LG ATNH12GRLE2 INSTALLATION MANUAL

P/NO : MFL67655408
www.lg.com
INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
TYPE : 4-WAY CEILING CASSETTE
ESPAÑOL
PORTUGUESE
ENGLISH
2
ENGLISH
• Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air condition­er is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:
TIPS FOR SAVING ENERGY
TIPS FOR SAVING ENERGY
3
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product
WARNING
It can result in serious injury or death when the directions are ignored
CAUTION
It can result in minor injury or product damage when the directions are ignored
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• Installation MUST conform with local building codes or, in the absence of local codes, with the Nation Electrical Code NFPA 70/ANSI C1-1003 or current edition and Canadian Electrical Code Part1 CSA C.22.1.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment mal­function, property damage, personal injury and/or death.
Installation
• Always perform grounding. - Otherwise, it may cause electrical shock.
• Don’t use a power cord, a plug or a loose socket which is damaged. - Otherwise, it may cause a fire or electrical shock.
• For installation of the product, always contact the service center or a professional installation agency. - Otherwise, it may cause a fire, electrical shock, explosion or injury.
• Securely attach the electrical part cover to the indoor unit and the service panel to the outdoor unit.
- If the electrical part cover of the indoor unit and the service panel of the outdoor unit are not attached securely, it could result in a fire or electric shock due to dust, water, etc.
• Always install an air leakage breaker and a dedicated switching board. - No installation may cause a fire and electrical shock.
• Do not keep or use flammable gases or combustibles near the air conditioner. - Otherwise, it may cause a fire or the failure of product.
• Ensure that an installation frame of the outdoor unit is not damaged due to use for a long time.
- It may cause injury or an accident.
• Do not disassemble or repair the product randomly. - It will cause a fire or electrical shock.
• Do not install the product at a place that there is concern of falling down. - Otherwise, it may result in personal injury.
• Use caution when unpacking and installing. - Sharp edges may cause injury.
Operation
• Do not share the outlet with other appliances. - It will cause an electric shock or a fire due to heat generation.
• Do not use the damaged power cord. - Otherwise, it may cause a fire or electrical shock.
!
!
!
SAFETY PRECAUTIONS
4
ENGLISH
• Do not modify or extend the power cord randomly. - Otherwise, it may cause a fire or electrical shock.
• Take care so that the power cord may not be pulled during operation. - Otherwise, it may cause a fire or electrical shock.
• Unplug the unit if strange sounds, smell, or smoke comes from it. - Otherwise, it may cause electri­cal shock or a fire.
• Keep the flames away. - Otherwise, it may cause a fire.
• Take the power plug out if necessary, holding the head of the plug and do not touch it with wet hands. - Otherwise, it may cause a fire or electrical shock.
• Do not use the power cord near the heating tools. - Otherwise, it may cause a fire and electrical shock.
• Do not open the suction inlet of the indoor/outdoor unit during operation. - Otherwise, it may electri­cal shock and failure.
• Do not allow water to run into electrical parts. - Otherwise, it may cause the failure of machine or electrical shock.
• Hold the plug by the head when taking it out. - It may cause electric shock and damage.
• Never touch the metal parts of the unit when removing the filter. - They are sharp and may cause injury.
• Do not step on the indoor/outdoor unit and do not put anything on it. - It may cause an injury through dropping of the unit or falling down.
• Do not place a heavy object on the power cord. - Otherwise, it may cause a fire or electrical shock.
• When the product is submerged into water, always contact the service center. - Otherwise, it may cause a fire or electrical shock.
• Take care so that children may not step on the outdoor unit. - Otherwise, children may be seriously injured due to falling down.
CAUTION
Installation
• Install the drain hose to ensure that drain can be securely done. - Otherwise, it may cause water leakage.
• Install the product so that the noise or hot wind from the outdoor unit may not cause any damage to the neighbors. - Otherwise, it may cause dispute with the neighbors.
• Always inspect gas leakage after the installation and repair of product. - Otherwise, it may cause the failure of product.
• Keep level parallel in installing the product. - Otherwise, it may cause vibration or water leakage.
Operation
• Avoid excessive cooling and perform ventilation sometimes. - Otherwise, it may do harm to your health.
• Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent. - The appearance of the air conditioner may deteriorate, change color, or develop surface flaws.
• Do not use an appliance for special purposes such as preserving animals vegetables, precision machine, or art articles. - Otherwise, it may damage your properties.
• Do not place obstacles around the flow inlet or outlet. - Otherwise, it may cause the failure of appli­ance or an accident.
!
SAFETY PRECAUTIONS
5
ENGLISH
6 INSTALLATION PLACES 7 THE INDOOR UNIT
INSTALLATION
8 Indoor Unit Drain Piping 9 Wiring Connection
11 REMOTE CONTROLLER
INSTALLATION
13 Wired remote controller installation
14 INSTALLATION OF DEC-
ORATIVE PANEL(ACCES­SORY)
16 TEST RUNNING
17 OPTIONAL OPERATION
17 Installer Setting -Test Run Mode 18 Installer Setting - Setting Address of
Central Control
19 Installer Setting -Thermistor 20 Installer Setting -Ceiling Height
Selection
21 Installer Setting-Group Setting 22 Installer Setting-Dry Contact Mode
Setting
23 Installer Setting-Celsius / Fahrenheit
Switching
24 Installer Setting -Optional Function
Setting
25 HOW TO SET E.S.P?
TABLE OF CONTENTS
TABLE OF CONTENTS
6
ENGLISH
INSTALLATION PLACES
INSTALLATION PLACES
- There should not be any heat source or steam near the unit.
