LG ATNH12GRLE2 INSTALLATION MANUAL

<![if ! IE]>

<![endif]>PORTUGUESE ESPAÑOL ENGLISH

INSTALLATION MANUAL

AIR CONDITIONER

Please read this installation manual completely before installing the product.

Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Please retain this installation manual for future reference after reading it thoroughly.

TYPE : 4-WAY CEILING CASSETTE

www.lg.com

P/NO : MFL67655408

<![if ! IE]>

<![endif]>ENGLISH

2

TIPS FOR SAVING ENERGY

 

 

TIPS FOR SAVING ENERGY

Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:

Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.

Block sunlight with blinds or curtains while you are operating the air conditioner.

Keep doors or windows closed tightly while you are operating the air conditioner.

Adjust the direction of the air flow vertically or horizontally to circulate indoor air.

Speed up the fan to cool or warm indoor air quickly, in a short period of time.

Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.

Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehumidifying functions.

For your records

Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:

Model number :

Serial number :

You can find them on a label on the side of each unit.

Dealer’s name :

Date of purchase :

SAFETY PRECAUTIONS 3

IMPORTANT SAFETY INSTRUCTIONS

READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.

Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product

! WARNING

It can result in serious injury or death when the directions are ignored

! CAUTION

It can result in minor injury or product damage when the directions are ignored

! WARNING

Installation or repairs made by unqualified persons can result in hazards to you and others.

Installation MUST conform with local building codes or, in the absence of local codes, with the Nation Electrical Code NFPA 70/ANSI C1-1003 or current edition and Canadian Electrical Code Part1 CSA C.22.1.

The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.

Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.

Installation

Always perform grounding. - Otherwise, it may cause electrical shock.

Don’t use a power cord, a plug or a loose socket which is damaged. - Otherwise, it may cause a fire or electrical shock.

For installation of the product, always contact the service center or a professional installation agency. - Otherwise, it may cause a fire, electrical shock, explosion or injury.

Securely attach the electrical part cover to the indoor unit and the service panel to the outdoor unit.

-If the electrical part cover of the indoor unit and the service panel of the outdoor unit are not attached securely, it could result in a fire or electric shock due to dust, water, etc.

Always install an air leakage breaker and a dedicated switching board. - No installation may cause a fire and electrical shock.

Do not keep or use flammable gases or combustibles near the air conditioner. - Otherwise, it may cause a fire or the failure of product.

Ensure that an installation frame of the outdoor unit is not damaged due to use for a long time.

-It may cause injury or an accident.

Do not disassemble or repair the product randomly. - It will cause a fire or electrical shock.

Do not install the product at a place that there is concern of falling down. - Otherwise, it may result in personal injury.

Use caution when unpacking and installing. - Sharp edges may cause injury.

Operation

Do not share the outlet with other appliances. - It will cause an electric shock or a fire due to heat generation.

Do not use the damaged power cord. - Otherwise, it may cause a fire or electrical shock.

<![if ! IE]>

<![endif]>ENGLISH

4 SAFETY PRECAUTIONS

<![if ! IE]>

<![endif]>ENGLISH

• Do not modify or extend the power cord randomly. - Otherwise, it may cause a fire or electrical

 

 

shock.

 

• Take care so that the power cord may not be pulled during operation. - Otherwise, it may cause a

 

fire or electrical shock.

 

• Unplug the unit if strange sounds, smell, or smoke comes from it. - Otherwise, it may cause electri-

 

cal shock or a fire.

 

• Keep the flames away. - Otherwise, it may cause a fire.

 

• Take the power plug out if necessary, holding the head of the plug and do not touch it with wet

 

hands. - Otherwise, it may cause a fire or electrical shock.

 

• Do not use the power cord near the heating tools. - Otherwise, it may cause a fire and electrical

 

shock.

 

• Do not open the suction inlet of the indoor/outdoor unit during operation. - Otherwise, it may electri-

 

cal shock and failure.

 

• Do not allow water to run into electrical parts. - Otherwise, it may cause the failure of machine or

 

electrical shock.

 

• Hold the plug by the head when taking it out. - It may cause electric shock and damage.

 

• Never touch the metal parts of the unit when removing the filter. - They are sharp and may cause

 

injury.

 

• Do not step on the indoor/outdoor unit and do not put anything on it. - It may cause an injury through

 

dropping of the unit or falling down.

 

• Do not place a heavy object on the power cord. - Otherwise, it may cause a fire or electrical shock.

 

• When the product is submerged into water, always contact the service center. - Otherwise, it may

 

cause a fire or electrical shock.

 

• Take care so that children may not step on the outdoor unit. - Otherwise, children may be seriously

 

injured due to falling down.

! CAUTION

Installation

Install the drain hose to ensure that drain can be securely done. - Otherwise, it may cause water leakage.

