from the chassis
carefully.
3. To remove the Discharge Grille.
Unhook the discharge grille and pull the discharge grille out from the chassis carefully.
4. To remove the Evaporator.
Remove 3 screws securing the evaporator(at the left 2EA in the Eva Holder, at the right 1EA).
Caution label
When repair, do not damage the Caution label.
Page 36
- 36 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Disassembly
Unhook the tab on the right inside of the chassis
at the same time, slightly pull the evaporator toward you until the tab is clear of the slot.
5. To remove the Motor Cover
Remove 2 securing screw.
Pull the motor cover out from the chassis
carefully.
6. To remove the Cross-Flow Fan
Loosen the screw securing the cross-flow fan to
the fan motor (do not remove).
Lift up the right side of the cross-flow fan and the
fan motor, separate the fan motor from the cross-flow fan.
Remove the left end of the cross-flow fan from
the self-aligning bearing.
Motor cover
Page 37
- 37 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Schematic Diagram
Schematic Diagram
44
ANI0
ANI1
ANI4
ANI3
ANI6 / LED1
ANI5
ANI7 / LED2
IT0
12
N
ANI2
3
8
11
10
9
7
6
5
4
A
2
1
RFE
V
31
X
18
15
Z
B
N
113T14I
TV
16
D
17
D
D
26
21
RDX
19
20
V22P
P
23
RESET
24
25
VSS0
X1
X2
27
28
VDD0
29
30
38
41
ADV
D
43
42
40
39
35
37
36
32
33
34
FORCE
FAN
12V
COMP
4WAY
FAN
L(AC)
LOAD
COMP
4WAY
OR
RD
YL
PK
BL
R1,R2=4.7K
(SRC1201S)
VOLTAGE GND
TCET1109-3208
R03L,1%
27K,1/4W
12K
R04L
PKM13EPY-4002
RY-4WAY
12V
66
103
6 6
FORCE
SW(FORCE)
OUTDOOR
220,1/4W
220,1/4W
R02G
OPERATION
LED1
LED2
R01G
2133
1
2
5
44
5
AC PART
220/10V
C12L
321
213
4
55
4
5V
220,25V
O I
7805
C05D
220/10
5V
+
103/25V
C04D
100/25V
C02D
VOLTAGE GND
DC LOW
C03D
103/25V
4.7K,1/6W R01D
+
ICO1A
S78DL05L
L02D
CHIP
R2
R1
Q01G
Q02G
Q03G
12V
L01D
BEAD
S
C05J
0.1uF,100V
4.7K,1/6W
5
8
102,1KV
C06D
R02D
UF4004
C01D
+
D01D
1
3
+
100,1/8W
R02J
27K,1/4W
C
+
D06J
1N4937
R01J
DC LOW
6.8/450 C03J
IC01L
INT
1uF,50V
SMPS
EE1916S
Lp=3.44mH
102,1KV
C06J
C04J
1K
2SC5343
Q01L
KTC3198-Y
LNK500P
IC01J
LINKSWITCH
D
C01L
103
NTC SCK-102
R01E
5V
R02E
20
BZ01E
103
C14L
R1,R2=4.7K
(SRC1201S)
Q01G~04G
R21H-26H
12.1K,1%
F3,OR3H
F1,OR1H
HIGH,OR6H
LOW,OR4H
MIDDLE,OR5H
F2,OR2H
