LG AUUH488C INSTALLATION MANUAL

Page 1
ENGLISH ESPAÑOL
LG Air Conditioner
INSTALLATION MANUAL
LG
website http://www.lgservice.com
IMPORTANT
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it thoroughly.
Page 2
2 Air Conditioner
Air Conditioner Installation Manual
TABLE OF CONTENTS
Safety Precautions .....3
Installation of Indoor,
Outdoor unit................6
The indoor unit
installation...................9
Remote controller
installation.................23
Wiring connection ....24
Connecting Pipes to
the Indoor Unit..........26
Installation to
decorative panel .......28
Indoor unit drain
piping.........................29
Test running..............32
Optional operation....34
Installation guide
at the seaside ............40
Connecting cable
• Four Type "A" Screw
• Hanging Bolt (W 3/8 or M10 length 650 mm)
• Pipes: Gas side
Liquid side
• Insulated drain hose
• Additional Drain hose Inner Dia
Cassette type............32 mm
Duct type...................25 mm
Convertible type........25 mm
Level
Screw driver
Electric drill
Hole core drill (ø70 mm)
• Flaring Tools set
• Torque Wrenches
• Hexagonal Wrench (4 mm, 5 mm)
• Gas-leak detector
Owner’s Manual
Thermometer
Installation
Requirements
Required Parts Required T ools
Page 3
Safety Precautions
Installation Manual 3
ENGLISH
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury. This symbol indicates the possibility of injury or damage.
WARNING
Be sure not to do.
Be sure to follow the instruction.
Safety Precautions
Installation
Install the panel and the cover of control box securely.
• There is risk of fire or electric shock.
Always install a dedicated circuit and breaker.
• Improper wiring or installation may cause fire or electric shock
Use the correctly rated breaker or fuse.
• There is risk of fire or electric shock.
Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
• There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
Do not disassemble or repair the product.There is r isk of fire or electric shock.
Always ground the product.
• There is risk of fire or electric shock.
WARNING
CAUTION
Page 4
4 Air Conditioner
Safety Precautions
Do not modify or extend the power cable.
• There is risk of fire or electric shock.
Be cautious when unpacking and installing the product.
Sharp edges could cause injury.Be especially careful of the case edges and the fins on the condenser and evaporator.
For installation, always contact the dealer or an Authorized Service Center.
• There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
• It may cause injury, accident, or damage to the product.
Be sure the installation area does not deteriorate with age.
If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
• Moisture may condense and wet or damage furniture.
Do not store or use flammable gas or combustibles near the product.
• There is risk of fire or failure of product.
It is recommended to install the indoor unit into the one big space, rather than into the some small spaces.
Operation
Gasolin
Page 5
Installation Manual 5
ENGLISH
Safety Precautions
Always check for gas (refrigerant) leakage after installation or repair of product.
• Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained away properly.
• A bad connection may cause water leakage.
Keep level even when installing the product.
• To avoid vibration or water leakage.
Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
• It may cause a problem for your neighbors.
Use two or more people to lift and transport the product.
• Avoid personal injury.
Do not install the product where it will be exposed to sea wind (salt spray) directly.
• It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
CAUTION
Installation
90˚
Page 6
6 Air Conditioner
Installation of Indoor, Outdoor Unit
Installation of Indoor, Outdoor Unit
1. Indoor unit Cassette type
• There should not be any heat source or steam near the unit.
• There should not be any obstacles to prevent the air circulation.
• A place where air circulation in the room will be good.
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
• The indoor unit must keep the maintenance space.
Duct type
• The place shall easily bear a load exceeding four times the indoor unit’s weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.(Suitable dimension “H” is necessary to get a slope to drain as figure.)
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical noise.
• The place where air circulation in the room will be good .
• There should not be any heat source or steam near the unit
Selection of the best location
Unit:cm
Ceiling
Ceiling Board
Ceiling Board
30 or more
Above 250
330 or less
100
or more
50 or more
50 or more
30 or less
Floor
Top view
(unit: mm)
Front view
Inspection hole
(600 X 600)
Control box
1000
Front
600600
H
Page 7
Installation of Indoor, Outdoor Unit
Installation Manual 7
ENGLISH
Convertible type
There should not be any heat source or steam near the unit.
There should not be any obstacles to prevent the air circulation.
A place where air circulation in the room will be good.
A place where drainage can be easily obtained.
A place where noise prevention is taken into consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from
the wall, ceiling, or other obstacles.
2. Outdoor unit
If an awning is built over the unit to prevent direct sunlight or rain exposure, be careful that heat radiation from the condenser is not restricted.
There should not be any animals or plants which could be affected by hot air discharged.
Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
More than
200 mm
More than eye-level
More than
200 mm
More than 500 mm
Fence or
obstacles
R
(Ceiling installation)
R
(Floor/Wall installation)
Sunroof
More than
200 mm
More than
200 mm
More than
More than
30cm
500 mm
More than 500 mm
More than 1000 mm
Page 8
8 Air Conditioner
Installation of Indoor, Outdoor Unit
3. Piping length and the elevation
Install the branch pipe so that pipe length and difference between high and low will not exceed below SPEC.
4. Refrigerant Additional Charging Method
For additional charging method, see below table.