Install the product so that the noise or hot wind from the outdoor unit may not cause any damage to the neighbors. - Otherwise, it may cause dispute with the neighbors.

Always inspect gas leakage after the installation and repair of product. - Otherwise, it may cause the failure of product.

Keep level parallel in installing the product. - Otherwise, it may cause vibration or water leakage.

Operation

Avoid excessive cooling and perform ventilation sometimes. - Otherwise, it may do harm to your health.

Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent. - The appearance of the air conditioner may deteriorate, change color, or develop surface flaws.

Do not use an appliance for special purposes such as preserving animals vegetables, precision machine, or art articles. - Otherwise, it may damage your properties.

Do not place obstacles around the flow inlet or outlet. - Otherwise, it may cause the failure of appliance or an accident.

TABLE OF CONTENTS

5

 

TABLE OF CONTENTS

6INSTALLATION PLACES 17 OPTIONAL OPERATION

7

THE INDOOR UNIT

17

Installer Setting -Test Run Mode

18

Installer Setting - Setting Address of

 

INSTALLATION

 

 

 

Central Control

8

Indoor Unit Drain Piping

19

Installer Setting -Thermistor

9

Wiring Connection

20

Installer Setting -Ceiling Height

11

REMOTE CONTROLLER

 

 

Selection

21

Installer Setting-Group Setting

 

INSTALLATION

22

Installer Setting-Dry Contact Mode

 

 

 

 

Setting

13 Wired remote controller installation

23

Installer Setting-Celsius / Fahrenheit

14

INSTALLATION OF DEC-

24

Switching

 

ORATIVE PANEL(ACCES-

Installer Setting -Optional Function

 

 

 

Setting

 

SORY)

 

 

 

25

HOW TO SET E.S.P?

16

TEST RUNNING

 

 

 

<![if ! IE]>

<![endif]>ENGLISH

<![if ! IE]>

<![endif]>ENGLISH

6 INSTALLATION PLACES

INSTALLATION PLACES

-There should not be any heat source or steam near the unit.

-There should not be any obstacles to prevent the air circulation.

-A place where air circulation in the room will be good.

-A place where drainage can be easily obtained.

-A place where noise prevention is taken into consideration.

-Do not install the unit near the door way.

-Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.

-The indoor unit must keep the maintenance space.

Ceiling

 

 

 

<![if ! IE]>

<![endif]>more

Ceiling Board

 

 

 

<![if ! IE]>

<![endif]>or

Ceiling Board

 

 

 

 

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>300

 

<![if ! IE]>

<![endif]>less

 

 

 

 

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>or

500 or

<![if ! IE]>

<![endif]>1000

<![if ! IE]>

<![endif]>or more

 

<![if ! IE]>

<![endif]>1000 or less

500 or

<![if ! IE]>

<![endif]>300

more

<![if ! IE]>

<![endif]>Above 250

more

 

 

 

 

 

 

 

 

Unit : mm

 

 

 

 

Floor

 

 

*Please use an annexed sheet or the corrugated cardboard on the bottom of packing as installation sheet.

 

Or

Annexed sheet

Packing corrugated

 

cardboard on the

 

bottom

*When using the bottom sheet, please use it after separating the installation sheet from packing of the product floor by using a knife etc as a picture below.

LG ATNH12GRLE2 INSTALLATION MANUAL

THE INDOOR UNIT INSTALLATION

7

 

THE INDOOR UNIT INSTALLATION

Ceiling

Level gauge

Ceiling board

!CAUTION

This air-conditioner uses a drain pump.

Install the unit horizontally using a level gauge.

During the installation, care should be taken not to damage electric wires.

!NOTE

Avoid the following installation location.

 

TP/TN/TM Series

 

 

1 Such places as restaurants and kitchen

 

 

 

where considerable amount of oil steam

 

875(Ceiling opening)

 

 

 

 

 

and flour is generated. These may cause

 

787(Hanging bolt)

 

 

 

 

 

heat exchange efficiency reduction, or

 

 

 

 

 

 

 

 

water drops, drain pump mal-function. In

<![if ! IE]>

<![endif]>671

<![if ! IE]>

<![endif]>sizeUnit840

<![if ! IE]>

<![endif]>(Hanging684 bolt)

<![if ! IE]>

<![endif]>875(Ceilingopening)

these cases, take the following actions;

such a place where it may not suck oily

 

 

 

 

- Make sure that ventilation fan is enough

 

 

 

 

to cover all noxious gases from this

 

840 Unit size

 

 

place.

 

 

 

 

- Ensure enough distance from the cook-

 

 

 

 

ing room to install the air conditioner in

 

 

 

 

steam.