- There should not be any obstacles to prevent the air circulation.
- A place where air circulation in the room will be good.
- A place where drainage can be easily obtained.
- A place where noise prevention is taken into consideration.
- Do not install the unit near the door way.
- Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
- The indoor unit must keep the maintenance space.
* Please use an annexed sheet or the corru-
gated cardboard on the bottom of packing as installation sheet.
* When using the bottom sheet, please use it
after separating the installation sheet from packing of the product floor by using a knife etc as a picture below.
Annexed sheet
Or
Packing corrugated
cardboard on the
bottom
Ceiling
Ceiling Board
500 or more
1000
or more
Ceiling Board
300 or more
500 or more
Above 250
1000 or less
Floor
Unit : mm
300 or less
7
ENGLISH
THE INDOOR UNIT INSTALLATION
Level gauge
Ceiling
Ceiling board
Unit:mm
Unit:mm
875(Ceiling opening)
787(Hanging bolt)
684
(Hanging bolt)
671
875(Ceiling opening)
840 Unit size
840 Unit size
TQ/TR Series
TP/TN/TM Series
585~660
517
461
517
585~660
523
570
570
319
CAUTION
• This air-conditioner uses a drain pump.
• Install the unit horizontally using a level gauge.
• During the installation, care should be taken not to damage electric wires.
!
- Select and mark the position for fixing bolts and piping hole.
- Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose.
- Drill the hole for anchor bolt on the wall.
NOTE
!
Avoid the following installation location.
1 Such places as restaurants and kitchen
where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions;
- Make sure that ventilation fan is enough to cover all noxious gases from this place.
- Ensure enough distance from the cook­ing room to install the air conditioner in such a place where it may not suck oily steam.
2 Avoid installng air conditioner in such
places where cooking oil or iron powder is generated.
3 Avoid places where inflammable gas is
generated.
4 Avoid place where noxious gas is generat-
ed.
5 Avoid places near high frequency genera-
tors.
THE INDOOR UNIT INSTALLATION
Air conditioner
Take enough distance
Cooking table
Use the ventilation fan for smoke-collecting hood with sufficient capacity.
8
ENGLISH
THE INDOOR UNIT INSTALLATION
The following parts is option.
Hanging Bolt - W 3/8 or M10Nut - W 3/8 or M10Spring Washer - M10Plate Washer - M10
Drill the piping hole on the wall slightly tilted to the outdoor side using a Ø 70 hole-core drill.
CAUTION
Tighten the nut and bolt to prevent unit falling.
!
Maintenance drain port
Upward routing not allowed
Pipe clamp
Indoor unit
Indoor Unit Drain Piping
- Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow.
- During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit.
- The outside diameter of the drain connection on the indoor unit is 32mm.
- Be sure to execute heat insulation on the drain piping.
- Install the drain raising pipes at a right angle to the indoor unit and no more than 300mm from the unit.
Piping material: Polyvinyl chloride pipe VP­25 and pipe fittings
Ceiling
Hanging bolt
(W3/8 or M10)
(W3/8 or M10)
Nut
Spring washer
(M10)
Wall
Indoor
Keep the length of the bolt from the bracket to 40mm
Flat washer for M10
(accessory)
Flat washer for M10
(accessory) Nut (W3/8 or M10)
Outdoor
Ceiling board
Adjust the same height
Air Conditioner body
Keep the length of 15~18mm between the air conditioner bottom surface and the ceiling surface
Paper model for installation
Set screw of paper model (4 pieces)
Open the ceiling board along the outer edge of the paper model
150mm
Ceiling board
5~7mm
9
ENGLISH
THE INDOOR UNIT INSTALLATION
700 or less
1 -1.5m
Clamp metal(attached) Drain hose(attached)
Drain raising pipe
300mm or less300mm or less300mm or less
Heat insulation material: Polyethylene foam with thickness more than 8 mm.
Drain test The air conditioner uses a drain pump to drain
water. Use the following procedure to test the drain
pump operation:
- Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end.
- Feed water to the flexible drain hose and check the piping for leakage.
- Be sure to check the drain pump for normal operating and noise when electrical wiring is complete.
- When the test is complete, connect the flexi­ble drain hose to the drain port on the indoor unit.
high humid atmosphere (dew point tempera­ture: more than 23°C), water drops are liable to fall. In this case, add heat insulation mate­rial according to the following procedure:
- Heat insulation material to be prepared... Adiabatic EPDM or NBR with thickness 10 to 20mm.
- Stick glass wool on all air conditioners that are located in ceiling atmosphere.
HEAT INSULATION
- Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 120°C).
- Precautions in high humidity circumstance: This air conditioner has been tested accord­ing to the "KS Standard Conditions with Mist" and confirmed that there is not any default. However, if it is operated for a long time in
Wiring Connection
- Open the control box cover and connect the Remote controller cord and Indoor power wires.
- Remove the control box cover for electrical connection between the indoor and outdoor unit. (Remove screws ¿)
- Use the cord clamper to fix the cord.
Remote controller cord
1
1
Connection cord between the indoor unit and the outdoor unit
Control box cover (On which the Electric Wiring Connection is put)
Fastening band (accessory)
Feed water
Drain Pump
Flexible drain hose (accessory)
Main drain pipe
Drain port
Glue the joint
Drain hose connection Use the clip (accessory)
Indoor unit
Refrigerant piping
Thermal insulator (accessory)
Drain pan