LG E12EM, E09EM, E18EM Installation Manual

Page 1
• Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air condi­tioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:
TIPS FOR SAVING ENERGY
• Do not use copper pipes having a collapsed.
- Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
• For R410A model, use piping, flare nut and tools which is specified for R410A refrigerant.
- Using of (R22) piping, flare nut and tools may cause abnormally high pressure in the refrigerant cycle (piping), and possibly result in explosion and injury.
• It is desirable that the amount of residual oil less than 40 mg/10m.
Operation
• Do not share the outlet with other appliances.
- It will cause an electric shock or a fire due to heat generation.
• Do not use the damaged power cord.
- Otherwise, it may cause a fire or electrical shock.
• Do not modify or extend the power cord randomly.
- Otherwise, it may cause a fire or electrical shock.
• Take care so that the power cord may not be pulled during operation.
- Otherwise, it may cause a fire or electrical shock.
• Unplug the unit if strange sounds, smell, or smoke comes from it.
- Otherwise, it may cause electrical shock or a fire.
• Keep the flames away.
- Otherwise, it may cause a fire.
• Take the power plug out if necessary, holding the head of the plug and do not touch it with wet hands.
- Otherwise, it may cause a fire or electrical shock.
• Do not use the power cord near the heating tools.
- Otherwise, it may cause a fire and electrical shock.
• Do not open the suction inlet of the indoor/outdoor unit during operation.
- Otherwise, it may electrical shock and failure.
• Do not allow water to run into electrical parts.
- Otherwise, it may cause the failure of machine or electrical shock.
• Hold the plug by the head when taking it out.
- It may cause electric shock and damage.
• Never touch the metal parts of the unit when removing the filter.
- They are sharp and may cause injury.
• Do not step on the indoor/outdoor unit and do not put anything on it.
- It may cause an injury through dropping of the unit or falling down.
Connecting cable (Optional Parts)
Vinyl tape (Wide)
• Apply after carrying out a drainage test.
• To carry out the drainage test, remove the air filters and pour water into the heat exchanger.
Saddle
Gas side piping (Optional Parts) Liquid side piping (Optional Parts) Additional drain pipe
Vinyl tape (Narrow) Drain Hose
Installation plate Sleeve Bushing-Sleeve Putty(Gum Type Sealant)
Bend the pipe as closely on the wall as possible, but be careful that it doesn't break.
Taping Direction
NOTE
!
• You should purchase the installation parts.
* The feature can be changed according to a type of model.
INSTALLATION MAP
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product.
WARNING
It can result in serious injury or death when the directions are ignored.
CAUTION
It can result in minor injury or product damage when the directions are ignored.
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• Air conditioner Shall be installed in accordance with national wiring regulations.
• If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similary qualified persons in order to avoid a hazard.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunc­tion, property damage, personal injury and/or death.
Installation
• Always perform grounding.
- Otherwise, it may cause electrical shock.
• Don’t use a power cord, a plug or a loose socket which is damaged.
- Otherwise, it may cause a fire or electrical shock.
• For installation of the product, always contact the service center or a professional installation agency.
- Otherwise, it may cause a fire, electrical shock, explosion or injury.
• Securely attach the electrical part cover to the indoor unit and the service panel to the outdoor unit.
- If the electrical part cover of the indoor unit and the service panel of the outdoor unit are not
attached securely, it could result in a fire or electric shock due to dust, water, etc.
• Always install an air leakage breaker and a dedicated switching board.
- No installation may cause a fire and electrical shock.
• Do not keep or use flammable gases or combustibles near the air conditioner.
- Otherwise, it may cause a fire or the failure of product.
• Ensure that an installation frame of the outdoor unit is not damaged due to use for a long time.
- It may cause injury or an accident.
• Do not disassemble or repair the product randomly.
- It will cause a fire or electrical shock.
• Do not install the product at a place that ther is concern of falling down.
- Otherwise, it may result in personal injury.
• Use caution when unpacking and installing.
- Sharp edges may cause injury.
• Thickness of copper pipes used are as shown “Flaring work” Table.