OPTION
DISPLAY
RECEIVER
GND
Vout
Vcc
SMAW-200
CN-DISP1
100,1/4W
C13L
104
R13L
66
77
44
33
55
8
77
8
5V
R12L
5.1K,1/8W
1K,1/6W
R11L
7
6
7
6
3
5
4
354
CN-OPTION
22
11
PIPE-TH
ROOM-TH
33
SMW-200
1
2
1
2
1
2
1
2
DC PART
CN-TH1
SMAW-200
4 4
OR3H
680pF/50V
OR1H
C11L
OR2H
5%
OR1H-6H
OR5H
Q04G
OR4H OR6H
R26H
R25H
R24H
R23H
R22H
OPERATION
TIMER
HIGH
MIDDLE
LOW
OPTION3
OPTION2
103
C01p
R05H
R04H
6.2K
CAT24WC01J
EEPROM
5V
R21H
5V
R02H
12.1K
10K
A0A1A2
4
3G2
1
C02HJ
C01H
R01H
103
103
R03H
10K
10K
OPTION1
PIPE
ROOM TH
7
R01P
WP
SCL
SDA
5
6
20K
5V
Vcc
8
R02P
R03D
100
20K
uPD78F9166GB
NEC(16K)
FAN-IN
FAN-OUT
C08D
103
C09D
5V
1N4148
R1
Q01M
R2
D01M
SMAW-200
FAN MOTOR
INDOOR
100nM/275V,436D
TVR10561
ZNR01J
R03F
100,1/2W
R02F
680,1/2W
1N4007
D02J
VOLTAGE GND
1N4148
2
3
DC HIGH
300K,1/2W
5V
1
4
R01L
D01L
R02L
300K,1/2W
D03J
1N4007
47nM/275V/435D
C02J
C01J
40mH/1A
NF01J
D04J
1N4007
1N4007
D05J
INT
56K
R05L
5V
D01J
1N4007
R14L
1K 20K
R15L
5V
10K,1/6W
C03T
R01F
560,1/4W
INDOOR FAN
12V
3
2
4
1
5
GND
12V
5V
33
22
11
44
55
250V/T2A
FUSE
RY-4WAY
RY-FAN
4
4
3
3
CN-N2
CN-N1
3
4
RY-COMP
G4A-1A-E-LG
1 1
112
3
132
1
100nM/275V/436D
T2
T1
TVR10561
ZNR01F
120,1/2W
C01F
R04F
CN-4WAY
CN-MOTOR
321
321
4
3
MOTOR
COMPRESSOR
R01P
R01P
AC220-240V
50/60HZ
1(L)
52431
34251
4WAY
2N
MOTOR
OUTDOOR FAN
SH-CAPACITOR
33
103
C01A
OSC01B
CRTL4.00MSOT
10uF/50V
C02A
R01A
1K
+
R01B
1M
103
C07D
5V
7
8
9
10
4.7K
S7136
IC01A
KIA7036P
3.6V
100
R03A
3
5V
2
1
CN-CENT
R02A
12V
55
34
11
5
4
12
13
6
2
14
15
3
16
1
INDOOR FAN
RY-COMP
22
11
SMAW-200
CN-U/D
RY-FAN
REALY CONNECTION
STEPPING MOTOR
(UP/DOWN)
IC01F
IL440-2
TR01F
SM1L43
Electric Control Device
Heat Pump Model(LED TYPE)
Page 38
- 38 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Wiring Diagram
Schematic Diagram
Indoor Unit
Models: AS-H0966KA2 (F09AHJ), AS-H126RKA2 (F12AHJ), AS-H186TKA2 (F18AHJ),
AS-H246TKA2 (F24AHJ)
Outdoor Unit
Models: AS-H0966KA2
(F09AHJ), AS-H126RKA2 (F12AHJ)
Models: AS-H186TKA2
(F18AHJ)
Models: AS-H246TKA2
(F24AHJ)
C
SR
RD
YL
YL
GN/YL
GN/YL
GN/YLBRBLBKRD
YL
YL
BR(OR)
BL
BK
FAN MOTOR
BR BL BK RD
HEATER
RD
BR
BRWH
BK(RD)
BK(RD)RD
T/B1
T/B3
T/B4
T/B2
REVERSING
VALVE
TERMINAL BLOCK
TO INDOOR UNIT
3854A20167Q
RY-S/CAPA
RY-COMP
SOFT STARTER PCB
COMP.
