LG AUUH608B INSTALLATION MANUAL

LG Ceiling Duct-Type Air Conditioner
INSTALLATION MANUAL
LG
IMPORTANT
• Please read this installation manual completely before installing the product.
• Please retain this installation manual for future reference after reading it thoroughly.
ENGLISH ESPAÑOL
2 Ceiling Duct Type Air Conditioner
Ceiling Duct Type Air Conditioner Installation Manual
TABLE OF CONTENTS
Safety precautions .....3
Installation of Indoor,
Outdoor unit................6
Connecting Pipes to the
Indoor Unit ................15
Connecting Pipes to the
Outdoor Unit .............17
Checking the Drainage
....................................17
Connecting Cables between Indoor Unit and
Outdoor Unit .............18
Air Purging of the Connecting Pipes and the
Indoor Unit ...............21
Group Control ...........22
Two Thermistor System....
....................................22
E.S.P (External Static
Pressure) Setting......23
How to set E.S.P?. ....24
Installation guide at the
seaside ......................25
Four Type “A” screws
Connecting cable
Pipes: Gas side .....1/2", 5/8", 3/4"
Liquid side .............1/4", 3/8", 1/2"
Insulated drain hose
Insulation materials
Additional Drain hose
(Inner Dia...............25 mm)
Level
Screw driver
Electric drill
Hole core drill (ø70 mm)
Flaring Tools set
Screw driver
Hexagonal Wrench (4 mm/5 mm)
Gas-leak Detector
Installation
Requirements
Required Parts Required Tools
Safety Precautions
Installation Manual 3
ENGLISH
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage.
Be sure not to do.
Be sure to follow the instruction.
WARNING
Installation
Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
• There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
• Do not disassemble or repair the product. There is risk of fire or electric shock.
Always ground the product.
• There is risk of fire or electric shock.
Install the panel and the cover of control box securely.
• There is risk of fire or electric shock.
Always install a dedicated circuit and breaker.
• Improper wiring or installation may cause fire or electric shock
Use the correctly rated breaker or fuse.
• There is risk of fire or electric shock.
WARNING
CAUTION
Safety Precautions
4 Ceiling Duct Type Air Conditioner
Operation
Do not modify or extend the power cable.
• There is risk of fire or electric shock.
Be cautious when unpacking and installing the product.
• Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator.
For installation, always contact the dealer or an Authorized Service Center.
• There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
• It may cause injury, accident, or damage to the product.
Be sure the installation area does not deteriorate with age.
• If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
• Moisture may condense and wet or damage furniture.
Do not store or use flammable gas or combustibles near the product.
• There is risk of fire or failure of product.
Gasolin
Safety Precautions
Installation Manual 5
ENGLISH
Installation
CAUTION
Always check for gas (refrigerant) leakage after installation or repair of product.
• Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained away properly.
• A bad connection may cause water leakage.
Keep level even when installing the product.
• To avoid vibration or water leakage.
Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
• It may cause a problem for your neighbors.
Use two or more people to lift and transport the product.
Avoid personal injury.
Do not install the product where it will be exposed to sea wind (salt spray) directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
90°
6 Ceiling Duct Type Air Conditioner
Installation of Indoor, Outdoor Unit
1. Selection of the best location
1) Indoor unit
Select location
Install the air conditioner in the location that satisfies the following conditions.
The place shall easily bear a load exceeding four times the indoor unit’s weight.
The place shall be able to inspect the unit as the figure.
The place where the unit shall be leveled.
The place shall allow easy water
drainage.(Suitable dimension “H” is necessary to get a slope to drain as figure.)
The place shall easily connect with the outdoor unit.
The place where the unit is not affected by an electrical noise.
The place where air circulation in the room will be good .
There should not be any heat source or steam near the unit
2) Outdoor unit
If an awning is built over the unit to prevent
direct sunlight or rain exposure, be careful that heat radiation from the condenser is not restricted.
There should not be any animals or plants
which could be affected by hot air discharged.
Ensure the spaces indicated by arrows from
the wall, ceiling, fence or other obstacles.
More than 300 mm
More than
300 mm More than 700 mm
Sunroof
Fence or
obstacles
H
600600
Top view
(unit: mm)
Front view
Front
Inspection hole
(600X600)
Control box
1000
Installation of Indoor, Outdoor Unit
Installation of Indoor, Outdoor Unit
Installation Manual 7
ENGLISH
3) Piping length and the elevation
4) Refrigerant Additional Charging Method
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
CAUTION:
Rated performance for refrigerant line length of:7.5m
Capacity is based on standard length and maximum allowance length is on
the basis of reliability.
Improper refrigerant charge may result in abnormal cycle.
Oil trap should be installed every 10 meters.
There is not additional charging of refrigerant by main pipe of 30m below. For additional charging method, see below table.
<Ref. Addition charging method>
(L1=Main Pipe)
Gas Liquid Standard Max. Standard Max.
7.5 50 5 30 80
3/4"(19.05 mm)
3/8"(9.5 mm)
Capacity
Pipe Size
Length A(m) Elevation B(m)
*Additional
(Diameter:Ø)
refrigerant(g/m)
60 kBtu/h
Single Refrigerant=(L1-30)*0.08
8 Ceiling Duct Type Air Conditioner
Installation of Indoor, Outdoor Unit
2. Indoor unit installation
Installation of Unit
Install the unit above the ceiling correctly.
Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
Apply a filter Accessory at air return hole.
Install the unit leaning to a drainage hole
side as a figure for easy water drainage.
A place where the unit will be leveled and that can support the weight of the unit.
A place where the unit can withstand its vibration.
A place where service can be easily performed.
CASE 1
POSITION OF SUSPENSION BOLT
CASE 2
POSITION OF CONSOLE BOLT
(Unit:mm)
Drainage hole
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local supply)
X 4
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local supply)
X 4
A
B
CD
(G)
H
I
EF
ABCDEF(G)H I
Dimension
Capacity
60 kBtu/h
1292 1230 570.5 54 680 30 120 1006 294