<Ref. Addition charging method>
(L1=Main Pipe, L2~L5 : Branch Pipe
CAUTION:
Rated performance for refrigerant line length of:7.5m
Capacity is based on standard length and maximum allowance length is on the
basis of reliability.
Improper refrigerant charge may result in abnormal cycle.
Oil trap should be installed every 10 meters.
When installing the branch pipe, direction and angle of installation is not limited.
Take care so that burrs and foreign material may not enter into the cutting surface when
connecting.
Connect a gas pipe of Ø19.05 by using the socket in the indoor unit and connect remaining those by cutting or direct insertion to the diameter of pipe.
Dont use the liquid pipe by too bending or twisting.
Pipe Length(m)
Total(Main+Branch) Main Pipe(L1) Branch Pipe----Total
Each In out (h1) In-In (h2) L1+L2/L3/L4/L5 Indoor-Indoor_(b)
Spec.
110
50 60 15 30
1 65 10
Branch
Main (L1)
h1
b
L2 L3
L4
L5
h2
Single (L1-30)*0.07
Duo (L1-30)*0.07+(L2+L3-20)*A
Trio (L1-30)*0.07+(L2+L3+L4-20)*A
Quartet (L1-30)*0.07+(L2+L3+L4+L5-20)*A
Branch pipe
Liquid side
Ø6.35 0.03 Ø9.52 0.05
A
Page 9
Installation Manual 9
ENGLISH
Select and mark the position for fixing bolts and piping hole.
Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose.
Drill the hole for anchor bolt on the wall.
CAUTION:
This air-conditioner uses a drain pump.
Horizontly install the unit using a level gauge.
During the installation, care should be taken not to damage electric wires.
Thoroughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the turbo fan, the fin of the heat exchanger and the drain pump, resulting in heat exchange reduction, spraying, dispersing of water drops, drain pump malfunction, etc. In these cases, take the following actions:
Make sure that the ventilation fan for smoke-collecting hood on a cooking table has
sufficient capacity so that it draws oily steam which should not flow into the suction of the air conditioner.
Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oily steam.
2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.
NOTICE
The indoor unit installation
The dimensions of the paper model for installing are the same as those of the ceiling opening dimensions.
Ceiling board
Level gauge
Ceiling
Use the ventilation fan for smoke-collecting hood with sufficient capacity.
Cooking table
Air conditioner
Take enough distance
Unit:mm
744 Unit size
744 Unit size
658 (Hanging bolt)
6666
790 (Ceiling opening)
790 (Ceiling opening)
572(Hanging bolt)
109
109
Unit:mm
570 Unit size
570 Unit size
450 (Hanging bolt)
7575
600 (Ceiling opening)
600 (Ceiling opening)
521(Hanging bolt)
39.5
39.5
Unit:mm
840 Unit size
840 Unit size
672 (Hanging bolt)
101.5101.5
875 (Ceiling opening)
875 (Ceiling opening)
785 (Hanging bolt)
45
45
The indoor unit installation
1. Cassette type
Page 10
10 Air Conditioner
Wall
5~7 mm
Indoor Outdoor
Set screw of paper model (4 pieces)
Paper model for installation
Ceiling board
150mm
Adjust the same height
Ceiling board
Ceiling
Flat washer for M10
(accessory)
Keep the length of the bolt
from the bracket to 40mm
Open the ceiling board along the outer edge of the paper model
Flat washer for M10
(accessory)
Hanging bolt
(W3/8 or M10)
Nut (W3/8 or M10)
Nut
(W3/8 or M10) Spring washer
(M10)
Air Conditioner body
The Indoor Unit Installation
The following parts is option. Hanging Bolt - W 3/8 or M10 Nut - W 3/8 or M10 Spring Washer - M10 Plate Washer - M10
CAUTION:
Tighten the nut and bolt
to prevent unit falling.
Drill the piping hole on the wall slightly tilted to the outdoor side using a Ø 70 hole-core drill.
Page 11
The Indoor Unit Installation
Installation Manual 11
ENGLISH
2. Duct type
CASE 1
POSITION OF SUSPENSION BOLT
Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
Apply a filter Accessory at air return hole.
(Unit:mm)
Dimension
Capacity
18 kBtu/h 24 kBtu/h
30 kBtu/h 36 kBtu/h
48 kBtu/h
ABCDEF(G)HI
932 880 355 45.5 450 30 87 750 163
1232 1182 355 45.5 450 30 87 830 186
1292 1230 477 56 590 30 120 1006 294
CASE 2
I
A B
(G)
H
Drainage hole
EF
C
D
Install the unit leaning to a drainage hole side as a figure for easy water drainage.
POSITION OF CONSOLE BOLT
A place where the unit will be leveled and that can support the weight of the unit.
A place where the unit can withstand its vibration.
A place where service can be easily
med.
perfor
M10 Nut M10 SP. washer M10 washer
M10 washer M10 SP. washer M10 Nut
X 4 X 4 X 4
X 4 X 4 X 4
(Local supply)
(Local supply)
Page 12
12 Air Conditioner
The Indoor Unit Installation
CAUTION:
Tighten the nut and bolt top
revent unit falling.
Select and mark the position for fixing bolts.
Drill the hole for set anchor on the face of ceiling.
Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling.
Mount the suspension bolts to the set anchor firmly.
Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers
.