START CAPACITOR
OPTION
PTC
CAPACITOR
4
H
CF
3
43
1(L) 2(N)
34
Page 39
- 39 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Schematic Diagram
Components Location
MAIN P.W.B ASSEMBLY
Q02G
R01E
Q01L
J19
R04L
C01L
J18
Q04G
BZ01E
C11L
J23
Q03G
J24
J22
R11L
CN-CENT
J21
J20
R15L
CN-OPTION
J8
D01J
OSC01B
R02E
C08D
J14
C05D
L02D
J13
IC01D
R02D
C06D
C02D
C03D
R01F
D01D
C02A
IC01A
J12
R14L
C04D
C14L
C03T
R01A
J17
R03A
R02A
R01D
L01D
J16
J11
J25
C01A
C01D
C05J
SMPS
C04J
R01J
C03J
D06J
R02J
R02L
C06J
D01L
NTC
D05J
IC01J
D04J
D03J
IC01F
R03F
TR01F
R02F
R01P
R02P
Q01G
1
12
R01B
23
MICOM
R03D
34
R03L
R05L
C07D
J9
J7
EEPROM
J01
J16
C09D
J15
R25H
R24H
R23H
R22H
R26H
C01P
IC01M
J6
J5
J4
Q01M
ZNR01J
IC01L
R01L
RY-4WAY
RY-FAN
D02J
C01J
C02J
C01F
NF01J
CN-U/D
CN-DISP1
C01H
OR4H
OR2H
R21H
OR1H
OR3H
J26
OR5H
OR6H
R03H
C12L
R12L
R05H
D01M
J2
C02H
R01H
R02H
R04H
CN-TH1
FUSE
CN-4WAY
RY-COMP
CN-MOTOR
ZNR01F
R04F
CN-N2
CN-N1
FUSE
250V/T2A
RY-COMP
PWB: 6870A90239A
D03J
IC01F
C03J
R02F
TR01F
R03F
NTC
D04J
CN-MOTOR
ZNR01F
D02J
R04F
C01F
CN-N2
NF01J
CN-N1
3
D01J
C02D
R02D
PWB ASM: 6871A20573
C04J
5
R01J
SMPS
8
D01D
R02L
D05J
4
C05J
IC01J
D06J
R02J
1
J11
C06J
D01L
C01D
C06D
C03D
R01F
C05D
IC01D
Q01L
J13
C14L
J12
IC01A
L01D
C02A
C04D
R01A
J14
R14L
R04L
C03T
BZ01E
C01L
J5
J4
C07D
R01L
ZNR01J
C01J
C02J
RY-4WAY
R03L
IC01L
RY-FAN
J7
J6
R03D
C08D
OSC01B
C01A
J9
C11L
R11L
J15
C09D
C01P
J01
J10
CN-CENT
4
D01M
CN-4WAY
J2
CN-U/D
J8
C01H
CN-TH1
C02H
CN-OPTION
C12L
CN-DISP1
TOP VIEW
BOTTOM VIEW
Page 40
- 40 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Schematic Diagram
DISPLAY ASSEMBLY
– 6871A20575
Page 41
- 41 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Troubleshooting Guide
INDOOR UNIT OUTDOOR UNIT
INDOOR UNIT OUTDOOR UNIT
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
HEAT EXCHANGE (CONDENSER)
COMPRESSOR
COMPRESSOR
ACCUMU LATOR
GAS SIDE
GAS SIDE
3-WAY VALVE
LIQUID SIDE
LIQUID SIDE
3-WAY VALVE
CAPILLARY TUBE
CAPILLARY TUBE
CHECK VALVE
(Heating Model only)
COOLING HEATING
REVERSING VALVE (Heating Model Only)
(1) Cooling Only Models
Refrigeration Cycle Diagram
(2) Cooling & Heating Models
Page 42
- 42 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
2-way, 3-way Valve
2-way Valve (Liquid Side) 3-way Valve (Gas Side)
Shaft position Shaft position Service port
Closed Closed Closed
(with valve cap) (with valve cap) (with cap)
Open Closed Open
(counter-clockwise) (clockwise) (push-pin or with
vacumm pump)
Open Open Closed
(with valve cap) (with valve cap) (with cap)
Closed Open Open
(clockwise) (counter-clockwise) (connected manifold
gauge)
Open Open Open
(with charging
cylinder)
Open Open Open
(with charging
cylinder)
Open Open
Open Open
Works
Shipping
Air purging (Installation)
Operation
Pumping down (Transfering)
Evacuation (Servicing)
Gas charging (Servicing)
Pressure check (Servicing)
Gas releasing (Servicing)
1.