 

 

Unit:mm

 

 

 

 

 

Air conditioner

TQ/TR Series

 

585~660

 

 

 

 

517

 

 

<![if ! IE]>

<![endif]>523

<![if ! IE]>

<![endif]>319

570

<![if ! IE]>

<![endif]>517

<![if ! IE]>

<![endif]>585~660

<![if ! IE]>

<![endif]>570

 

 

461

 

Unit:mm

-Select and mark the position for fixing bolts and piping hole.

-Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose.

-Drill the hole for anchor bolt on the wall.

Take enough distance

Cooking table

Use the ventilation fan for smoke-collecting hood with sufficient capacity.

2Avoid installng air conditioner in such places where cooking oil or iron powder is generated.

3Avoid places where inflammable gas is generated.

4Avoid place where noxious gas is generated.

5Avoid places near high frequency generators.

<![if ! IE]>

<![endif]>ENGLISH

<![if ! IE]>

<![endif]>ENGLISH

8

THE INDOOR UNIT INSTALLATION

 

 

 

 

 

 

 

 

 

Ceiling

 

 

Hanging bolt

Keep the length of the bolt

Air Conditioner body

<![if ! IE]>

<![endif]>150mm

 

Nut

Flat washer for M10

 

(W3/8 or M10)

from the bracket to 40mm

 

 

 

(W3/8 or M10)

(accessory)

Ceiling board

 

 

 

 

Spring washer

 

 

 

 

 

 

 

 

 

 

(M10)

 

 

Keep the length of 15~18mm

Ceiling

 

 

Flat washer for M10

between the air conditioner

 

 

bottom surface and the ceiling

board

 

 

(accessory)

 

surface

Set screw of

 

 

 

Nut

 

Paper model

 

 

 

(W3/8 or M10)

 

for installation

paper model (4 pieces)

 

 

 

Adjust the

Open the ceiling board

The following parts is option.

same height

 

 

along the outer edge of the

Hanging Bolt

- W 3/8 or M10

 

 

paper model

 

 

 

 

 

Nut

- W 3/8 or M10

Spring Washer - M10

Plate Washer - M10

Drill the piping hole on the wall slightly tilted to the outdoor side using a Ø 70 hole-core drill.

! CAUTION

Tighten the nut and bolt to prevent unit falling.

 

Wall

Indoor

Outdoor

 

<![if ! IE]>

<![endif]>5~7mm

Indoor Unit Drain Piping

-Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow.

-During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit.

-The outside diameter of the drain connection on the indoor unit is 32mm.

Piping material: Polyvinyl chloride pipe VP25 and pipe fittings

-Be sure to execute heat insulation on the drain piping.

-Install the drain raising pipes at a right angle to the indoor unit and no more than 300mm from the unit.

Pipe clamp

Upward

routing

 

 

not allowed

Indoor unit

 

Maintenance drain port

THE INDOOR UNIT INSTALLATION

9

 

300mm or less

1 -1.5m

 

<![if ! IE]>

<![endif]>700 or less

 

Drain raising pipe

Clamp metal(attached)

Drain hose(attached)

high humid atmosphere (dew point temperature: more than 23°C), water drops are liable to fall. In this case, add heat insulation material according to the following procedure:

Fastening band (accessory)

Heat insulation material: Polyethylene foam with thickness more than 8 mm.

Drain test

The air conditioner uses a drain pump to drain water.

Use the following procedure to test the drain pump operation:

-Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end.

-Feed water to the flexible drain hose and check the piping for leakage.

-Be sure to check the drain pump for normal operating and noise when electrical wiring is complete.

-When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.

Feed water

Flexible drain hose

 

(accessory)

 

Main

 

drain pipe

Drain

Drain Pump port Glue the joint

Drain hose connection Use the clip (accessory)

Indoor

Refrigerant

piping

unit

 

 

Thermal insulator

 

(accessory)

-Heat insulation material to be prepared...

Adiabatic EPDM or NBR with thickness 10 to 20mm.

-Stick glass wool on all air conditioners that are located in ceiling atmosphere.

Wiring Connection

-Open the control box cover and connect the Remote controller cord and Indoor power wires.

-Remove the control box cover for electrical connection between the indoor and outdoor unit. (Remove screws )

-Use the cord clamper to fix the cord.

Drain pan

HEAT INSULATION

-Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 120°C).

-Precautions in high humidity circumstance: This air conditioner has been tested according to the "KS Standard Conditions with Mist" and confirmed that there is not any default. However, if it is operated for a long time in

 

 

Remote

 

 

controller

 

 

cord

Connection

 

1

cord

 

 

between the

1

Control box cover

indoor unit and

 

 

(On which the

the outdoor

 

unit

 

Electric Wiring

Connection is put)

<![if ! IE]>

<![endif]>ENGLISH