- Never use copper pipes thinner than that in the table even when it is available on the market
!
!
!
• Do not place a heavy object on the power cord.
- Otherwise, it may cause a fire or electrical shock.
• When the product is submerged into water, always contact the service center.
- Otherwise, it may cause a fire or electrical shock.
• Take care so that children may not step on the outdoor unit.
- Otherwise, children may be seriously injured due to falling down.
• Do not turn on the breaker or power under condition that front panel, cabinet, top cover, control box cover are removed or opened.
- Otherwise, it may cause fire, electric shock, explosion or death.
CAUTION
Installation
• Install the drain hose to ensure that drain can be securely done.
- Otherwise, it may cause water leakage.
• Install the product so that the noise or hot wind from the outdoor unit may not cause any damage to the neighbors.
- Otherwise, it may cause dispute with the neighbors.
• Always inspect gas leakage after the installation and repair of product.
- Otherwise, it may cause the failure of product.
• Keep level parallel in installing the product.
- Otherwise, it may cause vibration or water leakage.
Operation
• Avoid excessive cooling and perform ventilation sometimes.
- Otherwise, it may do harm to your health.
• Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent.
- The appearance of the air conditioner may deteriorate, change color, or develop surface flaws.
• Do not use an appliance for special purposes such as preserving animals vegetables, precision ma­chine, or art articles.
- Otherwise, it may damage your properties.
• Do not place obstacles around the flow inlet or outlet.
- Otherwise, it may cause the failure of appliance or an accident.
!
Symbols used in this Manual
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that may cause harm to the air conditioner.
This symbol indicates special notes.
Features
!
INTRODUCTION
!
Air inlet vents
Air outlet vents
Base plate
Coolant piping
Connection wire
Drain hose
* The feataure can be changed according to type of model.
Air inlet
Operation lamp
Front grille
Signal receiver
Air deflector (Vertical louver & Horizontal vane)
Air outlet
On/ Off button
Select the best Location
Indoor unit
- There should not be any heat or steam near the unit.
- Select a place where there are no obstacles around of the unit.
- Make sure that condensation drainage can be conveniently routed away.
- Do not install near a doorway.
- Ensure that the interval between a wall and the left (or right) of the unit is more than 100mm. The unit should be installed as high as possible on the wall, allowing a minimum of 200mm from ceiling.
- Use a metal detector to locate studs to pre­vent unnecessary damage to the wall.
* The feature can be changed according to a
type of model.
More than 200
More than
100
More than
100
(Unit : mm)
More than
300
More than
300
Sunroof
Fence or obstacles
More than
700
More than
600
(Unit : mm)
Outdoor unit
- If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
- Ensure that the space around the back and sides is more than 300mm. The space in front of the unit should be more than 700mm of space.
- Do not place animals and plants in the path of the warm air.
- Take the weight of the air conditioner into ac­count and select a place where noise and vi­bration are minimum.
- Select a place where the warm air and noise from the air conditioner do not disturb neigh­bors.
INSTALLATION
Name Quantity Shape
Installation plate 1 EA
Type "A" screw
5 EA
Type "B" screw
2 EA
Type "C" screw
2 EA
Remote control
holder
1 EA
The feature can be changed according to a type of model.
Screws for fixing panels are attached to decoration panel.
Figure FigureName
Screw driver
Electric drill
Measuring tape, Knife
Hole core drill
Spanner
Torque wrench
Multi-meter
Hexagonal wrench
Ammeter
Gas-leak detector
Thermometer,
Level
Flaring tool set
Name
INSTALLATION TOOLS
INSTALLATION PARTS
Flaring Work
Main cause for gas leakage is due to defect of flaring work. Carry out correct flaring work in the following procedure.
Cut the pipes and the cable
1 Use the piping kit accessory or the pipes
purchased locally.
2 Measure the distance between the indoor
and the outdoor unit.
3 Cut the pipes a little longer than measured
distance.
4 Cut the cable 1.5m longer than the pipe
length.