2.
3.
4.
5.
6.
Valve cap
Open position Closed position
Pin
Service port
Service port cap
To outdoor unit
Flare nut
To piping connection
To outdoor unit
Hexagonal wrench (4mm)
Open position Closed position
To piping connection
Flare nut
Open
(with charging cylinder)
Open
(with charging cylinder)
Page 43
- 43 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Procedure
(1) Confirm that both the 2-way and 3-way valves
are set to the open position.
– Remove the valve stem caps and confirm that
the valve stems are in the raised position.
– Be sure to use a hexagonal wrench to operate
the valve stems.
(2) Operate the unit for 10 to 15 minutes.
(3) Stop operation and wait for 3 minutes, then
connect the charge set to the service port of the 3-way valve.
– Connect the charge hose with the push pin to
the service port.
(4) Air purging of the charge hose.
– Open the low-pressure valve on the charge set
slightly to air purge from the charge hose.
(5) Set the 2-way valve to the closed position.
(6) Operate the air conditioner at the cooling
cycle and stop it when the gauge indicates 1kg/cm2g.
(7) Immediately set the 3-way valve to the closed
position.
– Do this quickly so that the gauge ends up indi-
cating 3 to 5kg/cm2g.
(8) Disconnect the charge set, and mount the 2-
way and 3-way valves stem nuts and the ser­vice port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
Lo
Closed
Purge the air
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
Open
2-Way valve
3-Way valve
CLOSE
Pumping Down
Do not use the existing charge set for R-22. It is necessary to use new charge set for R-410A. The pressure of R-410A is 1.6 times higher than that of R-22. Thus, the high pressure side gauge of charge set should be used higher pressure gauge of 50kg/cm2 range.
Page 44
- 44 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Balance Refrigerant of the 3-way Valve
(Gas leakage)
Procedure
(1) Confirm that both the 2-way and 3-way valves
are set to the back seat.
(2) Connect the charge set to the 3-way valve’s
port.
Leave the valve on the charge set closed. Connect the charge hose to the service port.
(3) Open the valve (Lo side) on the charge set and
discharge the refrigerant until the gauge indi­cates 0 kg/cm2G.
– If there is no air in the refrigerant cycle (the
pressure when the air conditioner is not running is higher than 1 kg/cm2G), discharge the refrig­erant until the gauge indicates 0.5 to 1 kg/cm
2
G. if this is the case, it will not be neces-
sary to apply a evacuatin.
– Discharge the refrigerant gradually; if it is dis-
charged too suddenly, the refrigeration oil will also be discharged.
Lo
Open
Open
3-Way valve
3-Way valve
Gas side
CLOSEOPEN
Outdoor unit
Liquid side
Indoor unit
Page 45
- 45 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Evacuation
(All amount of refrigerant leaked)
Procedure
(1) Connect the vacuum pump to the center hose
of charge set center hose
(2) Evacuation for approximately one hour.
– Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).
(3) Close the valve (Lo side) on the charge set,
turn off the vacuum pump, and confirm that the gauge needle does not move (approxima­tely 5 minutes after turning off the vacuum pump).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or depleted, replenish as needed.