Old building New building
1 Set anchor 2 Plate washer 3 Spring washer 4 Nut
5 Suspension bolts
Local supply Set anchor Plate washer - M10 Spring washer - M10 Nut - W3/8 or M10 Suspension bolt - W3/8 or M10
Page 13
The Indoor Unit Installation
Installation Manual 13
ENGLISH
CAUTION
1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 5 mm.
Front of view
The unit must be horizontal or declined to the drain hose connected when finished
installation.
Ceiling
1~3 mm
CORRECT
Drainage hole
CAUTION FOR GRADIENT OF UNIT AND DRAIN PIPING
Always lay the drain with downward inclination (1/50 to 1/100). Prevent any upward flow or reverse flow in any part.
5mm or thicker formed thermal insulator shall always be provided for the drain pipe.
INCORRECT
Drainage hole
Lay the drain hose with a downward inclination so water will drain out.
Thermal insulator
Unit
Make sure to be closed.
Drainage hole
(Local supply)
Drainage pipe (Local supply)
CORRECT
Install the P-Trap (or U-Trap) to prevent a water leakage caused by the blocking of intake air filter.
Upward routing not allowed
INCORRECT
Applied U-Trap Dimension
A 70 mm B 2C C 2 x SP SP = External Pressure
(mmAq)
Ex) External Pressure
= 10 mmAq A 70 mm B 40 mm C 20 mm
C
A
B
U-Trap
Page 14
14 Air Conditioner
The Indoor Unit Installation
3. Convertible type
Before Installing, prepare Installation Plates
'Installation Plates' are attached at the bottom of indoor unit. Detach them by removing each 3 screws at both sides.
Detach 'Side Plate (R,L)' by removing each 2 screws on both sides.
Pull the upper right and left side of 'Inlet Grille' to the front, and it will stop at slightly tilted position.
Unhook the 'Inlet hanger' from the 'Hanger screw' on the both left and right side.
Detach the 'Inlet Grille' from the Indoor Unit.
Installation on the ceiling
Measure and mark the position for the Suspension bolts and the piping hole.
Drill the hole for anchor nut on the ceiling.
Before secure the Installation Plates, select the bent direction of the Installion Plate to the inside or the outside according to the installation circumstances.
Drill the piping hole on the wall slightly tilted to the outdoor side using a ø70 hole-core drill.
Side Plate
Install Plate
Inlet Grille
1)
2)
1076
Suspension
1236
bolt
Center-line for the
Inlet hanger
Hanger
screw
265
piping hole
265
Indoor Outdoor
WALL
5~7 mm
Page 15
The Indoor Unit Installation
Installation Manual 15
ENGLISH
Insert the nuts and washer onto the suspension bolts for locking the suspension bolts on the ceiling.
Mount the suspension bolts to the anchor-nuts firmly.
Secure the Installation plates onto the Suspension bolts (adjust level roughly.) using nuts, washers and spring washers.
Engage 2 hooks on the both left and right side of the unit to the lower slot of Installation Plates.
Adjust a level with a level gauge on the direction of left-right, back-forth by adjusting suspension bolts.
Move the hooks on the unit to the upper slot of Installation Plates.Then the unit will be declined to the bottomside so as to drain well.
1)
2)
Suspension
bolts
Spring washer
Max.
12mm
Anchor nut
Ceiling
Nut
Suspension
bolts
Nut
Washer
Lower slot
Level gauge
Washer
R
Suspension
bolt
Adjust a level
Installation plate
R
Upper slot
R
Page 16
16 Air Conditioner
The Indoor Unit Installation
1. Install declination of the indoor unit is very important for the drain of the convertible type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 7 mm.
3. If the Installation Plates are fixed to horizontal line, the indoor unit after installing will be declined to the bottomside.
Front of view
The unit must be horizontal or declined to the drain hose connected when finished installation.
The unit must be declined to the bottomside of the unit when finished installation.
Side of view
CAUTION
Ceiling
Drain hose
Ceiling
Ceiling
Page 17
The Indoor Unit Installation
Installation Manual 17
ENGLISH
Secure the unit to the Installation Plates with four M8 bolts and washers.
Hook up the Inlet Grille Hook to the cabinet.
Hang the Inlet Hanger to the screw.
Fit the projection hooks of the side plates to the
'Side Panel' and the 'Front Panel' by lifting it.
Fasten the screws.
R
Before working, refer to "Connecting pipe to
Indoor Unit" on page 21.
Inlet hanger
R
Hook
Cabinet Bottom
R
1
R
2
Page 18
18 Air Conditioner
The Indoor Unit Installation
Installation on the Wall
Select and mark the position for fixing bolts and piping hole. Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose.
Drill the hole for anchor nut on the wall.
Drill the piping hole on the wall slightly tilted to the outdoor side using a ø70 hole-core drill.
Secure the 'Install Plate' onto the wall with four
anchor bolts, washers and spring washers.
Before secure the Install Plates, select the bent direction of the 'Install Plate' to the inside or outside according to the installation circumstances.
more than
1076
260
265
Wall
Indoor Outdoor
5~7 mm
Spring washer
Nut
Washer
Anchor nut
Less than
12 mm
Wall
1236
Page 19
The Indoor Unit Installation
Installation Manual 19
ENGLISH
Install the Indoor unit onto Installation Plate.