Drill a Hole in the Wall
- Drill the piping hole with a ø65mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
Ø70
100
145
Right rear piping
Left rear piping
Place a level on raised tab
Unit Outline
199
148
(Unit : mm)
399 399
Installation Plate
Measuring Tape
Measuring Tape
Hanger
5-7mm
(3/16"~5/16")
Indoor
WALL
Outdoor
2 Mount the installation plate on the wall
with type "A" screws. If mounting the unit on a concrete wall, use anchor bolts.
- Mount the installation plate horizontally by aligning the centerline using Horizontal meter.
3 Measure the wall and mark the centerline.
It is also important to use caution concern­ing the location of the installation plate. Routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely.
Indoor unit
Fixing Installation Plate
The wall you select should be strong and solid enough to prevent vibration.
1 Before installation, confirm the position of
a screw between chassis and Installation plate.
Type "A" Screws
Type "A" Screws
Type "A" Screws
Installation Plate
Installation Plate
Installation Plate
Chassis
Hook
Chassis
Hook
Chassis
Hook
Ø65
Ø65
145 75
Right rear piping
Left rear piping
Installation Plate
Place a level on raised tab
Unit Outline
192192
(Unit : mm)
378 378
Copper
pipe
90°
Slanted Uneven Rough
Ø65
170
Right rear piping
Left rear piping
Place a level on raised tab
Unit Outline
217
175
(Unit : mm)
434 439
Ø65Ø65
123
Installation Plate
Ø70
Installation of Indoor Unit
1 Hook the indoor unit onto the upper por-
tion of the installation plate.( engage the three hooks at the top of the indoor unit with the upper edge of the installation plate) Ensure that the hooks are properly seated on the installation plate by moving it left and right
1
2
Installation plate
Good case
- Press on the tubing cover and unfold the tubing to downward slowly. And then bend to the left side slowly.
3 Pull back the tubing holder. 4 Remove pipe port cover and positioning
the tubing
* The feature can be changed according to a
type of model.
Right
Back side view
9K/12K
18K
Tubing holder
Backwards
Left
Pipe Port
Pipe Port
Right
Tubing holder
Backwards
Left
Drain Hose
Drain Hose
CAUTION
Installation Information. For right piping. Follow the instruction above.
!
Bad case
- Following bending case from right to left di­rectly may cause damage to the tubing.
* The feature can be changed according to a
type of model.
Indoor unit tubing Flare nut Pipes
Connecting the installation pipe and drain hose to the indoor unit.
1 Align the center of the pipes and suffi-
ciently tighten the flare nut by hand
2 Tighten the flare nut with a wrench
3 When needed to extend the drain hose of
indoor unit, assembly the drain pipe as shown on the drawing
Wrench
Indoor unit tubing
Open-end wrench (fixed)
Connection pipe
Flare nut
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
Wrap the insulation material around the connecting portion.
1 Overlap the connection pipe insulation ma-
terial and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there may be no gap.
2 Set the tubing cutting line upward.
Wrap the area which accommodates the rear piping housing section with vinyl tape.
3 Bundle the piping and drain hose together
by wrapping them with vinyl tape sufficient enough to cover where they fit into the rear piping housing section.
Insulation material
Gas Pipe
Liquid Pipe
Cutting Line
Cutting Line
Good Case Bad Case
* Tubing cutting line have to be upward.
Vinyl tape(narrow)
Connection pipe
Connecting cable
Vinyl tape (wide)
Wrap with vinyl tape
Indoor unit pipe
Pipe
Wrap with vinyl tape
Drain hose
Pipe
Vinyl tape(wide)
Outside Diameter Torque
mm inch kgf.m N.m Ø6.35 1/4 180~250 17.6~24.5 Ø9.52 3/8 340~420 33.3~41.2 Ø12.7 1/2 550~660 53.9~64.7
Ø15.88 5/8 630~820 61.7~80.4
- Finally, tighten the flare nut with torque wrench until the wrench clicks. When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
Liquid side piping (Smaller diameter)
Torque wrench
Gas side piping (Bigger diameter)
Outdoor unit
Outside Diameter Torque
mm inch kgf.m N.m
Ø6.35 1/4 180~250
17.6~24.5 Ø9.52 3/8 340~420 33.3~41.2 Ø12.7 1/2 550~660 53.9~64.7
Ø15.88 5/8 630~820 61.7~80.4
- Align the center of the pipings and suffi­ciently tighten the flare nut by hand.