Lo
Open
Open
Vacuum pump
3-Way valve
Outdoor unit
Liquid side
Indoor unit
Gas side
3-Way valve
CLOSE
OPEN
Use vacuum pump equipped with check value applied to be prevented from flowing backward.
Page 46
- 46 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Gas Charging
(After Evacuation)
Procedure
(1) Connect the charge hose to the charging
cylinder.
– Connect the charge hose which you dis-con-
nected from the vacuum pump to the valve at the bottom of the cylinder.
– If you are using a gas cylinder, also use a
scale and reverse the cylinder so that the sys­tem can be charged with liquid.
(2) Purge the air from the charge hose.
– Open the valve at the bottom of the cylinder
and press the check valve on the charge set to purge the air. (Be careful of the liquid refriger­ant). The procedure is the same if using a gas cylinder.
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant.
– If the system can not be charged with the spec-
ified amount of refrigerant, it can be charged with a little at a time (approximately 150g each time) while operating the air conditioner in the cooling cycle; however, one time is not suffi­cient, wait approximately 1 minute and then repeat the procedure (pumping down-pin).
(4) Immediately disconnect the charge hose from
the 3-way valves service port.
– Stopping partway will allow the gas to be dis-
charged.
– If the system has been charged with liquid
refrigerant while operating the air conditioner turn off the air conditioner before disconnecting the hose.
(5) Mount the valve stem nuts and the service
port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
This unit is charged with R-410A. Pay attention not to charge R-22.
\
This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner.
Lo
Charging cylinder
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
Open
3-Way valve
3-Way valve
OPEN
Open
Check valve
(1)
Page 47
- 47 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Additional gas charging
(Gas leakage)
When refrigerant is insufficient by leakage, recharge the unit with the refrigerant up to normal operating suc­tion pressure.
Use the graph or the equation below to get operating suction pressure according to indoor and outdoor tem­perature. Suction pressure was measured at 3-way valve service port after operating the unit for 10 minutes.
The method of using graph
- Find outdoor temperature.
- Find indoor temperature onto the curve of outdoor temperature.
- Read suction pressure at the axis of ordinates.
The method of using equation
-. Calculate suction pressure after putting indoor and outdoor temperature into the equation.
13
(At operating the Unit for 10 minutes)
Suction Pressure
(Kg/cm
2
.g)
Outdoor Temp.
(˚C)
Indoor Temp. (˚C)
12
11
10
9
8
7
6
5
5 10152025303540
50˚C
40˚C
30˚C
20˚C
10˚C
0˚C
P = 3 + 0.0123 x Tout
1.5
+ 0.8 x Tin
0.5
Where, P : Suction Pressure(kg/cm
2
.
g) Tout : Outdoor Temperature(˚C) Tin : Indoor Temperature(˚C)
Operating Suction Pressure
(According to Indoor & Outdoor Temperature)
Page 48
- 48 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
Temp. Difference
Temp. difference : approx. 0°C Current : less than 80% of
rated current
Temp. difference : approx. 8°C Current : less than 80% of
rated current
Temp. difference : less than 8°C Current : over the reated
current
Temp. difference : over 8°C
Operating Current
All amount of refrigerant leaked out. Check refrigeration cycle.
Refrigerant leakege
Clog of refrigeration cycle Defective compressor
Excessive amount of refrigerant
Normal
Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
1. The suction pressure is usually 8.5~9.5 kg/cm2G(Cooling) at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
NOTICE
NOTICE
Suction pressure Temperature
(Compared with (Compared with Cause of Trouble Description
the normal value) the normal valve)
Defective compressor Current is low. Defective 4-way reverse valve
Excessive amount of High pressure does not quickly
Normal refrigerant rise at the beginning of
operation.
Insufficient amount of Current is low.
Lower Higher refrigerant (Leakage)
Clogging Current is low.
High
Higher
Cycle Parts
Page 49
- 49 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Electronic Parts
Product does not operate at all.