Insert 2 hooks on the both left and right side of the unit to the inner slot (wall side) of the Installation Plate.
Secure the unit to the Installation Plate with four M8 bolts and washers.
Hook up the Inlet Grille Hook to the cabinet.
Hang the Inlet Hanger to the screw.
Fit the projection hooks of the side plates to the
'Side Panel' and the 'Front Panel' by lifting it.
Fasten the screws.
R
2
1
Before working, refer to "Connecting pipe
and cable to Indoor Unit" on page 21.
Inner slot
Page 20
20 Air Conditioner
The Indoor Unit Installation
Installation on the floor
Installation of Mount Bracket.
Select and mark the position for Mount Brackets and the piping hole.
Drill the hole for the anchor nut on the wall.
Drill the piping hole using a ø70 hole-core drill.
Secure the Mount Brackets on the wall with four
M4 screws.
Install the indoor unit onto the Mount Brackets.
Engage the slot at the back of the unit with Mount Bracket.
Drill the piping hole with 70mm dia, hole core drill.
Piping hole should be slightly slant to the outdoor side.
After Installing, reassemble detached parts.
Hang the 'Inlet Grille' and hook the 'Inlet Hanger' to the Hanger Screw.
Assemble the 'Side Plates(R,L)' with 2 screws on both left and right side.
From the left wall more than 760 mm
From the right wall more than 840 mm
Slot
Floor mount
bracket
Wall
Indoor Outdoor
448 mm
5~7 mm
Slot
Wall
Floor mount bracket
Install plate
Piping hole
Page 21
The Indoor Unit Installation
Installation Manual 21
ENGLISH
Installation on the ceiling (Connecting the pipes to the indoor unit)
The pipe can be connected to right side, bottom or back of the unit.
1. For the Right Side Piping
After bending an end of the connecting tube, align the center of the pipings and sufficiently tighten the flare nut with fingers.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
Connect the Drain Hose insulated to the drain outlet. Drain hose should be go through under the Hose Bracket as shown in figure .
Hang the drain hose on the hose hanger and fix it to the hole of the hose bracket with a screw.
2. For the Bottom Side Piping
Remove the knock-out on the bottomside of Inlet Grille
Align the center of the pipings and sufficiently tighten the flare nut with fingers.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
Connect the Drain Hose insulated to the drain outlet.
Hang the drain hose on the hose hanger and fix
it to the hole of cabinet bottom with a screw.
Connecting the Drain Hose
The drain hose can be connected to not only the right side but also left side of the unit.
If the drain hose is connected to the left side, it should go through the cabinet bottom.
Hang the drain hose on the hose hanger and fix it to the hole of cabinet bottom with a screw.
R
Drain Hose
Hose Hanger
Piping
Hose
Bracket
1
3
4
5
2
Hose Hanger
Hose Hanger
R
R
BOTTOM
Drain Hose
Page 22
22 Air Conditioner
The Indoor Unit Installation
Installation on the wall or floor (Connecting the pipes to the indoor unit)
1. For the Right Rear Piping
Remove the knock-out at the back side of the cabinet.
After bending an end of the connecting tube, align the center of the pipings and sufficiently tighten the flare nut with fingers.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
Connect the Drain Hose insulated to the drain outlet.
Tape the Drain Hose to the pipings to avoid coming off the drain-outlet.
2. For the Right Side Piping
After bending an end of the connecting tube, align the center of the pipings and sufficiently tighten the flare nut with fingers.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
Connect the Drain Hose insulated to the drain outlet.
Tape the Drain Hose to the pipings to avoid coming off the drain-outlet.
3. For the Right Bottom Piping
Align the center of the pipings and sufficiently tighten the flare nut with fingers.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
Connect the Drain Hose insulated to the drain outlet.
Connecting the Drain Hose
The drain hose can be connected to not only right side but also left side of the unit.
Piping
Taping
Drain Hose
Piping
Taping
Drain Hose
Piping
Taping
Drain Hose Connecting
Cable
Drain Hose
REAR
BOTTOM
Page 23
Installation Manual 23
ENGLISH
Remote Controller Preparation (Convertible type)
Remote control
box body
Cord clamp (accessory)
Lever carefully
the box open
using a screw
driver, etc.
Front case
The lower part
Face of wall
Under plate
Screw (accessory)
Remote Controller Installation
HO
W TO MOUNT ONTO A WALL
HOW TO INSERT BATTERIES
1. Remove the battery cover from the remote controller.
Slide the cover according to the arrow direction.
2. Insert the two batteries.
Be sure that the (+) and (-) directions are
correct.
Be sure that both batteries are new.
3. Re-attach the cover.
Slide it back into position.
Fix the under plate on the wall
Separate the under plate from Remote control box.
Fix the cord clamps on the wall by ø 3 tapping screws (accessory).
Fix the remote control cord.
DISASSEMBLING
ELECTRICAL
WIRING
Wire and make sure that terminal
numbers are matched on unit side and
remote controller side.
The maximum length of the cord is 100m.
If the length of the cord exceeds 50m,
use a wire size greater than 0.5mm
2
.
(Main board)
CN REMO
Do not use rechargeable batteries, such batteries differ from standard dry cells in shape, dimensions, and performance.
