LG AUUW4860 INSTALLATION INSTRUCTIONS

ENGLISH ITALIANO ESPAÑOL FRANÇAIS DEUTSCH
LG Air Conditioner
INSTALLATION MANUAL
LG
website http://www.lgservice.com
IMPORTANT
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it thoroughly.
2 Air Conditioner
Air Conditioner Installation Manual
TABLE OF CONTENTS
Safety Precautions .....3
Installation of Indoor,
Outdoor unit................6
The indoor unit
installation...................9
Remote controller
installation.................23
Wiring connection ....24
Connecting Pipes to
the Indoor Unit ..........26
Installation to
decorative panel .......28
Indoor unit drain
piping .........................29
Test running..............32
Optional operation....34
Connecting cable
• Four Type "A" Screw
• Hanging Bolt (W 3/8 or M10 length 650mm)
• Pipes: Gas side
Liquid side
• Insulated drain hose
• Additional Drain hose Inner Dia
Cassette type.............32mm
Duct type....................25mm
Convertible type.........25mm
Level
Screw driver
Electric drill
Hole core drill (ø70mm)
• Flaring Tools set
• Torque Wrenches
• Hexagonal Wrench (4mm, 5mm)
• Gas-leak detector
Owner’s Manual
Thermometer
Installation
Requirements
Required Parts Required Tools
Safety Precautions
Installation Manual 3
ENGLISH
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage.
WARNING
Be sure not to do.
Be sure to follow the instruction.
Safety Precautions
Installation
Install the panel and the cover of control box securely.
• There is risk of fire or electric shock.
Always install a dedicated circuit and breaker.
• Improper wiring or installation may cause fire or electric shock
Use the correctly rated breaker or fuse.
• There is risk of fire or electric shock.
Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
• There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
Do not disassemble or repair the product. There is risk of fire or electric shock.
Always ground the product.
• There is risk of fire or electric shock.
WARNING
CAUTION
4 Air Conditioner
Safety Precautions
Do not modify or extend the power cable.
• There is risk of fire or electric shock.
Be cautious when unpacking and installing the product.
Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator.
For installation, always contact the dealer or an Authorized Service Center.
• There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
• It may cause injury, accident, or damage to the product.
Be sure the installation area does not deteriorate with age.
If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
• Moisture may condense and wet or damage furniture.
Do not store or use flammable gas or combustibles near the product.
• There is risk of fire or failure of product.
It is recommended to install the indoor unit into the one big space, rather than into the some small spaces.
Operation
Gasolin
Installation Manual 5
ENGLISH
Safety Precautions
Always check for gas (refrigerant) leakage after installation or repair of product.
• Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained away properly.
• A bad connection may cause water leakage.
Keep level even when installing the product.
• To avoid vibration or water leakage.
Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
• It may cause a problem for your neighbors.
Use two or more people to lift and transport the product.
• Avoid personal injury.
Do not install the product where it will be exposed to sea wind (salt spray) directly.
• It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
CAUTION
Installation
90°
6 Air Conditioner
Installation of Indoor, Outdoor Unit
Installation of Indoor, Outdoor Unit
1. Indoor unit Cassette type
There should not be any heat source or steam near the unit.
There should not be any obstacles to prevent the air circulation.
A place where air circulation in the room will be good.
A place where drainage can be easily obtained.
A place where noise prevention is taken into consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from
the wall, ceiling, or other obstacles.
The indoor unit must keep the maintenance space.
Duct type
The place shall easily bear a load exceeding four times the indoor unit’s weight.
The place shall be able to inspect the unit as the figure.
The place where the unit shall be leveled.
The place shall allow easy water
drainage.(Suitable dimension “H” is necessary to get a slope to drain as figure.)
The place shall easily connect with the outdoor unit.
The place where the unit is not affected by an electrical noise.
The place where air circulation in the room will be good .
There should not be any heat source or steam near the unit
Selection of the best location
Unit:cm
Ceiling
Ceiling Board
Ceiling Board
30 or more
Above 250
330 or less
100
or more
50 or more
50 or more
30 or less
Floor
Top view
(unit: mm)
Front view
Inspection hole
(600X600)
Control box
1000
Front
600600
H
Installation of Indoor, Outdoor Unit
Installation Manual 7
ENGLISH
Convertible type
There should not be any heat source or steam near the unit.
There should not be any obstacles to prevent the air circulation.
A place where air circulation in the room will be good.
A place where drainage can be easily obtained.
A place where noise prevention is taken into consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from
the wall, ceiling, or other obstacles.
2. Outdoor unit
1. If an awning is built over the unit to prevent
direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
2. Ensure that the spaces indicated by arrows
around front, back and side of the unit.
3. Do not place animals and plants in the path
of the warm air.
4. Take the air conditioner weight into account
and select a place where noise and vibration are minimum.
5. Select a place so that the warm air and noise
from the air conditioner do not disturb neighbors.
Rooftop Installations:
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop mounting.
More than
20cm
more than
25cm
more than
More than eye-level
(Ceiling installation)
More than
20cm
(Floor/Wall installation)
75cm
More than
20cm
R
More than
R
20cm
more than
25cm
8 Air Conditioner
Installation of Indoor, Outdoor Unit
3. Piping length and the elevation
Install the branch pipe so that pipe length and difference between high and low will not exceed below SPEC.
4. Refrigerant Additional Charging Method
There is not additional charging of refrigerant by main pipe of 30m below.
For additional charging method, see below table.