(* Refer to Electronic Control Device drawing and Schematic diagram.)
Turn off Main Power
Turn on Main Power
Does "beeping" sound is made from the Indoor Unit?
Primarily, the operating condition of Micom is OK.
Check the voltage of power(About AC 220V, 60Hz)
(About AC 220/240V, 50Hz)
Main power's voltage
Voltage applied to the unit
Connecting method of Indoor/Outdoor connecting
cable
Check PWB Assembly
- Fuse
- Pattern damage
- Varistor(ZNR01J)
Check the connection housing for contacting
Connector related to CN-TAB1, RY-COMP NO.3
Connector related to CN-MOTOR
Connector contacting of Outdoor Fan/Compressor
Display PCB Assembly Check
Check each load(Indoor/Outdoor Fan Motor, Compressor, Stepping Motor) and contacting condition of related connector
Main PCB Board Operation Check
Items
SMPS Transformer (Indoor unit)
- Input Voltage
- Output Voltage(ZD02D)
IC04D(7805) Output (Indoor/Outdoor unit)
IC01A(KIA7036, Reset IC) X01(8MHz)
Replace Trans
Replace IC04D
Replace faulty parts
- About AC220V/240V±10% - Check the power voltage
- About DC12V
DC +5V
Voltage of Micom No. 2,
(DC +4.5V over) and Soldering condition.
Content Remedy
NO
YES
(After 10 seconds)
Page 50
- 50 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
The product is not operate with the remote controller.
Turn on Main Power
While the compressor has been stopped, the compressor does not operate owing to the delaying function for 3 minutes after stopped.
Caused by other parts except the remote control
Cause by the remote control
When the mark( ) is displayed in LCD screen, replace battery.
Check the contact of CN-DISP1 connector.
When the compressor stopped Indoor Fan is driven by a low speed. At this point the wind speed is not controlled by the remote controller. (When operated in the Sleeping Mode, the wind speed is set to the low speed by force.)
Check Display PCB Assembly
- Voltage between CN DISP1 - : DC +5V
Check the connecting circuit between the remote controller MICOM (No. ) - R17(2) - IR LED - TR - R16(2.2K).
Check point
Check the connecting circuit between CN-DIS1 ­R01L(5.1k) - C01L(680pF) - MICOM PIN
Check Receiver Assembly
Page 51
- 51 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Compressor/Outdoor Fan are unable to drive.
Turn on Main Power
Operate "Cooling Mode( )" by setting the desired temperature of the remote controller is less than one of the indoor temperature by 1°C at least.
When in Air Circulation Mode, Compressor/Outdoor Fan is stopped.
Check the sensor for indoor temperature is attached as close as to be effected by the temperature of Heat Exchanger(EVA).
When the sensor circuit for indoor temperature and connector are in bad connection or are not engaged, Compressor/Outdoor Fan is stopped.
Check the related circuit of RY-FAN.
Check the indoor temperature sensor is disconnected or not(About 10k/ at 25°C).
Turn off Main Power
Check the electrical wiring diagram of outdoor side.
Check the abnormal condition for the component of
Compressor/Outdoor Fan Motor.
Check the "open" or "short" of conmecting wires between indoor and outdoor.
Check Relay(RY - COMP) for driving compressor.
When the power(About AC220V/240V) is applied to the connecting wire terminal support transferred to compressor, PWB Assembly is normal.
Check the circuit related to the relay.
Check point COMP ON COMP OFF
Between Micom(No.
DC5V DC0V
62) and GND
Between IC01M(No. 14) Below DC 1V
About DC12V
and GND (app)
Page 52
- 52 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Check the TRIAC high speed operation by remote control.
(The Indoor Fan Motor is connected)
Turn off Main power
Check the connection of CN-MOTOR
Check the Fan Motor
Check the Fuse(AC250V/T2A)
Turn ON Main Power
Check the related circuit of indoor Fan Motor.