Romove the batteries from the remote controller if the air conditioner is not going to be used for some long time.
Wired Remote Controller Installation
Page 24
24 Air Conditioner
Wiring Connection
Open the control box cover and connect the Remote controller cord and Indoor power wires.
[Air inlet side view]
Control box cover
Indoor
power cord
Remote
controller
cord
Control box cover screw
Terminal Block (Outdoor Unit)
Terminal Block (Indoor Unit)
The power cord connected to the outdoor unit should be complied with the following specifications (Rubber insulation, type H05RN-F approved by HAR or SAA).
If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer of its service agent.
The connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (Rubber insulation, type H05RN-F approved by HAR or SAA).
CAUTION
20mm
G
N
/Y
L
NORMAL CROSS-SECTIONAL AREA 1.25mm
2
NORMAL CROSS-SECTIONAL AREA 5.5mm
2
20mm
G
N
/Y
L
WARNING:
Make sure that the screws of the terminal are free from looseness.
Wiring Connection
Page 25
Installation Manual 25
ENGLISH
Electrical Wiring
Wiring Connection
1. All wiring must comply with LOCAL REGULATIONS.
2. Select a power source that is capable of supplying the current required by the air conditioner.
3. Feed the power source to the unit via a distribution switch board designed for this purpose.
4.The ter minal screws inside the control box may be loose due to vibration during transport. Check the screws for loose connection. (Running the air conditioner with loose connection can overload and damage electrical components.)
5. Always ground the air conditioner with a grounding wire and connector to meet the LOCAL REGULATION.
CAUTION:
The circuit diagram is not subject to change without notice.
Be sure to connect wires according to the wiring diagram.
Connect the wires firmly, so that not to be pulled out easily.
Connect the wires according to color codes by referring the wiring diagram.
Air
Conditioner
Main power source
Circuit Breaker Use a 50A circuit breaker or time delay fuse.
1. Open the control board cover from the outdoor unit by removing the screws.
2. Connect wires to the terminals on the control board individually and secure the cables onto the control board with clamp.(Pass through the designated position)(See Fig.)
3. Secure the control board cover to the original position with the screws.
CAUTION: Perform grounding
This product should be
grounded.
Defective grounding could
cause an electric shock.
Connecting the cables to the outdoor unit
Connecting Cable
Power supply Cord
Page 26
26 Air Conditioner
Connecting Pipes to the Indoor Unit
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.
1. Cut the pipes and the cable.
Use the accessory piping kit or the pipes purchased locally.
Measure the distance between the indoor and the outdoor unit.
Cut the pipes a little longer than measured distance.
Cut the cable 1.5m longer than the pipe length.
2. Burrs removal
Completely remove all burrs from the cut cross section of pipe/tube.
Put the end of the copper tube/pipe to downward direction as you remove burrs in order to avoid to let burrs drop in the tubing.
3. Putting nut on
Remove flare nuts attached to indoor and outdoor units, than put them on pipe/tube having completed burr removal. (Not possible to put them on after flaring work)
4. Flaring work
Carry out flaring work using dedicated flaring tool for R-410A as shown below.
Firmly hold copper tube in a bar(or die) as indicated dimension in the table above.
5. Check
Compare the flared work with figure below.
If flare is noted to be defective, cut off the
flared section and do flaring work again.
Copper
tube
90°
Slanted Uneven Rough
Pipe
Reamer
Point down
Flare nut
Copper tube
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shining without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Outside diameter "A"
mm inch mm
Ø6.35 1/4 1.1~1.3 Ø9.52 3/8 1.5~1.7
Ø12.7 1/2 1.6~1.8 Ø15.88 5/8 1.6~1.8 Ø19.05 3/4 1.9~2.1
Connecting Pipes to the Indoor Unit
Preparation of Piping
Page 27
Installation Manual 27
ENGLISH
Connecting Pipes to the Indoor Unit
1. Form the piping according to its routing. Avoid bending and bending back the same piping point more than three times. (This will result in hardening the pipe.)
2. After deforming the piping, align centers of the union fitting of the indoor unit and the piping, and tighten them firmly with wrenches.
3. Connect pipe to the service valve or ball valve which is located below the outdoor unit.
4. After completing the piping connection, be sure to check if there is gas leakage in indoor and outdoor connection.
After completing the piping connection, execute vacuum drying for the connecting piping and the indoor unit. The vacuum drying must be carried out using the service por ts of both the liquid and gas side valves.
CAUTION:
Use two wrenches and
tighten with regular torque.
Union
Piping Connection
Vacuum drying
Pipe size Torque
mm inch kgf·m
Ø6.35 1/4 1.8~2.5 Ø9.52 3/8 3.4~4.2
Ø12.7 1/2 5.5~6.6 Ø15.88 5/8 6.3~8.2 Ø19.05 3/4 9.9~12.1
Page 28
28 Air Conditioner
Installation to Decorative Panel
1.Temporarily fix two decorative panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by amount 10mm in length.) The fixing screws (hexagon M5 screw) are included the decorative panel box.
2. Remove the air inlet grille from the decorative panel.(Remove the hook for the air inlet grille cord.)
3. Hook the decorative panel key hole ( ) on the screws fixed in step above, and slide the panel so that the screws reach the key hole edge.