CAUTION
- The circuit diagram is a subject to change without notice.
- The earth wire should be longer than the common wires.
- When installing, refer to the circuit dia­gram on the chassis cover.
- Connect the wires firmly so that they may not be pulled out easily.
- Connect the wires according to color codes, referring to the wiring diagram.
!
Chassis cover
12K/18K
9K
Connecting cable
Connecting cable
1(L) 2(N) 3
1(L) 2(N)
3
Connecting the Cables
Indoor unit
Connect the cable to the indoor unit by con­necting the wires to the terminals on the con­trol board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of the indoor unit.)
1 Insert the connecting cable through the
bottom side of indoor unit and connect the cable (You can see detail contents in 'Con­necting the cables' section)
2 Secure the cable onto the control board
with the cable retainer.
3 Tape the tubing pipe, drain hose and the
connection cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause overflow from the drain pan through the inside of the unit.
Burrs removal
1. Completely remove all burrs from the cut cross section of pipe/tube.
2. While removing burrs put the end of the copper tube/pipe in a downward direction while removing burrs location is also changed in order to avoid dropping burrs into the tubing.
Pipe
Reamer
Point down
Putting nut on
- Remove flare nuts attached to indoor and
outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after finishing flare work)
Flaring work
1 Firmly hold copper pipe in a bar with the di-
mension shown in the table below .
2 Carry out flaring work with the flaring tool.
Flare nut
Copper tube
Outside diameter A Thickness
mm inch mm mm
Ø6.35 1/4" 1.1~1.3 0.7
Ø9.52 3/8" 1.5~1.7 0.8
Ø12.7 1/2" 1.6~1.8 0.8
Ø15.88 5/8" 1.6~1.8 1.0
Ø19.05 3/4" 1.9~2.1 1.0
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Check
1 Compare the flared work with the figure
by.
2 If a flared section is defective, cut it off
and do flaring work again.
Connecting the Piping
1 Open the panel of the indoor unit. 2 Remove the chassis cover from the unit by
loosing 2 screws.
Chassis cover
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
2 Unlock the tubing holder from the chassis
and mount between the chassis and instal­lation plate in order to separate the bottom side of the indoor unit from the wall.
* The feature can be changed according to a
type of model.
Piping
1 Insert the connecting cable through the
bottom side of indoor unit and connect the cable (You can see detail contents in 'Con­necting the cables' section)
<Left side piping>
<Right side piping>
Control Cover
Terminal block
Connecting cable
1(L) 2(N) 3
Tubing Holder
2 Secure the cable onto the control board
with the cable retainer.
3 Lift up the cover of terminal block slightly. 4
Tape the tubing pipe, drain hose and the con­nection cable. Be sure that the drain hose is lo­cated at the lowest side of the bundle. Locating at the upper side can cause overflow from the drain pan through the inside of the unit.
<Left side piping>
<Right side piping>
* The feature can be changed according to a
type of model.
Control Cover
Terminal block
Connecting cable
1(L) 2(N) 3
Drain hose
Connecting pipe
Connecting cable
Tape
Drain hose
Connecting pipe
Connecting cable
Tape
Drain hose
NOTE
!
Insert the drain hose at left side when you use left side piping type.
CAUTION
If the extension drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from sweating (con­densation) could not damage furniture or floors.
• Foamed polyethylene or equivalent is recommended.
!
Indoor Outdoor
Indoor Unit Drain hose
Indoor Unit Drain hose
Insulation (More than 100~300mm length and 7mm thickness)
Extension drain hose
Finishing the indoor unit installation
1 Mount the tubing holder in the original
positon.
2 Ensure that the hooks are properly seated
on the installation plate by moving it left and right.
3 Press the lower left and right sides of the
unit against the installation plate until the hooks engage into their slots (clicking sound).
4 Finish the assembly by screwing the unit
to the installation plate by using two pieces of type "C" screws. And assemble a chas­sis cover.