The pin NO 63 of Micom, and the part for driving TRIAC(the input and output signal of IC01M, PIN NO 7, 10)
Check the pattern
Check the TRIAC
- TRIAC Open: Indoor Fan Motor never operate
- TRIAC short: Indoor Fan Motor always operates in case of ON or OFF.
When indoor Fan does not operate.
The voltage of PIN NO 1(orange) and 3(yellow) of CN-MOTOR.
About AC 180V over About AC 50V over
TRIAC is not damaged TRIAC Check
Page 53
- 53 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Confirm that the Vertical Louver is normally geared with the shaft of Stepping Motor.
If the regular torque is detected when rotating the Vertical Louver with hands Normal
Check the connecting condition of CN-U/D Connector
Check the soldering condition(on PWB) of CN-U/D Connector
If there are no problems after above checks
Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver
When Vertical Louver does not operate.
Check the operating circuit of the Vertical Louver
Confirm that there is DC +12V between pin (RED) of CN-U/D and
GND.
Confirm that there is a soldering short at following terminals.
- Between , , and of MICOM
- Between , , and of IC01M
- Between , , and of IC01M
60 61 62 63
Page 54
- 54 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
When Heating does not operate
Operate Heating Mode( ) by setting the desired temperature of the remote control is higher than one of the indoor temperature by 2°C at least.
In heating Mode, the indoor fan operates in case the pipe temperature is higher than 28°C.
Check the connector of intake and pipe sensor(thermistors)
Check the related circuit of RY-4WAY
Check the indoor room temperature is disconnected or not (about 10K/at 25°C).
Check the indoor pipe temperature is disconnected or not (about
5K/at 25°C).
Turn ON Main Power
Check the DC voltage on the PWB ASSEMBLY
The details of check are as followings
Check point
Between Micom
(NO.59) and GND
Between IC01M
(NO.11) and GND
Comp ON
DC 5V
Below DC 1V
Comp OFF
DC 0V
About DC
12V
Check point
Between Micom
(NO.51) and GND
Between IC02M
(NO.11) and GND
4 way ON
DC 5V
Below DC 1V
4 way OFF
DC 0V
About DC 12V
Check point
Between Micom
(NO.53) and GND
Between IC02M
(NO.12) and GND
Fan ON
DC 5V
Below DC 1V
Fan OFF
DC 0V
About DC 12V
Comp Relay.
4 way Relay
Outdoor fan Relay
Page 55
- 55 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Turn off Main Power
Check the electrical wiring diagram of outdoor side.
Check the abnormal condition for the component of
Compressor/Outdoor Fan Motor, 4 way.
Check the "open" or "short" of connecting wires between indoor and outdoor.
Page 56
- 56 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Exploded View
Exploded View
346810
146811
131410
359011
342800
147581
354210
268711A
135311
135316
267110
249951
733010
135313
152302
35211B
135516
352150
W0CZZ
Indoor Unit
Page 57
- 57 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Exploded View
554031
437212
435511
552202
552116
552201
554160
561410
549610
552113
550140
552203B
552203A
430411
447910
649950
552102B
552102A
437211
435301
559010
546810
349480
Outdoor Unit: 9K,18K Btu/h Models
Page 58
- 58 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Exploded View
559010
552202
552111
649950
430410
552203-2
546810
435301
437210
561410
567502
554160
552203-1
552116
447911
W0CZZ
552201
554031
237205
437212
237204
435511
550140
552102-1
Outdoor Unit: 12k Btu/h Models
Page 59
- 59 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Exploded View
554032
437212
435511
668713
W0CZZ
W0CZZ-2
552202
552116
553000
554160
550140
552203-2
552203-1
430410
435301
447910
649950
552111
552201
552102-2
437210
559010
435512
546810
552102-1
567502
Outdoor Unit: 24K Btu/h Model
Page 60
P/NO : 3828A20462S
MAY, 2008
Loading...