4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws)
5. Connect the louver motor connector and display connector.
6. After tightening these screws, install the air inlet grille (including the air filter).
Decorative panel fixing screws (hexagon M5 screws) Temporally fitting at 2 places (Tightening about 10 mm)
Install the panel after making sure that the piping side of the unit body matches the piping indication of the decorative panel
Control box cover
Piping side
Inlet GrilleInlet GrilleInlet Grille
Inlet GrilleInlet Grille
Louver motor
Decorative panel fixing screws (Hexagon M5 screw)
The arrow ( ) should point to the side where the pipes are.
Air conditioner unit
Decorative panel
Key holes
Display
Lead wire for louver motor and display
The decorative panel has its installation direction.
Before installing the decorative panel, always remove the paper template.
Installation to Decorative Panel
Page 29
Installation Manual 29
ENGLISH
Indoor Unit Drain Piping
CAUTION:
Install certainly the decorative panel.
Cool air leakage causes sweating.
Water drops fall.
Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow.
During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit.
The outside diameter of the drain connection on the indoor unit is 32 mm.
Be sure to execute heat insulation on the drain piping.
Install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the unit.
The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:
Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end.
Feed water to the flexible drain hose and check the piping for leakage.
Be sure to check the drain pump for normal operating and noise when electrical wiring is complete.
When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.
Air conditioner unit
Ceiling
board
Decorative panel
Decorative panel
Fit the insulator (this part) and be careful for cool air leakage
Good example
Air
Cool air leakage
(no good)
Bad example
Ceiling
board
Air conditioner unit
Maintenance drain port
Upward routing not allowed
Pipe clamp
Indoor unit
700 or less
1 -1.5 m
300 mm or less
Clamp metal(attached) Drain hose(attached)
Drain raising pipe
Feed water
Drain Pump
Drain pan
Flexible drain hose (accessory)
Main drain pipe
Glue the joint
Drain port
Drain hose connection Use the clip (accessory)
Piping material: Polyvinyl chloride pipe VP-25 and pipe fittings
Heat insulation material: Polyethylene foam with thickness more than 8 mm.
Drain test
Indoor Unit Drain Piping
Page 30
30 Air Conditioner
Indoor Unit Drain Piping
1. Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 120°C).
2. Precautions in high humidity circumstance: This air conditioner has been tested according to the "KS Standard Conditions with Mist" and confirmed that there is not any default.However, if it is operated for a long time in high humid atmosphere (dew point temperature: more than 23°C), water drops are liable to fall.In this case, add heat insulation material according to the following procedure:
Heat insulation material to be prepared...
Adiabatic glass wool with thickness 10 to 20 mm.
Stick glass wool on all air conditioners that
are located in ceiling atmosphere.
Indoor unit
Thermal insulator (accessory)
Fastening band (accessory)
Refrigerant piping
Heat insulation
Forming the piping
Form the piping by wrapping the connecting portion of the indoor unit with insulation material and secure it with two kinds of vinyl tape.
If you want to connect an additional drain
hose, the end of the drain outlet should be routed above the ground.Secure the drain hose appropriately.
In cases where the outdoor unit is installed below the indoor unit perform the following.
1.Tape the piping, drain hose and connecting cable from down to up.
2. Secure the tapped piping along the exterior wall using saddle or equivalent.
Gas side piping
Main cable
Tube PE
Foam
Connecting Cable (For heater)
Connecting Cable
Trap is required to prevent the electrical parts from entering the water.
Page 31
Indoor Unit Drain Piping
Installation Manual 31
ENGLISH
In cases where the Outdoor unit is installed above the Indoor unit perform the following.
1.Tape the piping and connecting cable from down to up.
2. Secure the taped piping along the exterior wall. Form a trap to prevent water entering the room.
3. Fix the piping onto the wall by saddle or equivalent.
Trap
Trap
Seal a small opening around the piping with gum type sealer.
Page 32
32 Air Conditioner
Test running
1. PRECAUTIONS IN TEST RUNNING
The initial power supply must provide at least 90% of the rated voltage. Otherwise, the air conditioner should not be operated.
CAUTION For test run, carry out the cooling operation firstly even during heating
season. If heating operation is carried out firstly, it leads to the trouble of compressor.Then attention must be paid.
Carry out the test run more than 5 minutes without fail. (Test run will be cancelled 18 minutes later automatically)
The test run is started by pressing the room temperature checking button and down timer button for 3 seconds at the same time.
To cancel the test run, press any button.
CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETE
After completing work, be sure to measure and record trial run properties, and store measured data, etc.
Measuring items are room temperature, outside temperature, suction temperature, blow out temperature, wind velocity, wind volume, voltage, current, presence of abnormal vibration and noise, operating pressure, piping temperature, compressive pressure.
As to the structure and appearance, check following items.
2. Connection of power supply
1. Connect the power supply cord to the independent power supply.
Circuit breaker is required.
2. Operate the unit for fifteen minutes or more.
3. Evaluation of the performance
1. Measure the temperature of the intake and discharge air.
2. Ensure the difference between the intake temperature and the discharge one is more than 8°C (Cooling) or reversely (Heating).
Is the circulation of air adequate? Is the draining smooth? Is the heat insulation complete
(refrigerant and drain piping)?
Is there any leakage of refrigerant?