<Ref. Addition charging method>
(L1=Main Pipe, L2~L5 : Branch Pipe
CAUTION:
Rated performance for refrigerant line length of:7.5m
Capacity is based on standard length and maximum allowance length is on the
basis of reliability.
Improper refrigerant charge may result in abnormal cycle.
Oil trap should be installed every 10 meters.
When installing the branch pipe, direction and angle of installation is not limited.
Take care so that burrs and foreign material may not enter into the cutting surface when
connecting.
Connect a gas pipe of Ø19.05 by using the socket in the indoor unit and connect remaining those by cutting or direct insertion to the diameter of pipe.
Dont use the liquid pipe by too bending or twisting.
Pipe Length(m)
Total(Main+Branch) Main Pipe(L1) Branch Pipe----Total
Each In out (h1) In-In (h2) L1+L2/L3/L4/L5 Indoor-Indoor_(b)
Spec.
110
50 60 15 30
1 65 10
Branch
Main (L1)
h1
b
L2
L3
L4
L5
h2
Single Refrigerant=(L1-30)*0.05
Double
Triple
D/Twin
Refrigerant=(L1-30)*0.05+(L2+L3-20)*0.03 Refrigerant=(L1-30)*0.05+(L2+L3+L4-20)*0.03 Refrigerant=(L1-30)*0.05+(L2+L3+L4+L5-20)*0.03
Installation Manual 9
ENGLISH
Select and mark the position for fixing bolts and piping hole.
Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose.
Drill the hole for anchor bolt on the wall.
CAUTION:
This air-conditioner uses a drain pump.
Horizontly install the unit using a level gauge.
During the installation, care should be taken not to damage electric wires.
Thoroughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the turbo fan, the fin of the heat exchanger and the drain pump, resulting in heat exchange reduction, spraying, dispersing of water drops, drain pump malfunction, etc. In these cases, take the following actions:
Make sure that the ventilation fan for smoke-collecting hood on a cooking table has
sufficient capacity so that it draws oily steam which should not flow into the suction of the air conditioner.
Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oily steam.
2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.
NOTICE
The indoor unit installation
The dimensions of the paper model for installing are the same as those of the ceiling opening dimensions.
Ceiling board
Level gauge
Ceiling
Use the ventilation fan for smoke-collecting hood with sufficient capacity.
Cooking table
Air conditioner
Take enough distance
Unit:mm
744 Unit size
744 Unit size
658 (Hanging bolt)
6666
790 (Ceiling opening)
790 (Ceiling opening)
572(Hanging bolt)
109
109
Unit:mm
570 Unit size
570 Unit size
450 (Hanging bolt)
7575
600 (Ceiling opening)
600 (Ceiling opening)
521(Hanging bolt)
39.5
39.5
Unit:mm
840 Unit size
840 Unit size
672 (Hanging bolt)
101.5101.5
875 (Ceiling opening)
875 (Ceiling opening)
785 (Hanging bolt)
45
45
The indoor unit installation
1. Cassette type
10 Air Conditioner
Wall
5~7mm
Indoor Outdoor
Set screw of paper model (4 pieces)
Paper model for installation
Ceiling board
150mm
Adjust the same height
Ceiling board
Ceiling
Flat washer for M10
(accessory)
Keep the length of the bolt
from the bracket to 40mm
Open the ceiling board along the outer edge of the paper model
Flat washer for M10
(accessory)
Hanging bolt
(W3/8 or M10)
Nut (W3/8 or M10)
Nut
(W3/8 or M10)
Spring washer
(M10)
Air Conditioner body
The Indoor Unit Installation
The following parts is option. Hanging Bolt - W 3/8 or M10 Nut - W 3/8 or M10 Spring Washer - M10 Plate Washer - M10
CAUTION:
Tighten the nut and bolt
to prevent unit falling.
Drill the piping hole on the wall slightly tilted to the outdoor side using a Ø 70 hole-core drill.
The Indoor Unit Installation
Installation Manual 11
ENGLISH
2. Duct type
CASE 1
POSITION OF SUSPENSION BOLT
Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
Apply a filter Accessory at air return hole.
(Unit:mm)
Dimension
Capacity
18K/24K
BTU/h
30K/36K
BTU/h
48K/60K
BTU/h
ABCDEF(G)HI
932 880 355 45.5 450 30 87 750 163
1232 1182 355 45.5 450 30 87 830 186
1292 1230 477 56 590 30 120 1006 294
CASE 2
I
A
B
(G)
H
Drainage hole
EF
C
D
Install the unit leaning to a drainage hole side as a figure for easy water drainage.
POSITION OF CONSOLE BOLT
A place where the unit will be leveled and that can support the weight of the unit.
A place where the unit can withstand its vibration.
A place where service can be easily
med.
perfor
M10 Nut
M10 SP. washer
M10 washer
M10 washer
M10 SP. washer
M10 Nut
X 4
X 4
X 4
X 4
X 4
X 4
(Local supply)
(Local supply)
12 Air Conditioner
The Indoor Unit Installation
CAUTION:
Tighten the nut and bolt top
revent unit falling.
Select and mark the position for fixing bolts.
Drill the hole for set anchor on the face of ceiling.
Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling.
Mount the suspension bolts to the set anchor firmly.
Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers
.
Old building New building
1 Set anchor 2 Plate washer 3 Spring washer
4 Nut
5 Suspension bolts
Local supply Set anchor Plate washer - M10 Spring washer - M10 Nut - W3/8 or M10 Suspension bolt - W3/8 or M10
Loading...
+ 27 hidden pages