Type 'C' screw
Outdoor unit
Connecting the Piping
- Remove the tubing cover from the unit by loosening the screw.
Cover control
Tubing Cover
Terminal Block
L N
1(L)2(N) 3
Power connecting cable
Power cord
Cord clamp
Terminal Block
Tubing Cover
• 18 K
9 K/12K
The power cord connected to unit should be selected according to the following na­tional wiring regulations. The supply cords of parts of appliances for outdoor use shall not be lighter than poly­chloroprene sheathed flexible cord. (code designation 60245 IEC 57, H05RN-F)
NORMINAL CROSS SEC-
TIONAL AREA
Grade
2.5~3.5kw
5.0kw 18K
1.0 1.5
5.0kw 18K
20A
5.0kw 18K
0.75
(mm2)
NORMINAL CROSS SECTIONAL AREA
Grade
2.5~3.5kw
0.75
(mm2)
10±3mm
20mm
GN/YL
Cover control
Outdoor UnitOutdoor Unit
Power connecting cable
Power cord
1(L)
L N
)N(2 3
Tubing Cover
L N 3
1(L) 2(N)
18K
9K/12K
Air
Conditioner
Main power source
Circuit Breaker Use a circuit breake or time delay fuse.
10±3mm
20mm
GN/YL
The power connecting cable with indoor and outdoor unit should be selected according to the following national wiring regulations. The supply cords of parts of appliances for outdoor use shall not be lighter than poly­chloroprene sheathed flexible cord. (code designation 60245 IEC 57, H05RN-F)
- Connect the wires to the terminals on the control board individually.
- Secure the cable onto the control board with the cord clamp.
- Use a recognized circuit breaker between the power source and the unit. A disconnecting device to adequately discon­nect all supply lines must be fitted.
Circuit Breaker(A)
Grade
2.5~3.5kw 15A
CAUTION
Provide the circuit breaker between power source and the unit as shown by
!
CAUTION
!
Outdoor
1 2 3
54 6 7
INSTALLATION MANUAL AIR CONDITIONER
TYPE : WALL MOUNTED
P/No : MFL68802301
ENGLISH
Page 2
In case, to install the outdoor unit on the sea­side, set up a windbreak not to be exposed to the sea wind.
Select a well-drained place.
- It should be strong enough like concrete to prevent the sea wind from the sea.
- The height and width should be more than 150% of the outdoor unit.
- It should be keep more than 70 cm of space between outdoor unit and the windbreak for easy air flow.
CAUTION
- Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
- Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance.
- If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it needs additional anticorrosion treatment on the heat exchanger.
!
Sea wind
Sea wind
Sea wind
Windbreak
Selecting the location(Outdoor Unit)
If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the outdoor unit on the opposite side of the sea wind direction.
Installation guide at the seaside
NOTE
!
- If you can’t meet above guide line in the seaside installation, please con­tact LG Electronics for the additional anticorrosion.
- Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water.
* Do not use seawater when you
clean up the heat exchanger.
Piping Length and Elevation
Capacity
(W)
Pipe Size
Standard Length
(m)
Max.
Length
(m)
Max.
Elevation
(m)
Additional Re­frigerant (g/m)
(after 5 m)
GAS LIQUID
mm inch mm inch
2.5k, 3.5k
5.0k
Ø9.52 3/8 Ø6.35 1/4 20
Ø12.7 1/2 Ø6.35 1/4 20710152055
A B
Outdoor unit
Indoor unit
A
Operation ranges
Mode Indoor temperature Outdoor temperature
Cooling 18°C ~ 32°C -10°C ~ 48°C
Heating 16°C ~ 30°C -10°C ~ 24°C
B
Outdoor unit
Indoor unit
A
B
CAUTION
Capacity is based on standard length and maximum allowable length is on the basis of relia­bility. Additional refrigerant must be charged after 5 m.
!
The table below indicates the temperature ranges the air conditioner can be operated within.
CAUTION
According to the confirmation of the above conditions, prepare the wiring as follows.