Is the remote controller switch operated? Is there any faulty wiring? Are not terminal screws loosened?
M4......118 N.cm{12 kgf.cm} M5......196 N.cm{20 kgf.cm}
M6......245 N.cm{25 kgf.cm} M8......588 N.cm{60 kgf.cm}
Test running
Thermometer
Page 33
Installation Manual 33
ENGLISH
CAUTION: After the confirmation of the above conditions, prepare the wiring
as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn­out of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device.
Proper starting power is not given to the compressor.
10) Use only 1 remote-controller contained in the Cassette type indoor unit, when you combine to use both cassette type indoor unit and different kind of indoor unit. After setting the ESP value in the Duct Type Indoor Unit, the main power turns off and then remove the remote controller.
HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning, temperature control, etc.).
Test running
Page 34
34 Air Conditioner
1.Two Thermistor System
(1) Open the rear cover of the wired remote-controller to set the mode. (2) Select one of three selectable modes as follows.
Position 1:The room temperature is controlled by the thermistor of the main body.
Position 2:The room themperature is controlled by the thermistor of the wired remote-
controller, control the temperature according to the position of wired remote­controller.
Position 3:The room temperature is controlled by lower temperature between the temperature of main body and of remote-controller sensor.
(3) Move the slide switch to set position.
(4) Close the rear cover and check if it works normally.
CAUTIO
N
:
Select the position after counselling with a customer.
In case of cooling mode, room temperature is controlled by the main body sensor.
To control the room temperature by a wired remote controller, install controller(room
temp. sensor) to sense the temperature more accurately.
Manufactured in the position 3.
Optional Operation
Optional Operation
TH
R14H
SW TH
REMO MAIN 2TH
OP7 R18H
R17H
OP6
LO
STAND
SW HIGH
HI
R03S
C070
R04S
R02S
R01S
OP3
OP2 OP1
R19H
R11H
R13H R12H
OP5R16H OP4
R15H
CO1H
REMO
Room T emp . sensor
2TH
MAIN
Position 2 Position 1 Position 3
Slide switch for ceiling height
Slide switch for 2 Thermistor
Page 35
Installation Manual 35
ENGLISH
2. Adjusting air volume to the height of ceiling (Cassette type)
You can choose the RPM(or air volume) of indoor motor according to the height of ceiling to supply the comfortable atmosphere to consumers.
Procedure
1. Choose the selectable position in the table after measuring the height of ceiling.
2. In the case of changing the height as "high" or "low", open the rear cover of the wired remote­controller.
3. Move the slide switch to the set position.
4. Close the rear cover and check if it works normally.
Optional Operation
Ceiling height Mode of slide switch Change of air volume Remark
more than 3.3 m High Ceiling Increasing
2.7~3.3 m Standard -
Manufactured in
less than 2.7 m Low Ceiling Decreasing
standard mode
Slide switch for 2 Thermistor
R13H R12H
TH
OP5R16H OP4
CO1H
Low ceiling
Standard (Default)
High Ceiling
STAND
Slide switch for ceiling height
Lo
Hi
OP3
R14H
SW TH
REMO MAIN 2TH
STAND
SW HIGH
OP2 OP1
R17H
LO HI
OP7 R18H
R15H
R19H
R11H
OP6
C070
R03S
R04S
R01S
R02S
Page 36
36 Air Conditioner
Optional Operation
3. E.S.P.(External Static Pressure) Setting (Duct type)
(1) Open the rear cover of the wired remote-controller to set the mode. (2) Select one of three selectable modes as follows.
Without Zone System
1. Position V-H, F-H:
This position sets the maximum E.S.P as a default set.
2. Position V-L:
This position sets the minimum E.S.P as a default set.
With Zone System
1. Position V-H:
Maximum E.S.P setting & Fan speed is varied according to the state of dampers bymicom.
2. Position F-H:
Maximum E.S.P setting & Fan speed doesn't vary according to the opening & Closing of dampers.
3. Position V-L:
Minimum E.S.P setting & Fan speed is varied according to the state of dampers bymicom.
* Maximum : 24K-6mmAq
Minimum : 0mmAq
(3) Move the slide switch to set position.
(4) Close the rear cover and check if it works normally.
TH
R14H
SW TH
REMO MAIN 2TH
OP7 R18H
R17H
OP6
LO
STAND
SW HIGH
HI
R03S
C070
R04S
R02S
R01S
OP3
OP2 OP1
R19H
R11H
R13H R12H
OP5R16H OP4
R15H
CO1H
V-L
V-H
F-H
Slide switch for ceiling height
Select the position after checking duct work and E.S.P of the unit.
Maunfactured in the position F-H.
CAUTION:
Page 37
Installation Manual 37
ENGLISH
Optional Operation
4. How to Set E.S.P?
Preheat
ZONE
Operation unit Program set
Room Temp
MED LO
AUTO JET
Heater Defrost Filter
Humidify Out door
Timer
On Set no. Time
Off
01 03 05 07 09 11 13 15 17 19 21 23
1234
OPERATION
FAN SPEED
SUB FUNCTION
SET TEMP
HI
AUTO SWING
Time
Preheat
ZONE
Operation unit Program set
Room Temp
MED LO
AUTO JET
Heater Defrost Filter
Humidify Out door
Timer
On Set no. Time
Off
01 03 05 07 09 11 13 15 17 19 21 23
1234
OPERATION
FAN SPEED
SUB FUNCTION
SET TEMP
HI
AUTO SWING
Time
Time
SUB FUNCTION
SET TEMP
OPERATIONAUTO SWING
Preheat
ZONE
Operation unit Program set
Room Temp
MED LO
AUTO JET
Heater Defrost Filter
Humidify Out door
Timer
On Set no. Time
Off
01 03 05 07 09 11 13 15 17 19 21 23
1234
FAN SPEED
HI
Time
SUB FUNCTION
SET TEMP
OPERATIONAUTO SWING
Preheat
ZONE
Operation unit Program set
Room Temp
MED LO
AUTO JET
Heater Defrost Filter
Humidify Out door
Timer
On Set no. Time
Off
01 03 05 07 09 11 13 15 17 19 21 23
134
FAN SPEED
HI
2
Timer
1
2
3
5
4
Timer
Procedure of RPM change:
Ex) External Static pressure is 6mmAq for 36 kBtu/h.
To protect the unit, compressor is designed to be off during E.S.P. setting.
Push the "On/Off" button. The unit will start.
Push the "Timer" and "Wind" button simultaneously for more then 3 seconds.
Push the "Up" of "Down" button for E.S.P adjustment. And, adjust the number which you want.(In this example, the number is "220". Refer to the table 1 on the next page.)
Shift the fan speed mode by pressing the fan speed button. And then, Adjust numbers of next steps by repeating the stage 3. (In this example, the numbers are "235" and "243" respectly)
Push the "Timer" and "Wind" button simultaneously for more than 3 seconds. Then, Wind Data is memorized by the EEPROM of the main PCB.
Note: The range of selection is from 1~254.Since, the display is two Digit only.
If the range selection is above 100 then the third digit will appear in the screen as shown.
Page 38
38 Air Conditioner
Optional Operation
[Table. 1]
Note: 1. Be sure to set the value refering table 1. Unexpected set value will cause mal-
function.
2.Table 1 is based at 230V. According to the fluctuation of voltage, air flow rate varies.
Static Pressure(mmAq)
CMM(CFM)
Model Name
18 kBtu/h Med 14.5(512) 245 238 235 230
24 kBtu/h Med 16.5(583) 235 230 220 200
30 kBtu/h Med 23(812) 173 173 175 175 170
36 kBtu/h Med 29(1024) 240 238 237 235 230
48 kBtu/h Med 35(1235) 250 245 240 235 230 220 215 210 200
Step
High 16.5(583) 235 230 225 215 180
Low 13(459) 254 252 248 245
High 18(636) 220 205 190 50
Low 14(494) 250 240 235 230
High 26.5(936) 153 150 150 148 130
Low 20(706) 190 190 190 190 190
High 32(1130) 230 230 225 220 150
Low 26.5(936) 245 245 243 243 240 240
High 40(1412) 230 225 220 215 205 200 190 180
Low 30(1059) 255 255 255 250 245 240 235 230
Setting Value
215 240
1 100 210
1 155 190
1 220
150 2 4 6 8 10 12 14
160
225
Page 39
Installation Manual 39
ENGLISH
Optional Operation
TEST_SW1
LED01T
1234
ZONE SW1
Main PCB
Fig.a Outdoor PCB diagram
C
B
JIG_SW
A
E
D
3. Auto Addressing Method Addressing work assigns address to each indoor unit.When firstly installing product or replacing the indoor unit PCB.Auto Addressing work should be done for simultaneous operation.
Work procedure
1) Set JIG_SW and ZONE SW1 correctly.
2) Turn on main power.
3) Press the TEST_SW1 for about 3 seconds within 3minutes After main power on.(
)
4) After step 3), the LED01T(green LED) rapidly flickers.When Addressing work is done, green LED is off, else LED stops flickering and lights continuously.
5) If you fail to perform the Addressing work, repeat step 2),3).
5. Outdoor Unit PCB Setting Procedure
1. JIG_SW Setting The position of the JIG_SW should be on the right side. If not then please slide the position to the right.(
)
2. ZONE SW1 Setting Set the ZONE SW1 as below Table.a (
)
S/W1 is not used.1 means S/W up.
0 means S/W down.
SW
, are unnecessary for this unit.
ZONE SW1
Indoor Unit No.
12
34
10
00
11
00
1
1
10
2(Duo)
1(Single)
3(Trio)
4(Quartet)
12
34
12
34
1
1
11
12
34
Table.a ZONE SW1 Setting
Page 40
40 Air Conditioner
Installation guide at the seaside
1.
Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunc­tion or inefficient performance.
3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it needs additional anticorrosion treatment on the heat exchanger.
1.
If you cant meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment.
2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water
Selecting the location(Outdoor Unit)
1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the outdoor unit on the opposite side of the sea wind direction.
2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
3) Select a well-drained place.
It should be strong enough like concrete to prevent the sea wind from the sea.
The height and width should be more than 150% of the outdoor unit.
It should be keep more than 70 cm of space between outdoor unit and the windbreak for easy air flow.
Sea wind Sea wind
Sea wind
Windbreak
CAUTION
Installation guide at the seaside
Page 41
P/No.: 3828A20601B
Loading...