1 Never fail to have an individual power
circuit specifically for the air condi­tioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control cover.
2 The screw which fasten the wiring in
the casing of electrical fittings are li­able to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3 Specification of power source. 4 Confirm that electrical capacity is suffi-
cient.
5 See that the starting voltage is main-
tained at more than 90 percent of the rated voltage marked on the name plate.
6 Confirm that the cable thickness is as
specified in the power source specifi­cation. (Particularly note the relation between cable length and thickness.
7 Always install an earth leakage circuit
breaker in a wet or moist area.
8 The following would be caused by volt-
age drop.
- Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function of the overload.
9 The means for disconnection from a
power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductors.
!
Checking the Drainage
To check the drainage.
1 Pour a glass of water on the evaporator. 2 Ensure the water flows through the drain
hose of the indoor unit without any leak­age and goes out the drain exit.
Drain piping
1 The drain hose should point downward for
easy drain flow.
Drain Pan
Drain Hose
Leakage Checking
Connecting area
drain hose
Leakage checking
Downward slope
In cases where the outdoor unit is installed above the Indoor unit perform the following.
1 Tape the piping and connecting cable from
down to up.
2 Secure the taped piping along the exterior
wall. Form a trap to prevent water entering the room.
3 Fix the piping onto the wall using saddle or
equivalent
Seal a small opening around the pipings with gum type sealant.
Trap
Trap
Air Purging
The air and moisture remaining in the refriger­ant system have undesirable effects as indi­cated below.
- Pressure in the system rises.
- Operating current rises.
- Cooling(or heating) efficiency drops.
- Moisture in the refrigerant circuit may freeze and block capillary tubing.
- Water may lead to corrosion of parts in the refrigeration system.
Therefore, after evacuating the system, take a leak test for the piping and tubing between the indoor and outdoor unit.
- Preparation Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
- Leak test Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.
Air purging with vacuum pump
CAUTION
To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
!
WARNING
There is a risk of fire and explo­sion.
- Inert gas (nitrogen) should be
used when you check plumbing leaks, cleaning or repairs of pipes etc. If you are using combustible gases includ­ing oxygen, product may have the risk of fires and explosions.
!
CAUTION
Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The knob of the 3­way valve must always be kept close.
- Pressurize the system to maximum
17.6kg/cm2G (R-22 model) or
28.1kg/cm2G (R-410A model) with dry ni­trogen gas and close the cylinder valve when the gauge reading reaches
17.6kg/cm2G (R-22model) or
28.1kg/cm2G (R-410A model). Next step is leak test with liquid soap.
!
- With a service valve wrench, turn the valve of liquid side counter-clockwise to fully open the valve
- Turn the valve of gas side counter clockwise to fully open the valve
- Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose.
- Replace the flare nut and its bonnet on the gas side service port and fasten the flare nut se­curely with an adjustable wrench. This process is very important to prevent leakage from the system.
Outdoor unit
Lo Hi
Manifold valve
Vacuum pump
Pressure gauge
Open Close
Finishing the Job
- Replace the valve caps at both gas and liquid side service valves and fasten them tight. This completes air purging with a vacuum pump.
- Replace the pipe cover to the outdoor unit by one screw Now the air conditioner is ready for test run.
* The feature can be changed according to a type
of model.
Operate the unit for 15~20 minutes, then check the system refrigerant charge:
- Measure the pressure of the gas side service valve.
- Measure the air temperature from inlet and outlet of air conditiioner.
- Ensure the difference between the inlet and outlet temperature is more than 8°C.
- For reference; the gas side pressure at opti­mum condition is shown on table (cooling)
The air conditioner is now ready to use.
*The feature can be changed according to a type
of model.
This is performed when the unit is relocated or the refrigerant circuit is serviced. Pump Down means collecting all refrigerant into the outdoor unit without the loss of refrig­erant.
- Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve.
- Open the gas side service valve halfway and purge the air in the manifold hose using the refrigerant.
- Close the liquid side service valve(all the way).
- Turn on the unit's operating switch and start the cooling operation.
- When the low-pressure gauge reading be­comes 1 to 0.5kg/cm
2
G(14.2 to 7.1 P.S.I.G.), fully close the gas side valve and then quickly turn off the unit. Now Pump Down procedure is completed, and all refrigerant is collected into the outdoor unit.
Discharge temperature
Discharge air
Inlet temperature
NOTE
!
If the actual pressure is higher than shown, the system is most likely over­charged, and charge should be removed. If the actual pressure are lower than shown, the system is most likely under­charged, and charge should be added.
CAUTION
Be sure to perform Pump Down proce­dure in the cooling mode.
!
Pump Down Procedure
Pump downEvaluation of the performance
Refrigerant
Outside ambi-
ent TEMP.
The pressure of
the gas side
R-22 35°C (95°F)
4~5kg/cm2G
(56.8~71.0
P.S.I.G.)
R-410A 35°C (95°F)
8.5~9.5kg/cm2G
(120~135 P.S.I.G.)
2 Do not make drain piping like the following.
* The feature can be changed according to a
type of model.
Do not raise
Water leakage
Accumulated drain water
Air
Waving
Water leakage
Tip of drain hose dipped in water
Water leakage
Ditch
Less than 50mm gap
Forming the Piping
Form the piping by wrapping the connecting portion of the indoor unit with insulation material and secure it with two kinds of vinyl tapes.
- If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.
In cases where the outdoor unit is installed below the indoor unit perform the following.
1 Tape the piping, drain hose and connecting
cable from down to up.
2 Secure the tapped piping along the exterior
wall using saddle or equivalent.
Trap is required to prevent water from entering into electrical parts.
Taping
Saddle
Drain hose
Pipings
Connecting cable
Seal a small opening around the pipings with gum type sealant.
Drain hose
Vinyl tape(narrow)
Pipe
Wrap with vinyl tape(wide)
- Do a leak test of all joints of the tubing(both indoor and outdoor) and both gas and liquid side service valves. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
- After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is re­duced to normal, disconnect the hose from the cylinder.
*The feature can be changed according to a
type of model.
- Remove the caps from the 2-way and 3-way valves.
- Remove the service-port cap from the 3-way valve.
- Apply a soap water or a liquid neutral deter­gent on the indoor unit connection or out­door unit connections by a soft brush to check for leakage of the connecting points of the piping.
- If bubbles come out, the pipes have leakage
- Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the "Lo" knob of the pressure Gauge is open. Then, run the vacuum pump. The operation time for evacuation varies with tubing length and capacity of the pump. The following table shows the time required for evacuation.
- When the desired vacuum is reached, close the knob of the 3-way valve and stop the vacuum pump.
Evacuation
Lo Hi
Indoor unit
Outdoor unit
Manifold valve
Charge hose
Nitrogen gas cylinder(in vertical standing position)
Pressure gauge
Liquid side
Outdoor unit Outdoor unit Outdoor unit
Cap
Gas side
3-way valve3-way valve
(Open)(Open)
2-way valve2-way valve
(Close)(Close)
3-way valve
(Close)
2-way valve
(Close)
Required time for evacuation when 30 gal/h
vacuum pump is used
If tubing length is
less than 10m (33 ft)
If tubing length is
longer than 10m (33
ft)
10 min. or more 15 min. or more
Soap water method
Test Running
- Check that all tubing and wiring are properly connected.
- Check that the gas and liquid side service valves are fully open.
Prepare remote controller
1 Remove the battery cover by pulling it ac-
cording to the arrow direction.
2 Insert new batteries making sure that the
(+) and (–) of battery are installed correctly.
3 Reattach the cover by pushing it back into
position.
NOTE
!
- Use 2 AAA(1.5volt) batteries. Do not use rechargeable batteries.
- Remove the batteries from the remote controller if the system is not used for a long time
- Fix the outdoor unit with a bolt and nut(ø10mm) tightly and horizontally on a con­crete or rigid mount.
- When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake.
- If the vibration of the unit is transmitted to the pipe, secure the unit with an anti-vibra­tion rubber.
Settlement of outdoor unit
Bolt
Tubing connection
98 10 11
Note - Memo -
1312
Loading...